A1 Air Circuit Breakers

CONTENTS

For industrial and residential


Features A1-02
External & Internal Configuration A1-06
Basic Operation A1-08
Operating Condition A1-09
Rating A1-10
Trip Relay A1-12
Operating Characteristic & Ordering Information A1-16
ZSI(Zone Selective Interlocking) A1-18
OCR Trip Performance Curve A1-19
Control Circuit Diagram A1-23
Accessories A1-24
Dimension A1-27

For nuclear power plants


Features A1-30
Rating A1-32
Trip Relay A1-34
Performance Curve A1-35
External & Internal Configuration A1-36
Draw-out Location A1-37
Control Circuit Diagram & Accessories A1-38
Dimension A1-41
Certification A1-42
A1-02

Air Circuit Breaker for industrial and residential

VITZRO TECH Air Circuit Breaker is a circuit breaker that passed new

IEC standard (IEC60947-2, LV switch equipment and control equipment-

circuit breaker) and KS standard (KSC 4620) development tests. It is a

premium circuit breaker that is convenient to use with a design that enables

a short breaking time and maximum safety and protection functions.

Performance
It provides a stable image and an excellent
breaking performance.
The front part and mechanism part of the product
are molded using an insulator to increase the safety of
operators.
The reliability of the product is enhanced based on a
precise configuration and an excellent breaking
capacity.
It is easy to perform maintenance using an overheat
alarm function that detects the temperature of Busbar
(R, S, T, N).
It has a superior switch performance and an excellent
durability.
A1-03
Air Circuit Breakers

Easy Compact
It is easy to perform maintenance and the parts It ensures a sufficient space for customers using
are compatible. a compact and lightweight device.
The mechanism part and auxiliary device are It is a compact product that is optimized for package
modularized for easy maintenance. panel system.
An overheat burn prevention function is built-in An external size is reduced to 80% of the existing
through a Shunt Coil. product which allows loading of 3 LV boards.
The parts are closely connected which enables a
convenient maintenance of users.

Product Guide
Item Specification
Rated Current 630 ~ 4000A
Breaking Capacity 65 ~ 100kA
Operation Method Motor operation, Manual operation
Voltage AC400V, AC690V
Installing Method Draw-out Type, Fixed Type
Trip Method Multifunction Trip Under-voltage Trip, Shunt Trip
Number of Poles 3P, 4P
Standard IEC60947-2, KSC4620
A1-04

Air Circuit Breakers

VITZRO TECH Air Circuit Breaker is designed and manufactured to

maintain various systems and compatibility that more than meets the

requirements of customers. It provides a convenience by reducing the

working hours when newly installing or expanding the device. In addition, it is

equipped with an intelligent protective function and a high-precision option

protective function that provides the best convenience for users since it can

be used quickly and easily.


A1-05
Air Circuit Breakers

Intelligent Convenience
It is designed in a safe and convenient It enhanced the users’ convenience and safety.
configuration by applying an Intelligent Trip Device.
The terminal box of the control circuit is attached to
It is easy to distinguish a trip state using a LED of the the front part.
Intelligent Trip Device. A draw-out rail guide is tremendously improved for
an easy draw-out.
It satisfies the requirements of an intelligent control
center and automation system such as a remote It is equipped with an intelligent protection function,
measurement, a remote control and so forth since it a function to select the high-precision setting and a
has a standard RS485 communication interface of the reliable power supply.
Intelligent Trip Device. Its reliability is improved using the meter and
applying the highly-precise current detecting circuit.
It enhanced the reliability and convenience through
digitalization(conversational setting) and Korean
language support of over-current protective device.

It is easy to monitor in precision (indicating,


protecting, setting, breaking) from a low current (1A)
to a maximum current (4000A).
It is applied with a Shunt Coil overheat burn
prevention function that improved the reliability and
convenience.
A1-06
External & Internal Configuration

9
2

3
10 11

5 4

8 12 7 6

It is a premium product which the top ❶ Control Terminal


External Configuration ❷ Charge Handle
priority is the user’s safety.
It is designed considering various protective ❸ Rating Name Plate
functions, safety and convenience in order ❹ Charge/Discharge Indicator
❺ ON / OFF Indicator
to satisfy the diverse needs of customers.
❻ Draw-in/out Handle
Insertion Point
❼ Draw-in/out Indicator
❽ Draw-in/out Handle
❾ Trip Relay
❿ OFF Button
ON Button
Counter
A1-07
Air Circuit Breakers

10 11 12 13

5
14
15
6

16
8

❶ Upper Cover Moving Contact


Internal Configuration
❷ Control Terminal Fixed Contact
❸ Auxiliary Switch Cradle
❹ Closing/Trip Coil Clip
❺ Charge handle CB Connecting Conductor
❻ Mechanism Load Part Conductor
❼ Charge gear
❽ Front Mold cover
❾ Draw in/out Device
❿ Arc Chamber
A1-08
Basic Operation/Trip Method/Standards/Certification

