2008-GM Tutorial 1 Nelson
2008-GM Tutorial 1 Nelson
2008-GM Tutorial 1 Nelson
Inside view
of 1898
oil breaker
Line No. 26
Voltage Ratings
Rated kV 138
Max Design kV 145
Min kV for rated MVA 132
Interrupting Ratings
3-Phase Rated MVA 10,000
Amperes at Rated Voltage 42,000
Max Amperes 44,000
Amount of dc
“asymmetry” is a
function of the
point on the voltage
wave when the
fault starts
8 cycle 1.0
5 cycle 1.1
3 cycle 1.2
I.4
2 C b P ak er
cl e Breaker
1.2
3 Cyc ie breaker
8 Cyc|e breaker
1.0
0 0. 5 I. 0 2. 0 2. 5 3. 0 4. 0
C i rcu i t Br eak er 0p en i ng T i m €2 - C Y C I es
60
( Tr i p- to- cont act - sepd rat i on )
Line No. 5C
Nominal Voltage Class kV 138
Nominal MVA Class 10,000
Rated Values
Rated Maximum Voltage kV 145
Rated Voltage Range Factor - K 1.10
Rated Short Circuit at Rated Max kV 37,000
10,000MVA 1
I1964 145kV 3 1.1 37kA
145kV
37kA 38.9kA
138kV
38.9kA1.2 46.5kA
• R10 Series:
10, 12.5, 16, 20, 25, 31.5, 40, 50, 63, 80, 100
O - t - CO - t΄ - CO
where, O = Open
CO = Close-Open
t΄= 3 min
t = 15 s for circuit breakers not rated for
rapid reclosing and
= 0.3 s for circuit breakers rated for rapid
reclosing duty
• C37.04 revision
• C37.09 revision
• Application guides as required
• C37.082 – Sound Pressure Levels
• Long Line Fault TRV
• Gas Bushings for HV Breakers and GIS