CGS-A™ Series
GAS BOILER
9700609
C GS _ 0 A
He a ti ng C o ntr a c to r P ho ne Numb e r
A d d re s s
DANGER CAUTION
Indicates an imminently hazardous situation Indicates a potentially hazardous situation which,
which, if not avoided, will result in death, serious if not avoided, may result in moderate or minor
injury or substantial property damage. injury or property damage.
WARNING NOTICE
Indicates a potentially hazardous situation which, Indicates special instructions on installation,
if not avoided, could result in death, serious injury operation, or maintenance which are important
or substantial property damage. but not related to personal injury hazards.
I. Pre-Installation
NOTICE
Before using copper for steam piping, consider the following characteristics of copper piping:
1) High coefficient of thermal expansion can induce mechanical stresses and cause expansion/
contraction noises if not accounted for in the piping system design and installation,
2) High heat transfer rate (heat loss) of un-insulated copper piping must be included in the normal piping
and pickup factors used to size the boiler,
3) Soldering or brazing pastes and fluxes that end up in the system can cause poor heat transfer, surging,
an unsteady water line and wet steam if not thoroughly removed during boil out procedure and,
4) Galvanic corrosion of the adjoining metal may occur due to dissimilar metals in certain water chemistries
if dielectric unions are not used.
Oxygen contamination sources are system leaks C. Remove Jacket Front Panel. Remove parts bag from
requiring addition of makeup water, fittings, and oxygen vestibule area.
permeable materials in distribution system. Eliminate
oxygen contamination by repairing system leaks, D. Install Safety Valve in Tapping 'E'. See Figure 4. Use
repairing fittings, and using nonpermeable materials in ¾ NPT x 3" nipple and ¾ elbow provided. Safety Valve
distribution system. must be installed with spindle in vertical position.
5
E. Install Drain Valve in Tapping 'F'. See Figure 4. D 2" Return (Standard)
E ¾" Safety Valve
F 2" Drain Valve Return (Alternate)
G 2" Supply
H ¾" Limit
Probe Low Water Cutoff
K ¾"
(Plugged with McDonnell & Miller 67 LWCO)
Figure 5: Assembly Diagram for McDonnell & Miller 67 Low Water Cutoff
6
A. Size gas piping. Design system to provide adequate gas For materials or conditions other than those listed
supply to boiler. Consider these factors: above, refer to National Fuel Gas Code, NFPA
1. Allowable pressure drop from point of delivery to 54/ANSI Z223.1, or size system using standard
boiler. Maximum allowable system pressure is ½ engineering methods acceptable to authority having
psig. Actual point of delivery pressure may be less; jurisdiction.
contact gas supplier for additional information. B. Connect boiler gas valve to gas supply system.
Minimum gas valve inlet pressure is listed on rating
label. 1. Use methods and materials in accordance with local
plumbing codes and requirements of gas supplier. In
2. Maximum gas demand. Table 4 lists boiler input
absence of such requirements, follow National Fuel
rate. Also consider existing and expected future gas
Gas Code, NFPA 54/ANSI Z223.1.
utilization equipment (i.e. water heater, cooking
equipment). 2. Use thread (joint) compounds (pipe dope) resistant
to action of liquefied petroleum gas.
3. Length of piping and number of fittings. Refer to
Table 5 for maximum capacity of Schedule 40 pipe. 3. Install sediment trap, ground-joint union and manual
Table 6 lists equivalent pipe length for standard shut-off valve upstream of boiler gas control valve.
fittings. See Figure 7.
4. Corrections for the specific gravity of natural gas
can be found in Table 7.
30 70 28 ¾
40 105 42 ¾
50 140 56 ¾
60 175 70 ¾
70 210 84 ¾
Figure 7: Pilot and Gas Piping, Intermittent Ignition
80 245 98 ¾
(EI)
Table 5: Maximum Capacity of Schedule 40 Pipe in CFH For Natural Gas Pressures of 0.5 psig or Less
Length\ 0.3 inch w.c. Pressure Drop 0.5 inch w.c. Pressure Drop
[Feet] ½ ¾ 1 1¼ ½ ¾ 1 1¼
10 132 278 520 1,050 175 360 680 1,400
20 92 190 350 730 120 250 465 950
30 73 152 285 590 97 200 375 770
40 63 130 245 500 82 170 320 660
50 56 115 215 440 73 151 285 580
60 50 105 195 400 66 138 260 530
70 46 96 180 370 61 125 240 490
80 43 90 170 350 57 118 220 460
90 40 84 160 320 53 110 205 430
100 38 79 150 305 50 103 195 400
Table 6: Fitting Equivalent Lengths Table 7: Specific Gravity Correction Factors for
Natural Gas
Nominal Pipe Size
Fitting Specific Correction Specific Correction
½ ¾ 1 1¼
Gravity Factor Gravity Factor
45° Ell 0.7 1.0 1.2 1.6 0.50 1.10 1.30 1.07
90° Ell 1.6 2.1 2.6 3.5 0.55 1.04 1.40 1.04
Tee 0.60 1.00 1.50 1.00
3.1 4.1 5.2 6.9
(As Elbow) 0.65 0.96 1.60 0.97
0.70 0.93 1.70 0.94
4. All above ground gas piping upstream from manual 0.75 0.90
shut-off valve must be electrically continuous and 0.80 0.87
bonded to a grounding electrode. Do not use gas
piping as grounding electrode. Refer to National at ½ psig or less, isolate boiler from gas supply
Electrical Code, ANSI/NFPA 70. piping by closing boiler's individual manual shutoff
