1 Scope............................................................. 2
2 Conflicts and Deviations................................. 2
3 References..................................................... 2
4 General Requirements................................... 3
5 Design............................................................ 5
6 Nameplates.................................................... 6
7 Piping............................................................. 6
1 Scope
This specification defines the minimum requirements for instrument control panels and
cabinets for location in outdoor areas.
Excluded from this specification are control panels provided in packaged equipment
and field instrument junction boxes.
2.1 Any conflicts between this specification and other applicable Saudi Aramco
Materials System Specifications (SAMSSs), Engineering Standards (SAESs),
Standard Drawings (SASDs), or Industry Standards, Codes, and Forms shall be
resolved in writing by the Company or Buyer Representative through the
Manager, Process & Control Systems Department of Saudi Aramco, Dhahran.
2.2 Direct all requests to deviate from this specification in writing to the Company or
Buyer Representative, who shall follow internal company procedure SAEP-302
and forward such requests to the Manager, Process & Control Systems
Department of Saudi Aramco, Dhahran.
3 References
Material or equipment supplied to this specification shall comply with the latest edition
of the references listed below, unless otherwise noted.
Page 2 of 9
Document Responsibility: Instrumentation 34-SAMSS-821
Issue Date: 5 October 2005
Next Planned Update: 1 November 2010 Instrument Control Cabinets - Outdoor
4 General Requirements
4.1 Environmental
Temperature:
Page 3 of 9
Document Responsibility: Instrumentation 34-SAMSS-821
Issue Date: 5 October 2005
Next Planned Update: 1 November 2010 Instrument Control Cabinets - Outdoor
Page 4 of 9
Document Responsibility: Instrumentation 34-SAMSS-821
Issue Date: 5 October 2005
Next Planned Update: 1 November 2010 Instrument Control Cabinets - Outdoor
Other pollutants present in the atmosphere under the most extreme conditions
are:
H2S 20 ppm (vol/vol)
Hydrocarbon 150 ppm (vol/vol)
SO2 10 ppm (vol/vol)
CO 100 ppm (vol/vol)
NOx 5 ppm (vol/vol)
O3 1 ppm (vol/vol)
5 Design
5.1 Enclosures
5.1.1 In outdoor plant areas, the panel/cabinet shall be NEMA 250/NEMA ICS
6 Type 4 or IEC 60529, Type IP65.
5.1.2 In outdoor plant and other industrial areas located in severe corrosive
environments as defined in Paragraph 4.2, enclosures shall be NEMA
Type 4X or IEC 60529 Type IP66, manufactured of 316L stainless steel.
Galvanized and/or painted or coated carbon steel sheet metal enclosures
are not permitted.
Commentary Note:
5.2 Electrical
The panel/cabinet and all components within the panel shall be suitable
for the electrical area classification where the panel will be installed.
The classification of the area in which the panel will be used, shall be
specified in the Purchase Order.
Page 5 of 9
Document Responsibility: Instrumentation 34-SAMSS-821
Issue Date: 5 October 2005
Next Planned Update: 1 November 2010 Instrument Control Cabinets - Outdoor
5.2.3 Relays
Pushbuttons, pilot lights and switches shall be heavy duty, oil-tight, and
shall meet the area classification of the installed location.
6 Nameplates
Nameplates shall be attached to the cabinets using stainless steel screws. The
nameplate shall be made of corrosion resistant material. The lettering shall be clearly
legible. Internal nameplates (within the cabinet) shall also be installed using stainless
steel screws. Using adhesive nameplates is not acceptable.
7 Piping
No process piping of any kind shall be allowed in a control cabinet. The only fluid
allowed is instrument air.
7.1.2 Pneumatic piping which does not have a pressure indication on the
instruments it connects shall be provided with a plugged tee for testing.
Page 6 of 9
Document Responsibility: Instrumentation 34-SAMSS-821
Issue Date: 5 October 2005
Next Planned Update: 1 November 2010 Instrument Control Cabinets - Outdoor
7.1.4 All open fittings and bulkhead connections shall be plugged or capped
during transportation.
7.2.1 Air headers shall be sized for the capacity of all instruments plus 20%
spare for future additions.
7.2.3 Stainless steel take-off nipples shall be provided at the top of the air
header for connection of the instruments. Each take-off nipple shall
have a ¼-inch isolating valve with a tag for connected instrument
identification. The isolating valve shall be rated at 3000 psi, stainless
steel construction, with ¼" female NPT connections. Packing type
valves shall have stainless steel stems. 20% spare take-off stainless
steel nipples with plugged isolating valves shall be installed for future
requirements.
7.2.4 The air header shall be sloped 1 to 100 downstream and have a ½-inch
drain valve with plug on the bottom at the lower end of the header.
The end of the air header shall be capped with a 2-inch plugged valve.
Vertical headers shall have a blowdown valve at the lower end.
Page 7 of 9
Document Responsibility: Instrumentation 34-SAMSS-821
Issue Date: 5 October 2005
Next Planned Update: 1 November 2010 Instrument Control Cabinets - Outdoor
7.3.2 Each filter and regulator shall have adequate capacity to serve the
entire panel. It shall be suitable for an air-supply pressure between 400
and 860 kPa and a regulated header pressure of 170 kPa. The filter
shall be of the metal bowl type.
7.3.3 The station shall be equipped with suitable valving and coupling for
removal of each filter and regulator during normal operation without
service interruption.
7.4.1 Tubing
7.4.2 Tube fittings shall be 316 stainless steel and shall be compression type
Crawford Fitting Swagelok, Parker Hannifin CPI or A-lok, Hoke
Gyrolok or equivalent to the above as approved by Supervisor,
Instrumentation Unit, Process Instrumentation Division, Process &
Control Systems Department. Interchange of tube fitting component
parts from different manufacturers is not allowed.
7.4.5 Tubing runs and Bulkhead fitting layouts shall be included in the
documentation provided to Saudi Aramco.
Page 8 of 9
Document Responsibility: Instrumentation 34-SAMSS-821
Issue Date: 5 October 2005
Next Planned Update: 1 November 2010 Instrument Control Cabinets - Outdoor
Revision Summary
5 October 2005 This revision is intended to address comments generated as part of the Instrumentation
Standards Value Engineering conducted on March 5-9, 2005.