Professional Documents
Culture Documents
Mechanical Characterization of 3D Printable Concrete PDF
Mechanical Characterization of 3D Printable Concrete PDF
Mechanical Characterization of 3D Printable Concrete PDF
h i g h l i g h t s
a r t i c l e i n f o a b s t r a c t
Article history: The current study deals with test methods for characterizing the mechanical behaviour of 3D printed wall
Received 16 May 2019 elements. At first, the effect of interfaces present in a printed concrete element was examined through an
Received in revised form 7 August 2019 assessment of porosity and bond shear test. The porosity was evaluated using specimens extracted from
Accepted 12 August 2019
the bulk as well as from the interfaces between horizontal and vertical layers of printed concrete. It was
found that the porosity in the bulk was lower by 6–8% as compared to the mould cast concrete. On the
other hand, the porosity at the interface between horizontal and vertical layers was found to be higher by
Keywords:
11–14% and 10–16% respectively. Therefore, although the bulk in 3D printed elements is more densified,
3D printable concrete
Porosity
the interfaces are weak with higher porosity. The interfaces were further evaluated by a direct bond shear
Bond shear test test. Compared to the shear strength of the mould cast concrete, the shear strength at interface between
Compressive strength the horizontal and vertical layers was found to be lower by 24–25% and 22–30% respectively. The com-
Flexural strength pressive strength of the printed concrete was similar when tested in different loading directions but
lower by 12–22% as compared to the mould cast concrete. This reduction in compressive strength may
be due to the higher porosity at the interfaces present in printed concrete elements. The flexural strength
was found to depend on the region subjected to the maximum bending moment. When tested along the
direction where the maximum bending moment and therefore the maximum bending stress occurs at the
weaker interfaces between layers, the flexure strength was lower by about 32–40%. On the other hand,
the flexural strength was found to increase by 13–20% when tested in directions where maximum bend-
ing stress is induced in the bulk concrete, having a lower porosity as compared to the mould cast con-
crete. Finally, some perspectives are provided on formulating a structural design procedure for a 3D
printed wall element.
Ó 2019 Elsevier Ltd. All rights reserved.
1. Introduction Over the years construction has been a traditional industry, and
has lagged behind the other industries in using automation and
Additive manufacturing (AM) is a technique which uses a three- implementing the same level of technological advancement [3].
dimensional computed-aided design (CAD) model to fabricate a Recently there has been a growing interest in examining the pro-
physical object [1]. AM techniques have proven to be beneficial spects of 3D printing in the construction industry. In such a pro-
in many industrial processes. Many industries such as automotive, cess, a structure is formed by the layer-wise deposition of
aerospace and industries manufacturing consumer based products material based on a CAD model. In a typical 3D printing process,
have been using such techniques to optimize the cost and time of at first a set of commands called G code are generated using the
their manufacturing process [2]. computer model of the object to be printed. The material is then
extruded out through the print head based on the print path dic-
tated by the G code. Once the concrete extrudes out as a filament
⇑ Corresponding author. from the print head, it must possess enough strength to resist
E-mail address: manusanthanam@gmail.com (M. Santhanam). deformation under its own weight as well as due to the weight
https://doi.org/10.1016/j.conbuildmat.2019.116710
0950-0618/Ó 2019 Elsevier Ltd. All rights reserved.
2 A.V. Rahul et al. / Construction and Building Materials 227 (2019) 116710
of layers being deposited above it. Since the concrete can self sup- at the bulk, vertical and horizontal interfaces, and compared with
port, such a form of construction eliminates the need of formwork. that of mould cast concrete. The strength at the vertical and hori-
It also offers great potential in terms of time saving, and providing zontal interface is further characterized by conducting a bond
design and geometric flexibility [4–6]. shear test. The bond strength is compared to the shear strength
Most of early research work on concrete 3D printing was of mould cast concrete. In the second stage of study, the anisotropy
focused on mixture design and in understanding the rheological of the printed specimens and its reasons are examined by testing
requirements for the process control [7,8]. Thereafter, there were cubes and beams, cut out from a 3D printed wall prototype. Com-
studies examining the mechanical behaviour of printed concrete parisons are made with respect to the strength values of mould
elements. For instance, Le et al. [9] showed that 3D printable con- cast concrete. Finally, based on the results obtained form the study,
crete elements can be anisotropic. In the study, compressive and perspectives on the structural design of a 3D printed wall element
flexural strengths were evaluated in different loading directions are provided.