Air Circuit Breaker is equipped with the following functions to safely use the
Basic Operation
CB wires so as to not only protect the loading part equipments, but also to
prevent accidents including fire and human damages.
Circuit Closing
A closing operation of mechanism provides the current to the load. When the current is
applied through the closing operation, some loads generate far larger inrush current
than the rated current (In). (That is, a motor becomes 7~8In for several seconds)
The closing should be operated promptly in order to prevent any damages (damages
due to Arc) due to this inrush current which is dangerous at the contact. If the circuit
breaker meets the standard, it should endure the current that is 15~20 times bigger
than the rated current and it should be opened quickly when failures occur during
closing or after closing.
Current Conducting
A current conducting within the rated current should not exceed the allowable
temperature and during an over-current conducting, the conducting should be safely
performed till the breaking time. Furthermore, if the circuit breaker is used for a
selective breaking, the downstream circuit breaker should be designed to endure a
high electromagnetic repulsion force so that it can allow a short circuit current during
the breaking time.
Circuit Opening, Current Breaking
A current breaking can be generated through an optional operation of mechanism
(through manual and remote control).
With the current conducting, the circuit breaker will be operated automatically using an
auxiliary trip device (under voltage trip device, ground trip device and etc) to open the
circuit safely.
Although the circuit breaker maintains the closing Position based on OCR when the
over-current is generated, it shall be automatically operated to open the circuit safely.
Isolation
When the circuit breaker is opened, it requires a Specific Isolation Level between the
Charge part and Discharge part.
Maximum Leakage Current Test between Input and Output under the rated voltage
(Max, Ue)
Impulse Voltage

When an over-current is generated in the above functions, there are the


Trip Method following circuit-breaking methods to apply.
Failure Breaking (Instantaneous Operation)
If an abnormal amount of current flows in the circuit due to a failure such as short-
circuit, ACB will instantly break the circuit to minimize the impact due to the failure.
This is called an instantaneous operation.
Delay Breaking
If an abnormal amount of current (for example, an inrush current of the transformer, an
inrush current of the condenser and a start electric current of the motor) flows in the
circuit, ACB maintains the current conducting state for a certain period of time and if
the abnormal current is maintained afterwards, the circuit will be broken. And, in case
of a short circuit current, the impact of the failure will be minimized during the delay
time set by customers considering the breaking time of the downstream circuit breaker
at the selective breaking. If the downstream circuit breaker fails to function and the
abnormal current is generated continuously, the circuit after the delay time will be
broken. This is called a delay breaking.
A1-09
Air Circuit Breakers

Overload Breaking (Time Delay)


If a current that exceeds the rated current flows continuously, the wire gets hot and if
neglected, it may result in fire. ACB will break the circuit before the temperature of wire
gets to a dangerous level. This is called an overload breaking.
Ground Fault Breaking
When a current flows from the circuit or charge part of load to the ground due to failures
such as contact or destruction of insulator, it is called a ground fault. When the ground
current flows, the current is induced to the neighboring cables due to an
electromagnetic induction and a dislocation climb will be generated which will impact or
even damage the other devices. If a person touches it, it may lead to casualties because
of an electric shock. To prevent these kinds of failures, the circuit is broken when the
grounding is generated and this is called a ground fault breaking.

VITZROTECH VIDER ACB is installed at the distribution line (1000V or under) to


Standards
protect the equipments by circuit-breaking under air status when fault currents
such as the over-current, short-circuit and ground fault are generated. It
prevents fire from occurring and protects people from getting hurt.
VITZROTECH ACB was tested to meet the following international standards and
it acquired the certificates, allowing it to be used safely and conveniently.
Acquisition of KS Standard(KSC 4620)
IEC 60947 - 1
Part 1 : General Rules Low - voltage switchgear and controlgear
IEC 60947 - 2
Part 2 : Circuit Breakers Low - voltage switchgear and controlgear
ACB has acquired the following certificates and these can be provided, if requested
appropriately.
CB Certificates (IEC 60947)
Test report (KEMA/KERI)

CE Certification Mark
Certification
CE Mark represents that all duties are met for the products manufactured according to
the EU instructions. CE Mark shows the decision of the manufacturer or the authorized
representative who complied with the suitable preparations including the product
evaluation process.
A1-10
Rating

Type V□-630 V□-800 V□-1000 V□-1250

Frame Size AF 630 80 1000 1250

Rated Current In A 200, 400, 630 800 1000 1250

Rated Insulation Voltage Ui V 1000

Rated Operational Voltage Ue V 690

690V/600V/550V kA 50
Rated Ultimate Short Circuit
500V/480V/460V kA 65
Breaking Capacity Icu
415V/380V/230V/220V kA 65

Rated Service Short Circuit Breaking Capacity Ics kA 100

Rated Short Time Witstand Current Icw, 1s kA 50

Number of Poles Poles 3P,4P

Mechanical Life Cycles 30,000


Endurance
Electrical Life Cycles 20,000

Fixed Type mm 316x300 / 411x300


Dimension WxD (3P/ 4P)
Draw-out Type mm 353x407 / 448x407

Fixed Type mm 41 / 53 41 / 53 41 / 53 43 / 55
Weight (3P/4P)
Draw-out Type mm 65 / 84 65 / 84 65 / 84 68 / 84
A1-11
Air Circuit Breakers

Type V□-1600 V□-2000 V□-2500 V□-3200 V□-4000

Frame Size AF 1600 2000 2500 3200 4000

Rated Current In A 1600 630,800,1000,1250,1600,2000 2500 2500, 3200 4000

Rated Insulation Voltage Ui V 1000

Rated Operational Voltage Ue V 690

690V/600V/550V kA 65 85

Rated Ultimate Short Circuit 500V/480V/460V kA 85 100


Breaking Capacity Icu
415V/380V/230V/220V kA 85 100

Rated Service Short Circuit Breaking Capacity Ics kA 100 100

Rated Short Time Witstand Current Icw, 1s kA 50 85

Number of Poles Poles 3P,4P

Mechanical Life Cycles 30,000


Endurance
Electrical Life Cycles 20,000

Fixed Type mm 376x300 / 492x300


Dimension WxD (3P/ 4P)
Draw-out Type mm 413x407 / 528x407

Fixed Type mm 43 / 55 45 / 58 48 / 62 59 / 77 65 / 83
Weight (3P/4P)
Draw-out Type mm 68 / 88 70 / 92 75 / 95 90 / 117 98 / 125
A1-12
Trip Relays

