Professional Documents
Culture Documents
IR2 Generic Manual
IR2 Generic Manual
IR2 Generic Manual
This document has been approved for use by qualified personnel only.
Document No 11800501
Issue: 01
www.eaton.com/telecompower
e-mail: - dc.info@eaton.com
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |2
Manual
Eaton Power System Handbook
Revision History
Abbreviations
AC – Alternating Current
DC – Direct Current
Eaton Corporation disclaims any liability for direct, indirect, incidental, special or consequential damages arising out of the
application or use of any information contained in this document. The foregoing disclaimer applies to damages or personal
injury, property damage, loss of operation, loss of profits, loss of product or loss of time, whether incurred by the
purchaser, the purchaser’s employees or third party.
Information in this document does not constitute a warranty, representation or guarantee concerning the suitability or
performance of Eaton products. No such warranty, representation or guarantee is expressed or implied.
Furthermore, information contained in this document, does not guarantee or imply any ownership of site specific design. It
is therefore the total responsibility of the installation designer to ensure compliance with any legal or statutory
requirements in the country of use.
Additionally, information contained in this document is subject to change without further notice.
Eaton, Powerware, Intergy, CellSure, SiteSure, PowerManagerII and DCTools are trade names, trademarks, and/or service
marks of Eaton Power Quality Corporation or its subsidiaries and affiliates. Unless otherwise noted, brands, product
names, trademarks or registered trademarks are the property of their respective holders.
Subject to the right to use its equipment, Eaton Corporation does not convey any right, title or interest in its intellectual
property, including, without limitation, its patents, copyrights and know-how.
No part of this document may be reproduced or transmitted in any form, by any means or for any purpose other than the
Customer’s personal use, without the express written permission of Eaton Corporation.
Document produced and published by the Engineering Department of Eaton Electric Ltd, Bognor Regis, West Sussex.
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |3
Manual
Eaton Power System Handbook
Table of Contents
Introduction ............................................................................................................................................ 6
Purpose ........................................................................................................................................... 6
Personal Protection in Restricted Access Areas.............................................................................. 6
Health and Safety ............................................................................................................................ 6
Reporting Problems with this Manual ............................................................................................ 6
Contact Information........................................................................................................................ 6
Symbols Used in this Document ..................................................................................................... 7
Standards and Approvals ................................................................................................................ 8
Health & Safety Guidelines ................................................................................................................. 9
Introduction .................................................................................................................................... 9
The Electricity at Work Regulations 1989 and The Health and Safety at Work etc. Act 1974 ....... 9
BS7671 Requirements for Electrical Installations ........................................................................... 9
Warnings ....................................................................................................................................... 10
Manual Handling ........................................................................................................................... 14
Battery Safety................................................................................................................................ 14
Anti-Static Precautions.................................................................................................................. 16
Wiring Colours............................................................................................................................... 17
Mechanical Installation Instructions ................................................................................................. 18
Introduction .................................................................................................................................. 18
Installation Fixings Required ......................................................................................................... 19
Installation Tools Required ........................................................................................................... 19
Positioning and Floor Fixing .......................................................................................................... 19
Joining Multiple Cabinets .............................................................................................................. 21
SC200 System Controller............................................................................................................... 23
Alarm Connections ........................................................................................................................ 24
Rectifiers ....................................................................................................................................... 26
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |4
Manual
Eaton Power System Handbook
Commissioning .................................................................................................................................. 29
Task 1 - Analog Inputs ................................................................................................................... 29
Task 2 - System Controls ............................................................................................................... 30
Task 3 - System Alarms ................................................................................................................. 34
Task 4 - Digital Inputs .................................................................................................................... 37
Task 5 - Digital Outputs (Relays) ................................................................................................... 37
Commissioning Completion .......................................................................................................... 37
Troubleshooting ................................................................................................................................ 38
Worldwide Support ........................................................................................................................... 42
Appendix A ........................................................................................................................................ 43
Alarm PCB Connections (IOBGP-00).............................................................................................. 43
Appendix B ........................................................................................................................................ 46
Equipment Incident Report........................................................................................................... 46
Appendix C ........................................................................................................................................ 48
Circuit Diagrams ............................................................................................................................ 48
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |5
Manual
Eaton Power System Handbook
Introduction
Purpose
This document provides installation and commissioning guidance for installing Eaton power systems.