and compared with that of the mould cast specimens. The mould
cast specimens had high compressive and flexural strengths of
2. Materials and mix proportions
about 107 N/mm2 and 11 N/mm2 respectively. On the other hand,
the compressive and flexural strengths of printed specimens were
Portland cement conforming to IS 12269 [17] was used in the
lower and varied from 91 to 102 N/mm2 and 6 to 17 N/mm2
study. Class F fly ash conforming to ASTM C618 [18] and silica
respectively, depending on the loading direction. Panda et al. [10]
fume conforming to ASTM C1240 [19] were used as supplementary
also observed similar results when comparing the compressive
cementitious materials. Attapulgite clay with an average particle
and flexural strengths of 3D printed and mould cast geopolymer
size of 1.5–2 lm was used as a rheology modifier. Tables 1 and 2
concrete. A 15 7 mm rectangular nozzle was used in their study.
show the oxide composition of the binders and the clay particles
Apart from this, a few other researchers have also reported aniso-
respectively. A polycarboxylic ether (PCE) based superplasticizer
tropic behaviour for printed concrete elements [11–13]. Le et al. [9]
and hydroxypropyl methylcellulose (HPMC) based viscosity modi-
also observed the presence of voids at the junction between four
fying agent (VMA) were used as chemical admixtures. The VMA
filaments when circular nozzle was used. The voids were more pre-
was used in the solid form and the superplasticizer was used in
dominant in the case of poorly printed specimens. The number and
the liquid form. The solid content of the superplasticizer was
size of the voids were considerably reduced in the case of well
34%. Polypropylene (PP) fibers were used in all the mixes. The
printed specimens having a higher dosage of superplasticizer.
length and thickness of the fibers were 12 mm and 40 lm respec-
The well printed specimens were found to have a higher density
tively. Two grades of quartz sand (sand 1 and sand 2) and quartz
as compared to mould cast specimens. The reason for this higher
powder were used as fine aggregates. The specific gravities of
density is not well understood. It may because of the higher com-
materials used are shown in Table 3. Fig. 1 shows the particle size
paction and packing density achieved during the extrusion of the
distributions (PSD) of the materials used. Laser diffraction was
printed elements.
used to determine the PSD of quartz powder, fly ash and cement.
Contrary to the results obtained by Le et al. [9], Nerella et al.
Since it was not possible to disperse the densified silica fume prior
[11] found that the compressive strength of printed specimens
to laser diffraction, the PSD shown is as given by the manufacturer.
was higher by about 10% as compared to mould cast specimens
Sieve analysis was used in determining the PSD of sand 1 and 2.
when tested along certain directions. These contradictions in the
results indicate that the mechanical properties would also be
dependant on the type of mix used, the printer system and the 2.1. Mix proportion
print parameters used in a particular study. For instance, Panda
et al. [14] showed that the tensile bond strength can depend on Three mixture formulations (SF, NC and VM mix) were used in
the print parameters such as time gap between two successive lay- the study (see Table 4). For the SF mix, silica fume was used as a
ers, print speed and the height from which the nozzle is depositing
the layer. It was found that the bond strength decreased with Table 1
Chemical composition of cement, silica fume and fly ash.
increasing time gap between layers. Further, the increase in print
speed or the height of the nozzle from the deposited layer also Chemical composition Quanitiy (% by mass)
led to the decrease in the tensile bond strength. The decrease in Cement Silica fume Fly ash
tensile bond strength with increased time gap was also observed CaO 64.59 0.4 1.28
by a few other researchers [9,10]. Al2O3 4.17 – 29.95
Some of the recent studies have shown that the ambient condi- SiO2 19.01 96.8 59.32
tions during printing can also have an effect on the bond strength Fe2O3 3.89 – 4.32
(Na2O)e 0.16 – 0.16
between layers. For instance, Roussel [15] measured the interface
LOI 1.40 – –
strength when the layers were protected from drying and also
when exposed to drying. It was found that the interface strength
reduced by even up to 50% when the printed layers were exposed
Table 2
to drying. Similar observations were also made in the study by San-
Chemical composition of attapulgite clay used in the study.
