Indian Standard
CROSS-LINKED POLYETHYLENE INSULATED
THERMOPLASTIC SHEATHED CABLES —
SPECIFICATION
PART 1 FOR WORKING VOLTAGES UP TO AND INCLUDING 1 100 V
( First Revision )
(Incorporating Amendment Nos. 1, 2 & 3)
UDC 621.315.221.8-678.742.2
© BIS 2008
Price Group 5
IS : 7098 (Part 1) - 1988
Indian Standard
CROSS-LINKED POLYETHYLENE INSULATED
THERMOPLASTIC SHEATHED CABLES —
SPECIFICATION
PART 1 FOR WORKING VOLTAGES UP TO AND INCLUDING 1 100 V
( First Revision )
0. F O R E W O R D
0.1 This Indian Standard (Part 1) (First covered in a separate Indian Standard later. In
Revision) was adopted by the Bureau of Indian the meanwhile, users are advised to consult the
Standards on 22 December 1988, after the draft manufacturers for information on this aspect.
finalized by the Power Cables Sectional 0.5 A special category of cables with improved
Committee had been approved by the fire performance has been included in this
Electrotechnical Division Council. standard. Classification of such cables is given
0.2 This standard was first published in 1977. in Appendix A.
This revision has been undertaken to align it 0.6 In the preparation of this standard,
with the international practices and to take assistance has been derived from IEC
into account the experience gained during this Publication 502 (1983) ‘Extruded solid dielectric
period in the manufacture of these types of insulated power cables for rated voltage from
cable in the country. 1 kV to 30 kV’, issued by the International
0.3 Particular attention is drawn to the Electrotechnical Commission.
limitations of the short circuit ratings of the 0.7 This edition 2.3 incorporates Amendment
types of cable covered by this standard owing to No. 1 (April 1994), Amendment No. 2 (February
the absence of the metallic sheath and the 2007) and Amendment No. 3 (November 2007).
possible loss of the electrical contact between Side bar indicates modification of the text as the
the strands of the armour wire as a result of result of incorporation of the amendments.
corrosion or the presence of compound between
them. A separate standard about recommended 0.8 For the purpose of deciding whether a
short circuit ratings of these types of cable is particular requirement of this standard is
under preparation. complied with, the final value, observed or
calculated, expressing the result of a test, shall
0.4 Attention is also drawn to the fact that the be rounded off in accordance with IS : 2-1960*.
current rating of the types of cable covered by The number of significant places retained in
this standard are different from those of paper the rounded off value should be the same as
insulated metal sheathed cables. This standard that of the specified value in this standard.
does not include any data on the current
ratings but information on this aspect will be *Rules for rounding off numerical values ( revised ).
1
IS : 7098 (Part 1) - 1988
NOTE — Normal cables to this standard can be classified 3.1.1 Mining cables to be used in gassy mines
as meeting the requirement of category 0.1. shall be of copper conductor only.
2. TERMINOLOGY
4. INSULATION
2.0 For the purpose of this standard the
following definitions, in addition to those given 4.1 The insulation shall be of crosslinked poly-
in IS : 1885 (Part 32)-1971* shall apply. ethylene conforming to the requirements given
in Table 1.
2.1 Routine Tests — Tests made by the manu-
facturer on all finished cable lengths to TABLE 1 PROPERTIES OF XLPE INSULATION
demonstrate the integrity of the cable. ( Clause 4.1 )
2.2 Type Test — Tests required to be made S L NO . PROPERTY REQUIREMENT
before supply on a general commercial basis on (1) (2) (3)
a type of cable in order to demonstrate
i) Tensile strength 12.5 N/mm2, Min
satisfactory performance characteristics to
ii) Elongation at break 200 percent, Min
meet the intended application.
