Download as pdf or txt
Download as pdf or txt
You are on page 1of 37

MINISTRY OF EDUCATION OF YOUTHS

AND SPORTS

INSTITUTE OF TECHNOLOGY OF CAMBODIA


DEPARTMENT OF INDUSTRIAL AND MECHANICAL

FINAL YEAR THESIS

Tittle: Designing, Installation and Testing of VRF System

Students : TITH Sopheara and VENG Socheat


Specialty : Mechanical engineering
Advisor : Mr. KHOUN Rithymean
Academic Year : 2016- 2017
1
Contents
I. General Introduction
II. Definition
III. Panasonic VRF system
IV. Load calculation
V. Selection
VI. VRF system installation
VII. Testing and Commissioning
VIII.Conclusion

2
I. General Introduction
 Presentation of Internship
• From: 20 February to 20 May 2017
• Company: Comin Khmere
• Position : MVAC trainee
• Project: TK Royal One (Cambodia)

3
II. Definition
What is VRF systems?
• Variable refrigerant flow vary the flow of refrigerant to
indoor units based on demand. There are 2 types of VRF
system, heat pump and heat recovery system.

4
II. Definition
What is VRF Heat pump ?
• VRF heat pump provide heating or cooling but not
simultaneous heating and cooling

5
II. Definition
What is VRF heat recovery?
• VRF heat recovery can operate simultaneous in
heating or cooling mode.

6
III. Panasonic VRF System
Variable refrigerant flow (VRF) is an air-conditioning system
configuration where there is one outdoor unit and multiple
indoor units.

7
III. Panasonic VRF System
1. Outdoor unit

The outdoor unit of VRF


system, sometimes called the
outside unit or condenser.

(Carin, 2016)

8
III. Panasonic VRF System
DC twin rotary compressor:
The component of compressor are:
1. Electric motor
2. Compression mechanism
3. Accumulator
The compressor is the heart of the
refrigeration cycle.

(Bhatia, 2014)

9
III.Panasonic VRF System
a. 2-WAY Mini-FSV LE1 Series
 Use for cooling or heating mode only
Capacity range from 4HP to 6HP
COP: 4.21 in case of 4 HP
 Cooling operation possible up to 46 °C
And low as -20 °C for heating mode
 Max connectable 9 units with length 150m

(Hiong, 2016-2017)

10
III.Panasonic VRF System
b. 2-WAY FSV-EX ME2 Series
 Use for cooling or heating mode only
 Capacity range from 8HP to 80HP
 Operation temperature as high as 52°C
for cooling and as low as -20 °C for
heating mode
 Max connectable 64 units with max
length 1,000m

(Hiong, 2016-2017)

11
III.Panasonic VRF System
c. 3-WAY FSV MF2 Series
 Using for simultaneous heating and cooling
 Capacity range from 8HP to 42HP
 Temperature operation as high as 46°C for
cooling and as low as -20 for heating
 Max connectable 52 units with pipe length
up to 500m

(Hiong, 2016-2017)

12
III.Panasonic VRF System
2. Indoor unit
There are many types of indoor units such as:
• F2 type : Cooling Capacity 2.2kW to 16kW

• M1 type : Cooling Capacity 2.2kW up to 5.6kW

• Z1 type : Cooling Capacity 2.2kW to 7.3kW

• E2 type : Cooling Capacity 18kW to 28kW

13
III.Panasonic VRF System
2. Indoor unit
• E1 type : Cooling Capacity 7.3kW to 28kW

• U1 type : 4-way cassette, Cooling Capacity 2.2kW to 16kW

• Y2 type : 4-way mini cassette, Cooling Capacity 2.2kW to 5.6kW

• L1 type : 2-way cassette, Cooling Capacity 2.2kW to 7.3kW

• D1 type : 1-way cassette, Cooling Capacity 2.8kW to 7.3kW

• P1 type : Floor standing, Cooling Capacity 2.2kW to 7.3kW

14
IV.Load Calculation
 Feature of the Building TK Royal One

http://www.cambodiancondos.com/condo-developments/tk-royal-one/ 15
IV. Load Calculation
1. Estimate Method
Q=S.R
• Q: Total heat load [Btu.h-1]or [W]
• S: room area [m2]
• R: The rate of cooling [Btu.h-1.m-2]

Calculation total heating load for TKR1 “ Reception


room’’ which has S = 62.4 m2
• R = 900 Btu.h-1.m-2
Thus, Q = 56160 Btu.h−1 =16.45kW