WARNINGS
Restricted Access Area
The Power System must be installed in a Restricted Access Area.
Cabinet Fixing
Cabinet(s) must be securely fixed to a concrete or other non-combustible surface,
capable of supporting the weight of the cabinet(s) including its full fit-out of
rectifier / batteries
Health & Safety
Any maintenance, additions or modifications to the Power System, must only be
performed by suitably trained and qualified personnel, using fully insulated tools.
Refer to the Health & Safety Guidelines.
Energy Hazard
This power system contains high voltage and high energy sources within.
Live working on the Power System, will require the temporary addition of
supplementary insulation to equipment within the cabinet, for example, when
working directly above the rectifier magazine, an insulating cover must be fitted
over the magazine.
Contact Information
Manufacturers Address
Eaton Electrical Ltd
Durban Road
Bognor Regis
West Sussex
England
PO22 9QT
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |6
Manual
Eaton Power System Handbook
SYMBOL
WARNING
Advice on hazardous conditions. Possibility of personnel injury and/or equipment
damage
CAUTION
Advice on seriously hazardous conditions. Possibility of severe/fatal personnel
injury and/or serious equipment damage
ELECTRICAL HAZARD
Advice on electrically hazardous conditions. Possibility of severe/fatal personnel
injury and/or serious equipment damage
FLOW ARROW
Advises that the procedure continues below.
NOTE
Note or advice on further information.
RECYCLING
Advice on the recycling of components or equipment.
DISPOSAL
Dispose in accordance with local environmental regulations.
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |7
Manual
Eaton Power System Handbook
Eaton power systems have invoked the following standards and approvals.
LVD and EMC directives 2006/95/EC and 2004/108/EC respectively invoking EN60950-1 and EN300
386.
This Telecommunications Power Supply System complies with or exceeds the following Standards:
EN300 386: Electromagnetic Compatibility and Radio Spectrum Matters (ERM); Telecommunications
Network Equipment; Electromagnetic Compatibility (EMC) requirements.
This Telecommunications Power Supply System output is classed as earthed SELV at a hazardous
energy level.
WEEE Directive
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |8
Manual
Eaton Power System Handbook
This document is to be a complement to general safety rules when working with power systems and
other electrical systems. Local health and safety documentation must also be fully adhered to when
carrying out work associated with power.
Contact the Network Operations Centre (NOC) before commencing work. Inform people around the
equipment that work is in progress and that equipment may be live during the course of the work
that will be carried out.
The Electricity at Work Regulations 1989 and The Health and Safety at Work etc. Act
1974
The Electricity at Work Regulations came into force on the 1st April 1990 and is made under The
Health and Safety at Work etc. Act 1974. The regulations apply to all places of work and impose
duties on people in respect of electrical systems, equipment and all work activities on or near
electrical equipment.
The Electricity at Work Regulations 1989 state principles of electrical safety in a form that can be
applied to any electrical equipment and work activity. They apply to all electrical systems and
equipment whether manufactured, purchased or installed even if this pre-dates the Regulations.
Where this is the case, this does not necessarily mean that it contravenes the Regulations. The
equipment or system need only be replaced when it becomes un-safe or needs to be modified. The
frequency of work on the electrical equipment or installation, the practicality of providing screening
from live conductors and the inconvenience of making the equipment or system dead are key factors
in deciding on replacement.
WARNING:
A breach of the requirements contained within this directive may be used in
criminal and or civil proceedings as evidence that statutory requirements have been
contravened.
11800501_IR2 Generic Copyright © 2011-2014 Eaton Corporation. All Rights Reserved Page |9
Manual
Eaton Power System Handbook
Warnings
WARNING: Isolation
There must be an isolator external to the DC power system to provide emergency
shutdown or isolation of all AC power to the system.