iii) Ageing in air oven
NOTE — These tests are of such a nature that after they
a) Treatment : Temperature 135±3ºC
have been made, they need not be repeated unless
changes are made in the cable materials of design which Duration 7 days
might change the performance characteristics. b) Tensile strength variation ±25 percent, Max
c) Elongation variation ±25 percent, Max
2.3 Acceptance Tests — Tests carried out on iv) Hot set
samples taken from a lot for the purpose of accep- a) Treatment : Temperature 200±3ºC
tance of the lot. Time under load 15 minutes
2.4 Optional Tests — Special tests to be carried Mechanical stress 20 N/cm2
out, when required, by agreement between the b) Elongation under load 175 percent, Max
purchaser and the supplier. c) Permanent elongation (set) after 15 percent, Max
cooling
2.5 Earthed System — An electric system
v) Shrinkage
which fulfills any of the following conditions:
a) Treatment : Temperature 130±3ºC
a) The neutral-point or the mid-point connec- Duration 1 hour
tion is earthed in such a manner that, even b) Shrinkage 4 percent, Max
under fault conditions, the maximum vi) Water absorption (gravimetric)
voltage that can occur between any conduc- a) Treatment : Temperature 85±2ºC
tor and the earth does not exceed 80 percent Duration 14 days
of the nominal system voltage; b) Water absorbed 1 mg/cm2, Max
vii) Volume resistivity:
b) The neutral-point or the mid-point connec- a) at 27ºC 1 × 1014 ohm-cm,
tion is not earthed but a protective device is Min
installed which automatically cuts out any b) at 90ºC 1 × 1012 ohm-cm,
part of the system which accidently Min
becomes earthed; or
c) In case of ac systems only, the neutral- 5. FILLER AND INNER SHEATH
point is earthed through an arc suppression
5.1 The fillers and inner sheath shall be of the
coil with arrangement for isolation within
following:
1 h of occurrence of the fault for the
non-radial field cables and within 8 h for a) Vulcanized or unvulcanized rubber, or
radial cables, provided that the total of such b) Thermoplastic materials.
periods in a year does not exceed 125 h.
5.2 Vulcanized or unvulcanized rubber or ther-
2.6 Unearthed System — An electric system moplastic material used for inner sheath shall
which does not fulfil the requirement of the not be harder than XLPE and PVC used for
earthed system ( see 2.5 ). insulation and outer sheath respectively. Fillers
and Inner sheath materials shall be so chosen as
SECTION 2 MATERIALS to be compatible with the temperature ratings of
3. CONDUCTOR the cable and shall have no deleterious effect on
any other component of the cable.
3.1 The conductor shall be composed of plain
copper or aluminium wires complying with 6. ARMOURING
IS : 8130-1984†.
6.1 Armouring shall be of the following:
*Electrotechnical vocabulary: Part 32 Cables, conductors a) Galvanized round steel wire, or
and accessories for electricity supply.
†Specification for conductors for insulated electric b) Galvanized steel formed wire (strip),
cables and flexible cords ( first revision ). c) Any metallic non-magnetic wire/strip.
2
IS : 7098 (Part 1) - 1988
requirement of tests applicable for the required Single Core Single Core
category (15.1.1 and 15.2.1). Armoured Unarmoured and
Cables Multi-core Cables
SECTION 3 CONSTRUCTION (1) (2) (3)
8. CONDUCTOR mm2 mm mm
1.5 1.0 0.7
8.1 The construction of the conductor shall be 2.5 1.0 0.7
as follows: 4 1.0 0.7
6 1.0 0.7
Nominal Cross-Section Solid/ Flexibility Class
Stranded ( Ref IS : 10 1.0 0.7
3
IS : 7098 (Part 1) - 1988
5 Core : Red, yellow, blue, black and TABLE 4 LAY-UP OF CORES FOR CABLES
grey; ( Clause 11.2 )
6 Core and : Two adjacent cores (counting (1) (2)
above and direction core) in each NO. OF CORES LAY-UP
layer, blue and yellow, re- 2 2
maining cores, grey; or 3 3
4 4
c) By numerals either by applying numbered 5 5
strips or by printing on the cores as follows 6 6
( see Note 2 ): 7 1-6
2 Core : 0, 1 8 1-7
9 1-8
3 Core : 0, 1, 2, 3 10 2-8
4 Core : 0, 1, 2 and 3 11 3-8
12 3-9
NOTE 1 — For identification by using coloured strips, 13 3-10
red, yellow and blue colours shall be used to identify the 14 4-10
phase conductors, and black to identify reduced neutral 15 5-10
conductor.
