Professional Documents
Culture Documents
TTC-1000 Folleto PDF
TTC-1000 Folleto PDF
Transformer Temperature
Controller
DESCRIPTION
The Transformer Temperature Controller (TTC) is a full feature single or dual tem-
perature measurement and control device for the management of transformer
cooling and Load Tap Changer (LTC) conditioning monitoring applications. A signifi-
cant advantage of the TTC is it does not require calibration.
calibration Because the accuracy
is guaranteed over the entire temperature range, the temperature probes are inter-
changeable and can be installed up to 250 feet from the controller. There are no
maintenance items such as potentiometers or batteries. Just set it and go.
The TTC has four programmable output relays with Trip Duty rated form C con-
tacts. The built-in programmable scheme logic provides the ability to:
• Control Fans and Pumps
The TTC also includes an RS-232 communications interface for settings and status
that uses the terminal emulation software installed on your PC and does not require
special software. Setting files can be either uploaded or downloaded. There are
many additional features available including analog outputs and time stamped min/
max temperature display all with a Life Time Warranty at an affordable price and
now with DNP3.0 communications .
• Four independent temperature set points per temperature probe with settable
pickup and drop out temperatures for hysteresis.
• AUX CT input for winding hot spot temperature measurement based on top oil
temperature. Clip on CT provided.
• Minimum and maximum temperature display time stamped with date and
time.
• DNP3.0 Level 1 Communications, read all binary and analog outputs and com-
mand cooling remotely (optional).
• Dual optically isolated inputs for remote cooling control or reporting liquid level
or sudden pressure alarms through DNP3.0 (optional).
• Lifetime Warranty
GROUND
CONNECTION DIAGRAM
CTS
RTS
N/C
N/C
N/C
Rx
Tx
9
1
DB-9, RS-232
TTC-1000-XXX
TB4
DO/
2-Wire RS-485 1 RI
DNP 3.0 2 DO/
RI
Interface
COM
COM
TB3 TB1
REF
TMP
TMP
REF
TB2
12
11
10
10
12
11
9
1
COM
NC
+
+
NO
NO
NO
NO
COM
COM
COM
COM
NC
NC
NC
NC
-
Analog Output, A2 (optional)
Power In
38 to 160VDC or 120VAC
MOUNTNG
Probe #1
Temperature Probe
TTC-PROBE-01-XXX 7.00 5.00
Oblong
0.312 X 0.500
Lexan Window
12.75
Liquid-Tight
Cable Strain Reliefs
3.312
1/2 - NPT Cable Fitting 3/4 - NPT Cable Fittings
Ground Stud
1.500
1/4-20x1/2
0.000
0.000 1.750 3.500 5.25
SPECIFICATIONS
Power Supply Input Ope ra ting Range : 38 VDC to 160 VDC or 120 VAC +/- 10%, 3 Watts
Max.
O pe r a ting Te mpe r a tur e Ra nge : -35 °C to +85 °C, 95% Relative Humidity (non condensing)
Te mpe r a tur e M e a s ur e me nt Ra nge : 0 °C to +160 °C
LTC Diffe r e ntia l M e a s ur e me nt Ra nge : -20 to +20 °C
Te mper a tur e M ea s ur e me nt Accur a cy: Avg error over entire measurement range ± 1 °C.
Absolute error at any temperature ± 1.5 °C.
O utput Conta ct Ra ting: 30 amps make for 250 msec, 10 amps continuous at 250VAC.
O ptica lly Isolate d Inputs : Operates from 38 to 160VDC. External wetting voltage required.
Ala r m Conta ct Ra ting: 0.15 amp continuous at 160VDC
Ana log O utput: Selectable, 0 to 1 mA or 4 to 20 mA.
Maximum load 9,500 ohms (0 to 1mA), 450 ohm (4 to 20 mA).
Communica tions Inte r fa ce s : Front Panel Mounted RS-232 DB-9 Null Modem Interface
SCADA Inte r fa ce : DNP3.0 Level 1 Protocol using half duplex RS-485 interface.
AUX CT Input: 0 to 10A
Pa ne l M ount V e r s ion Dime ns ions : 5.32” W x 2.61” H x 6” D
N EM A 4 Enclos ur e V e r s ion Dime ns ions : 10” H x 6” W x 3” D
Sur ge Withsta nd/F as t Tr a nsie nt: Relay outputs and station battery inputs: ANSI C37.90.1
EM I Withs ta nd: ANSI C37.90.2
Die le ctr ic Withs ta nd: 3000 VDC for 10 seconds