If the equipment is to be isolated, the following areas must be considered:
AC and DC inputs from all sources
Output from parallel systems
Power factor correction and filter capacitors
Battery. Use of the isolator, if fitted, may not be sufficient, as it may be necessary
to work close to the isolator's connections. In this case, also remove at least one
cable from the battery and isolate the exposed connections.
"Isolation" in terms of the UK Electricity at Work Regulations means the methods
by which it is assured that hazards such as batteries and power cannot be re-
connected inadvertently by those working on the equipment, or by others. Such
methods include having a switch in view at all times (an external readily accessible
isolator), and the use of lock-outs.
WARNING: AC Rating
Ensure that the AC incoming supply voltage, number of phases and frequency
aligns with that marked adjacent to the equipment AC input terminals. For three
phase input, the rotation can be in any order.
Refer to the design diagram supplied with the equipment to ensure that the AC
input and DC output earth wiring and termination is dimensioned correctly.
WARNING: Rectifiers
Do not install the rectifiers until the room has been cleaned and is dust free.
To reduce the risk of electric shock and maintain optimum system cooling, always
cover empty rectifier slots with blanking panels.
To avoid electrical shock, do not place hands inside the rectifier magazine.
Rectifier cases may exceed 100ºC (212ºF), especially after prolonged operation. Use
suitable gloves when removing a rectifier from the magazine.
Do not attempt to disassemble faulty rectifiers. Return them (in their original
packaging) with a copy of the Equipment Incident Report in the appropriate guide or
manual.
Ensure that any upstream Residual Current Devices (RCDs) are appropriately rated
for the rectifiers' maximum earth leakage current (see Specifications in the
appropriate guide or manual for value).
WARNING: DC Distribution(s)
The DC Common of the DC power system can be connected to earth (ground). If
this connection is made all of the following conditions must be met:
The equipment and the DC power system must be located within the same
premises.
No switching or disconnecting devices are allowed in the conductor between the
DC common line and the point of connection to the earth electrode conductor.
For all installations, use the appropriate connector for the conductor size as
specified by the connector manufacturer. And use only the connector
manufacturer's recommended tooling or tooling approved for that connector.
Follow all applicable local and national rules and regulations when making field
connections.
Tighten all electrical connections to the torques stated in the appropriate guide or
manual or on the OEM's label.
Refer to the design diagram supplied with the equipment to ensure that the AC
input and DC output earth wiring and termination is dimensioned correctly.
WARNING: Smoking
Smoking is generally prohibited in buildings.
Manual Handling
In the UK, The Manual Handling of Loads Regulations, 1993, require that all persons are familiar with
the Regulations, that they take care to minimize risk of injury to themselves and others, that they
are properly trained, and that the correct equipment is used.
Battery Safety
For Eaton supplied equipment, mechanical battery lifting aids must be used at all times.
Safety checks
Before inserting/closing battery protection devices (fuses, links, MCBs or MCCBs):
Anti-Static Precautions
Wiring Colours
Function Alphanumeric Colour
Earth
Protective conductors Green-and-yellow
AC Power Circuit
Phase of single-phase circuit L Brown
Neutral of single- or three-phase circuit N Blue
Phase 1 of three-phase AC circuit L1 Brown
Phase 2 of three-phase AC circuit L2 Black
Phase 3 of three-phase AC circuit L3 Grey
DC Power Circuit
Positive Common (0V) M Black (red heatshrink)
Negative Live (-48V) L- Blue
2200mm
2200mm
600mm 600mm
Preliminary Works
Before installation ensure that:
All areas of floor are protected from damage by the transport of the equipment. Use
hardboard or a similar material. This material must be removed once installation is
complete.
No space is necessary at the sides or rear. Allow distances from other equipment as required by the
installation requirements of that equipment (although the cabinet does not require space at the
sides or rear, adjacent equipment may do so).