jayan et al. [16]. They showed that the bond strength was found to
depend on the surface moisture content at the interface between Chemical composition Quanitiy (% by mass)
the layers. The removal of surface moisture due to evaporation SiO2 55.2
caused a reduction in the bond strength. Al2O3 12.2
Fe2O3 4.05
The work presented in this paper focuses on developing test
TiO2 0.49
methods which can be used for the characterization of the CaO 1.98
mechanical behaviour of a 3D printed wall element. Based on the MgO 8.56
strength values obtained from the different tests conducted, a pro- K2O 0.68
cedure is suggested for its structural design. The study comprises Na2O 0.53
P2O5 0.65
of two stages. In the first stage, the interface of printed concrete LOI 15.66
is examined. The porosity of the printed concrete is determined
A.V. Rahul et al. / Construction and Building Materials 227 (2019) 116710 3
Table 3 Table 4
Specific gravities of materials used. Mixture proportions used (based on a previous study [20]).
takes two minutes to complete an entire perimeter. Since, there are 3.2. Determination of porosity
four horizontal layers for the actual structure, the time gap
between two vertical layers will be eight minutes. Therefore for For both mould cast and printed concrete, porosity was deter-
the laboratory studies, the time gap between two horizontal layers mined by using 20 10 10 mm specimens. For the mould cast
was kept as two minutes and that between two vertical layers was concrete, the specimens were cut out from 50 50 50 mm
kept as eight minutes. cubes. Four specimens were assessed and the average value was
The different stages in the printing process of the wall proto- reported. For the printed concrete, a total of two wall prototypes
type are schematically shown in Fig. 3. At first, a single filament were printed to obtain two specimens each from locations 1–6
of length 240 mm was extruded (Fig. 3a). After this the nozzle (shown in Fig. 4). The assessment of porosity was made at the bulk,
was moved horizontally by 30 mm (width of the nozzle) and an horizontal and vertical interfaces of the wall element. For the
adjacent horizontal layer was printed next to the first layer assessment of porosity in the bulk concrete, the specimens cut
(Fig. 3b) after a time gap of two minutes. Following this, the nozzle out vertically from the location 3 and 4 were used. For the interface
was raised by 30 mm (height of the nozzle) and horizontally between two horizontal layers, the specimens extracted vertically
moved to align on top of the first layer. A vertical layer was depos- from the locations 1 and 2 were used. For the interface between
ited on top of first layer after a total time gap of eight minutes after two vertical layers, specimens extracted horizontally from the
the deposition of the first layer (Fig. 3c). This process was contin- locations 5 and 6 were assessed.
ued until the entire specimen comprising of six vertical and two The determination of porosity was by the vacuum saturation
horizontal layers was printed (Fig. 3d). Since the height of the noz- method. The specimens were first oven-dried at 50 °C for seven
zle was 30 mm, the expected height of the wall prototype having days. After this, they were placed in a vacuum desiccator for 3 h
six vertical layers was 180 mm. But 2–3% compression was to remove any excess moisture and also to allow the specimens
observed in the wall prototype for all the mixes. The average to cool to the room temperature (25–30 °C). Following this, the
heights of wall prototype were 176.3 ± 1.1, 175.8 ± 1.3 and specimens were kept immersed in the desiccator filled with cal-
175.1 ± 1.4 mm for SF, NC and VM mix respectively. cium hydroxide solution and maintained under vacuum. After
Fig. 4. Extracting specimens from the wall element for the assessment of porosity.
