siemens.com/power-technologies
“The project results covered all required aspects of the Terms of
Reference and contain important information for an improved net-
work protection system. We are looking forward to continue our
business relationship with Siemens PTI.”
Dr. Thomas Ansah, CEO at GRIDCo
All protection setting parameters were In this state-of-the-art approach, the · assessment of the performance of
collected in the field and imported into protection system performance is as- the existing protection system,
the system model. The zero-sequence sessed by simulation, and not only us- showing its specific characteristics,
and mutual coupling was amended to ing the classical approach of solely de- behavior, weak points and limita-
simulate single-phase faults with the picting setting values. The new meth- tions
highest possible accuracy. The model odology sets itself apart from the con-
· development of newly improved
building process was complemented ventional, and individual, evaluations
protection settings, grading rules,
with multi-level data plausibility checks of distance, differential and overcur-
scheme recommendations and an
for highest data quality. rent time relay characteristics by as-
under-frequency load shedding
sessing the combined ‘system’ re-
Scenario Building: To systematically scheme based on the review find-
sponse with all main and back-up pro-
assess protection system performance, ings. Validation of new settings by
tection relays in the power system.
a multitude of fault scenarios with var- simulation before approval
ying fault location, type and arc re- The quality of the protection system
· recommendations for the efficient
sistance were defined. performance is depicted by color-
future strategic development of the
coding that is meaningful for both
Simulation and Performance Assess- protection system
technical and non-technical staff. Re-
ment: Siemens PTI’s SIGUARD PSA (Pro-
sults can be aggregated for complete · knowledge transfer for staff
tection Security Assessment) solution
network regions or detailed for indi- through regular workshops and cus-
was used to simulate selectivity, sensi-
vidual power system components or tomized training
tivity and speed of the protection sys-
protection relays. This allows the iden-
tem. In each scenario, all stages of the It was demonstrated that the adapta-
tification of incorrect settings, weak-
entire fault clearance sequence were tion of protection settings can help in-
nesses and limitations of protection
simulated in detail. This provides deep crease system security and maximize
system.
insight into the protection system re- utilization of the existing system,
sponse for a given fault condition. All The high degree of automation ena- which in turn avoids CAPEX invest-
currents, voltages and impedances bles the efficient assessment of a very ment.
measured by protection devices are large number of fault scenarios and
available. complex system conditions, and mini-
mizes the individual treatment of spe-
Generation system stability was as-
cial cases.
sessed for the existing and newly pro-
posed and improved under-frequency Protection System Improvement:
load shedding schemes, taking into False or improvable protection settings
account different system configura- were corrected using a rule-based al- Published by
tions. In total, hundreds of thousands gorithm. The underlying protection Siemens AG 2017
of fault scenarios were simulated. The grading rules were improved by iterat-
results were automatically assessed ing simulation, assessment and setting
Energy Management Division
and visualized in a concise way with improvement until optimum results Freyeslebenstrasse 1
SIGUARD PSA. were reached. In this way, system-wide 91058 Erlangen, Germany
coordination and optimization of the
protection settings was achieved. In
For more information, please contact:
addition, the quality of the new protec- power-technologies.energy@siemens.com
tion settings is ensured before approv-
al. AL=N, ECCN=EAR99
Subject to changes and errors. The infor-
Key achievements mation given in this document only con-
The benefits of the systematic protec- tains general descriptions and/or perfor-
tion system review and improvement mance features which may not always
project were: specifically reflect those described, or
which may undergo modification in the
· complete data survey, documenta- course of further development of the
Figure 2: SIGUARD PSA protection performance
visualization (color code: red - fault not
tion and modeling of the power and products. The requested performance fea-
cleared, orange/yellow – over-/underfunction) protection system with validated tures are binding only when they are ex-
high quality
pressly agreed upon in the concluded con-
tract.