Bear in mind the space required for door opening. The minimum recommended space is 840mm
The doors are right opening (hinges on the right hand side).
When installing on a raised "Computer floor", locate the first cabinet over one tile. If load spreading
is required due to cabinet weight then this must be installed prior to cabinets being installed.
Recommended procedure:
416.0 TYP
FRONT
The footprint diagram above shows the cabinet dimensions and location of floor fixings.
Mechanical Connection
Join together multiple cabinets using the linking plates and M4 screw fixings provided. Two brackets
are used at the top of the cabinet on the lid and two are used at the bottom on the lower side rail
(see pictures below).
Note that the picture below shows both positive and negative busbars together. Some system will
have the positive busbar positioned at the top or bottom of the cabinet but the method of suiting
the busbar to adjoining cabinets is the same.
Busbar Fishplate
The SC200 is supplied preconfigured with either a default configuration file, or with one factory
customized for a particular application. This ensures fast and problem free installation.
If on-site changes are needed then these can be easily made from the front panel or with a Windows
PC using DCTools configuration software.
The front panel incorporates a high-resolution back-lit color LCD display with easy to read characters
and easy to use menu system. All system values and alarms can be displayed and the keypad
provides easy access to check or edit settings.
The SC200 works with separate system I/O boards for powerful and user-friendly interfacing. Easy
and low cost I/O expansion is possible by adding additional I/O boards.
Features
• Ethernet interface built-in
• SNMP agent
• Battery mid-point monitoring (if enabled)
• Eaton Fuel Saver
• SMS alarm messages (with GSM modem)
• Comprehensive system control functions
• Color display with user-friendly menus
• Setup via web, keypad or DCTools configuration software
• Different language options
• Optional extra I/O boards or SiteSure-3G modules for expansion
• Smart Alarms
• Modbus
• Battery time remaining during discharge
Alarm Connections
Introduction
The power system is controlled by an Eaton SC200 Controller, which is connected to the system
Input/Output interface board IOBGP-00.
All system monitoring and alarm connections are made on the IOBGP.
The I/O board includes a range of sense inputs for DC power system control and monitoring. It also
allows real time data collection from building services and other external devices, and relay outputs
for alarm signals or control of external devices.
For input and output specifications and connector pin-outs see document no IPN 997-00012-50,
SC200 System Controller Operation Handbook. The Latest version of the handbook is available from
www.powerquality.eaton.com/DC-Manuals
SC200-00 IOBGP-00
IOBGP Connections:
XH9 Bus voltage sense input XH8 LVD power input connector
XH15A & B Digital inputs D1-D6 (6 user XH16- Digital (relay) outputs RY1-RY6 (6)
defined) XH21
XH12 Battery Mid-point Monitoring XH5 LVD2 control connector
inputs
YH11 Power and RXP comms input XH4 LVD1 control connector
XH6 Current sense inputs (3) XH7 Temperature sense inputs (2)
The Alarm Outputs from the IOBGP Board are made in the screwless terminal blocks XH16 and XH21
and are numbered RY1 to RY6.
The wire size for connection to these terminal blocks is in the range between 0.5 - 2.0mm².
For Troubleshooting regarding the I/O board LED signals, see document no IPN 997-00012-50, SC200
System Controller Operation Handbook.
Rectifiers
This system utilizes one of the following Eaton rectifiers.
Rectifier APR-Rectifiers
AC Supply 120V/208-240V, 50/60Hz (nominal)
185-275V full output power up to 50°C [122°F]
90-185V reduced output power
Power Factor 0.99 (50 – 100% output current)
Operating Temperature -40°C – +70°C [-40°F – +158°F].
Output current is de-rated above 50°C [122°F] and below -10°C
[14°F]
Dimensions H,W,D 3U: 133mm [5.25”], 42mm [1.65”],
266mm [10.45”] overall
Weight 1.7kg [3.7 lb]
For details of rectifier alarms and configuration, see the appropriate controller handbook.