one hour, the vacuum was released and the specimens were kept a Zwick Roell testing machine fitted with a 5 kN load cell. The fix-
immersed in the solution for another duration of 18 h. The vacuum ture for bond shear test is shown in Fig. 6. With the interface at the
saturated porosity (q) is given by centre, the cylindrical specimen is placed horizontal in the grooves
of upper and lower jaws of the fixture. The jaws are then pulled
M1 M2
q¼ 100 ð1Þ apart at a constant displacement rate of 0.1 mm/minute. The fail-
M1 M3 ure load is divided by the cross-sectional area of the cylinder to
In the above equation, M 1 is the mass of the saturated specimen obtain the bond shear strength. The cylindrical specimens cut out
in air, M2 is the mass of the dried specimen in air and M 3 is the from mould cast cubes were also tested in a similar manner to
mass of the saturated specimen in water. Similar methods has been obtain the shear strength of mould cast concrete.
previously used by other researchers to determine the porosity of
cementitious materials [23,24]. 3.4. Determination of compressive strength
3.3. Determination of bond strength The compressive strength was determined by using
50 50 50 mm cubes. For printed concrete, six cubes were cut
Cylindrical specimens having 25 mm diameter and 40 mm out from the wall element and tested in three different loading
height were used for the bond shear test. The locations from which direction (D1, D2 and D3) as shown in Fig. 7. The locations from
specimens were extracted from the wall element are shown in where the cubes were extracted are shown in Fig. 8. Since the
Fig. 5. For characterizing the interface between horizontal layers, width of wall element was 60 mm and the required width of cube
six cylindrical specimens each were cut out horizontally from loca- was 50 mm, a slice of 5 mm was removed from both sides to cut
tion 1 and 2. Similarly for the vertical layers, six specimens each out the cubes from the locations shown in Fig. 8. The locations 1
were cut out vertically from location 3 and 4. Cylindrical speci- and 4 were used to obtain cubes for loading along D1 direction
mens were also cut out from 50 50 50 mm mould cast cube while locations 2 and 5, and locations 3 and 6 were used for load-
specimens to assess the shear strength of mould cast concrete. ing along D2 and D3 directions respectively. Six wall prototype ele-
Direct bond shear test methods can be used to determine the ments were printed such as to obtain a total of twelve cubes each
strength of overlay materials [25]. For the current study, a direct for the three loading directions. Twelve cubes of 50 50 50 mm
bond shear test was performed on the cut out specimens by using size were also prepared in standard moulds. For both the printed
Fig. 5. Extracting specimens from the wall element for bond shear test.
6 A.V. Rahul et al. / Construction and Building Materials 227 (2019) 116710
Fig. 8. Extracting cubes from the wall element for compression test.
4. Results and discussions
and mould cast cubes, the loading rate and testing procedure was 4.1. Porosity
in accordance with ASTMC109/C109M [21].
The porosities determined for the three mixes are shown in
3.5. Determination of flexural strength Fig. 12. Compared to the mould cast concrete, the porosity of the
specimens extracted from the interface between horizontal layers
The flexural strength was determined by a three-point bending was found to be higher by 13.3, 12.9 and 11.5% for SF, NC and
test using 160 40 40 mm beams. The mould cast beams were VM mixes respectively. Likewise, for the specimens extracted from
prepared in standard moulds. For printed concrete, beams were the interface between vertical layers, the porosity was higher by
cut out from three different locations as shown in Fig. 9. Since 15.3, 11.9 and 10.6% respectively. Also, as seen in Fig. 12, the poros-
the width of wall element was 60 mm and the required width of ity was found to be similar for both vertical and horizontal inter-
beams was 40 mm, a slice of 10 mm was removed from both sides faces. The higher porosities indicate weak joints being formed at
to cut out the beams from locations indicated in Fig. 9. When sub- the interface of the printed concrete specimen. Contrary to this,
A.V. Rahul et al. / Construction and Building Materials 227 (2019) 116710 7
Fig. 9. Extracting beams from the wall element for flexural test.