C. Pressure test. The boiler and its gas connection must valve.
be leak tested before placing boiler in operation. 2. Locate leaks using approved combustible gas
1. Protect boiler gas control valve. For all testing over detector, soap and water, or similar nonflammable
½ psig, boiler and its individual shutoff valve must solution. Do not use matches, candles, open flames,
be disconnected from gas supply piping. For testing or other ignition source.
10
11
F. Install Vent Connector from vent damper to chimney venting system are located and other spaces of the
or gas vent. See Figure 10. building. Turn on clothes dryers and any appliance
not connected to the common venting system.
1. Do not connect into same leg of chimney serving an Turn on any exhaust fans, such as range-hoods and
open fireplace. bathroom exhausts, so they will operate at maximum
2. Vent connector must not be smaller than vent speed. Do not operate a summer exhaust fan. Close
damper outlet. Type B is recommended, but single- fireplace dampers.
wall vent pipe may be used. Arrange venting system d. Place in operation the appliance being inspected.
so only the boiler is served by vent damper device. Follow the Lighting (or Operating) Instructions.
3. Where two or more appliances vent into a common Adjust thermostat so appliance will operate
vent, the area of the common vent should be at least continuously.
equal to the area of the largest vent plus 50% of the e. Test for spillage at the draft hood relief opening after
area in the additional vent(s). Do not connect the 5 minutes of main burner operation. Use the flame
vent of this appliance into any portion of mechanical of a match or candle, or smoke from a cigarette,
draft systems operating under positive pressure. cigar or pipe.
4. Vent connector should have greatest possible initial f. After it has been determined that each appliance
rise above vent damper consistent with headroom remaining connected to the common venting system
available and required clearance from adjacent properly vents when tested as outlined above, return
combustible building structure. doors, windows, exhaust fans, fireplace dampers and
5. Vent connector should slope upward from vent any other gas-burning appliance to their previous
damper to chimney or gas vent not less than one condition of use.
inch in four feet. No portion of vent connector g. Any improper operation of the common venting
should run downward or have dips or sags. Vent system should be corrected so the installation
connector must be securely supported. conforms with the National Fuel Gas Code, NFPA
6. Vent connector should be installed above bottom 54/ANSI Z223.1. When resizing any portion of
of chimney to prevent blockage. Inserted into but the common venting system, the common venting
not beyond inside wall of chimney liner. Seal tight system should be resized to approach the minimum
between vent connector and chimney. size as determined using the appropriate tables in
Part 11 in the National Fuel Gas Code, NFPA 54/
G. If an Existing Boiler is Removed: ANSI Z223.1.
When an existing boiler is removed from a common
venting system, the common venting system is likely
to be too large for proper venting of the appliances
remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system are
not in operation:
a. Seal any unused openings in the common venting
system.
b. Visually inspect the venting system for proper
size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion, and other
deficiencies which could cause an unsafe condition.
c. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common Figure 10: Typical Vent System Installation
12
A. General. Install wiring and ground boiler in accordance Table 8: Wiring Diagrams
with requirements of authority having jurisdiction, or
in absence of such requirements the National Electrical Low Water Ignition System
Code, ANSI/NFPA 70. Figure No.
Cutoff Intermittent (EI)
B. Connect Vent Damper. See Figure 9. 24V Probe X 15
1. Carefully remove Transformer from Junction Box. Float X 17
2. Remove 7/8" knockout from top of Junction Box.
3. Attach Vent Damper wiring harness into top of F. Wire boiler. Boiler is rated for 120 VAC, 60 hertz, less
Junction Box. than 12 amperes. Provide individual branch circuit with
fused disconnect. Connect to black and white wires and
4. Connect Vent Damper Wiring Harness to Vent green ground screw. Install Transformer on Junction
Damper Receptacle. Box.
C. Wire Low Water Cutoff (McDonnell & Miller 67 G. Vent Damper Sequence of Operation. See Figure 11.
Only). Attach Black wire to Terminal '1'. Attach Black-
White wire to Terminal '2'. 1. Vent Damper continuously powered at Terminal 1.
2. Call for heat energizes Vent Damper through
D. Install thermostat. Locate on inside wall Terminal 5.
approximately 4 feet above floor. Do not install on
outside wall, near fireplace, or where influenced by 3. Vent Damper reaches fully open position. Power is
drafts or restricted air flow, hot or cold water pipes, sent back to gas control circuit through Terminal 2.
lighting fixtures, television, or sunlight. Allow free air
4. Call for heat ends. Vent Damper closes.
movement by avoiding placement of furniture near
thermostat. Note: After Vent Damper is installed and operated
through one cycle, the control circuit will operate only
E. Wire thermostat. Provide Class II circuit between when Vent Damper is connected in control circuit.
thermostat and boiler. Connect to Blue transformer lead
and Brown relay lead. Set thermostat heat anticipator
to 0.4 amps. If system tends to overheat above
thermostat's temperature setting, reduce heat anticipator
setting by 0.1 or 0.2 amps. If system tends to
shortcycle without reaching desired room temperature,
increase heat anticipator setting by 0.1 or 0.2 amps.
