Swain2018 PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
1

Grid Synchronization of a PV System with


Power Quality Disturbances using Unscented
Kalman Filtering
Sudarshan Swain and Bidyadhar Subudhi, Senior Member, IEEE

 domain approach such Discrete Wavelet Transform (DWT) [3]


Abstract—This paper proposes a new grid integration control provides better estimation accuracy but with increased
scheme for a single-stage PV system connected three phase grid complexity and computation burden. Phase-Locked Loop
that implements an Unscented Kalman Filter algorithm (UKF) to (PLL) synchronization schemes such as Synchronous
abstract the fundamental components of the PCC voltage and load
Reference Frame PLL (SRF-PLL) are proposed for grid
current. The DC link capacitor voltage and the PCC voltage are
regulated using a Proportional Integral (PI) controller. UKF connected systems [4]. However, SFR-PLL produces
effectively extracts the fundamental components of the PCC inaccurate estimation for an unbalanced grid.
voltage and the load current by updating the Kalman gain such Current developments on synchronization techniques with
that the estimation error variances for the elements of the state the grid are mostly based on the state estimation methods.
vector estimated is minimized. The simulation and real-time Conventional Weighted Least Square (WLS) estimation
studies show that the proposed UKF-PI control scheme effectively technique for state estimation, is reported in [5]. A least
extracts the maximum PV power and mitigates load current
squares-Kalman technique is proposed in [6] to observe and
harmonics decreasing the Total Harmonic Distortion (THD) of the
utility grid current under distorted grid voltage condition. The
check the grid voltage flicker and fluctuations. Kalman Filter
THD is within the limits prescribed by the IEEE 519. The (KF) also has been used for harmonic compensation and grid
performance of the proposed scheme is verified under grid voltage synchronization by efficiently estimating the harmonic
sag and swell conditions. The results obtained envisage that components in the load current and fundamental component of
effective grid synchronization is achieved with Power Quality the PCC voltage [7-8]. But, KF provides optimal estimate only
Disturbances i.e. the grid current is sinusoidal whilst the PCC for linear system. A popular choice for nonlinear application of
voltage is regulated by providing appropriate reactive power. KF is the Extended KF (EKF). EKF based schemes has been
reported for smart power grid synchronization [9-10].
Index Terms— Grid synchronization, PV system, Unscented Linearization approximation adopted in EKF matches only up
Kalman Filter (UKF), Unscented Transforms (UT), sigma to the first term of the actual signal. In [11], a more accurate
points nonlinear approximation method Unscented Transforms (UT)
is reported, which matches the true value of the signal up to its
I. INTRODUCTION third term. UT approximation propagates the covariance and
friendly nature and declining price of PV mean through the nonlinear system function. A set of sigma
E NVIRONMENT
modules have given high impetus to synchronize PV power points are chosen to preserve the nonlinear nature of the system.
UKF which uses UT has been successfully employed for
into the grid, to meet the increasing load demand. Grid
synchronization is a challenging task especially when the PCC estimating parameters of induction motor drive and
voltage is distorted by local nonlinear loads and also due to grid synchronous generator application [12-14] providing excellent
disturbances (sag and swell conditions).
LlB RlB

Therefore, for effective grid synchronization, a fast and (L B )


accurate algorithm is necessary which estimates the ilB PCC

fundamental components of the PCC voltage accurately while ilA


Grid
( Pl , Ql ) il
LlA RlA

considering the power quality disturbances. Various grid (LA )


Lg vg
synchronization of PV system have been reported in literature PV
Array
[1-10]. Zero-crossing method used for grid synchronization is I PV
VSI ig ( Pg , Qg )
( Pi , Qi ) ii
sensitive to harmonics [1]. Grid synchronization scheme based
vp
on Improved Linear Sinusoidal Tracer (ILST) [2] with a fixed Cdc Lf
cutoff frequency yields inaccurate estimation of the
fundamental component for frequency variation. Frequency Fig. 1. Topology of single stage grid integrated PV system with multiple
loads connected at the PCC

Sudarshan Swain and Bidyadhar Subudhi are with the Dep. of Electrical
Engg., NIT, Rourkela, Odisha, 769008, India. E-mail:
sudarshan.nitrkl@gmail.com, bidyadhar@nitrkl.ac.in.

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
2

estimation results. In view of the above successful application current ig is the same as the load current il. As the nonlinear load
of UKF, it is intended to employ UKF for achieving effective LA draws a non-sinusoidal current ila, the grid current ig also
synchronization of a PV system to a grid under Power Quality becomes non sinusoidal. Since ig is distorted, it distorts the PCC
Disturbances. The contributions of the paper are listed as: voltage vp, which in turn distorts the linear load at PCC. A
 Faster and accurate estimation of fundamental components distorted utility grid further increases the harmonic content of
of the distorted load current and PCC voltage using UKF vp while voltage sag or swell condition directly affect vp. Hence
 Providing active power control and maximizing the active it affects the loads connected at the PCC. In order to achieve
power injection into the grid at unity power factor (UPF) efficient grid synchronization, the VSI needs to be controlled
whilst maintaining the grid current sinusoidal. such that it ig becomes sinusoidal.
 Regulation of the PCC voltage.
The rest of paper is organized as follows. The proposed UKF- III. PROPOSED UKF-PI BASED CONTROL ALGORITHM FOR
PI control scheme for grid synchronization of a PV system GRID SYNCHRONIZATION OF PV SYSTEM
presented in Section II. In Section III, both simulation and Fig.2 shows the configuration of the proposed UKF-PI based
experimental results with analysis are provided. The paper is control strategy for PV system connected to a three phase grid.
concluded in Section IV. The proposed control scheme is comprised of four components
as follows:
II. PROBLEM STATEMENT
A. Generation of Unit Vector Template of PCC Voltage
PV systems need to be synchronized with the utility grid so
that the excess power available after suppling the local loads are For effective grid synchronization under distorted grid
injected into the grid. Topology of PV system integrated to a voltage condition, the fundamental components of vp needs to
utility grid with multiple loads at the PCC is presented in Fig. be extracted accurately. The fundamental components of vp are
1. Applying KVL to the loop (PCC to grid) and KCL at the PCC extracted employing the UKF algorithm. UKF filter updates the
in Fig. 1 we obtain covariance and mean of the states of a nonlinear system using
dig
UT such that it minimizes the mean square error of the states.
v p  vg  Lg (1.(a)) The state space model of a system is given as
dt
ig  ilA  ilB  ii (1.(b)
xk 1  f  xk   wk ; yk  h  xk   vk (2)