16 5-11
NOTE 2 — Identification by numerals is applicable up to 17 5-12
4 core cables. For control cables, numerals 0 and 1 shall 18 0-6-12
be adopted for counting core and direction core 19 1-6-12
respectively; remaining cores shall not be numbered. 20 1-7-12
21 1-7-13
10.2 For reduced neutral conductors, the core 22 2-7-13
shall be black. 23 2-7-13
24 2-8-14
10.3 For cables having more than 5 cores, as an 25 2-8-15
alternate to the provisions of 10.1 the core 26 3-9-14
identification may be done by numbers. In that 27 3-9-15
case the insulation of cores shall be of the same 28 3-9-16
colour and numbered sequentially, starting by 29 4-10-15
number 1 in the inner layer. The numbers shall 30 4-10-16
be printed in Hindu-Arabic numerals on the 31 4-10-17
32 5-11-16
outer surface of the cores. All the numbers shall 33 5-11-17
be of the same colour, which shall contrast with 34 5-11-18
the colour of the insulation. The numerals shall 35 5-12-18
be legible. 36 0-6-12-18
37 0-6-12-18
10.4 For reduced neutral conductors, the core 38 1-6-12-19
shall have ‘0’ number. 39 1-6-13-19
40 1-7-13-19
11. LAYING UP OF CORES 41 1-7-13-20
42 2-8-13-19
11.1 In twin, three and multi-core cables, the 43 2-8-14-19
cores shall be laid up together with a suitable 44 2-8-14-20
lay, the outermost layer shall have right-hand 45 2-8-14-21
lay and the successive layer shall be laid with 46 3-9-14-20
47 3-9-15-20
opposite lay. Where necessary, the interstices 48 3-9-15-21
shall be filled with non-hygroscopic material. 49 3-9-15-22
50 3-9-16-22
11.2 The recommended plan for lay-up of multi-
51 4-10-16-21
cores up to 100 shall be in accordance with 52 4-10-16-22
Table 4. 53 4-10-16-23
54 4-10-17-23
12. INNER SHEATH (COMMON 55 4-11-17-23
COVERING) 56 5-11-17-23
57 5-11-17-24
12.1 The laid up cores shall be provided with an 58 5-11-18-24
inner sheath applied either by extrusion or by 59 5-12-18-24
wrapping. It shall be ensured that it is as 60 0-6-12-18-24
circular as possible. 61 1-6-12-18-24
62 1-6-12-18-24
12.2 The inner sheath shall be so applied that 63 1-7-12-18-25
it fits closely on the laid up cores and it shall be 64 1-7-13-18-25
65 1-7-13-19-25
possible to remove it without damage to the
( Continued )
insulation.
4
IS : 7098 (Part 1) - 1988
5
IS : 7098 (Part 1) - 1988
the conductor as specified in IS : 8130-1984* by g) The resistivity of the round steel wire/
more than 33 percent. To satisfy this, formed steel wire shall meet the
substitution of galvanized wires/strips in requirements of IS : 3975-1999.
armouring by required number of tinned copper
wire/strips is permissible.