CAUTION
This boiler contains controls which may cause the boiler to shut down and not restart without service. If
damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather;
or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the
boiler is inoperative.
Figure 12: Wiring Diagram, Intermittent Ignition (EI) and Hydrolevel Model 400
or McDonnell & Miller PS-802-24
Low Water Cutoff
do not attempt to place boiler in operation. The
I. Sequence of Operation with Intermittent Ignition source of blockage must be corrected by trained and
(EI). skilled personnel from a qualified service agency
1. Normal Operation before resetting switch.
a. Thermostat calls for heat. Vent Damper opens. d. Flame Roll-out Switch. Automatically interrupts
b. Ignition Module energized. Pilot Valve opens. boiler operation when flames or excessive heat are
Igniter energized to ignite Pilot Burner. present in vestibule. Vent Damper remains open with
c. Sensor proves presence of pilot flame. Main Valve call for heat. Control is single use device. If flame
opens and ignites Main Burners. roll-out switch is activated do not attempt to place
boiler in operation. The source of blockage must
d. Call for heat ends. Ignition Module is de-energized.
be corrected and the flame roll-out switch replaced
Main Valve and Pilot Valve close, extinguishing
by trained and skilled personnel from a qualified
pilot and main burners. Vent Damper closes.
service agency.
2. Safety Shutdown e. Sensor: senses pilot flame and causes ignition
a. Low Water Cutoff. Automatically interrupts main module to turn off main burner and pilot burner gas
burner operation when surface of boiler water falls flow should pilot burner flame extinguish. Ignition
to lowest permissible operating level. Vent damper module will try to relight pilot for approximately 85
closes. Normal operation resumes when water seconds after pilot burner flame is extinguished. If
returns to normal level. pilot burner flame can not be reestablished, Ignition
b. Limit: Automatically interrupts main burner Module will shutdown.
operation when steam pressure exceeds set point. Five to six minutes after shutdown, Ignition Module
Maximum allowable pressure is 15 psi. Vent Damper automatically restarts ignition sequence. Sequence
closes. Normal operation resumes when steam continues until pilot burner flame is reestablished or
pressure falls below set point. call for heat ends. Ignition Module can be manually
reset by adjusting thermostat to end call for heat
c. Blocked Vent Switch. Automatically interrupts
for one minute.
main burner operation when excessive vent system
blockage occurs. Vent Damper remains open with Vent Damper remains open with call for heat.
call for heat. If blocked vent switch is activated For Electronic Ignition Troubleshooting Guide, see
Figure 20.
14
Figure 13: Wiring Diagram, Intermittent Ignition (EI) and McDonnell & Miller 67 Low Water Cutoff
K. Sequence of Operation with Intermittent Ignition of blockage must be corrected by trained and skilled
(EI). personnel from a qualified service agency before
1. Normal Operation resetting switch.
a. Thermostat calls for heat. Vent Damper opens. d. Flame Roll-out Switch. Automatically interrupts
b. Ignition Module energized. Pilot Valve opens. boiler operation when flames or excessive heat are
Igniter energized to ignite Pilot Burner. present in vestibule. Vent Damper remains open with
call for heat. Control is single use device. If flame
c. Sensor proves presence of pilot flame. Main Valve
roll-out switch is activated do not attempt to place
opens and ignites Main Burners.
boiler in operation. The source of blockage must
d. Call for heat ends. Ignition Module is de-energized. be corrected and the flame rollout switch replaced
Main Valve and Pilot Valve close, extinguishing by trained and skilled personnel from a qualified
pilot and main burners. Vent Damper closes. service agency.
2. Safety Shutdown e. Sensor: senses pilot flame and causes ignition
a. Low Water Cutoff. Automatically interrupts main module to turn off main burner and pilot burner gas
burner operation when surface of boiler water falls flow should pilot burner flame extinguish. Ignition
to lowest permissible operating level. Vent damper module will try to relight pilot for approximately 85
closes. Normal operation resumes when water seconds after pilot burner flame is extinguished. If
returns to normal level. pilot burner flame can not be reestablished, Ignition
b. Limit: Automatically interrupts main burner Module will shutdown.
operation when steam pressure exceeds set point. Five to six minutes after shutdown, Ignition Module
Maximum allowable pressure is 15 psi. Vent Damper automatically restarts ignition sequence. Sequence
closes. Normal operation resumes when steam continues until pilot burner flame is reestablished or
pressure falls below set point. call for heat ends. Ignition Module can be manually
c. Blocked Vent Switch. Automatically interrupts reset by adjusting thermostat to end call for heat
main burner operation when excessive vent system for one minute.
blockage occurs. Vent Damper remains open with Vent Damper remains open with call for heat.
call for heat. If blocked vent switch is activated do For Electronic Ignition Troubleshooting Guide, see
not attempt to place boiler in operation. The source Figure 20.
