SPECIFICATIONS & OPTIONS
STANDARDS WINDINGS & ELECTRICAL PERFORMANCE
Newage Stamford industrial generators meet the All generator stators are wound to 2/3 pitch. This
requirements of BS EN 60034 and the relevant sections of eliminates triplen (3rd, 9th, 15th …) harmonics on the
other national and international standards such as voltage waveform and is found to be the optimum design
BS5000, VDE 0530, NEMA MG1-32, IEC60034, CSA for trouble-free supply of non-linear loads. The 2/3 pitch
C22.2-100, AS1359. design avoids excessive neutral currents sometimes seen
Other standards and certifications can be considered on with higher winding pitches. A fully connected damper
request. winding reduces oscillations during paralleling. This
winding, with the 2/3 pitch and carefully selected pole and
DESCRIPTION tooth designs, ensures very low levels of voltage waveform
distortion.
The STAMFORD PI range of synchronous ac generators
are brushless with a rotating field. They are separately TERMINALS & TERMINAL BOX
excited by the STAMFORD Permanent Magnet Generator
(PMG). This is a shaft mounted, high frequency, pilot Standard generators feature a main stator with 6 ends
exciter which provides a constant supply of clean power brought out to the terminals, which are mounted on the
via the Automatic Voltage Regulator (AVR) to the main frame at the non-drive end of the generator. A sheet steel
exciter. The main exciter output is fed to the main rotor, terminal box contains the AVR and provides ample space
through a full wave bridge rectifier, protected by surge for the customers' wiring and gland arrangements. It has
suppression. removable panels for easy access.
The PI range generators complete with a PMG are All generator rotors are dynamically balanced to better than
available with one of two AVRs. Each AVR has soft start BS6861:Part 1 Grade 2.5 for minimum vibration in
voltage build up and built in protection against sustained operation. Two bearing generators are balanced with a half
over-excitation, which will de-excite the generator after a key.
minimum of 8 seconds.
Underspeed protection (UFRO) is also provided on both INSULATION/IMPREGNATION
AVRs. The UFRO will reduce the generator output voltage
proportional to the speed of the generator below a pre-
The insulation system is class 'H', and meets the
settable level.
requirements of UL1446.
All wound components are impregnated with materials and
The MX341 AVR is two phase sensed with a voltage
processes designed specifically to provide the high build
regulation of ± 1 %. (see the note on regulation).
required for static windings and the high mechanical
strength required for rotating components.
The MX321 AVR is 3 phase rms sensed with a voltage
regulation of 0.5% rms (see the note on regulation). The QUALITY ASSURANCE
UFRO circuit has adjustable slope and dwell for controlled
recovery from step loads. An over voltage protection circuit
Generators are manufactured using production procedures
will shutdown the output device of the AVR, it can also trip
having a quality assurance level to
an optional excitation circuit breaker if required. As an
BS EN ISO 9001.
option, short circuit current limiting is available with the
addition of current transformers.
NOTE ON REGULATION
The stated voltage regulation may not be maintained in the
Both the MX341 and the MX321 need a generator
presence of certain radio transmitted signals. Any change
mounted current transformer to provide quadrature droop
in performance will fall within the limits of Criteria 'B' of EN
characteristics for load sharing during parallel operation.
61000-6-2:2001. At no time will the steady-state voltage
Provision is also made for the connection of the
regulation exceed 2%.
STAMFORD power factor controller, for embedded
applications, and a remote voltage trimmer.
NB Continuous development of our products entitles us to change
specification details without notice, therefore they must not be
regarded as binding.
2
PI734A
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
A.V.R. MX341 MX321
VOLTAGE REGULATION ± 1% ± 0.5 % With 4% ENGINE GOVERNING
SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)
PROTECTION IP23
WINDING LEADS 6
MAIN STATOR RESISTANCE 0.0016 Ohms PER PHASE AT 22°C STAR CONNECTED
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
MAXIMUM OVERSPEED 2250 Rev/Min
BEARING DRIVE END BALL. 6228 C3
BEARING NON-DRIVE END BALL. 6319 C3
1 BEARING 2 BEARING
WEIGHT COMP. GENERATOR 2760 kg 2710 kg
3
PI734A
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES
4
PI734A
Winding 312
60
THREE PHASE EFFICIENCY CURVES
Hz
5
PI734A
Winding 312
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 500 1000 1500 2000 2500
LOCKED ROTOR kVA
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 500 1000 1500 2000 2500 3000
LOCKED ROTOR kVA
6
PI734A
SYMMETRICAL
ASYMMETRICAL
CURRE NT (Am p s)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
60 100000
Hz
SYMMETRICAL
ASYMMETRICAL
CURRE NT (Am p s)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
7
PI734A
Winding 312 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
kVA 1140 1175 1175 1150 1225 1260 1260 1235 1275 1315 1315 1290 1310 1350 1350 1325
kW 912 940 940 920 980 1008 1008 988 1020 1052 1052 1032 1048 1080 1080 1060
Efficiency (%) 94.5 94.6 94.8 95.0 94.3 94.4 94.6 94.8 94.1 94.2 94.4 94.7 94.0 94.1 94.3 94.6
kW Input 965 994 992 968 1039 1068 1066 1042 1084 1117 1114 1090 1115 1148 1145 1121
60Hz Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
kVA 1275 1395 1405 1415 1370 1500 1510 1525 1425 1560 1570 1585 1465 1605 1615 1630
kW 1020 1116 1124 1132 1096 1200 1208 1220 1140 1248 1256 1268 1172 1284 1292 1304
Efficiency (%) 94.5 94.5 94.6 94.8 94.3 94.2 94.4 94.6 94.1 94.1 94.3 94.5 94.0 94.0 94.2 94.4
kW Input 1079 1181 1188 1194 1162 1274 1280 1290 1211 1326 1332 1342 1247 1366 1372 1381
DIMENSIONS