14. OUTER SHEATH
13.6 The round steel wires/formed steel wires
taken from the cable shall meet the following 14.1 The outer sheath shall be applied by
requirements. extrusion. It shall be applied:
a) The tensile strength of round steel
wire/formed steel wire shall be not less a) Over the insulation in case of unarmoured
than 250 N/mm2 and not more 580 single core cables;
N/mm2.
b) The elongation at break of round steel b) Over the inner sheath in case of
wire/formed steel wire shall be not less unarmoured twin, three and multi-core
than 6 percent. cables; and
c) Round steel wire shall meet the
requirements of torsion test. The gauge c) Over the armouring in case of armoured
length between vices and the minimum cables.
number of turns without break shall be as
per Table 6 of IS : 3975-1999.
14.2 Colour or outer sheath shall be black or
*Specification for conductors for insulated electric
any other colour as agreed to between the pur-
cables and flexible cords ( first revision ). shaser and the supplier.
6
IS : 7098 (Part 1) - 1988
CONDUCTOR Two Core Three Core Four Core Four Core with
Reduced Neutral
Round Strip Round Strip Round Strip
wire wire wire Round Strip
4.0× 6.1× 4.0× 6.1× 4.0× 6.1× wire
0.8 1.4 0.8 1.4 0.8 1.4 4.0× 6.1×
mm mm mm mm mm mm 0.8 1.4
mm mm
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13)
mm2 ohm/ ohm/ ohm/ ohm/ ohm/ ohm/ ohm/ ohm/ ohm/ ohm/ ohm/ ohm/
km km km km km km km km km km km km
1.5 6.71 — — 6.35 — — 5.82 — — — — —
2.5 6.07 — — 5.73 — — 5.24 — — — — —
4 5.45 — — 5.14 — — 4.69 — — — — —
6 4.91 — — 4.63 — — 4.21 — — — — —
10 4.25 — — 3.99 — — 3.62 — — — — —
16 3.57 — — 2.89 4.77 — 2.62 4.32 — — — —
25 3.00 4.95 — 2.68 4.42 — 2.29 3.78 — 2.36 3.90 —
35 2.88 4.75 — 2.52 4.16 — 2.12 3.49 — 2.18 3.60 —
50 2.47 4.07 — 2.20 3.64 — 1.93 3.18 — 1.99 3.28 —
70 2.15 3.55 — 1.49 3.12 — 1.24 2.59 — 1.29 2.70 —
95 1.53 3.21 — 1.31 2.75 — 1.12 2.34 — 1.18 2.48 —
120 1.38 2.88 — 1.17 2.45 — 1.01 2.11 — 1.12 2.34 —
150 1.26 2.63 — 1.05 2.19 — 0.737 1.95 1.07 1.01 2.10 —
185 1.14 2.38 — 0.767 2.03 1.11 0.652 1.72 0.944 0.715 1.89 1.03
240 0.791 2.09 1.14 0.675 1.78 0.976 0.590 1.55 0.855 0.625 1.64 0.905
300 0.726 1.92 1.05 0.619 1.63 0.896 0.409 1.37 0.755 0.577 1.52 0.836
400 0.627 1.65 0.908 0.428 1.43 0.791 0.377 1.26 0.697 0.384 1.28 0.710
500 0.421 1.41 0.778 0.379 1.27 0.701 0.245 1.04 0.581 0.358 1.19 0.662
630 0.376 1.25 0.695 0.264 1.13 0.627 0.214 0.910 0.507 0.241 1.03 0.571
NOTE 1 — The resistance of armour for single core cables has not been covered, since such cables are generally
armoured with non-magnetic materials ( see 13.2 ).
NOTE 2 — The resistance of the armour may be measured at room temperature and corrected to 20ºC by means of
correction factors given in IS : 10810 (Part 42) - 1984 ‘Methods of test for cables: Part 42 Resistivity test of armour wires
and strips and conductance test of armour (wires/strips)’.