15
CAUTION NOTICE
Avoid operating this boiler in an environment CGS-A boilers built for installation at altitudes
where saw dust, loose insulation fibers, dry wall greater than 2,000 feet above sea level have
dust, etc. are present. If boiler is operated under been specially orificed to reduce gas input rate
these conditions, the burner interior and ports 4 percent per 1,000 feet above sea level per the
must be cleaned and inspected daily to insure National Fuel Gas Code, NFPA 54/ANSI Z223.1,
proper operation. Section 8.1.2 and Appendix F. High altitude
boiler models are identifiable by the third digit in
4. Adjust thermostat to lowest setting. Refill boiler to the model number suffix on the rating label:
normal water line.
CGS _ OA _ _ - _ _ 2: less than 2000 ft. elevation
M. Check limit. CGS _ OA _ _ - _ _ 5: 2000 to 5000 ft. elevation
1. Adjust thermostat to highest setting.
2. Observe pressure gauge. When pressure is indicated,
adjust limit to setting below observed pressure. Table 9: Gas Flow Rate in Cubic Feet per Hour
Main burners should extinguish.
3. Adjust limit to setting above observed pressure. Seconds Size of Gas Meter Dial
Ignition sequence should begin. for One One-Half One Two Five
Revolution Cu. Ft. Cu. Ft. Cu. Ft. Cu. Ft.
4. Adjust thermostat to lowest setting. Adjust limit to
desired setting. 30 60 120 240 600
32 56 113 225 563
N. Check Vent Damper Operation. Vent Damper must be
34 53 106 212 529
in open position when main burners are ignited.
36 50 100 200 500
O. Adjust gas input rate to boiler (Natural Gas). 38 47 95 189 474
1. Adjust thermostat to highest setting. 40 45 90 180 450
3. Clock gas meter for at least 30 seconds. Use Table 9 56 32 64 129 321
to determine gas flow rate in Cubic Feet per Hour. 58 31 62 124 310
60 30 60 120 300
4. Determine Input Rate. Multiply gas flow rate by gas
heating value. 62 29 58 116 290
64 29 56 112 281
5. Compare measured input rate to input rate listed on
rating label. 66 29 54 109 273
68 28 53 106 265
a. Boiler must not be overfired. Reduce input
rate by decreasing manifold pressure. Do not 70 26 51 103 257
reduce more than 0.3 inch w.c. If boiler is still 72 25 50 100 250
overfired, contact New Yorker Boiler Company 74 24 48 97 243
for replacement Gas Orifices. 76 24 47 95 237
b. Increase input rate if less than 98% of rating 78 23 46 92 231
label input. Increase manifold gas pressure no 80 22 45 90 225
more than 0.3 inch w.c. If measured input rate is
still less than 98% of rated input:
17
i. Remove Main Burners per procedure in 9. Return other gas-fired appliances to previous
Section VIII. Service. conditions of use.
ii. Remove gas orifices. Drill one (1) drill size P. Adjust gas input rate to boiler (LP/Propane).
larger (drill size is stamped on orifice, or see
Section IX. Repair Parts). 1. Adjust thermostat to highest setting.
iii. Reinstall gas orifices and main burners. 2. Check manifold pressure. Adjust gas valve pressure
Measure input rate. regulator to obtain 10 inches w.c. manifold pressure.
6. Recheck Main Burner Flame. Adjust gas valve pressure regulator as necessary
(turn adjustment screw counterclockwise to
7. Follow instructions to TURN OFF GAS TO decrease manifold pressure, or clockwise to increase
APPLIANCE. See Figure 16 for intermittent manifold pressure). If pressure can not be attained,
ignition (EI). Remove manometer. check gas valve inlet pressure. If less than minimum
8. Follow Lighting or Operating Instructions to place gas supply pressure listed on rating label, contact
boiler in operation. See Figure 16 for intermittent gas supplier for assistance.
ignition (EI). Adjust thermostat to normal setting. 3. Recheck Main Burner Flame
18
4. Follow instructions to TURN OFF GAS TO Open boiler fill valve sufficiently to permit a steady
APPLIANCE. See Figure 16 for intermittent trickle of water from the pipe. Continue this slow
ignition (EI). Remove manometer. boiling and trickle of overflow for several hours
5. Follow Lighting or Operating Instructions to place until the water coming from the overflow is clear.
boiler in operation. See Figure 16 for intermittent 8. Follow instructions TO TURN OFF GAS TO
ignition (EI). Adjust thermostat to normal setting. APPLIANCE. See Figure 16 for intermittent
ignition (EI).