Fig. 12. Comparison of porosities in the bulk and interfaces of printed concrete with that of mould cast concrete.
for the specimens extracted from the bulk of the printed concrete, It is to be noted that the bond strength can depend on the print
the porosity was found be lower by 7.1, 6.9 and 7.3% as compared parameters, especially the time gap between the deposition of lay-
to mould cast concrete for SF, NC and VM respectively. This ers [9,10,14]. For the current study, the time gap between two hor-
reduced porosity observed in the bulk concrete may be because izontal layers was two minutes while it was eight minutes for the
of a higher compaction and packing achieved during the extrusion vertical layers. In an earlier study, Le et al. [9] conducted tensile
process. bond tests on printed concrete elements and found a strength
Therefore, for the time gap and other print parameters used in reduction of about 23% for time gaps of 0 to 15 min. This reduction
the current study, a 3D printed element has a more densified bulk is similar to the values observed in the current study. Also, it is to
but a more porous interface compared to a monolithic element be noted that preventing drying can reduce the strength reduction
made with the same concrete. This higher porosity at the interfaces at the interface [15,16]. However, for the current study no specific
may result in a relatively lower compressive and flexural strength care was taken to control drying of the layers. All experiments
for printed elements as will be seen in the subsequent sections of were conducted at the ambient conditions of 30 C and 70% relative
this article. humidity.
The results of the bond shear tests are shown in Fig. 13. Com- The results of the compressive strength tests are shown in
pared to the shear strength of the respective mould cast concrete, Fig. 14. For all the loading directions (D1, D2 and D3), the compres-
the bond shear strength between vertical layers were found to be sive strength of the printed concrete was lower as compared to the
lower by 29.2, 26.4 and 22.5% for SF, NC and VM mix. For the inter- mould cast concrete. For the loading direction D1, the strength was
face between horizontal layers, the reduction in strength was 24.3, lower by 16.5, 14.2 and 12.8% for SF, NC and VM mix respectively.
24.1 and 24.1% respectively. This further indicates a weaker joint The strength decrease along D2 direction was 19.3, 18.6 and 15.5%
formed at the vertical and horizontal interfaces. These results are while along D3 direction, it was 21.3, 19.6 and 16.5%.
in agreement with the trends observed in the porosity The decreased compressive strength observed for the printed
measurements. specimens can be explained as being due to presence of weaker
Fig. 13. Comparison of bond shear strength with shear strength of mould cast concrete.
A.V. Rahul et al. / Construction and Building Materials 227 (2019) 116710 9
80
Mix SF Mix NC Mix VM
70
50
40
30
20
10
0
Mould cast Printed - along D1 Printed - along D2 Printed - along D3
Fig. 14. Comparison of compressive strength of printed concrete with that of mould cast concrete.
interfaces with increased porosities existing between layers. Under occurs in the bulk concrete. As seen in the porosity measurement,
a compression load, cracks may initiate from these weaker inter- the bulk concrete is more densified and has a lower porosity as
faces causing the printed concrete to fail at relatively low stress compared to the mould cast concrete. This may explain the rela-
levels as compared to mould cast concrete specimens. As seen in tively higher flexural strengths obtained when tested along E2
Fig. 14, the compressive strength values obtained along D1, D2 and E3 directions.
and D3 are similar. Hence, no anisotropic behaviour was seen in
the printed concrete when subjected to compression.
4.5. Design perspectives for a 3D printed wall
4.4. Flexural strength At present, a problem pertaining to the use of 3D printed struc-
tures is that there are no standardized procedures for characteriz-
The results of flexural strength tests are shown in Fig. 15. The ing its mechanical behaviour [26]. There is a need to understand
flexural strength was found to decrease only when tested along how the values obtained from the mechanical characterization
E3 direction. The strength decreased by 40, 35.8 and 32.9% for SF, can be utilized in formulating a structural design procedure. To
VM and NC mix respectively. On the other hand, when tested along address this, we provide some perspectives on the design of a 3D
E1 and E2 directions, the flexural strength was found to increase. printed wall. Further, we demonstrate how the values obtained
The increase when tested along E1 direction was 13.1, 14.2 and from the current test procedures can be utilized in obtaining the
15.5% and when tested along E3 direction, it was 18.1, 18.8 and parameters required for the structural design.
