PROTECTION LIST

CIRCUIT BREAKER TO BE TRIPPED/ OR TO REMOTE SUPERVISORY SCADA SUPERVISORY


TYPE OF RELAY

ALARM BE LOCKED/ OR TO BE RECLOSE PANEL INDICATION INDICATION


TO BE USED
FUNCTION
DEVICE

NUMBER

(LETTERING)
LOCAL FAULT

OPERATION
INDICATOR

LOCAL-MAN

ITEMS
ALARM IN

TYPE OF
LOCKOUT

OPERATION MODE OPERATION MODE

REMOTE
SIGNAL
RELAY

HEAVY
FAULT

LIGHT
FAULT

ALARM
OPEN
DOOR

LBD
SWITCH 43A (MANUAL) SWITCH 43A (AUTO) SCADA ALARM INFORMATION
POSITION POSITION
1 SELF TRIPPED 54P BY 54P MAIN UNIT SELF TRIPPED BY
SR PROTECTION

54P HSCB 54P BELL 54P YES HIGH


RECLOSE DEVICE (82P)* OVER CURRENT
OVERCURRENT
CUBICLE

2 RECLOSE FAILURE FOR 54P 82P NTJ-30 82P BELL 86P


54P 54P
YES HIGH MAIN UNIT LOCKED OUT
(LOCKED) (LOCKED)
3 SELF TRIPPED 54F BY 54F HSCB 54F BELL 54F
54F
YES HIGH
OUTGOING FEEDER NO.X SELF
RECLOSE DEVICE (82F) TRIPPED BY OVER CURRENT
OVERCURRENT
DC OUTGOING FEEDER

4 ΔI RELAY FOR DC FEEDER 50F FE-12 50F BELL 54F


54F
YES HIGH
OUTGOING FEEDER NO.X TRIPPED
RECLOSE DEVICE (82F) BY ΔI
5 RECLOSE FAILURE FOR 54F 82F NTJ-30 82F BELL 86F
54F
YES HIGH
OUTOGING FEEDER NO.X LOCKED
(LOCKED) OUT
6 TRIPPING SIGNAL BY LBD 85FR LBD 85FR BELL 54F
54F
YES HIGH OUTGOING NO.X TRIPPED BY LBD
RECLOSE DEVICE (82F)
(RECIEVING)
NEGATIVE

7 DC GROUNDED OVERVOLTAGE 64P IKD-0ZK01 64P BELL 86.86P.86F


52 & 54P & 54F 52 & 54P & 54F
YES HIGH GROUNDING FAULT
(LOCKED) (LOCKED)
8 OVERCURRENT OF DISTRIBUTION 51D KIO-C6R 51D BELL 52
52D
YES HIGH
TRAFO DISTRIBUTION TRIP BY
RECLOSE DEVICE (79D) OVERCURRENT
TRANSFORMER
DISTRIBUTION 20kVA TRAFO

9 SHORT CIRCUIT OF 50D KIO-C6R 50D BELL 86D


52 52D
YES HIGH
TRAFO DISTRIBUTION TRIP BY
(LOCKED) (LOCKED) SHORT CIRCUIT
DISTRIBUTION TRANSFORMER
10 RECLOSE FAILURE FOR 52D 79D NTJ-30 79D BELL 86D
52D
YES HIGH
VCB TRAFO DISTRIBUTION
(LOCKED) LOCKED OUT
11 HIGH TEMPERATURE RAISE OF 26TD
DIAL TYPE
26TD BELL YES WARN
HIGH TEMPERATURE OF TRAFO
METER DISTRIBUTION
DISTRIBUTION TRANSFORMER
12 GROUNDED OVERVOLTAGE OF 6kV
6kV BUS CUBICLE

64B (& 52D


TIMER) KIEI-KR 64B BELL 52D YES HIGH 6kV GROUNDING FAULT
RECLOSE DEVICE (79D)
CIRCUIT
13 UNDERVOLTAGE OF 6kV BUS 27B KIU-KR 27B BELL 52L1 & 52L2 52L1 & 52L2 YES HIGH 6kV UNDERVOLTAGE
14 OVERCURRENT OF 6kV OUTGOING 51L KIO-C6R 51L BELL 52L
52L
YES HIGH
6kV OVERCURRENT OUTGOING
(NON RECLOSING) FEEDER
FEEDER
AC OUTGOING CUBICLE

15 SHORT CIRCUIT OF 6kV 50L KIO-C6R 50L BELL 86L


52L 52D
YES HIGH
6kV SHORT CIRCUIT OUTGOING
(LOCKED) (LOCKED) FEEDER
OUTGOING FEEDER
16 DIRECTIONAL GROUND OF 67GL
KIG-CFR 67G BELL 52L
52D
YES HIGH
6kV DIRECTIONAL GROUND OF
(&64B) (NON RECLOSING) OUTGOING FEEDER
OUTGOING FEEDER
17 UNDERVOLTAGE OF 6kV 27L KIU-KR 27L WARN
6kV UNDERVOLTAGE OUTGOING
FEEDER
OUTGOING FEEDER
18 1200V LBS & 6kV LBS (POWER
50kVA
TRAFO

47 SDV-FH 27L BELL YES WARN POWER FUSE BLOW


FUSE FUSING)
19 PANEL DOOR OPENED 92 92 BELL YES WARN PANEL DOOR OPEN

OTHERS
20 IMCOMPLETE OF AUTOTIMER 48 48 BELL YES WARN AUTO RECLOSE FAIL
CLOSED AND/OR AUTO RECLOSE
21 EMERGENCY STOP 5E BELL
ALL CIRCUIT BREAKER ALL CIRCUIT BREAKER
YES HIGHT EMERGENCY
(LOCKED) (LOCKED)