14.3 Thickness of Outer Sheath sheath. The thickness of such extruded sheath shall not
be less than the sum of the inner sheath thickness
14.3.1 Unarmoured Cables — The average specified in Table 5 and the nominal outer sheath
thickness of PVC outer sheath of unarmoured thickness specified in col 3 of Table 8 and the smallest of
cables shall be not less than the nominal value the measured values shall not be less than the sum of
specified under col 3 of Table 8 and the smallest the inner-sheath thickness specified in Table 5 and the
minimum value of outer-sheath thickness specified in
of the measured values shall not be less than col 4 of Table 8.
the minimum value specified in col 4 of Table 8.
NOTE — In case of multi-core unarmoured cables, it is 14.3.2 Armoured Cables — The thickness of
permissible to supply the inner and outer sheaths in a outer sheath shall be not less than the
single extrusion out of the material intended for outer minimum values specified in col 5 of Table 8.
7
IS : 7098 (Part 1) - 1988
SECTION 4 TESTS
a) Tests on conductor
i) Annealing test (for copper) IS : 8130-1984† 1
ii) Tensile test (for aluminium) IS : 8130-1984† 2
iii) Wrapping test (for aluminium) IS : 8130-1984† 3
iv) Resistance test IS : 8130-1984† 5
b) Tests for round steel wire/formed steel
wire (strip) armour:
1) Dimensions 13.3 of Part 36 of
IS 7098 (Part 1) IS 10810
2) Physical tests on round/formed wire:
i) Tensile strength 13.6(a) of Part 37 of
IS 7098 (Part 1) IS 10810
ii) Elongation at break 13.6(b) of Part 37 of
IS 7098 (Part 1) IS 10810
iii) Torsion test for round wires 13.6(c) of Part 38 of
IS 7098 (Part 1) IS 10810
iv) Winding test for formed wires 13.6(d) of Part 39 of
IS 7098 (Part 1) IS 10810
v) Uniformity of zinc coating 13.6(e) of Part 40 of
IS 7098 (Part 1) IS 10810
vi) Mass of zinc coating 13.6(f) of Part 41 of
IS 7098 (Part 1) IS 10810
vii) Resistivity 13.6(g) of Part 42 of
IS 7098 (Part 1) IS 10810
c) Test for thickness of insulation and sheath 9, 12 and 14 6
Tables 2, 4 and 6
d) Physical tests for insulation
i) Tensile strength and elongation at break Table 1 7
ii) Ageing in air oven Table 1 11
iii) Hot set test Table 1 30
iv) Shrinkage test Table 1 12
v) Water absorption (gravimetric) Table 1 33
e) Physical tests for out sheath
i) Tensile strength and elongation at break IS : 5831-1984§ 7
ii) Ageing in air oven IS : 5831-1984§ 11
iii) Loss of mass in air oven IS : 5831-1984§ 10
iv) Shrinkage test IS : 5831-1984§ 12
v) Hot deformation IS : 5831-1984§ 15
vi) Heat shock test IS : 5831-1984§ 14
vii) Thermal stability IS : 5831-1984§ ||
f) Insulation resistance (volume resistivity test) Table 1 43
g) High voltage test 16.2 45
h) Flammability test 16.3 53
8
IS : 7098 (Part 1) - 1988
Over Up to and Including Nominal Minimum
(1) (2) (3) (4) (5)
mm mm mm mm mm
— 15 1.8 1.24 1.24
15 25 2.0 1.40 1.40
25 35 2.2 1.56 1.56
35 40 2.4 1.72 1.72
40 45 2.6 1.88 1.88
45 50 2.8 2.04 2.04
50 55 3.0 2.20 2.20
55 60 3.2 2.36 2.36
60 65 3.4 2.52 2.52
65 70 3.6 2.68 2.68
70 75 3.8 2.84 2.84
75 — 4.0 3.00 3.00
*Fictitious calculation method for determination of dimensions of protective coverings of cables: Part 1 Elastomeric and
thermoplastic insulated cables.