8.1 OCR Options


OCR (Over Current
Trip Relay) Type Type Normal-Type Standard-Type

Appearance

•L / S / I / G
Current Relay •L / S / I / G
•ZSI(Selective Breaking)
Additional Relay - •Leakage(Selectable)
Measurement Function - •Current(R/S/T/N)

•Overload Protective Relay:DOOutput


Pre Trip Alarm - (Alarm) PTAGround unavailable
when PTA is used
Communications - •Modbus/RS-485

•Self Power
- Power runs when 20% of the load
•Self Power current is In
Power - Power runs when 20% of - External power used during the
the load current is In communication
•AC/DC 110~220V
•DC24~48V

RTC Timer •Available •Available


•Long Time Delay
•Long Time Delay Trip •Short Time Delay/Instantaneous
Trip Display LED Time Delay
•Ground Fault
•10ea : Display Faults
Fault Record -
(Phase/Current/Date/Time)

Event Record - •10ea : Knob Setting

Operation Button - •Reset, S/I, LTD


Menu, Move, Enter
A1-13
Air Circuit Breakers

Overall Appearance & Part Names


Normal Type OCR
The state-of-the-art, high-speed 32Bit ARM MICRO CONTROLLER is used.
The current value can be checked; it displays the load factor and the line status can
be easily checked.
Depending on the rated current, it can be handled simply by changing the program.
It is easy to identify the faults by displaying the cause of trip.
(Long-time delay, short-time delay, instantaneous delay, low-voltage, unbalanced
current and overheating)

LED
Displays the trip data and overload
status

TRIP
When the current load is over 113%,
it flickers; when CB trips, it is turned
ON and when turned OFF, it is switched
off.
A1-14
Trip Relays

Overall External Configuration & Name


Standard Type
Overload Protection : Long Time Delay Protection
Short-Circuit Protection Short Time Delay & Instantaneous Delay Protection
lt On/Off Selection(Short Time Delay)
Ground Fault Protection lt On/Off Selection
ZSI(Zone Selective interlocking) Function enables easier interlocking for protection
Built-in with advanced MCU Basic measured current, high-precision measurement
Fault Recording Function 10 cases of fault type, fault phase, fault value and its
generated time
4 Digital Outputs (DO)
Communication Function Modbus/RS485

❶ LED
Indicator Trip data and Overload status
1 PTA(Pre Trip Alarm) : Overload Protective Relay DO Output
LTD(Long Time Delay) : Indicators Long Time Delay Relay Operation
STD/INST(Short Time Delay/Instant) : Indicators Short Time Delay &
2 Instantaneous Delay Operation
GFT/ELT: Indicators Ground Fault Operation
Alarm : Overload warning alarm (Turned On when 90% or more,
Flickering The full note cannot be seen)

❷ LED
3 Indicator measurement and data of each RSTN phase
4 ❸ Reset Key
5 Reset after OCR relay operation, Reset after Battery Check

❹ S/I
6
Isd : Short Time Delay Current Setting,
7
Tsd : Short Time Delay Time Setting,
8 li : Instantaneous Time Current Setting

❺ LTD
Ir : Long Time Delay Current Setting,
Tr : Long Time Delay Time Setting

❻ MENU
Initial screen, Move between setting menus
❼ Move Cursor
Move to Menu or Reset : Left/Right Move of screen cursor or setting
❽ Enter
Move to Lower Menu or Input Setting
A1-15
Air Circuit Breakers

Long-Time, Short-Time & Ground Fault Protection


OCR(Over Current Instantaneous Delay Protection
trip Relay)

Operating Characteristics
Long Time Delay Protection

Current Setting (A) Iu=Inx... 0.5 0.6 0.7 0.8 0.9 1


Tripping between 1.05 and 1.20×I1 Ir=Inx.. 0.80 0.83 0.85 0.88 0.90 0.93 0.95 0.98 1 OFF

Time delay(s) Tr@(1.5xIr) 12.5 25 50 100 200 300 400 500 600 750
Accuracy. ±15% Tr@(6xIr) 0.5 1 2 4 8 12 16 20 24 30
or below 100ms Tr@(7.2xIr) 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 21

Short Time Delay Protection

Current Setting (A) Isd=Irx... 1.5 2 2.5 3 4 5 6 8 10 OFF


Accuracy. ±15%

Time delay (s) Settings I2t off 0.5 0.1 0.2 0.3 0.4
@10xIr I2t on 0.1 0.2 0.3 0.4
Time delay(ms)at10xIr Tsd(max resettable time) 20 80 160 255 340
(I2t OffI2tOn) Tsd(max break time) 80 140 240 345 460

Instantaneous Delay Protection

Current Setting (A) Ii=Inx... 2 3 4 6 8 10 12 15 OFF


Accuracy. ±15%
Tripping time Max break time : 50ms
Ground Fault Protection

Current Setting (A) Ii=Inx... 2 3 4 6 8 10 12 15 OFF


Accuracy. ±15%

Time delay (s) I2t off 0.05 0.1 0.2 0.3 0.4
@1xIn I2t on 0.1 0.2 0.3 0.4
Tg(max resettable time) 20 80 160 255 340
Tg(max break time) 80 140 240 345 460
Leakage Protection (option)
Current Setting (A) Ig 0.5 1 2 3 5 10 20 30 OFF