The SC200 Controller Handbooks can be downloaded from www.powerquality.eaton.com/DC-
Manuals
Rectifier Indicators
The rectifier has three LEDs providing visual indication of the status of the rectifier.
WARNING: Rectifiers
To reduce the risk of electric shock and maintain optimum system cooling, always
cover empty rectifier slots with blanking panels.
To avoid electric shock do not place hands inside the rectifier shelf/magazine.
Do not attempt to disassemble faulty rectifiers. Return them for service or
replacement in their original packaging.
Keep fingers clear when inserting rectifiers to avoid injury
The rectifier may be hot, especially after prolonged operation. Use suitable gloves.
To avoid damage to the rectifier connector, do not rest it on its connector, once it
has been removed from the shelf.
Step 1
Step 2
Step 3
Removing Rectifiers
The Eaton APR48 Rectifiers are hot-pluggable and do not require the system or rectifier to be off
before removing.
Grip the rectifier front panel with one hand and slowly pull it out from the shelf, supporting the base
of the rectifier with your other hand.
Commissioning
This section is a generic guide to the commissioning tasks normally performed on a DC system. Local
site and equipment arrangements may require different tasks to be completed or a reduced number
of tests from the ones documented below.
Task Description
1 Analog Inputs
2 System Controls
3 System Alarms
4 Digital Inputs
5 Digital Outputs (Relays)
Notes
1. When the rectifiers are turned off, the battery current will supply all the current to the load.
At this time the battery current will equal the load current.
This test assumes there is a current sensor on the DC Load Bus. If batteries are not installed
on the system, connect the load bank to the battery bus.
If the battery current is determined by a summation, conduct the load current test before
the battery current test.
2. The test should be done at the maximum expected system load current.
This test assumes there is a current sensor on the DC load bus.
3. As the analog inputs can be configured for many different types of analog signal, tests have
not been detailed on this test sheet.
User assigned analog inputs are not available on all systems.
Notes
1. AVC must be enabled. Allow up to 1 minute for the system to stabilize after load or voltage changes.
2. Breathing on the sensor can increase the temperature.
3. Battery Current Limit control process may have to be turned off to allow the Fast Charge voltage to
reach its value within the 1 minute test duration.
4. For details see Generator Control Option in the System Controller Operation Handbook.
5. There may be slight current fluctuations above and below the configured current limit setting. This
can be due to the current control within the factory preset deadband.
Confirmation of this control process may be witnessed in the Fast Charge test.
6. There may be a delay of up to 2 minutes before the currents stabilize between rectifiers.
7. There may be a delay of up to 10 seconds before the LVD changes state.
APS systems may not display a Manual Connect alarm on the SC200 if the system voltage is above the
LVD disconnect voltage.
Perform the test on each LVD control module within the system.
For manual LVD operation see details.
For an explanation of LVD LED indications see Troubleshooting.
Notes
Notes
1. As the Digital Inputs can be configured for many different digital input devices, specific tests
have not been detailed on this test sheet.
Notes
1. Digital Outputs can also be checked as other system tests are performed.
2. This digital output is typically configured as the Monitor OK relay. Test extended alarms by
removing the power to the I/O board. This will de-energize the relay.
Commissioning Completion
Restore the original (backed-up prior to the testing) configuration file.
Use DCTools/Web to change any configuration file settings that were noted as incorrect during the
Commissioning tests.
Troubleshooting
Use the table to troubleshoot minor installation and operational problems.
Return items for replacement or repair with a completed Equipment Incident Report.
Rectifier yellow LED on. Rectifier power limit or current limit is Power system is charging the batteries.
active. If required, activate the Battery Current
Limit control process.
High system output voltage. Equalize, Fast Charge and/or Disable active function(s) in system
Temperature Compensation is active. controller if not required.
Incorrect float voltage setting at system Correct the float voltage setting of the
controller. system controller.
Record new setting.
Faulty rectifier. Locate the rectifier with the highest
output current and remove this one first.
