Nama : Sony Adyatama

NIM : I0717039

1. GAUSS-SEIDEL (MAXITER 2)

maxiter =

Ybus =

1.0667 - 4.9700i 0.0000 + 0.0000i -0.6667 + 2.0000i -0.4000 + 1.2000i 0.0000 + 0.0000i

0.0000 + 0.0000i 0.8333 - 3.8800i -0.5000 + 1.5000i 0.0000 + 0.0000i -0.3333 + 1.0000i

-0.6667 + 2.0000i -0.5000 + 1.5000i 2.9842 -17.5110i -1.1765 + 4.7059i -0.6410 + 3.2051i

-0.4000 + 1.2000i 0.0000 + 0.0000i -1.1765 + 4.7059i 2.2175 -13.9310i -0.6410 + 3.2051i

0.0000 + 0.0000i -0.3333 + 1.0000i -0.6410 + 3.2051i -0.6410 + 3.2051i 1.6154 -11.2803i

WARNING: Iterative solution did not converged after 2 iterations.

Press Enter to terminate the iterations and print the results

ITERATIVE SOLUTION DID NOT CONVERGE

Maximum Power Mismatch = 3.65813

No. of Iterations = 3

Bus Voltage Angle ------Load------ ---Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar Mvar

1 1.020 0.000 0.000 0.000 112.077 642.887 0.000

2 1.011 7.784 0.000 0.000 50.000 375.062 0.000

3 0.788 26.739 40.000 60.000 0.000 0.000 0.000

4 1.035 2.001 -60.000 -40.000 0.000 0.000 0.000


5 0.502 9.644 40.000 60.000 0.000 0.000 0.000

Total 20.000 80.000 162.077 1017.950 0.000

Line Flow and Losses

--Line-- Power at bus & line flow --Line loss-- Transformer

from to MW Mvar MVA MW Mvar tap

1 112.077 642.887 652.584

3 -50.816 204.116 210.347 15.049 229.550

4 -5.001 68.406 68.588 0.060 139.521

2 50.000 375.062 378.380

3 -25.389 137.977 140.293 6.800 156.725

5 15.484 108.135 109.238 8.629 95.959

3 -40.000 -60.000 72.111

1 65.865 25.434 70.605 15.049 229.550

2 32.189 18.748 37.251 6.800 156.725

4 146.495 58.765 157.842 24.775 522.028

5 52.846 173.320 181.198 7.468 182.318

4 60.000 40.000 72.111

1 5.061 71.116 71.296 0.060 139.521

3 -121.720 463.263 478.987 24.775 522.028

5 13.444 360.230 360.480 18.758 313.456


5 -40.000 -60.000 72.111

2 -6.855 -12.175 13.973 8.629 95.959

3 -45.378 8.998 46.262 7.468 182.318

4 5.314 -46.774 47.074 18.758 313.456

Total loss 81.539 1639.559


2. NEWTON-RAPHSON (MAXITER 2)

WARNING: Iterative solution did not converged after 2 iterations.

Press Enter to terminate the iterations and print the results

ITERATIVE SOLUTION DID NOT CONVERGE

Maximum Power Mismatch = 0.578985

No. of Iterations = 3

Bus Voltage Angle ------Load------ ---Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar Mvar

1 1.020 0.000 0.000 0.000 46.143 410.894 0.000

2 1.000 -61.778 0.000 0.000 50.000 310.792 0.000

3 0.125 -26.362 40.000 60.000 0.000 0.000 0.000

4 0.227 10.730 -60.000 -40.000 0.000 0.000 0.000

5 -0.132 -59.879 40.000 60.000 0.000 0.000 0.000

Total 20.000 80.000 96.143 721.686 0.000

Line Flow and Losses

--Line-- Power at bus & line flow --Line loss-- Transformer

from to MW Mvar MVA MW Mvar tap

1 46.143 410.894 413.477

3 73.065 296.955 305.812 55.176 282.745

4 27.337 167.929 170.140 25.472 148.486


2 50.000 310.792 314.788

3 34.049 221.347 223.950 40.598 206.091

5 38.165 168.038 172.317 42.702 184.064

3 -40.000 -60.000 72.111

1 -17.889 -14.210 22.846 55.176 282.745

2 6.550 -15.256 16.603 40.598 206.091

4 -8.879 2.611 9.255 2.579 27.110

5 -1.035 12.581 12.624 3.878 24.867

4 60.000 40.000 72.111

1 -1.865 -19.443 19.532 25.472 148.486

3 11.457 24.499 27.045 2.579 27.110

5 -5.113 30.089 30.521 5.696 39.931

5 -40.000 -60.000 72.111

2 4.537 16.026 16.656 42.702 184.064

3 4.913 12.286 13.232 3.878 24.867

4 10.809 9.842 14.618 5.696 39.931

Total loss 176.101 913.294


3. GAUSS-SEIDEL (MAXITER 100)

maxiter =

100

Ybus =

1.0667 - 4.9700i 0.0000 + 0.0000i -0.6667 + 2.0000i -0.4000 + 1.2000i 0.0000 + 0.0000i