19.5% respectively for SF, VM and NC mix. These results indicate The results shown in Sections 4.1 and 4.2 indicate that the
that printed concrete elements exhibit anisotropic behaviour in interfaces between the layers of a 3D printed element are weaker
flexure. with higher porosity as compared to the bulk. Therefore, the design
The reason for this anisotropic behaviour can be explained of a 3D printed wall can be considered analogous to that of a con-
based on the region that is subjected to maximum bending crete masonry wall with bed joints. For a masonry wall, axial com-
moment in the three-point bending test. The flexural tests along pression, out-of-plane flexure, in-plane and out-of-plane shear (see
the E1 direction are performed with vertical beams extracted from Fig. 16) are important aspects to be considered in the design [27].
the location 1 in Fig. 9. In this case, the maximum bending moment The design requirements with respect to each of these aspects for a
and therefore the maximum bending stress develops across the 3D printed wall are presented in the following sections.
interface existing at the center of the beam. Since the interface is It should be noted that the comparison to a masonry wall may
weak and has a higher porosity, the beam fails at a low stress level not be applicable for all cases. In systems where the interlayer
as compared to the mould cast concrete. On the other hand for the bonding is good, the design may be carried out like a conventional
loading along E2 and E3 directions, the maximum bending stress monolithic concrete structure without the need to consider the
Fig. 15. Comparison of flexural strength of printed concrete with that of mould cast concrete.
10 A.V. Rahul et al. / Construction and Building Materials 227 (2019) 116710
can be further improved by utilizing this geometric flexibility. For E1 direction, the maximum bending moment and hence the
instance, consider a loading case where the out-of-plane flexure maximum flexural stress, occurs at the interface between verti-
along E1 is more critical. As seen in Eq. (4), apart from the bending cal layers existing at the center of the beam. Since the interface
resistance, f b , the moment carrying capacity also depends on sec- is weaker with higher porosity relative to the bulk, this resulted
tion properties such as the moment of inertia. With 3D printed in a reduced flexural strength along this direction. For the three
structures, the designer has the flexibility to choose more efficient mixes, the flexural strength was lower by about 32–40% when
cross-sections. For instance, choosing a hollow rectangular section tested along E1 direction. On the other hand, the flexural
with the same cross-sectional area increases the moment of inertia strength increased by 13–20% as compared to the mould cast
and therefore, the moment carrying capacity along the E1 direc- concrete when tested along E2 and E3 directions. This is
tion. Such shapes can be easily 3D printed without any additional because for these loading cases, the maximum flexural stress
formwork cost as compared to a conventional concrete structure. is induced in the bulk of the printed concretes which has a rel-
In the foregoing sections, a design procedure for a 3D printed atively lower porosity as compared to the mould cast concrete.
wall element, analogous to that of unreinforced concrete masonry 5. A problem concerning the use of 3D printed structures is how
was presented. However, it is to be noted that for a safe design, the the different tests conducted for characterizing its mechanical
failure of the structure must occur in a ductile manner. For this, behaviour can be utilized in formulating a structural design
understanding the post-crack behaviour of 3D printed concrete procedure. Based on the recommendations for unreinforced
elements becomes important. Further, the possibility of introduc- concrete masonry, a structural design procedure was presented
ing reinforcements needs to be explored. These are part of the for 3D printed concrete wall elements. Expressions for assess-
ongoing studies at IIT Madras. ment of axial compression, out-of-plane flexure, in-plane and
out-of-plane shear are provided. Further, the authors point
5. Summary and conclusions out the importance of geometric flexibility in design of 3D
printed structures. Since, no additional cost is required for
In the current study, test methods for characterizing the formworks, complex and more efficient sections can be speci-
mechanical behaviour of 3D printed wall elements were presented. fied by a designer to improve the load carrying capacities of
At first, the effect of interfaces in printed concrete elements was 3D printed elements.
examined. For this, an assessment of porosity was made in the bulk
and in the interfaces between the horizontal and the vertical layers
of printed concrete elements. The bond strength was evaluated by Declaration of Competing Interest
performing direct bond shear tests. Further, compression and flex-
ure tests were carried out in different loading directions to exam- The authors declare that they have no known competing finan-
ine the anisotropic behaviour of the printed concrete. The porosity cial interests or personal relationships that could have appeared
and the strength values were compared to that obtained for mould to influence the work reported in this paper.
cast concrete. Finally, some perspectives on the structural design of
a 3D printed wall element were provided. The major conclusions
Acknowledgements
from the study are as follows:-.
