LEGENDS & SYMBOLS

A 2Core,18AWG Shielded Cable


B 4Core,22AWG Individually Shielded Cable
1-Run Cable
2-Runs Cable
TH
Wall/Space mount Humidity & Temperature Sensor
DPT
Air Differential Pressure Transmitter

DI RET DI DI RET DI DI RET DI DI RET DI


DI RET DI DI RET DI DI RET DI DI RET DI
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan On/Off Status-1 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan HOA Status-2 Air differential pressure switch

1 2 3 4 5 6 78
9 10 11 12 13 14 15 16
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan On/Off Status-2 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan HOA Status-3 MD Motorized Damper Actuator
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan On/Off Status-3 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan HOA Status-4
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan On/Off Status-4 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan HOA Status-5
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan On/Off Status-5 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan HOA Status-6
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan On/Off Status-6 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan HOA Status-7
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan On/Off Status-7 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Trip Status-1
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan HOA Status-1 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Trip Status-2

CLIENT :

ASPIRE ZONE
FOUNDATION

DI-16 (I/O MODULE # 1) END USER:

ASPIRE
KATARA
HOSPITALITY

PROJECT MANAGEMENT:

PROJACS
CONSULTANT

CONTRACTOR:

ALI BIN ALI


CONTRACTING

DESIGN CONSULTANT:

DI RET DI DI RET DI DI RET DI DI RET DI


DI RET DI DI RET DI DI RET DI DI RET DI

FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Trip Status-3 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Proof of airflow-4 (4701070)

1 2 3 4 56 7 8
9 10 11 12 13 14 15 16

FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Trip Status-4 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Proof of airflow-5 (4701070)
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Trip Status-5 FAF-UB-1 Fan Proof of airflow (4701070) MEP CONTRACTOR:

FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Trip Status-6 FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Proof of airflow-7 (4701070)
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Trip Status-7 FAF-UB-1 to 2, EAF-UB-1 to 3: Fire Alarm Status
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Proof of airflow-1 (4701070) Incoming Lighting circuit Open/Close Status
FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Proof of airflow-2 (4701070) Lighting circuit power fail status BMS SPECIALIST:

FAF-UB-1 to 2, EAF-UB-1 to 3: Fan Proof of airflow-3 (4701070) Outgoing Lighting circuit On/Off status-1

PROJECT NAME:
SNAN FOOD HALL-N4,
COMMERCIAL PLAZA (ORANGERIE)
LOCATION: PIN NO.

DRAWING TITLE:

DI-16(I/O MODULE # 2) DDCP-B-1


FIELD DEVIE WIRING DETAILS

Project No. Discipline Date Scale Stage Originator

NOV. 14, 2019 NTS

Format Drawn Checked Approved

RAB DRD TK

Drawing No. Sheet No.