Q. Clean Heating System. Oil from new piping 9. Drain boiler in a manner and to a location that hot
connections and sediment in existing piping must be water can be discharged with safety.
removed from the system to prevent unsteady water line
and carry-over of entrained water into supply main. 10. Refill boiler to normal water line. If water in gauge
glass does not appear to be clear, repeat steps (1
1. Fill boiler to normal waterline. thru 3) and boil out the boiler for a longer time.
2. Follow Lighting or Operating Instructions to place S. Second Boilout for Stubborn Cases. If unsteady water
boiler in operation. See Figure 16 for intermittent line, foaming or priming persist, proceed as follows:
ignition (EI).
1. Connect hoses from boiler and return main drain
3. Operate the boiler with steam in the entire system valves to floor drain. Close shut off valve in
for several days to bring system oil and dirt back to Hartford Loop and open drain valve in return main.
the boiler. Fill boiler to normal water level.
4. Drain condensate from drain valve in wet return. 2. Follow Lighting or Operating Instructions to place
Operate boiler until condensate runs clean. boiler in operation. See Figure 16 for intermittent
ignition (EI).
R. Boil-out boiler. 3. Operate boiler at this water level for at least 30
1. Follow instructions TO TURN OFF GAS TO minutes after the condensate begins to run hot.
APPLIANCE. See Figure 16 for intermittent 4. Follow instructions TO TURN OFF GAS TO
ignition (EI). APPLIANCE. See Figure 16 for intermittent
2. Drain boiler until 1" of water is visible in gauge ignition (EI).
glass. 5. Close all radiator valves. Remove all supply main
3. Run temporary hose or piping from boiler drain air valves and plug the openings in supply main.
valve to an open drain or some other location where 6. Draw about 5 gallons of hot water from boiler into a
hot water may be discharged safely. Do not install container and dissolve into it the appropriate amount
valve in this line. of a recommended boilout compound. Remove
4. Drain about 5 gallons of hot water from boiler into a safety valve from boiler and pour this solution into
container and dissolve into it an appropriate amount boiler, then reinstall safety valve.
of recommended boil out compound. Remove 7. Follow Lighting or Operating Instructions to place
safety valve and add solution to boiler water through boiler in operation. See Figure 16 for intermittent
exposed tapping using a funnel. ignition (EI).
8. Keep operating boiler while feeding water to boiler
NOTICE slowly. This will raise water level in boiler slowly
Check with local authorities or consult local so that water will be boiling hot and will rise slowly
water treatment services for acceptable chemical into supply main and back through return main,
cleaning compounds. flowing from drain hose at about 180°F. Continue
until water runs clear from drain hose for at least 30
5. Run temporary hose or piping from boiler tapping minutes.
"E" to an open drain or some other location where 9. Stop feeding water to boiler but continue operating
hot water may be discharged safely. Do not install boiler until excess water in boiler flows out through
valve in this line (See Figure 4). supply main and water lowers (by steaming) until it
6. Follow Lighting or Operating Instructions to place reaches normal level in boiler.
boiler in operation. See Figure 16 for intermittent 10. Follow instructions to TURN OFF GAS TO
ignition (EI). APPLIANCE. See Figure 16 for
7. Operate sufficiently to boil the water without intermittent ignition (EI).
producing steam pressure. Boil for about 5 hours.
19
11. Drain boiler. Open all radiator valves. Reinstall T. Add Boiler Water Treatment.
all supply main air valves. Open shut off valve in
Hartford Loop. 1. Low pressure steam boilers such as this CGS-A
Series should be maintained with appropriate water
12. When boiler has cooled down sufficiently (iron treatment compounds. Add suitable water treatment
sections are not too hot to touch), close the drain compounds as recommended by your qualified water
valves at boiler and in return main and feed water treatment company.
slowly up to normal level in boiler.
2. Remove temporary drain valve and overflow piping
13. Follow Lighting or Operating Instructions to place and reinstall safety valve. Boil or bring water
boiler in operation. See Figure 16 for temperature to 180°F promptly in order to drive off
intermittent ignition (EI). the dissolved gases in the fresh water.
14. Allow boiler to steam for 10 minutes.
3. Make pH or Alkalinity Test.
15. Follow instructions to TURN OFF GAS TO
After boiler and system have been cleaned and
APPLIANCE. See Figure 16 for
refilled as previously described, test the pH of the
intermittent ignition (EI).
water in the system. This can easily be done by
16. Draw off one quart of water from bottom gauge drawing a small sample of boiler water and testing
glass fitting and discard. Draw off another quart with hydrion dispenser gives the reading in pH.
sample and if this sample is not clear, repeat the Hydrion paper is inexpensive and obtainable from
cycle of draining the boiler and return main and any chemical supply house or through your local
refilling the boiler until sample is clear. druggist. The pH should be higher than 7, but
If the boiler water becomes dirty again at a later date due to lower than 11. Add some of the washout chemical,
additional sediment loosened up in the piping: if necessary, to bring the pH within the specified
1. Follow instruction to TURN OFF GAS TO range.
APPLIANCE. See Figure 16 for intermittent 4. Boiler is now ready to be put into service.
ignition (EI).
2. Close shut off valve in Hartford Loop and open U. Combustion Chamber Burn-off
drain valve in return main. 1. The mineral wool combustion chamber panels
3. Follow Lighting or Operating Instructions to place contain a cornstarch based binder that must be
boiler in operation. See Figure 16 for intermittent burned out a installation to prevent odors during
ignition (EI). subsequent boiler operation.