If the first rectifier removed is not faulty,
remove each of the remaining rectifier
modules one at a time, until the faulty
rectifier is found. (The output voltage
returns to normal when faulty rectifier is
removed.)
Replace faulty rectifier with one that is
working.
Return the faulty rectifier for service.
System has no DC output (rectifiers are Load fuse or MCB open. Check the load fuses or MCBs.
on).
LVD has disconnected the load. Use DCTools/Web to check LVD is
enabled and set to correct values. (LVD
status LED on the I/O board is on when
LVD is connected.)
Check that the I/O board is connected
(Power LED is on).
Check that the LVD control and power
cables are connected.
Check the connections from the load bus
to the LVD.
System has no battery input Battery MCB open. Switch on the required battery MCB(s).
LVD has disconnected the battery. Use DCTools/Web to check LVD is
enabled and set to correct values. (LVD
status LED on the I/O board is on when
LVD is connected.)
Check that the I/O board is connected
(Power LED is on).
Check that the LVD control and power
cables are connected.
Check the connections from the battery
bus to the LVD.
String Fail Alarm The Battery Mid-point Monitoring See Battery Mid-point Monitoring
system has detected a voltage section of SC200 manual.
imbalance in one of the battery strings.
A Battery Mid-point Monitoring sense Check the sense wires.
wire is disconnected.
I/O board Power/Comms OK LED is off I/O board is not powered or faulty. Check connection to YH3 on I/O board.
Replace I/O board if faulty.
I/O board Power/Comms OK LED is I/O board is responding to an Identify None, this is normal operation.
flashing. command from the SC200.
LVD1 and/or LVD2 Status LEDs (on I/O LVD is connected (contactor closed). None, this is normal operation.
board) are on.
LVD1 and/or LVD2 Status LEDs are off LVD is disconnected (contactor open). None, this is normal operation.
(I/O board Power On LED is on).
LVD1 and/or LVD2 Status LEDs are The LVD contactor is in the wrong state Check the electrical and mechanical
flashing. (SC200 internal state does not match operation of the contactor and auxiliary
signal from LVD auxiliary switch). switch.
Check all wiring and connectors.
LVD contactor(s) not operating. LVD settings incorrect. Use DCTools/Web to check LVD is
enabled and set to correct values. Check
that the LVD manual control is set to
AUTO. See details in the System
Controller Operation Handbook.
Check that the LVD is correctly mapped
to the I/O board. See details in the
System Controller Operation Handbook.
LVD contactor is disconnected. Check that the LVD control and DC
power cables are connected.
Worldwide Support
For product information and a complete listing of worldwide sales offices, visit Eaton's website at:
www.eaton.com/telecompower or email: DCinfo@eaton.com
For technical support contact either your local Eaton DC product representative or the closest office
from the following list.
Canada: 1-800-461-9166
China: +86-571-8848-0166
India: +91-11-4223-2325
Appendix A
Alarm PCB Connections (IOBGP-00)
Connector Type Purpose Pin Description
XS1 DB9M RS232 Serial Interface 1 -
2 RD (Receive Data)
3 TD (Transmit Data)
4 DTR (Data Terminal Ready)
5 Common (Ground)
6 -
7 RTS (Request to Send)
8 -
9 -
XS31 RJ45 Ethernet Interface 1 Rx
2 Rx
3 Tx
4 -
5 -
6 Tx
7 -
8 -
YS11 RJ45 RXP System Communications 1 +24/48V (System bus voltage)
2 +24/48V (System bus voltage)
3 -
4 RS485-A
5 RS485-B
6 -
7 0V
8 0V
USB USB B USB Serial Interface 1 VCC (+5 V DC)
2 Data -
3 Data +
4 Ground
1 8
Appendix B
Equipment Incident Report
Please enter as much information as you can. Send the completed form, together with the item for repair to
your nearest authorized service agent. NOTE: Only one fault to be recorded per form.
For further information contact your Eaton DC product supplier or Eaton Corporation, Telecommunications
Power Solutions. Telephone: +44 1243 810500, Fax: +44 1243 810683.
