03/11/2016
ONE ADRIATICO PLACE
Seismic Analysis and Design
where:
Fx = lateral force applied to level x
W= weight at a particular level
h= height at a particular level above the base
Ft =portion of the base shear considered concentrated
at the top (level n) in addition to the computed Fn
= 0.07TV 0.25V(for T > 0.70 sec.)
= 0 (for T 0.70 sec.)
03/11/2016
ONE ADRIATICO PLACE
Seismic Analysis and Design
03/11/2016
ONE ADRIATICO PLACE
Seismic Analysis and Design
03/11/2016
UBC '97 BASE SHEAR
SOUTH LUZON MEDICAL CENTER
No. of floors, n = 10
Total height of building, hn = 45.00 m
Soil Profile Type, SD (From Table 16-J)
Seismic Zone Factor, Z = 0.40 (From Table 16-I)
Importance Factor, I = 1.25 (From Table 16-K)
Numerical Coefficient, R = 8.5 (From Table 16-N)
Seismic Source Type C (From Table 16-U)
Closest distance to known Seismic Factor 10.00 km
Near-Source Factor, Na = 1.00 (From Table 16-S)
Near-Source Factor, Nv = 1.00 (From Table 16-T)
Cv I
V= W
RT
T = Ct (hn)3/4 Ct = 0.0731
= 1.27 sec.
T 1.30T
= 1.651 sec.
V = 0.057 W
or 5.7 % of W
The total design base shear need not exceed the following:
2.5 Ca I
V= W = ### W
R
or 16.18 % of W
The total design base shear shall not be less than the following:
V = 0.11 Ca I W = ### W
or 6.05 % of W
In addition, for Seismic Zone 4, the total base shear shall also not be less than the following:
0.80 Z Nv I
V= W = ### W
R
or 4.71 % of W
03/11/2016
Vertical Distribution of Seismic Forces
V = Ft + Fx
where:
W = weight at a particular level
h = height at a particular level above the base
Ft = portion of the base shear considered concentrated
at the top (level n) in addition to the computed Fn
= 0.07TV 0.25V (for T 0.70 sec.)
= 0 (for T 0.70 sec.)
V = 11899.09 kN
STOREY Wxhx
hx Wx Fx
LEVEL HEIGHT Wxhx Wihi
m. m. kN kN
4TH 3.2 14.0 4087 57218 0.105 1252.665
3RD 3.2 10.5 23157 243148.5 0.447 5323.21
2ND 3.2 7 23157 162099 0.298 3548.81
GND 3.2 3.5 23157 81050 0.149 1774.40
03/11/2016
Static Force Procedure AGT 3-Jun-04
SOUTH LUZON MEDICAL CENTER
03/11/2016
03/11/2016
VERTICAL DISTRIBUTION OF LATERAL FORCES, Fx
V = Ft + Fx
(V - Ft) Wxhx
=
Wxhx
where:
W = weight at a particular level
h = height at a particular level above the base
Ft = portion of the base shear considered concentrated
at the top (level n) in addition to the computed Fn
Vx = Ft + Fi
Mx = Ft (hn - hx) + Fi (hi - hx)
Vx
Mx
c. MTx = Vx (0.05H)
+m. +
Vx
0.05H
PLAN
HORIZONTAL TORSIONAL MOMENTS (Sec. 2.2.5.6)
Ex.
e
shear MT = Vx e
wall + + MT
Vx
0.04h
Rw
0.03h
Rw
nor 0.004h
P-DELTA EFFECTS (Sec. 2.2.5.9)
Vx
P
Mx
EXAMPLE 1: Determination of Seismic Lateral Forces using the NSCP (1992)
Equivalent-Static-Force Method.
1 2 3 4 5 6 7
A
7.5 m.
B
7.5 m.
6 bays @ 10m.
PLAN
4.0 m.
4.0 m.
4.0 m.
LONGITUDINAL SECTION
3 DATA:
2 W1 = 7873 kN
1 W2 = 7873 kN
W3 = 6782 kN
Z= 0.4 (Manila)
I= 1.00 (Standard Occupancy)
Rw = 12 (Concrete Moment Resisting Frame, No shear wall
S= 1.50 (Soil Type 3)
Hence :
ZICW
V=
Rw
V = 2065.1 kN
STOREY hx h Wx Wh Fx Vx Mx
Wxhx kN
LEVEL m m kN Wh kN kN-m
Sample Calculation:
W2h2
F2 = (V - Ft)
Wh
62984
= (2065-0)
175860
= 740
0.040 h
=
Rw
= 0.0133 m
= 13.333 mm
= 0.5249 in
3 3 Rd2
=
d Rd2