15.1.1 The following shall constitute additional type tests for cables with improved fire performance
as per the categories given in Appendix A:
Category Test For Requirements For Test Method
Refer Refer Part No. of
IS 10810
01 No additional tests
C1 a) Oxygen index test 16.9 58
b) Flame retardance test on 16.10 61
single cable
c) Flame retardance test on 16.11 62
bunched cables
d) Temperature index 16.14 64
C2 a) Oxygen index test 16.9 58
b) Flame retardance test on 16.10 61
single cable
c) Flame retardance test on 16.11 62
bunched cable
d) Test for specific optical 16.12 Under consideration
density of smoke
e) Smoke density 16.15 63
f) Test for halogen acid gas 16.13 59
evolution
g) Temperature index 16.14 64
NOTES
1. For category C1, tests (a) and (d) are to be performed on samples taken from outer sheath, as applicable, and
prepared in the manner given in the relevant test method.
2. For category C2, tests (a), (e), (f) and (g) are to be performed on samples taken from outer sheath, as applicable, and
prepared in the manner given in the relevant test method.
15.2 Acceptance Tests — The following shall 15.2.1 The following shall constitute additional
constitute acceptance tests: acceptance tests for cable with improved fire
a) Annealing test (for copper), performance as per the categories given in
b) Tensile test (for aluminium), Appendix A:
c) Wrapping test (for aluminium), Category Test
d) Conductor resistance test, 01 No additional tests
e) Test for thickness of insulation and sheath,
f) Hot set test for insulation, C1 a) Oxygen index test
g) Tensile strength and elongation at break b) Flame retardance test on single
test for insulation and sheath, cable
h) High voltage test, and C2 a) Oxygen index test
j) Insulation resistance (volume resistivity) b) Flame retardance test on single
test. cable
9
IS : 7098 (Part 1) - 1988
c) Test for specific optical density of measured at the front and rear of the cable
smoke assembly.
d) Test for halogen acid gas evolution NOTE — Requirements for this test are split in 3
categories that is, A, B, and C as described in IS 10810
15.2.2 A recommended sampling plan for (Part 62). For the purpose of this standard, category B
acceptance tests is given in Appendix B. and C test methods shall be used. In the absence of any
15.3 Routine Tests — The following shall special requirements for method B, method C shall be
used for both the categories C1 and C2.
constitute routine tests:
a) Conductor resistance test, 16.12 Test for Specific Optical Density of Smoke
b) High voltage test, and Under consideration.
c) Resistance test for armour (for mine cable 16.13 Test for Halogen Acid Gas Evolution
only).
The level of HCl evolved shall not exceed 20
15.4 Optional Tests — The following shall
percent by weight.
constitute optional tests:
a) Cold bend test for outer sheath (IS : 16.14 Test for Temperature Index
5831-1984* and Part 20 of IS : 10810†); The measured value of temperature index shall
b) Cold impact test for outer sheath (IS : be 21 at a temperature of 250ºC.
5831-1984* and Part 21 of IS : 10810†); and
16.15 Smoke Density Test
c) Resistance test for armour (other than
mining cable) (Table 7). Under consideration.
16. DETAIL OF TESTS SECTION 5 IDENTIFICATION, PACKING
16.1 General — Unless otherwise stated in AND MARKING
this standard, the tests shall be carried out in
accordance with appropriate parts of 17. IDENTIFICATION
IS : 10810†, taking into account additional 17.1 Manufacturer’s Identification — The
information given in this standard.
manufacturer shall be identified throughout the
16.2 High Voltage Test length of the cable by means of a tape bearing the
16.2.1 High Voltage Test at Room Temperature manufacturer’s name or trade-mark, or by
( Type, Acceptance and Routine Test ) — The manufacturer’s name or trade-mark being
cables shall withstand a voltage of 3 kV ac (rms) indented, printed or embossed on the cable. In
at a frequency of 40 to 60 Hz or a dc voltage of case none of these methods can be employed, or
7.2 kV, between conductors and between if the purchaser so desires, colour identification
conductors and ECC (if any) for a period of 5 threads in accordance with a scheme to be
minutes for each test connection. approved by the Bureau of Indian Standards
16.3 Flammability Test — Period of burning (BIS) shall be employed. The indentation,
after removal of the flame shall not exceed 60 printing or embossing shall be done only on the
seconds and the unaffected (uncharred) portion outer sheath.