16
Another room calculate by Estimate method
AREA Ratio Cooling Capacity
Items Type of Room
m² Btu/h.m2 kW Btu/h
1 Conference Hall 265.45 1200 93.36 318540
2 Break Room 49.07 750 10.78 36802
3 Coffee Shop 73.6 1300 28.04 95680
4 Financial Office 98.14 850 24.48 83419
5 Hall 35.5 700 7.28 24850
6 Office 56.5 850 14.07 48025
7 Meeting Room 31.95 900 8.40 28755
8 Service Counter 36.8 1300 14.02 47840
9 Shop 87.7 800 20.56 70160
10 Toilet 38 500 5.56 19000

17
IV. Load Calculation
2. Manual Method
The Manual Method is the method used to calculate the cooling load
of the building space with minimum errors.
Total heating load:
QT = QS + Q L [W]
oTotal sensitive loads

QS = QStr + QSRm +QSRv +QSoc +QSecl +QSequip

oTotal latent loads

QL = QLr + QLoc +QLequip

18
IV.Load Calculation
Calculation heating load for TKR1 “ Reception Area’’
oTotal sensitive loads
QS = 14445.26 W

oTotal latent loads


QL = 1197.58W

Total heating load:


QT= 14445.26 W + 1197.58W = 15642.84 W = 15.64 kW

19
IV.Load Calculation

Verify the cooling capacity coefficient R [Btu/h.m2]:


• Manul method: R= 53367Btu.h−1 / 62.4 m2 = 855 Btu.h−1
• Estimate method: R = 900 Btu.h−1

From the calculation above by manual method, we see that


error of cooling rate approximate 5 % compared to
estimation method

20
V. Selection
1. Selection indoor unit
The total cooling load required is 109.8 kW

(Hiong, 2016-2017) 21
V. Selection
The characteristic of outdoor unit model U-40ME2R8
are:
• Cooling capacity 113 kW
• Using with power supply 400/415 V/3-phase/50 Hz
• Electrical rating for cooling option: 57.3 A
• Refrigerant amount at shipment: 22.0 kg
• Air flowrate: 48600 m3 h-1

22
V. Selection
2. Selection indoor unit
 For Conference Hall of TKR1:

The requirement of cooling load is 93.36 kW.


Catalogue of model mid static duct E1 type chosen that
Its cooling capacity from 7.3 kW to 28 kW.
E1 type is a kind of saving energy, the power input
45% less (compared to H1 type)
4 of S-224ME1E5 were chosen: Cooling capacity 4 ×
22.4kW = 89.6kW
23
V. Selection

(Hiong, 2016-2017)
24
VI.VRF System Installation
1. Air duct installation 2. Indoor unit installation

25
VI.VRF System Installation
3. Copper pipe installation

26
VI.VRF System Installation
4. Drainage water pipe installation

27
VI.VRF System Installation
5. Outdoor unit installation

28
VII. Testing and Commissioning

Before we start operation VRF, we have to:

1. Test refrigerant pipe

2. Adding refrigerant

3. Check at main power on

4. Testing and commissioning

29
1. Test refrigerant pipe

a. Check for any leakage in the b. Perform vacuum drying to


refrigerant piping remove all moisture

30
2. Adding refrigerant
• Keeping the valve of the outdoor

unit closed

• If the specified amount of

refrigerant cannot be charged, fully

open the valves of the outdoor unit

at liquid and gas sides, operate the

air conditioner in COOL mode

31
3. Check at main power on
Check on the outdoor unit
Check on the setting indoor unit

a. Check ON the rotary switches of b. Check ON the setting indoor unit


outdoor unit

32
4. Testing and commissioning
• Incoming supply for outdoor phrase sequence for 3 phases,
Incoming Voltage (380~415V).
• Incoming voltage for Indoor 220~240V and ensure power supply all
Indoor unit is turn "ON".

• Once all the setting is set and check, then start addressing the system
by short-circuit pin CN-30

33
 Start addressing the system by short-circuit pin CN-30
 Normal USB Printer  Panasonic Flash Writer – 8F000900210 / Part Code – 6233214375

Wire  To be purchase from Panasonic

Laptop - Window 7 professional – 32


or 64 bits operation system

(Oudom, 2017) 34
a. Indoor fan speed and temperature. b. Outdoor Compressor temperature,
Gas temperature and etc.

OUTDOOR Screen
INDOOR Screen

(Oudom, 2017)
 After the result have to be printed out by manufacture and to be attached in
Testing and Commissioning form for VRF recording.

35
VIII. Conclusion
• The calculation cooling load by estimation and manual
seem a litter bit difference value. The selection of the
systems that suitable for reception area and conference
hall is outdoor unit model U-40ME2R8 which maximum
cooling capacity is 113 kW.
• To get the best result of VRF system, we have to
understand about plan and condition for installation of
indoor unit, outdoor unit, air duct, copper pipe, and
drainage water pipe.
• VRF testing and commissioning is a part which we use
the method statement to carry on indoor unit, outdoor unit
operation after installation.

36
Thank you for your
attention!!!
Thank You For Your
Question? Attention !

Q&A
37

You might also like