Date:
Customer Information
Company:
Postal Address:
Return Address:
(Not PO Box)
Contact Name:
Location of Failure
Reference No: __________ RMA: __________ NCR: __________ Signature: _________________ Date:
__________
Appendix C
Circuit Diagrams
A B C D E F G
A1 DO NOT SCALE THIRD ANGLE PROJECTION IF IN DOUBT ASK
L1 L2 L3 N E L1 L2 L3 N E N E L1 L2 L3 N E L1 L2 L3
GR/1 40A
GR/1 40A
GR/1 40A
GR/1 40A
BN/1 40A
BN/1 40A
BN/1 40A
BN/1 40A
BK/1 40A
BK/1 40A
BK/1 40A
BK/1 40A
GY/1
GY/1
GY/1
GY/1
BL/1
BL/1
BL/1
BL/1
4
+VE -VE
COM LIVE
GR/2
BL/2
5
GR/1 40A
GR/1 40A
GR/1 40A
GR/1 40A
BN/1 40A
BN/1 40A
BN/1 40A
BN/1 40A
BK/1 40A
BK/1 40A
BK/1 40A
BK/1 40A
GY/1
GY/1
GY/1
GY/1
BL/1
BL/1
BL/1
BL/1
L1 L2 L3 N L1 L2 L3 N N L1 L2 L3 N L1 L2 L3
AC DISTRIBUTION
RECTIFIER MAGAZINE 1
Ø1 Ø2 N Ø3
E
7
RECTIFIERS ON PHASE = 3 RECTIFIERS ON PHASE = 3 RECTIFIERS ON PHASE = 4
USED ON ............
RECTIFIER MAGAZINE 2
Ø1 Ø2 N Ø3
8
E
RECTIFIER MAGAZINE 3
9 Ø1 Ø2 N Ø3
10
RECTIFIER MAGAZINE 4
Ø1 Ø2 N Ø3
11
+VE -VE
COM LIVE
DRAWN MATERIAL
12
TOLERANCES
± 0.2 ...,XX FINISH
NOTES: ± 0.3 ...,X
± 0.5 UNLESS
OTHERWISE STATED
BN/1 = BROWN 6mm ² TRI-RATED UL1015 ANGLES .....± 0.5° CHK'D Details DCN/FIN No. Date Issue
BK/1 = BLACK 6mm ² TRI-RATED UL1015
TITLE
GR/1 = GREY 6mm ² TRI-RATED UL1015 NOTES: LARGER CROSS SECTIONS MAY BE USED THROUGHOUT.
BL/1 = BLUE 6mm ² TRI-RATED UL1015 LIVE (-VE) IS GREY. GROUND BLUE IF CABLE OR BARE IF COPPER BAR.
GY/1 = GREEN/YELLOW 6mm ² TRI-RATED UL1015 © 2012 Eaton Power Solutions Ltd
Not to be used for any purpose other than that for which supplied.
SCALE DIMS IN DRAWING No.
GR/2 = GREY 25mm ² TRI-RATED UL1283 Supplied without contractual or other liability for errors or omisions
where used for manufacture by the company.