4. Allow condensate to flow to drain until it has run 2. Ventilate the boiler room, set the high limit to its
clear for at least 30 minutes while feeding water to maximum setting, set the thermostat to call for heat.
boiler so as to maintain normal water level. Allow the boiler to fire for at least an hour or until
5. Follow instructions to TURN OFF GAS TO the odor from the cornstarch has dissipated.
APPLIANCE. See Figure 16 for intermittent 3. Return the high limit and thermostat to their desired
ignition (EI). settings.
6. Drain boiler, open shut off valve in Hartford Loop,
then repeat step R. above. V. Review User's Information Manual and system
operation with owner or operator.
20
WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualified service
agency. Inspections should be performed at intervals specified in this manual. Maintain manual in a legible
condition.
Keep boiler area clear and free of combustible materials, gasoline and other flammable vapors and liquids.
Do not place any obstructions in boiler room that will hinder flow of combustion and ventilation air.
A. General. Inspection and service should be conducted Table 10 cross-references the ignition module terminal
annually, except as noted. Turn off electrical power and designations to the ignition terminal numbers in the
gas supply while conducting service or maintenance. wiring ladder diagrams. Table 11 provides green LED
Follow instructions TO TURN OFF GAS TO status codes and recommended service action where
APPLIANCE. See Figure 16 for Intermittent Ignition applicable.
(EI). 1. Pilot flame current in micro amps can be measured
CAUTION using any standard micro-ammeter by inserting the
meter probes into the module holes labeled FLAME
Label all wires prior to disconnection when CURRENT as shown in Figure 17.
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper 2. Flame current must be measured with pilot valve
operation after servicing. open/pilot lit but the main valve closed.
3. Disconnect MV lead wire from the module before
measuring flame current. Trying to measure the pilot
B. Flame Current Measurement Procedure. flame current in series with the wiring will not yield
See Figure 17 “Measuring pilot flame current with the accurate reading.
micro-ammeter”.
4. The minimum steady pilot flame signal must be 1
μAmp (microampere) DC (direct current).
8. Apply moderate amount of good quality pipe dope 4. If cleaning is required, remove canopy from cast
to probe threads, leaving two end threads bare. iron heat exchanger. Boiler cement should be
Install probe in Tapping 'K'. Mount control on probe. scraped from canopy and heat exchanger.
Attach wire(s) between control and probe. 5. Thoroughly clean flueways with flue brush.
9. Fill boiler to normal waterline. Add water treatment 6. Clean heating surface accessible from combustion
as needed. chamber using straight handle wire brush.
23
7. Install canopy
a. Verify that sealing surfaces between canopy and
heat exchanger are clean.
b. Secure canopy to heat exchanger with carriage
bolts, nuts, and washers.
c. Seal gap between canopy and heat exchanger
with high temperature boiler cement or Dow
Corning Silastic 732 RTV, Dow Corning Silastic
736 RTV, Polybac #500 RTV, or Sil-bond RTV
4500 (Acetoxy). Do not use other adhesives or
sealants.
8. Install Main Burners per Paragraph H. Install Jacket
Vestibule Panel.
24
Table 12: Pilot Burner Location I. Check operation. Follow steps D through P from
Section VII: System Start-up.
Boiler Main Burner with Pilot Burner Located
Model Pilot Bracket * Between Main Burners * J. Lubrication. There are no parts requiring lubrication
by service technician or owner.
CGS-30 2 2&3
CGS-40 2 2&3
CGS-50 4 4&5
CGS-60 6 6&7
CGS-70 7 7&8
CGS-80 9 9 & 10
* Main burners numbered left to right as viewed from front
of boiler.
25
POWER TO CHECK LINE VOLTAGE POWER, LOW VOLTAGE TRANSFORMER, LIMIT CONTROLLER, THERMOSTAT (CONTROLLER), AND WIRING. ALSO,
MODULE? (24 V NO CHECK AIR PROVING SWITCH ON COMBUSTION AIR BLOWER SYSTEM (IF USED) AND THAT THE VENT DAMPER END SWITCH (IF USED)
NOMINAL) IS MADE.
YES
30 SECOND
PREPURGE NO REPLACE S8670
DELAY?(S8670
ONLY)
YES
CHECK IGNITION CABLE, GROUND WIRING, CERAMIC INSULATOR, AND SPARK GAP AND CORRECT.
YES CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR BUCKLING. TAKE PROTECTIVE ACTION TO SHIELD CABLE
AND BOOT FROM EXCESSIVE TEMPERATURES.
TURN GAS SUPPLY ON AND
RECYCLE "CALL FOR HEAT."
CHECK THAT ALL MANUAL GAS VALVES ARE OPEN, SUPPLY TUBING AND PRESSURES ARE GOOD, AND PILOT BURNER
ORIFICE IS NOT BLOCKED (PILOT GAS FLOWING).
CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL.