from the lower edge of the top clamp shall be at
least 50 mm. 17.2 Cable Identification — In order to
distinguish these electric cables from telephone
16.9 Oxygen Index Test
cables, the word ‘electric’ shall be indented,
The test on samples of inner/outer sheath shall printed, or embossed throughout the length or
be done at 27 ± 2ºC. The oxygen index shall not the cable. In case of cables intended for use in
be less than 29. mines, the word ‘mining’ also shall be indented,
16.10 Flame Retardance Test on Single Cables printed or embossed throughout the length of the
After the test, there should be no visible damages cable. The indentation, printing or embossing
on the test specimen within 300 mm from its shall be done only on the outer sheath.
upper end. Mark from mixing devices, soot or
17.2.1 The following special cables shall be
changing of the colour are not considered
damages. identified by indenting, embossing or printing
the appropriate on the outer sheath throughout
16.11 Flame Retardance Test on Single Cables the cable length, in addition to the existing
After burning has ceased, the cables should be marking requirements:
wiped clean and the charred or affected portion
should not have reached a height exceeding Type of Cables Legend
2.5 m above the bottom edge of the burner, Improved fire performance for FR
category C1
*Specification of PVC insulation and sheath of electric
cables ( first revision ). Improved fire performance for FR-LSH
†Methods of test for cables. category C2
10
IS : 7098 (Part 1) - 1988
17.3 Cable Code — The following code shall b) Manufacturer’s name or trade-mark;
be used for designating the cable: c) Type of cable and voltage grade;
Sl No. Constituent Code Letter d) Number of cores;
i) Aluminium conductor A e) Nominal cross sectional area of conductor;
ii) XLPE insulation 2X f) Cable code;
iii) Steel round wire armour W g) Length of cable on the drum;
iv) Non-magnetic round wire armour Wa h) Number of lengths on the drum (if more
than one);
v) Steel strip armour F
j) Direction of rotation of drum (by means of
vi) Non-magnetic strip armour Fa
an arrow);
vii) Double steel strip armour FF
k) Gross mass;
viii) Double steel round wire armour WW m) Country of manufacture; and
ix) PVC outer sheath Y n) Year of manufacture.
NOTE — No code letter for conductor is required when
the conductor material is copper. 18.2.1 The cable (drum or label) may also be
marked with the Standard Mark.
18. PACKING AND MARKING NOTE — The use of the Standard Mark is governed by
18.1 The cable shall be wound on a drum ( see the provisions of the Bureau of Indian Standards Act
IS : 10418-1982* ) and packed. The ends of the 1986 and the Rules and Regulations made thereunder.
The Standard Mark on products covered by an Indian
cable shall be sealed by means of non-hygrosopic Standard conveys the assurance that they have been
sealing material. produced to comply with the requirements of that
18.2 The cable shall carry the following infor- standard under a well defined system of inspection,
testing and quality control which is devised and
mation either stencilled on the drum or supervised by BIS and operated by the producer.
contained in a label attached to it: Standard marked products are also continuously
checked by BIS for conformity to that standard as a
a) Reference to this Indian Standard, for further safeguard. Details of conditions under which a
example, Ref IS : 7098 (Part 1); licence for the use of the Standard Mark may be granted
to manufacturers or producers may be obtained from
*Specification for drums for electric cables. the Bureau of Indian Standards.
APPENDIX A
( Clause 0.4, 0.5, 1.5, 15.1.1 and 15.2.1 )
11
IS : 7098 (Part 1) - 1988
APPENDIX B
( Clause 15.2.2 )
SAMPLING OF CABLES
12
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.