Time delay (ms) Tg Alarm 140 230 350 800 950


Accuracy:±1 Time (ms)
A1-16
Operating Characteristics & Ordering Information

Long Time Delay


OCR
Characteristics •A function to protect overload
•Time delay that is inversely proportional to the fault current
Standard Current Setting Knop: lr
- Economic type & Standard type Setting Range, 6stages: (0.5~1.0)×ln
- lu : (0.5-0.6-0.7-0.8-0.9-1.0)×ln
- lr : (0.8-0.83-0.85-0.88-0.9-0.93-0.95-0.98-1.0-Off)×lu
Delay Tim Setting Knop : tr
- Operation Time Standard: Operation Time at 6xIr
- Setting Stages (9): 0.5-1-2-4-8-12-16-20-24-30 Off sec
Relay Pick-up Current
- Pick-up relay current:Relayed at current of (1.15)xIr or above
Calculation based on the biggest load current among R/S/T/N

Short Time Delay


•A function to protect fault current (over-current)
•Time delay and definite time that is inversely proportional to the fault current
Standard Current Setting Knop : lsd
- Setting Stage: (1.5-2-2.5-3-4-5-6-8-10-Off)×lr
Delay Time Setting Knop : Tsd
- Operation Time Standard: Operation Time at 10xIr
- Inverse Time (lt On) : 0.1-0.2-0.3-0.4sec
- Definite Time (lt On) : 0.05-0.1-0.2-0.3-0.4sec
Calculation based on the biggest load current among R/S/T/N
ZSI (Zone Selective Interlocking) Instantaneous relay operation under
protective interlocking when ZSI function is set

Instantaneous Time Delay


•A function to protect short-circuit
•When the fault current is above the set value, it shall be
dealt with within the shortest time possible to prevent accidents.
Standard Current Setting Knop : li
- Setting Range: (2-3-4-6-8-10-12-15-Off)×lu
Calculation based on the biggest load current among R/S/T/N
Overall breaking time shall be 50ms or under

Ground Fault Delay


•A function to protect ground fault
•When the ground current is above the set value, it shall be broken after the
time delay
Standard Current Setting Knop : Ig
- Setting Range: (0.2-0.3-0.4-0.5-0.6-0.7-0.8-1.0-Off)×ln
Delay Time Setting Knop : tg
- Inverse Time (lt On) : 0.1 - 0.2 - 0.3 - 0.4 sec
- Definite Time (lt On) : 0.05 - 0.1 - 0.2 - 0.3 - 0.4 sec
Ground Current = Vector Sum of R-Phase + S-Phase + T-Phase + N-Phase
ZSI (Zone Selective Interlocking) Instantaneous relay opera-
tion under protective interlocking when ZSI function is set
Ground Fault Protecting Function is included in the basic OCGR type
(CT Type built-in)
A1-17
Air Circuit Breakers

Leakage (GFT)
OCR
Characteristics •A function to protect leakage; optional function
•When the leakage current is above the set value, it shall be broken after the time delay
Standard Current Setting Knop : Ig
- Setting Range: 0.5-1-2-3-4-5-10-20-30-Off(A)
Leakage (GFT)
- Trip Time : 140-230-350-800ms
- Alarm Time : 140-230-350-800-950 ms
External CT used and exclusive for ZCT
Necessity of using external CT
- Internal CT Type (Basic Type): Ground Fault Protection Protect 20%~100%
of the ACB rated current
- In case of a large-capacity ACB, the ground fault operating current will also
increase, which requires no ground fault] protection function. For example,
in case of 4000A ACB, the minimum ground fault relay current is
4000A x 20% = 800A.
- Thus, an external CT shall be installed to control the ground sensitivity
current, and it is optional to protect the ground fault (leakage).

Ordering VABV S 20 06 4 D a1 1 Accessories


Information
Series 20 630A ~ 2000A No. of Poles Operation Mode(Voltage)
VIDER ACB 32 2500A ~ 3200A 3 3poles A1 AC220
40 4000A 4 4poles A2 AC110
D1 DC110

Type Rated Current Installing Method Installing Method


With Standard 06 630A F Fixed Type 0 None
S
Type OCR
08 800A D Draw-Out Type 1 OCGR Standard Type
With Normal 10 1000A S Shutter Type 2 OCGR Normal Type
N Type OCR
12 1250A 3 OCR Standard Type
E Without OCR 16 1600A 4 OCR Normal Type
20 2000A
25 2500A
32 3200A Option
40 4000A 1 UVT Under Voltage Trip
2 CTD Condenser Condenser Trip Device
3 KL Key lock Closing
4 PTA OCR External Contact (AL)
5 MI Mechanical Inter lock
6 PL Position lock
7 DC Front Dust Cover
8 LH Lifting hook
9 TS Temperature Sensor Monitoring Device
10 IB Phase-Phase Barrier Insulation
11 MIP Prevention of Erroneous Insertion
12 OT OCR Tester
A1-18
ZSI / OCR Trip Characteristic Curve

ZSI (Zone elective A Zone Selective Interlocking function is intended to protect the load
Interlocking) equipments when the fault current is generated. It minimizes the delay time
and reduces damages to the air circuit breaker and load equipments for the
safety.
An ACB that executes the ZSI outputs the ZSI signal in order for the lower level
equipment to delay the operation of the upper level equipment under a short-time
delay or a ground fault.
The OCR (Over-Current Relay) of the ACB located at the fault spot performs an
instantaneous trip without time delay to remove the fault.
The upper level ACB that received the ZSI fault signal performs an operation based
on theshort-time delay or groundfault delay time setting in the system set for
protection. However, the upper level ACB that did not receive the ZSI fault signal from
the lower level ACB will carry out an instantaneous trip without time relay.
For the ZSI to operate normally, the operating time for protection should be properly
set so that the lower level ACB precedes the upper level ACB when the over-
current/short-time/ground fault load signal is input.