NO
PILOT BURNER CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE, IF VOLTAGE IS OK, REPLACE GAS CONTROL. IF NOT,
LIGHTS? REPLACE MODULE.
NOTE: IT MAY BE NECESSARY TO RECYCLE THE "CALL FOR HEAT" MORE THAN ONCE TO CLEAR THE PILOT SUPPLY TUBES OF AIR.
YES
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE "CALL FOR HEAT."
CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
SPARK CLEAN FLAME ROD.
STOPS WHEN CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD AND MODULE.
NO
PILOT IS CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR.
LIT? CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE.
ADJUST PILOT FLAME.
IF PROBLEM PERSISTS, REPLACE MODULE.
YES
CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE. IF NO VOLTAGE, REPLACE MODULE.
MAIN BURNER NO CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS CONTROL INCLUDING SAFETY CONTROLS WIRED IN THE CIRCUIT. IF
LIGHTS? OKAY, REPLACE GAS CONTROL.
YES
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE "CALL FOR HEAT."
CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWNS MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL
SYSTEM AT THE TIME OF CHECKOUT.
RUNS UNTIL "CALL NO CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE. PILOT FLAME MUST NOT BE MOVING AROUND DUE TO
FOR HEAT" OUTSIDE AIR FLOWS, ETC.
ENDS? ADJUST PILOT FLAME. CHECK GAS PRESSURE MEETS APPLIANCE SPECIFICATIONS WHILE APPLIANCE MAIN BURNER IS ON AND ALL
OTHER GAS APPLIANCES ON THE SUPPLY ARE OPERATING AT FULL RATE.
IF CHECKS ARE OKAY, REPLACE MODULE.
YES
All CGS-A™ Series repair parts may be obtained through your local New Yorker Boiler Co., Inc. authorized distributor. Should
you require assistance in locating a New Yorker distributor in your area, or have questions regarding the availability of New
Yorker products or repair parts, please contact New Yorker's main office:
New Yorker Boiler Co., Inc.
P.O. Box 10
Hatfield, PA 19440-0010
Phone: (215) 855-8055
Attn: Customer Service Department
Quantity
Description Part No.
30 40 50 60 70 80
61760301 1 --- --- --- --- ---
27
Quantity
Description Part No.
30 40 50 60 70 80
Main Burner Orifice, #45 (Pink) (Natural Gas) 822711 --- 5 7 --- --- ---
Main Burner Orifice, #48 (Natural Gas) 822726 4 --- --- 10 12 ---
Main Burner Orifice, #49 (Yellow) (Natural Gas) 822709 --- --- --- --- --- 15
Main Burner Orifice, 1.25 mm (Purple) (LP) 822705 --- --- 7 --- --- ---
Main Burner Orifice, #55 (Green) (LP) 822708 --- 5 --- --- --- ---
Main Burner Orifice, #56 (LP) 822707 --- --- --- --- --- 15
Main Burner Orifice, 3/64" (Blue) (LP) 822704 4 --- --- 10 12 ---
Pilot Tubing, 1/4" OD x 30" Lg. Aluminum 8236122 1 1 1 --- --- ---
Pilot Tubing, 1/4" OD x 40" Lg. Aluminum 8236123 --- --- --- 1 1 1
Gas Valve, Honeywell VR8304P4298 (Natural Gas) 81660161 --- --- --- --- 1 1
Gas Valve, Honeywell VR8304P4280 (LP/Propane) 81660160 --- --- --- --- 1 1
28
Quantity
Description Part No.
30 40 50 60 70 80
Safety Valve, 15 psi, 3/4 NPT, Conbraco 13-511-08 81660530 1 1 1 1 1 1
Gauge Glass Set, Conbraco 20-104-10 (with 9" Gauge Glass) 8056020 1 1 1 1 1 1
Syphon 806603006 1 1 1 1 1 1
Vent Damper
Effikal RVGP-4" 8116321 1 --- --- --- --- ---
29
Warning:
The Repair Parts list designates parts that contain refractory ceramic fibers
(RCF). RCF has been classified as a possible human carcinogen. When
exposed to temperatures about 1805°F, such as during direct flame contact,
RCF changes into crystalline silica, a known carcinogen. When disturbed as a
result of servicing or repair, these substances become airborne and, if inhaled,
may be hazardous to your health.
30
31
Limited Warranties
For Residential Cast Iron Steam Boilers
By this Warranty Statement New Yorker Boiler Co., Inc. (“New Yorker”) d) The boiler must be vented in accordance with chimney
issues limited warranties subject to the terms and conditions stated recommendations set forth in New Yorker’s Installation, Operating
below. These limited warranties apply to residential cast iron steam and Service Instructions.
boilers labeled with the New Yorker® brand which are sold on or after 8. Exclusive Remedy New Yorker’s obligation in the event of any
March 1, 2004 breach of these warranties is expressly limited to the repair or
replacement of any part found to be defective under conditions of
ONE YEAR LIMITED WARRANTY
normal use.