The authors express their sincere gratitude towards Tvasta
1. For all the three mixes considered in the study, the porosity was
Manufacturing Solutions Private Limited for developing the test
found to be higher for the specimens extracted from the inter-
bed printer used in the study. The authors would like to thank
faces between horizontal and vertical layers compared to the
Active Minerals International, LLC for the supply of Attapulgite
mould cast concrete. The porosity was higher by 11–14% for
clay.
specimens extracted from interface between horizontal layers
while it was 10–16% for the specimens extracted from the inter-
face between vertical layers. On the contrary, the porosity was References
found to be lower by about 6–8% for the specimens extracted
[1] B. Mueller, Additive manufacturing technologies–rapid prototyping to direct
from the bulk in the printed concrete. Overall, this suggests that digital manufacturing, Assembly Automation 32 (2012) 2.
although the bulk in printed concrete is more dense as com- [2] T. Wohlers, Rapid prototyping & tooling state of the industry: 1998 worldwide
pared to mould cast concrete, the interface forms weak regions progress report, Mater. Technol. 13 (4) (1998) 174–176, https://doi.org/
10.1080/10667857.1998.11752797.
with higher porosity. [3] S. Martinez, A. Jardon, A. Gimenez, C. Balaguer, J. Navarro, C. Barcena,
2. For all the three mixes studied, the bond shear strength at the Robotized lean assembly in the building industry, in: Proceedings of the
interface between the horizontal and vertical layers was found 25th International Symposium on Automation and Robotics in Construction
(ISARC), 2008, pp. 195–201.
to be lower by 24–25% and 22–30% respectively as compared to [4] R.A. Buswell, R. Soar, A.G. Gibb, A. Thorpe, Freeform construction: mega-scale
the shear strength determined for mould cast concrete. This rapid manufacturing for construction, Autom. Constr. 16 (2) (2007) 224–231,
indicates a weak joint being formed at the interface between https://doi.org/10.1016/j.autcon.2006.05.002.
[5] R.A. Buswell, A. Thorpe, R. Soar, A.G. Gibb, Design, data and process issues for
layers for the printed concrete. These results are in agreement mega-scale rapid manufacturing machines used for construction, Autom.
with the trends observed in the porosity measurements. Constr. 17 (8) (2008) 923–929, https://doi.org/10.1016/j.autcon.2008.03.001.
3. Due to the presence of weak interfaces in the printed concrete, [6] S. Lim, R.A. Buswell, T.T. Le, S.A. Austin, A.G. Gibb, T. Thorpe, Developments in
construction-scale additive manufacturing processes, Autom. Constr. 21
the compressive strength was lower by 12–22% as compared to (2012) 262–268, https://doi.org/10.1016/j.autcon.2011.06.010.
the mould cast concrete. The compressive strength was found [7] T.T. Le, S.A. Austin, S. Lim, R.A. Buswell, A.G. Gibb, T. Thorpe, Mix design and
to be similar when tested along the three loading directions fresh properties for high-performance printing concrete, Mater. Struct. 45 (8)
(2012) 1221–1232, https://doi.org/10.1617/s11527-012-9828-z.
D1, D2 and D3. Therefore, no anisotropic behaviour was
[8] A. Kazemian, X. Yuan, E. Cochran, B. Khoshnevis, Cementitious materials for
observed when subjected to compression loads for printed construction-scale 3d printing: laboratory testing of fresh printing mixture,
concrete. Constr. Build. Mater. 145 (2017) 639–647, https://doi.org/10.1016/
4. The flexural strength of the printed concrete was found to j.conbuildmat.2017.04.015.
[9] T.T. Le, S.A. Austin, S. Lim, R.A. Buswell, R. Law, A.G. Gibb, T. Thorpe, Hardened
depend on the region subjected to the maximum bending properties of high-performance printing concrete, Cem. Concr. Res. 42 (3)
moment in the three-point bending test. When tested along (2012) 558–566, https://doi.org/10.1016/j.cemconres.2011.12.003.