ZSI Input

② ZSI Input
ZSI Output

In case of a Fault A
- ACB① independently performs the instantaneous trip.
In case of a Fault B
- ACB② performs the instantaneous trip and ACB① delays till the set time,
then perform the instantaneous trip.
- If ACB② cannot break the fault current (ZSI signal not output), ACB① performs
the instantaneous trip to protect the system.
A1-19
Air Circuit Breakers

OCR Trip Characteristic Curves Long Time Delay


Operating Time

Set Current
A1-20
OCR Trip Characteristic Curve

Short Time Delay


OCR Trip Characteristic Curves
Operating Time

Set Current
A1-21
Air Circuit Breakers

Instantaneous Time Delay, Ground Fault


OCR Trip Characteristic Curves
Operating Time

Rated Current
A1-22
OCR Trip Characteristic Curve / Control Circuit Diagram

Pre Trip Alarm(PTA)


OCR Trip Characteristics Curves
Operating Time

Set Current
Control Circuit
Wiring Diagram

57<7: +TW[QVO
5IQVKQZK]Q\ ,QOQ\IT\ZQXZMTIa )]`QTQIZaKWV\IK\[ +WUU]VQKI\QWV
+PIZOM +WQT
=><
<ZQX+WQT
Air Circuit Breakers
A1-23
A1-24
Accessories

Trip Coil(Shunt Coil: SHT)


Accessories
•Controller to trip CB externally
•Voltage is supplied to C1, C2 of both coil ends with voltage input at 200ms instantaneous time
•CB trip completed with the coil excited
Shunt Coil Rated Voltage & Characteristics
Rated Voltage(Vn) Operating Power Consumption(VA or W) Trip
DC(V) AC(V) Voltage Range(V) lnrush Steady-state Time(ms)

24~30 - 0.75 ~1.1Vn


48~60 48 0.75 ~1.1Vn
100~130 100~130 0.75 ~1.1Vn 200 5 40ms
200~250 200~250 0.75 ~1.1Vn
- 380~480 0.75 ~1.1Vn
* Note The available voltage range is the minimum rating range of each rated voltage (Vn)

Wire Specification
•Power consumption of about 200VA, rated voltage (Vn) DC 24~30(V), DC/AC 48(V) trip coil used
•Recommended maximum wire length
Rated Voltage(Vn)
Wire Type DC 24~30(V) DC/AC 48(V)
#16AWG(1.31㎟) #18AWG(0.823㎟) #16AWG(1.31㎟) #18AWG(0.823㎟)
Operating 100% 80m 45m 330m 200m
Voltage 85% 45m 27m 210m 120m

Closing coil(CC)
•Controller closed externally
•When the voltage is supplied to A1, A2 of both coil ends with voltage input at 200ms instanta
neous time
•CB closing is completed when the coil operates
Closing Coil Rated Voltage & Characteristics
Rated Voltage(Vn) Operating Voltage Range(V) Power Consumption(VA or W) Trip
DC(V) AC(V) Pick up Drop out lnrush) Steady-state Time(ms)

24~30 -
48~60 48
50ms or
100~130 100~130 0.65~0.85Vn 0.4~0.6Vn 200 5
under
200~250 200~250
- 380~480
* Note The operating voltage range is the minimum rating range of each rated voltage (Vn)

Wire Specification
•Power consumption of about 200VA, rated voltage (Vn) DC 24~30(V), DC/AC 48(V) trip coil used
•Recommended maximum wire length
Rated Voltage(Vn)
Wire Type DC 24~30(V) DC/AC 48(V)
#16AWG(1.31㎟) #18AWG(0.823㎟) #16AWG(1.31㎟) #18AWG(0.823㎟)
Operating 100% 30.5m 18m 155m 95m
Voltage 85% 25m 15m 135m 80m
A1-25
Air Circuit Breakers

Accessories Motor(M)
•External operating power is used to charge the CB closing spring
•Manual charging, if there is no external power
•Operating Voltage Range: Voltage 85%~110%
Input Power(V) DC 24~30V AC/DC 48~60V AC/DC 100~130V AC/DC 200~250V AC 380~480V
Motor Load Current 5A 3A 1A 0.5A 0.3A
Motor Rotation(RPM) 16,000~19,000 rpm
Insulated Withstand Voltage 2kV/min
Start Load Current(max.) Less than 5 times of the load current
Insulated Withstand Voltage 2kV/min
Operating Temperature Range -20℃~60℃
Durability 20,000 cycles (Load Continuous Operating Times : 2times/mi
Charge Time 5sec or more
Charge End Contact 15A at 250V AC

Under Voltage Trip device(UVT)


•CB tripping when it falls below the set voltage
•When the control power is not input, there is no electrical and mechanical closing of CB
•It is for instantaneous time operation, so when it shall be used for delay operation,
it shall be connected to UVT delay controller.
•It is used by inputting 65%~85% of the rated voltage to both ends (31,32) of UVT coil.
UVT Coil Rated Voltage & Characteristics
Rated Voltage(Vn) Operating Voltage Range(V) Power Consumption(VA or W) Delay
DC(V) AC(V) Pick up Drop out lnrush Steady-state Time(s)
48~60 48
100~130 100~130
0.65~0.85Vn 0.4~0.65Vn 200 5 1, 2, 3
200~250 200~250
- 380~480

Trip Alarm Contact(AL)