BL/2 = BLUE 25mm ² TRI-RATED UL1283 mm
SHEET OF
11800501_IR2 Generic
RJ45
RJ45
0V
-48V DCD/ACD
RJ45
IOBGP-00 YH3
Eaton Power System Handbook
11612002
COM
BL/1 BL/1 BL/1 BATTERY
COM BUS COM BUS COM BUS LVD
POWER MIDPOINT
GR/1 GR/1 GR/1
LIVE BUS LIVE BUS LIVE BUS XH8 POWER CURRENT TEMP XH12A
S3 S1
RXP SENSOR SENSE
YH11 XH6 XH7
BUS
LVD1 VOLTAGE
S2 XH4 XH9
RM10 - RECTIFIER MAGAZINE 2 VFN-00
TB1
0V
-48V
RJ45
P1 LCD2
BL/1 BL/1 BL/1 HX5
COM BUS COM BUS COM BUS P2
GR/1 GR/1 GR/1 LIVE RY6 RY5 RY4 RY3 RY2 RY1 XH15B XH15A
LIVE BUS LIVE BUS LIVE BUS 6 USER DIGITAL OUTPUTS 6 USER DIGITAL INPUTS
0V
-48V
RJ45
BL/1 BL/1 BL/1
COM BUS COM BUS COM BUS
GR/1 GR/1 GR/1
LIVE BUS LIVE BUS LIVE BUS
RJ45
SC
SEE NOTES
IOBGP MIRRORED 02
FIRST DRAFT 01
SEE NOTES
CIRCUIT DIAGRAM
RM10 DC + COMMS + IOBGP (4 x RM10)
NTS
P a g e | 50
1 1 11612000
Manual
SYxxxxxx
11800501_IR2 Generic
BLACK
WHITE
RJ45 BLACK
WHITE
11607802
Eaton Power System Handbook
COM
LVD BATTERY
POWER MIDPOINT
XH8 POWER CURRENT TEMP XH12A
S3 S1
RXP SENSOR SENSE
YH11 XH6 XH7
RXP BUS
LVD1 VOLTAGE
S2 XH4 XH9
VFN-00
RS232 USB
TB1
P1 LCD2
HX5
GREY P2
LIVE RY6 RY5 RY4 RY3 RY2 RY1 XH15B XH15A
Ethernet 6 USER DIGITAL OUTPUTS 6 USER DIGITAL INPUTS
0V -48V
BUS BUS
IOBGP MIRRORED 02
FIRST DRAFT 01
SEE NOTES
CIRCUIT DIAGRAM
SC200 + VFN + IOBGP CONNECTIONS
NTS
P a g e | 51
1 1 11607800
Manual
SYxxxxxx
11800501_IR2 Generic
RJ45
IOBGP-00 DCD/ACD
YH3
11613202
Eaton Power System Handbook
LVD BATTERY
POWER MIDPOINT
XH8 POWER CURRENT TEMP XH12A
RXP SENSOR SENSE
YH11 XH6 XH7
BUS
LVD1 VOLTAGE
XH4 XH9
LCD2
HX5
P5
P1 P2 P3 RY6 RY5 RY4 RY3 RY2 RY1 XH15B XH15A
FFN-00 6 USER DIGITAL OUTPUTS 6 USER DIGITAL INPUTS
S2 S1 P4
RJ45
IOBGP MIRRORED 02
FIRST DRAFT 01
SEE NOTES
CIRCUIT DIAGRAM
FFN + IOBGP CONNECTIONS (1 x FFN)
NTS
P a g e | 52
1 1 11613100
Manual
SYxxxxxx
MCB SENSE TO FFN CONNECTION
11800501_IR2 Generic
ADDITIONAL MCB SENSE WIRES
CONNECT TO P2 TO P4
P5
P1 P2 P3
FFN-00
11614201
S2 S1 P4
Eaton Power System Handbook
BUS BUS
BUS BUS
SC
SEE NOTES
FIRST DRAFT 01
SEE NOTES
CIRCUIT DIAGRAM
FUSE/MCB TO FFN CONNECTION
NTS
1 1 11614200
P a g e | 53
Manual
SYxxxxxx
11800501_IR2 Generic
RJ45 RJ45 RJ45 TO ADDITIONAL
SLAVE CABINETS
(OPTIONAL)
11613701
Eaton Power System Handbook
S3 S1 S3 S1 S3 S1 S3 S1
S2 S2 S2 S2
VFN-00 VFN-00 VFN-00 VFN-00
TB1 TB1 TB1 TB1
P1 P1 P1 P1
P2 P2 P2 P2
LIVE LIVE LIVE LIVE
FIRST DRAFT 01
SEE NOTES
CIRCUIT DIAGRAM
CABINET INTERCONNECTION
NTS
1 1
P a g e | 54
11613700
Eaton Power System Handbook