12 A.V. Rahul et al. / Construction and Building Materials 227 (2019) 116710
[10] B. Panda, S.C. Paul, L.J. Hui, Y.W.D. Tay, M.J. Tan, Additive manufacturing of [19] ASTM C1240-15, Standard Specification for Silica Fume Used in Cementitious
geopolymer for sustainable built environment, J. Cleaner Prod. 167 (2017) Mixtures, ASTM International (2015).
281–288, https://doi.org/10.1016/j.jclepro.2017.08.165. [20] A. Rahul, M. Santhanam, H. Meena, Z. Ghani, 3d printable concrete: mixture
[11] V. Nerella, M. Krause, M. Näther, V. Mechtcherine, Studying printability of design and test methods, Cem. Concr. Compos. 97 (2019) 13–23, https://doi.
fresh concrete for formwork free concrete on-site 3d printing technology org/10.1016/j.cemconcomp.2018.12.014.
(CONprint3D), in: Proceeding for the 25th Conference on Rheology of Building [21] ASTM C109/ C109M-16a, Standard Test Method for Compressive Strength of
Materials, 2016. Hydraulic Cement Mortars (using 2-in. or [50-mm] cube specimens), ASTM
[12] B. Panda, S.C. Paul, M.J. Tan, Anisotropic mechanical performance of 3d printed International (2016).
fiber reinforced sustainable construction material, Mater. Lett. 209 (2017) [22] ASTM C348-14, Standard Test Method for Flexural Strength of Hydraulic-
146–149. cement Mortars, ASTM International (2014).
[13] S.C. Paul, Y.W.D. Tay, B. Panda, M.J. Tan, Fresh and hardened properties of 3d [23] Y. Bu, R. Spragg, W. Weiss, Comparison of the pore volume in concrete as
printable cementitious materials for building and construction, Arch. Civil determined using ASTM C642 and vacuum saturation, Adv. Civil Eng. Mater. 3
Mech. Eng. 18 (1) (2018) 311–319, https://doi.org/10.1016/j.acme.2017.02.008. (1) (2014) 308–315.
[14] B. Panda, S.C. Paul, N.A.N. Mohamed, Y.W.D. Tay, M.J. Tan, Measurement of [24] Y. Dhandapani, M. Santhanam, Assessment of pore structure evolution in the
tensile bond strength of 3d printed geopolymer mortar, Measurement 113 limestone calcined clay cementitious system and its implications for
(2018) 108–116, https://doi.org/10.1016/j.measurement.2017.08.051. performance, Cem. Concr. Compos. 84 (2017) 36–47.
[15] N. Roussel, Rheological requirements for printable concretes, Cem. Concr. Res. [25] R. Leutner, Untersuchung des schichtenverbundes beim bituminösen oberbau,
112 (2018) 76–85, https://doi.org/10.1016/j.cemconres.2018.04.005. Bitumen 41 (3) (1979).
[16] J.G. Sanjayan, B. Nematollahi, M. Xia, T. Marchment, Effect of surface moisture [26] R.A. Buswell, W.L. de Silva, S. Jones, J. Dirrenberger, 3d printing using concrete
on inter-layer strength of 3d printed concrete, Constr. Build. Mater. 172 (2018) extrusion: a roadmap for research, Cem. Concr. Res. 112 (2018) 37–49, https://
468–475. doi.org/10.1016/j.cemconres.2018.05.006.
[17] IS 12269 I.S.D, Specification for 53 grade ordinary Portland cement. Bureau of [27] Allowable stress design of concrete masonry based on the 2012 IBC and 2011
Indian Standards, New Delhi, 2013.. MSJC. National Concrete Masonry Association; 2013..
[18] ASTM C618-17a, Standard Specification for Coal Fly Ash and Raw or Calcined
Natural Pozzolan for Use in Concrete, ASTM International (2017).