DESCRIPTION
The Transformer Temperature Controller (TTC) is a full feature single or dual tem-
perature measurement and control device for the management of transformer
cooling and Load Tap Changer (LTC) conditioning monitoring applications. A signifi-
cant advantage of the TTC is it does not require calibration.
calibration Because the accuracy
is guaranteed over the entire temperature range, the temperature probes are inter-
changeable and can be installed up to 250 feet from the controller. There are no
maintenance items such as potentiometers or batteries. Just set it and go.

The TTC has four programmable output relays with Trip Duty rated form C con-
tacts. The built-in programmable scheme logic provides the ability to:
• Control Fans and Pumps

• Provide high temperature alarms

• Generate Trip signals

• Provide LTC Condition Alarm

• Periodic exercising of fan banks

The TTC also includes an RS-232 communications interface for settings and status
that uses the terminal emulation software installed on your PC and does not require
special software. Setting files can be either uploaded or downloaded. There are
many additional features available including analog outputs and time stamped min/
max temperature display all with a Life Time Warranty at an affordable price and
now with DNP3.0 communications .

Advanced Power Technologies


FEATURES

The TTC-1000 is an advanced microprocessor based transformer temperature con-


troller that contains a full compliment of programmable features:

• Dual universal temperature probes measure temperature from 0 to 160 °C,


Without Calibratio n.

• Contains no maintenance items and does not require calibration.

• Four independent temperature set points per temperature probe with settable
pickup and drop out temperatures for hysteresis.

• Built-in LTC condition monitoring. Mag mount probe available.

• AUX CT input for winding hot spot temperature measurement based on top oil
temperature. Clip on CT provided.

• Dual load pickup set points for transformer pre-cooling.

• Built-in fan bank alternate feature.

• Three independent time set points for daily fan exercising.

• Programmable scheme logic with four programmable form C relay outputs.

• Dedicated form B Device Alarm Relay with built in self check.

• Minimum and maximum temperature display time stamped with date and
time.

• DNP3.0 Level 1 Communications, read all binary and analog outputs and com-
mand cooling remotely (optional).

• Dual analog outputs programmable to 0 to 1 or 4 to 20 mA (optional).

• Dual optically isolated inputs for remote cooling control or reporting liquid level
or sudden pressure alarms through DNP3.0 (optional).

• Operates over a wide voltage range of 38 to 160 VDC or 120 VAC.

• Mounting available in a NEMA 4X enclosure, heater option available.

• Substation hardened to ANSI Fast Transient and Surge Withstand of C37.90.1


and RFI/EMI requirements of C37.90.2.

• Lifetime Warranty
GROUND
CONNECTION DIAGRAM

CTS

RTS
N/C

N/C

N/C
Rx
Tx
9

1
DB-9, RS-232

TTC-1000-XXX
TB4
DO/
2-Wire RS-485 1 RI
DNP 3.0 2 DO/
RI
Interface

COM

COM
TB3 TB1

REF
TMP
TMP

REF
TB2
12

11

10

10
12

11
9

1
COM
NC
+

+
NO

NO

NO

NO
COM

COM

COM

COM
NC

NC

NC

NC

-
Analog Output, A2 (optional)

Analog Output, A1 (optional)


CHASSIS WHT RED BLK Aux CT
OUT4 OUT3 OUT2 OUT1 ALARM Input (0-
GROUND
10A)

Power In
38 to 160VDC or 120VAC

WHT RED BLK


Probe #2 (optional)
Temperature Probe
TTC-PROBE-01-XXX

MOUNTNG

Probe #1
Temperature Probe
TTC-PROBE-01-XXX 7.00 5.00

Oblong
0.312 X 0.500

Lexan Window
12.75

Liquid-Tight
Cable Strain Reliefs

3.312
1/2 - NPT Cable Fitting 3/4 - NPT Cable Fittings

Ground Stud
1.500
1/4-20x1/2

0.000
0.000 1.750 3.500 5.25
SPECIFICATIONS
Power Supply Input Ope ra ting Range : 38 VDC to 160 VDC or 120 VAC +/- 10%, 3 Watts
Max.
O pe r a ting Te mpe r a tur e Ra nge : -35 °C to +85 °C, 95% Relative Humidity (non condensing)
Te mpe r a tur e M e a s ur e me nt Ra nge : 0 °C to +160 °C
LTC Diffe r e ntia l M e a s ur e me nt Ra nge : -20 to +20 °C
Te mper a tur e M ea s ur e me nt Accur a cy: Avg error over entire measurement range ± 1 °C.
Absolute error at any temperature ± 1.5 °C.
O utput Conta ct Ra ting: 30 amps make for 250 msec, 10 amps continuous at 250VAC.
O ptica lly Isolate d Inputs : Operates from 38 to 160VDC. External wetting voltage required.
Ala r m Conta ct Ra ting: 0.15 amp continuous at 160VDC
Ana log O utput: Selectable, 0 to 1 mA or 4 to 20 mA.
Maximum load 9,500 ohms (0 to 1mA), 450 ohm (4 to 20 mA).
Communica tions Inte r fa ce s : Front Panel Mounted RS-232 DB-9 Null Modem Interface
SCADA Inte r fa ce : DNP3.0 Level 1 Protocol using half duplex RS-485 interface.
AUX CT Input: 0 to 10A
Pa ne l M ount V e r s ion Dime ns ions : 5.32” W x 2.61” H x 6” D
N EM A 4 Enclos ur e V e r s ion Dime ns ions : 10” H x 6” W x 3” D
Sur ge Withsta nd/F as t Tr a nsie nt: Relay outputs and station battery inputs: ANSI C37.90.1
EM I Withs ta nd: ANSI C37.90.2
Die le ctr ic Withs ta nd: 3000 VDC for 10 seconds

TTC- 1000- w x y z ORDERING INFORMATION

Panel Mounting 0 4 form C Outputs, No inputs


NEMA 4X Enclosure 3 1 6 form C Outputs, No inputs
NEMA 4X w/Heater 4 2 4 form C Outputs, 2 inputs
3 6 form C Outputs, 2 inputs

No telemetry outputs 0 1 Single Probe


Single analog output 2 2 Dual Probe TTC- PROBE- 0 t -zzz
Dual analog output 3 3 AUX CT, Single Probe
RS485w/Dnp3 Level 1 5 4 AUX CT, Dual Probe

Universal Thermowell Probe 1


Magnetic Surface Mount Probe 2
Probe lead length, 10 to 250 ft

Advanced Power Technologies, LLC


Advanced Power Technologies 240 Dr. MLK Jr. Blvd
Newark, NJ 07102
Phone: (973) 621-6600
Fax: (973) 621-6625
web: www.advpowertech.com