Dynasty has upgraded their UPS line and replaced all but one of their UPS series batteries with
their new High Max Rate Series (MR). The case length and width for their new MR series remain
the same as their now discontinued batteries. Therefore, replacement banks are a perfect fit.
The case heights on the new MR series batteries are slightly less due to changes in the terminals.
Capacities are increased on each type and all of the MR series are rated as fire retardant (FR).
We have prepared a reference chart below to aid in selecting replacements. All specifications
and ratings are also included in this document. Product specification sheets for the discontinued
batteries are available upon request at sales@dcbattery.com
41-9027
Available Through: DC Battery Specialists • 160 NW 73 St. • Miami, FL 33150 • Phone 305.758.5041
www.dcbattery.com • e-mail: sales@dcbattery.com
UPS
SPECIFICATIONS
Operating Temperature Range Discharge: -40˚F (-40˚C) to +160˚F (71˚C)
with temperature compensation Charge: -10˚F (-23˚C) to +140˚F (60˚C)
Nominal Operating Temperature Range +74˚F (-23˚C) to +80˚F (27˚C)
Recommended Maximum Charging C/5 amperes @ 20hr rate
Current Limit
Float Charging Voltage 13.65 ± 1.5 VDC average per 12V unit (6.75 to 6.90 per 6V unit)
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Self Discharge Up to 6 months at 25˚C and then a freshening charge is required. For higher temps,
the time interval will increase. freshening charge is required.
For higher temperatures the time interval will be shorter.
For lower temperatures time interval will decrease equalization charge.
Equalize charge and 14.40 to 14.80 VDC average per 12V unit @ 77˚F (25˚C) (7.20 to 7.40 VDC per 6V unit.)
cycle service voltage
Terminal: Flag 0.22 in. clearance hole to accept 0.1875 in. bolt (UPS12-100MR)
Terminal: Inserted Threaded copper alloy insert terminal to accept
10-32 UNF bolt (UPS12-150MR, UPS12-210MR)
⁄4-20 UNC bolt (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MR, UPS12-540MR, UPS6-620MR)
1
DIMENSIONS
*All dimensions in millimeters. All dimensions are for reference only. Contact a C&D Representative for complete dimension information.
Available Through: DC Battery Specialists • 160 NW 73 St. • Miami, FL 33150 • Phone 305.758.5041
www.dcbattery.com • e-mail: sales@dcbattery.com
UPS
UPS12-100MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 158 111 87 73 56 46 42 39 34 24
1.70 168 115 90 75 57 47 43 40 35 24
1.67 172 117 91 75 57 47 43 40 35 24
1.65 174 118 91 76 57 47 43 40 35 25
1.60 179 119 92 76 58 47 43 40 35 25
UPS12-150MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 270 182 141 115 86 69.0 63.0 58.0 49.7 35.0
1.70 282 188 144 118 87 70.0 63.9 58.8 50.4 35.5
1.67 288 192 148 120 89 71.1 64.9 59.5 51.0 36.0
1.65 292 196 150 122 90 71.8 65.3 60.0 51.5 36.3
1.60 296 200 152 123 91 72.5 66.0 60.5 51.8 36.5
UPS12-210MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 340 240 195 164 121 98 90 83.0 71.8 51.0
1.70 366 252 201 168 123 99 91 84.2 72.8 52.0
1.67 376 257 206 170 125 101 92 85.0 73.3 52.4
1.65 380 259 207 171 126 101 93 85.4 73.8 52.6
1.60 392 261 209 172 127 102 93 86.0 74.2 52.8
Available Through: DC Battery Specialists • 160 NW 73 St. • Miami, FL 33150 • Phone 305.758.5041
www.dcbattery.com • e-mail: sales@dcbattery.com
UPS
UPS12-300MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 496 360 282 234 174 140 128 118 103 74
1.70 530 373 294 240 177 142 130 120 104 75
1.67 550 382 300 244 179 144 131 121 105 76
1.65 566 387 303 246 181 146 133 122 106 77
1.60 580 391 306 248 183 147 134 123 107 78
UPS12-350MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 540 410 327 274 205 164 149 137 118 85
1.70 596 425 337 283 211 167 152 140 120 86
1.67 620 440 350 290 217 171 155 141 122 87
1.65 640 455 360 298 219 173 157 144 123 88
1.60 672 470 370 303 222 175 159 145 125 89
UPS12-400MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 616 461 377 312 230 184 168 154 133 96
1.70 680 490 390 319 234 187 170 156 135 97
1.67 720 505 400 325 237 189 172 158 136 98
1.65 740 515 406 329 239 191 174 160 137 99
1.60 770 525 412 333 241 193 175 161 138 100
Available Through: DC Battery Specialists • 160 NW 73 St. • Miami, FL 33150 • Phone 305.758.5041
www.dcbattery.com • e-mail: sales@dcbattery.com
UPS
UPS12-490MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 660 525 444 385 300 245 224 208 183 133
1.70 740 570 472 401 310 252 231 214 186 135
1.67 773 590 488 412 317 256 236 218 189 136
1.65 800 614 500 418 322 260 238 220 191 137
1.60 840 644 513 428 327 264 241 222 192 138
UPS12-540MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
DIECUT
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 723 564 472 405 320 261 239 220 190 136
1.70 825 625 512 432 334 270 247 226 193 137.5
1.67 868 654 537 450 344 277 252 230 198 139
1.65 904 679 554 459 350 282 256 234 200 141
1.60 952 696 564 465 354 284 258 237 202 143
UPS6-620MR
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell 5 10 15 20 30 40 45 50 60 90
1.75 840 680 575 500 395 320 297 275 242 168
1.70 890 720 600 520 405 332 306 280 243 170
1.67 940 750 620 525 410 333 309 285 245 173
1.65 950 760 630 532 414 335 311 288 248 176
1.60 1000 790 650 550 420 340 315 290 250 178
Available Through: DC Battery Specialists • 160 NW 73 St. • Miami, FL 33150 • Phone 305.758.5041