One Year Limited Warranty for Residential Cast Iron Steam Boilers
9. Limitation of Damages Under no circumstances will New Yorker
New Yorker warrants to the original consumer purchaser at the original
be liable for incidental, indirect, special or consequential
installation address that its residential cast iron steam boilers will be free
damages of any kind under these warranties, including,
of defects in material and workmanship under normal usage for a period
without limitation, injury or damage to persons or
of one year from the date of original installation. In the event that any
property and damages for loss of use, inconvenience or loss
defect in material or workmanship is found during the one-year period
of time. New Yorker’s liability under these warranties shall under
following the date of installation, New Yorker will, at its option, repair the
no circumstances exceed the purchase price paid for the boiler
defective part or provide a replacement free of charge, F.O.B. its factory.
involved. Some states do not allow the exclusion or limitation of
TEN YEAR LIMITED WARRANTY incidental or consequential damages, so the above limitation or
Ten Year Pressure Vessel Limited Warranty for Residential Cast Iron exclusion may not apply to you.
Steam Boilers New Yorker warrants to the original consumer purchaser 10. Limitation of Warranty - these limited warranties are given in lieu
at the original installation address that the pressure vessel of its of all other express warranties and set forth the entire obligation of
residential cast iron steam boilers will be free of defects in material and New Yorker with respect to any defect in a residential cast iron steam
workmanship under normal usage for a period of 10 years from the boiler. New Yorker shall have no express obligations, responsibilities
date of original installation. In the event that any defect in material or or liabilities of any kind, other than those set forth herein.
workmanship is found during the ten year period following the date of
ALL APPLICABLE IMPLIED WARRANTIES, IF ANY, INCLUDING
installation, New Yorker will, at its option, repair the defective pressure
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR
vessel or provide a replacement free of charge, F.O.B. its factory.
PARTICULAR PURPOSE, ARE EXPRESSLY LIMITED IN
EXCEPTIONS AND EXCLUSIONS
DURATION TO A PERIOD OF ONE YEAR, EXCEPT THAT IMPLIED
1. Components Manufactured by Others - following the expiration of
WARRANTIES, IF ANY, APPLICABLE TO THE PRESSER VESSEL
the foregoing one year limited warranty, all component parts of a
OF A RESIDENTIAL CAST IRON STEAM BOILER SHALL BE LIMITED
boiler which are manufactured by others (such as burners, burner
IN DURATION TO THE LESSER OF THE DURATION OF SUCH
controls, circulator, tankless water heater, and New Yorker Link)
IMPLIED WARRANTY OR A PERIOD OF TEN YEARS.
shall be subject only to the manufacturer’s warranty, if any.
2. Removal and Replacement Costs - these warranties do not cover Some states do not allow limitations on how long an implied warranty
expenses of removal or reinstallation. The consumer purchaser lasts, so the above limitation may not apply to you
will be responsible for the cost of removing and replacing any
PROCEDURE FOR OBTAINING WARRANTY SERVICE
defective part and all labor and related materials connected
Upon discovery of a condition believed to be related to a defect in
therewith. Replacement parts will be invoiced to the distributor in
material or workmanship covered by these warranties, the original
the usual manner and will be subject to adjustment upon proof of
consumer purchaser should notify the installer, who will in turn notify
defect.
the distributor. If this action is not possible or does not produce a
3. Proper Installation - these warranties are conditioned upon
prompt response, the original consumer purchaser should write to New
the installation of the boiler in strict compliance with New Yorker’s
Yorker Boiler Co., Inc. at P.O. Box 10, Hatfield, PA 19440-0010, giving
Installation, Operating and Service Instructions. New Yorker
full particulars in support of the claim.
specifically disclaims any liability of any kind which arises from or
The original consumer purchaser is required to make available for
relates to improper installation.
inspection by New Yorker or its representative the parts claimed to be
4. Improper Use or Maintenance - these warranties will not be
defective and, if requested by New Yorker, to ship those parts prepaid
applicable if the boiler is used or operated over its rated capacity,
to New Yorker at the above address for inspection or repair. In addition,
is installed for uses other than home heating, or is not maintained
the original consumer purchaser agrees to make all reasonable efforts
in accordance with New Yorker’s Installation, Operating and Service
to settle any disagreement arising in connection with any warranty claim
Instructions and hydronics industry standards.
before resorting to legal remedies in the courts.
5. Improper Operation - these warranties will not be applicable if the
boiler has been damaged as a result of being improperly serviced THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU
or operated, including but not limited to the following: operated with MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO
insufficient water; allowed to freeze; subjected to flood conditions; STATE.
or operated with water conditions and/or fuels or additives which
cause unusual deposits or corrosion in or on the pressure vessel or
associated controls.
6. Geographic Limitations - these warranties apply only to boilers
installed within the 48 contiguous United States.
7. Installation Requirements - in order for these warranties to be
effective:
a) The boiler must be installed in a single or two-family residential
dwelling. This warranty does not apply to boilers installed in
apartments or for commercial or industrial applications.
b) The boiler must be installed in strict compliance with New
Yorker’s Installation, Operating and Service Instructions, including
the installation of a low water cut-off, by an installer regularly
engaged in boiler installations.
c) Boiler sections must not have been damaged during shipment or
installation.
18