0.0000 + 0.0000i 0.8333 - 3.8800i -0.5000 + 1.5000i 0.0000 + 0.0000i -0.3333 + 1.0000i

-0.6667 + 2.0000i -0.5000 + 1.5000i 2.9842 -17.5110i -1.1765 + 4.7059i -0.6410 + 3.2051i

-0.4000 + 1.2000i 0.0000 + 0.0000i -1.1765 + 4.7059i 2.2175 -13.9310i -0.6410 + 3.2051i

0.0000 + 0.0000i -0.3333 + 1.0000i -0.6410 + 3.2051i -0.6410 + 3.2051i 1.6154 -11.2803i

WARNING: Iterative solution did not converged after 100 iterations.

Press Enter to terminate the iterations and print the results

ITERATIVE SOLUTION DID NOT CONVERGE

Maximum Power Mismatch = 1.83292

No. of Iterations = 101

Bus Voltage Angle ------Load------ ---Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar Mvar

1 1.020 0.000 0.000 0.000 128.261 397.393 0.000

2 1.010 -49.041 0.000 0.000 50.000 212.677 0.000

3 0.522 19.850 40.000 60.000 0.000 0.000 0.000

4 0.374 -29.227 -60.000 -40.000 0.000 0.000 0.000

5 0.649 86.987 40.000 60.000 0.000 0.000 0.000

Total 20.000 80.000 178.261 610.070 0.000


Line Flow and Losses

--Line-- Power at bus & line flow --Line loss-- Transformer

from to MW Mvar MVA MW Mvar tap

1 128.261 397.393 417.579

3 -0.177 235.469 235.469 20.756 207.989

4 50.644 146.154 154.680 20.591 139.656

2 50.000 212.677 218.475

3 -32.262 233.587 235.805 45.604 244.017

5 4.199 220.294 220.334 79.450 317.572

3 -40.000 -60.000 72.111

1 20.933 -27.479 34.544 20.756 207.989

2 77.867 10.430 78.562 45.604 244.017

4 86.369 118.839 146.909 18.416 176.678

5 -91.014 110.356 143.046 27.590 253.091

4 60.000 40.000 72.111

1 -30.053 -6.498 30.747 20.591 139.656

3 -67.952 57.840 89.235 18.416 176.678

5 -53.919 116.220 128.119 49.687 341.536

5 -40.000 -60.000 72.111


2 75.251 97.278 122.987 79.450 317.572

3 118.604 142.735 185.581 27.590 253.091

4 103.606 225.315 247.994 49.687 341.536

Total loss 262.094 1680.539


4. NEWTON RAPHSON (MAXITER 100)

WARNING: Iterative solution did not converged after 100 iterations.

Press Enter to terminate the iterations and print the results

ITERATIVE SOLUTION DID NOT CONVERGE

Maximum Power Mismatch = 4.2313

No. of Iterations = 101

Bus Voltage Angle ------Load------ ---Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar Mvar

1 1.020 0.000 0.000 0.000 8.663 433.363 0.000

2 1.000 44880.077 0.000 0.000 50.000 361.991 0.000

3 0.227 26597.283 40.000 60.000 0.000 0.000 0.000

4 -0.321 82987.416 -60.000 -40.000 0.000 0.000 0.000

5 -0.095 40972.944 40.000 60.000 0.000 0.000 0.000

Total 20.000 80.000 58.663 795.354 0.000

Line Flow and Losses

--Line-- Power at bus & line flow --Line loss-- Transformer

from to MW Mvar MVA MW Mvar tap

1 8.663 433.363 433.449

3 89.461 279.009 293.000 50.092 271.495

4 23.559 156.246 158.012 19.764 134.759


2 50.000 361.991 365.428

3 14.233 236.533 236.961 47.550 229.938

5 42.859 158.224 163.926 37.476 167.929

3 -40.000 -60.000 72.111

1 -39.369 -7.514 40.080 50.092 271.495

2 33.317 -6.595 33.963 47.550 229.938

4 -25.777 21.813 33.767 7.195 67.455

5 1.714 32.044 32.090 6.429 42.233

4 60.000 40.000 72.111

1 -3.794 -21.486 21.819 19.764 134.759

3 32.972 45.643 56.307 7.195 67.455

5 -2.327 54.643 54.692 8.239 59.807

5 -40.000 -60.000 72.111

2 -5.383 9.705 11.098 37.476 167.929

3 4.715 10.188 11.226 6.429 42.233

4 10.566 5.165 11.760 8.239 59.807

Total loss 176.745 973.617