•When CB is tripped due to OCR (Over Current Relay), the control signal is output
and the fault information on the CB trip is provided (Auxiliary inside the CB)
•Previous CB information is output externally with the trip indicator device owing to the
fault current
•AL is operated only under the trip based on OCR and not operated when it is turned OFF
•In case of a manual reset CB, after the CB trip, the reclosing operation is done after the
AL(Alarm) switch is reset
•In case of an automatic reset CB, after the CB trip, the AL switch is reset when the remote
reset device is operated. Then, the trip alarm switch is operated during the trip operation.
Electrical Characteristics of Trip Alarm Contact
Standard Type High-Capacity
Type
Resistance Load Inductive Load Resistance Load Inductive Load
250V 10A 6A 10A 10A
AC 125V 10A 6A 10A 10A
Contact 250V 0.3A 0.3A 3A 1.5A
Capacity
125V 0.5A 0.6A 10A 6A
DC
125V 0.5A 0.6A 10A 6A
No. of Available Contacts Standard OFF-Charge Type, 4a4b
A1-26
Accessories / Dimension

Accessories

Manual Reset Button Fixed Bracket (Cradle Mounting Bracket)


•After the CB trip due to OCR, it is a configuration that enables •Mechanical mounting of CB body on the Cradle
to reset using a Reset Button •Bracket to fix the CB body at the connecting location
•MRB only operates under the trip owing to OCR, and does not •All draw-in/out is impossible when mounted
operate when CB is turned OFF
•Press MRB to reset the CB for CB reclosing after the trip Pad Lock/Position Lock
ACB is operated in position (CONNECTED, TEST,
Counter DISCONNECTED) when drawn-in/out. When the ACB body is
•A device to indicator the CB ON/OFF counts drawn-in/out within the cradle, the handle will be locked
without moving at an idle status.
Auxiliary Switch (Contact)
•LOCK is operated with the draw-in button popped out.
•A contact used to remotely monitor the CB ON/OFF status
•LOCK is cancelled by pressing the draw-in button in order to
Auxiliary Switch & Charge Method continue the draw-in/out operation.
AX Standard Type OFF Charge 3a3b •When the lock is used as shown in the picture, ACB body
cannot be drawn-in/out to/of the cradle.
AC Standard Type ON Charge 3a3b

BX Standard Type OFF Charge 4a5b


OCR Tester
BC Standard Type ON Charge 4a4b A device to test whether OCR trip relay operates normally
without power
Key Lock •Possible to input maximum of 17times the rated current
•A lock device used to prevent unauthorized operation of •Input each current, value, size and phase of R/S/T/N
certain CB, when using more than 2 CBs. Key Lock for •Frequency can be changed
preventing closing(ON)
•Testing long-time delay/short-time delay / instantaneous /
Lifting Hook ground fault protection functions

•A safety device used to easily move CB Dust Cover


•Used by attaching the hook to both handles of arc cover
•Installed by attaching to the door frame
Condenser Trip Device (CTD) •It is mounted on the distribution panel to cover the front part,
preventing dust from entering.
•A device for the CB trip within the set time when the control
•ACB can be seen since it is transparent and the cover can be
power of ACB is turned OFF. It is used by connecting to the
opened/ closed even when the ACB is drawn-out to the test
shunt coil.
position.
Rating
Rating Specification Temperature Sensor
Type CTD-100 CTD-200 •It detects and indicators the set temperature.
Rated Input Voltage(V) AC 100/110 AC 200/220 •When the temperature rises above the set temperature,
it will be indicatored by an alarm.
Available Trip Time within 2min within 1min
•It is sent via a basic RS-485 communication.
Charging Time within 5sec within 5sec

Condenser Capacity 400μF 160μF Phase-Phase Barrier


Frequency(Hz) 50/60 50/60 •Ensures the phase-phase clearance
Rated Charging Voltage( V) 140/155 280/310 •It prevents the phase-phase short circuit to be used safely.
Input Voltage Change 85~110 85~110
Range(%) Prevention of erroneous insertion
•A configuration to prevent the mismatching of cradle rating and
body rating
Safety Control Cover
•The assembling position shall differ depending on the rating.
•To protect control terminal and to prevent
damages due to the foreign substances
•Rating and Poles; 8 types
A1-27
Air Circuit Breakers

Draw-Out Type ACB (2000AF)


Dimension

3P 4P

Rated Current T(mm) W(mm)


1600A or under 15 60
2000A 20 60

Fixed Type ACB (2000AF)

3P 4P

Rated Current T(mm) W(mm)


1250A or under 10 50
1600A 15 60
2000A 20 60
A1-28
Dimension

Draw-Out Type ACB (2500~3200A)


Dimension

3P 4P

Rated Current T(mm) W(mm)


2500A 20 100
3200A 25 100

Fixed Type ACB (2500~3200A)

3P 4P

Rated Current T(mm) W(mm)


2500A 20 85
3200A 25 82
A1-29
Air Circuit Breakers

Draw-Out Type ACB (4000A)


Dimension

3P 4P
LOAD

Rated Current 4000A


LINE
T(mm) 30
W(mm) 100

Fixed Type ACB (4000A)

3P 4P

LOAD

LINE Rated Current 4000A


T(mm) 30
W(mm) 100
A1-30

Air Circuit Breaker for nuclear power plant

VITZRO TECH Air Circuit Breaker Class 1E for Nuclear Power Plants is produced through a

nuclear power quality certification system and development tests were conducted

based on KEPI END 1000~3000. In addition, it was recognized for its superior quality via

passing development tests based on ANSI C37, 13(1990) and KEPIC EED 1200.

