Guidance on Selection of Arc-Rated Clothing and Other PPE for Use When Incident Energy Exposure Is Determined
For more detailed information or other options refer to NFPA 70E 2015 Edition, Table H.3(b) or CSA Z462 Table H.2
The minimum PPE for all Enbridge Worksites in the field shall be: safety glasses, safety boots, full-length pants and long sleeved shirts, hard hat,
& gloves. FR Garments are required to be worn as daily work wear when inside fenced or operating Facilities.
FR Garments for electrical workers shall meet the minimum ATPV of 8 cal/cm2 (HRC 2) and increase as required by Arc Flash hazards.
Workers should wear only clothing made with a natural fiber (e.g., cotton, wool) or approved FR undergarments below FR outerwear.
Incident Energy Exposure Untreated natural fiber