Date: 2011-01-18

Enquiry dated:
Project: EWA - Bin Laden
Quotation-no.: 09-040-5
Item: Freezer Room
Reference:

Evaporator (dx) S-GHF 050.2H/27-ENJ50.E


Capacity: 16.3 kW Refrigerant: R404A(1)
Surface reserve: 0.1 % Evaporation temp.: -28.0 °C
Air flow: 13500 m³/h Superheating: 5.0 K
Air velocity: 2.7 m/s
Air inlet: -19.8 °C 95 % Condensing temp.: 55.0 °C
Air outlet: -22.6 °C 100 % Subcooled temp.: 54.7 °C
Air pressure: 1013 mbar
Condensate: 2.33 kg/h Mass flow: 957 kg/h
Heat transf. coeff.: 45.84 W/(m²·K)
Fans: 2 Piece(s) 3~400V 60HzY/(--)
Data per motor (nominal data): Noise pressure level: 57 dB(A) in 3.0 m(2)
Speed: 1300 min-1 / (--) Noise power level: 79 dB(A)
Capacity (mech./el.): 0.38 kW/0.70 kW Air throw: approx. 42 m(3)
Current: 1.25 A(4) Frost: 1.0 mm
Casing: AlMg3, Powder coated RAL 9003 Tubes: Copper
Surface: 80.6 m² Fins: Aluminum
Tube volume: 28.6 l Distr. press. drop: 0.8 bar
Fin spacing: 7.00 mm Outlet connection: 54.0 * 2.00 mm
Dry weight: 143 kg(5) Inlet connection: 35.0 mm
Max. operating pressure: 32.0 bar
Page 1/2

Dimensions:(5)
Length: 2470 mm
Width: 665 mm
·

Height: 745 mm(5)


Unnamed

No. suspensions: 6
(S = Outlet connection: 54.0 * 2.00 mm, Capillary tubes: 8.0 * 1.00 mm, 650 mm)
(1) Fluid group 2 according to pressure equipment directive 97/23/EG and directive 67/548/EWG
·

(2) by using the enveloping surface method acc. to EN 13487


Güntner Product Calculator Customer, 2011.03/2010-11-10, PL 1/2011

(3) Distance at which an air velocity of 0.5 m/s can still be measured isothermally in an ideal space. The achievable penetration
depth of the air flow in the cold room depends on the spatial geometry and other factors.
(4) The current consumption can differ in dependance of the air temperature and of the variations of system voltage according to
the VDE guidance.
(5) Dimensions and weights are not valid for all possible options! They may differ for units with accessories or special units (S-...).
S-GHF 050.2H/27-ENJ50.E Project: EWA - Bin Laden
Quotation-no.: 09-040-5
Item: Freezer Room
Reference:

F A C E E
ØD

K
B 45° L

File: EMF\GHN2a_2_UNI.emf

L = 2470 mm B = 665 mm H = 745 mm


E = 1000 mm F = 545 mm C = 240 mm
A = 550 mm ØD = 11 mm K = G1¼

Drain according to DIN ISO 228-1 with G-thread (flat gasket).


Attention: Drawing and dimensions not valid for all accessory options!

Accessories Piece(s)
Page 2/2

El. defrost for coil and tray 400V-3~N-11.15kW(1) 1


(1) Fuse protection according to connected load on connection diagram, max. 25 A
·
Unnamed
·