Utility
Its performance was certified through a nuclear
power test based on an international standard
certification.
international standard certification.
It was internationally recognized for its performance
by obtaining major domestic and overseas standard
certifications including a local nuclear power test
(KERI) and an overseas KEMA certificate
(IEC60947-2 Test).
Nuclear Power Performance Verification
(KEPIC END 1000 - 3000)
- Aging analysis - Operation Cycling Test
- Seismic Test
A1-31
Air Circuit Breakers

Safety Reliability
ACB for nuclear power plants can be used within It is enhanced with the reliability by adopting a high-
the range of 3 poles and 800AF~3200AF and it functional microprocessor over-current trip device.
provides various options.

It is easy to perform an inspection after the failures using


the attached indicator lamp that enables to check which
elements were operated during the failures. Also, the
contact for each failure is output to be used at a remote
control and monitoring station.
It is resistant to an external surge since it is built-in with
a surge protection circuit.
Interlock device - Mechanical interlock unit (MI) A test terminal is installed for an easy inspection.
Close/Open push button locking device (BL) Malfunctions are not generated due to a vibration or an
UVT & UVT controller impulse since it is designed in a shock-resistant
Position switch (TOC) configuration.
Mechanical operating switch (MOC)
Condenser Trip device (CTD)
OCR alarm contact (2a)
A1-32
Rating

For Nuclear Power


Plant (ANSI C37.13
Applied)

Type VAB 16-08

Rated Voltage(Ue) 480V

Rated Insulation Voltage(Ui) 690V

Max. Rated Voltage 508V

Number of Poles(P) 3

Rated Current(In) 800A

Rated Frequency 60 Hz

Rated Short Time Withstand Current(Icw) 30kArms

30kArms(Sym.)
Instantaneous Operation
Rated Short Circuit 35.1kArms(Asym.)
Breaking Current
Short Time Operation 30kArms(Sym.)

(Operation Time: 40ms) 35.1kArms(Asym.)

Rated Short Circuit Making Current(Icm) 69kApeak

Rated Breaking Time ≤5 cycle

Nuclear Power Electric Class Class 1E

Nuclear Power Quality Class Q

Seismic Performance Ⅰ

Operational Duty O - 15sec - CO

Rated Operation Times (Under Rated Load) 5,000 times

Operation Mode Motor spring stored energy

Operating Control Voltage DC 125V

Control Voltage DC 125V

Spring Charging Time < 15sec

Rated Closing Time < 0.05sec

Rated Trip Time < 0.04sec

Number of Auxiliary Contacts 4NO+4NC

Weight 98kg

Cirtificate & Approval ANSI C37.13

* The weight includes the skeleton.


A1-33
Air Circuit Breakers

For Nuclear Power


Plant (ANSI C37.13
Applied)

Type VAB 16-08

Rated Voltage(Ue) 480V

Rated Insulation Voltage(Ui) 690V

Max. Rated Voltage 508V

Number of Poles(P) 3

Rated Current(In) 2000A 3200A

Rated Frequency 60 Hz

Rated Short Time Withstand Current(Icw) 50kArms 65kArms

50kArms(Sym.) 65kArms(Sym.)
Instantaneous Operation
Rated Short Circuit 58.5kArms(Asym.) 76.1kArms(Asym.)
Breaking Current
Short Time Operation 50kArms(Sym.) 65kArms(Sym.)

(Operation Time: 40ms) 58.5kArms(Asym.) 76.1kArms(Asym.)

Rated Short Circuit Making Current(Icm) 115kApeak 149.5kApeak

Rated Breaking Time 2,000 times ≤5 cycle 1,000 times

Nuclear Power Electric Class Class 1E

Nuclear Power Quality Class Q

Seismic Performance Ⅰ

Operational Duty O - 15sec - CO

Rated Operation Times (Under Rated Load) 2,000 times 1,000 times

Operation Mode Motor spring stored energy

Operating Control Voltage DC 125V

Control Voltage DC 125V

Spring Charging Time < 15sec

Rated Closing Time < 0.05sec

Rated Trip Time < 0.04sec

Number of Auxiliary Contacts 4NO+4NC

Weight 136kg 190kg

Cirtificate & Approval ANSI C37.13


A1-34
Trip Relay/Performance Characteristic Curve

Trip Relays - OCR


For Nuclear
Power Plant 8 Base Current 4 Instantaneous
5 LTD
6 STD

9 Test
Terminal

3 Short Time
7 Reset Button 1 Indicator Lamp 2 Long Time

Base Current [Io]


Type Current Setting [Ict] (A) Setting Range [Io] (A)
80 48≤ Io ≤80
160 96≤ Io ≤160
VAB 16-08 320 192≤ Io ≤320
630 378≤ Io ≤630
800 480≤ Io ≤800
80 48≤ Io ≤80
160 96≤ Io ≤160A
320 192≤ Io ≤320A
630 378≤ Io ≤630
VAB 32-20 800 480≤ Io ≤800
1000 600≤ Io ≤1000
1250 750≤ Io ≤1250
1600 960≤ Io ≤1600
2000 1200≤ Io ≤2000
2500 1500≤ Io ≤2500
VAB 40-32
3200 1920≤ Io ≤3200

Function Setting Method


❶ Base current(×Ict=Io) ❻ Short Time Delay
It is used to set the base current and it can be It is used to set the short time delay of short
adjusted to 3 stages up to 60%~100% of time and it can be adjusted to 3 stages up to
CT current. 0.1sec~0.4sec.
❷ Long time Pickup(×Io=I1) ❼ Reset Button
It is used to set the operating current of long time It is used to reset the failure cause indicator lamp
pickup and it can be adjusted to 4 stages up to after the operation of OCR.
70%~100% of Base Current (Io). (Must reset after the operation of OCR)
❸ Short time Pickup(×Io=I2) ❽ Lamp
It is used to set the operating current of short time •O.L (Over Load) Overload Status Indicator Lamp
pickup and it can be adjusted to 4 stages up to •LTD : Long Time Operation Indicator Lamp
400%~1000% of Base Current (Io). •INST : Instantaneous Operation Indicator Lamp
•STD : Short Time Operation Indicator Lamp
❹ Instantaneous Pickup(×Io=I3)
It is used to set the operating current of in ❾ Test terminal
stantaneous pickup and it can be adjusted It is a terminal to inspect OCR using a
to 4 st ges up to 400%~1600% of Base Tester.(Testable using an exclusive Tester)
Current (Io).
❺ Long Time Delay * Note)
It is used to set the long time delay of long time and it 1.Customers can select the options on STD, INST, LTD, LAMP and CONTACT.
can be adjusted to 9 stages from 600% of the operating 2. An external contact is output to remote control the failure status of
current to 0.5sec~30sec. Lamp’s external contact system.
A1-35
Air Circuit Breakers

For Nuclear Power


Plant ACB
Over Current Trip
A1-36
Trip Relay/Performance Characteristic Curve

External Configuration


❶ Charging handle
❷ Close/Open indicator ❶
❸ Key-lock
❹ Position indicator ❷ ❼
❺ Open button
❻ Counter ❸ ❽
❼ Spring charged indicator
❹ ❾
❽ Key-lock
❾ Racking screw & shutter ❺ ❿
❿ Close button

Draw-Out Device Configuration


Auto Control Jack Connector

Draw-In/Out Rail Roller

Internal Configuration
❶ Upper Cover
❷ Control Terminal
❸ Auxiliary Switch
❹ Closing/Trip Coil
❺ Charge handle
❻ Mechanism
❼ Charge gear
❽ Front Mold cover
❾ Draw in/out Device
❿ Arc Chamber
Moving Contact
Fixed Contact
Cradle
Clip
CB Connecting Conductor
Load Part Conductor
A1-37
Air Circuit Breakers

Draw-Out Location

Test Connected
A main circuit is disconnected, a control A main circuit and a control circuit are
circuit is connected and an operation test connected.
on a circuit breaker is possible.

Draw - out position Disconnected


A main circuit and a control circuit are
disconnected.
A1-38
Control Circuit Diagram / Accessories

Control Circuit Diagram for Nuclear Power Plant


Control Circuit
Diagram

* Note) 1. L : LTD, S : STD, I : INST


A1-39
Air Circuit Breakers

Accessories UVT, CTD, SST, OCC,


OCA,
Under Condenser Safety Trip cause KIT, Key lock
Alam contact
Voltage Trip trip device shutter contact

Instantaneous It is used at
Lock in open type
a trip during
Type (Open impossible)
a power
(≤ 0.15sec) Applied to OCR OCR
failure or
draw-out type Alarm Contact External Contact
used as a
Delay Type Lock in close type
rectifier (for
(≥ 0.5sec) (Open impossible)
DC power).

Key lock, KIT Motor Closing


There are a“Lock in open”type that doesn’t allow
Closed for a circuit breaker and a“Lock in close”
type that doesn’t allow Open. Mechanical and
electrical operations are possible.

Condenser Trip Device, CTD


It is used at a trip during a power failure (use as
Condenser Trip Device, CTD) or used as a rectifier
(for DC power).
When used as a CTD
If G, H terminals are connected to a Trip Circuit,
it performs TRIP immediately in case of a power
failure. If TRIP should be implemented in a certain
time, it can be used by adding S/W. (Yet, normal
operation is possible within 30 seconds)
When use as a rectifier
C.D and E.F output terminals should be used as DC
* Note) The above circuit diagram is a“Lock in open”
power. (Close, Open, Motor, OCR Power and etc) type.

CTD Internal Circuit Diagram External Dimension


A1-40
Accessories / Dimension

Under Voltage Trip (UVT) automatically trips the ACB when the control power is
Under Voltage Trip
dropped below the working voltage. When the voltage is recovered up to the pick-
up voltage, The re-closing of ACB is possible. UVT consists of a trip device and a
under voltage trip controller. A coil is built inside the ACB and UVT Controller is
installed in the body (fixed type) or in the left side of the draw-out type.
There are an instantaneous-type and a delay-type to be used based on its purpose.

Rating
Rating Voltage Working Voltage Operating
Type Remarks
50-60Hz Drop Voltage Pick-up Voltage Time

100-120V 48-60 67.5-80


Instantaneous
Type 200-240V 96-120 135-165
≤0.15sec Power
(I) 360-400V 160-207 240-288 Consumption:
430-470V 188-245 282-344 5VA
Input Power:
100-120V 48-60 67.5-80
Delay Type 50VA
200-240V 96-120 135-165
(D) ≥0.5sec
360-400V 160-207 240-288
430-470V 188-245 282-344

Circuit Diagram

Trip Coil
Driving
Power
AC Power
Power
Control

Comparator

* Note) 1. Combined use of under voltage trip and voltage trip is possible.
2. * marked AUX.SW is not installed and do use the 1a contact of AUX.SW.
3. A1 and A2 are Test contacts and a-contact at pick-up state.

External Terminal Functions


V1, V2 UVT Input Power
S1, S2 External Reset Contact
A1, A2 Test Contact
A1-41
Air Circuit Breakers

800/2000A
For Nuclear Power
Plant

Front View Side View Back View

Rating A B C D E
800A 330 15 85 330 275
2000A 465 25 130 465 410
Terminal Dimension

3200A

Front View Side View Back View

Terminal Dimension
A1-42
Certification
A1-43
Air Circuit Breakers