Assuming that the inverter is not triggered initially, the total where vk and wk are the measurement and process noises
load power (Pg and Qg) is supplied by the grid. Hence grid respectively, f(xk) and h(xk) are nonlinear state transition and

Solar PV I PV Voltage source Inverter


Array iga igb
Grid
ii PCC v pc v gc
Vdc C dc v pb vgb
VPV
v pa vga
Lf iLb iL Lg
iLa ig

G a Ga Gb Gb Gc Gc LL R L Non-Linear Load

VPV PV array voltage II Vdc


PI
Vdc DC-link voltage
Controller VPV
I PV PV array cuurent InC MPPT
iLabc
Max. PV power Algorithm I PV
Load current extraction Vdc*
iiabc Inverter current iga igb igc 1 iLa
Active load current
igabc Grid current 3 Ia Caluclation I La Fundamental
*
*
iga i *
i *
component
iLb
igabc Reference grid current gb gc
ABS SH
xqabc Ib extraction of Load
Quadrature unit vector I Lb
xiabc In-phase unit vector i * iia* Current using UKF iLc
ZCD
qa * I Lc
Sabc Switching signal * i
ib
Ic
iqb
*
iqc iic* uqa uqb uqc
uia uib uic
v pa v pa
In-Phase xˆ  xˆ  K k *  yk  yˆ k 
 

v pb k k
Unscented v pb
Estimation of Unit Vector K k  Pxy Py Transformation
Quadrature v pc  
P  P  K k * Py * K T v pc
k k k

uqc uqb uqa


Fundamental component extraction of PCC Voltage using UKF
Regulation of v pa
 v pa  v pb  v pc 
PCC Voltage 2 v pb
VE 
1 IQ PI VE 3 v pc
3 Controller
VE*

Fig.2. Schematic diagram of UKF-PI synchronization scheme for PV system connected to a three phase grid.

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
3

measurement vectors respectively. Using the covariance and T


xk   x1k x2k x3k   [2cos 1Ts sk 1 sk 2 ]T (14)
   
mean of xk i.e xˆ
( j)
k 1 and P k 1 , the sigma point x k 1 is chosen [11].
Therefore,
 j   j
xˆk 1  xˆ k 1 x j  1, 2......, 2r xk  f  xk 1  , yk  h( xk ) (15)
   
T T
 j  n j  
x  rP k 1 and x  nP k 1 j  1, 2......, n (3) Hence, f ( xk 1 )   x1 x1 k 1  x2 k 1  x3 k 1
T
x2 k 1  ,
j j  k 1 
2r number of sigma points are considered. The priori state h(x k )  x1k x2 k  x3 k

estimate xˆk is obtained by summing the vector xˆk as in eq (4).
( j)

Using f(xk-1) and h(xk), the estimated states xˆk are obtained.
The vector xˆk is obtained from f ( xˆk 1 )
( j) ( j)

Based on xˆk , the fundamental component of the PCC voltage


1 2n  j 

xˆ 
k  xˆk
2n i 1
(4) (vpa, vpb, vpc) are extracted. The in-phase [uia, uib, uic] and
quadrature [uqa, uqb, uqc] unit vector templates of the PCC
The priori error covariance estimate is obtained as
voltage are obtained as in [15].
1 2r  j
 xˆk  xˆk    xˆ    xˆ 
T
Pˆk  
 Qk
i
k k (5)
2r j 1 B. Extraction of Active current component
Qk is the process error covariance matrix. The measurement The magnitude of the active load current (Ia, Ib, Ic) are
equation is updated by the sigma points xk , which is chosen
( j) obtained as in [15]. Incremental conductance (InC) Maximum
 
power point tracking (MPPT) algorithm is used to extract the
using the estimated mean and covariance of xk i.e. xˆk and Pk maximum power of the PV array as it is simple and easy to
xˆk   xˆk  x   i  1, 2......, 2r implement in practical condition with faster accuracy [16]. The
j j

capacitor voltage Vdc is regulated at Vdc* using the PI controller.


   
T T
 j n j 
x  rPk and x  rPk i  1, 2......, r (6) Ii accounts for the switching loss and capacitor leakage loss in
j j
VSI, minus the real PV power extracted from PV array.
The predicted measurement estimate yˆ k is found by summing
I i  K Pdc *Vedc  K Idc  Vedc dt (16)
the vector yˆ k j  . The vector yˆ k j  obtained using h( xˆk j  ) Vedc  Vdc  Vdc
*

i  i 
where
yˆ k  h( xˆk ) (7) The amplitude of the active reference grid current per phase
2n
1  j are given as:
yˆ k  
2n j 1
yˆ k (8)
 I a  Ib  I c  Ii 
IP  (17)
3
The covariance of the predicted measurement yˆ k is given as
C. Extraction of Reactive current component
1 2r   j     j 
T
Py    yˆ k  yˆ k   yˆ k  yˆ k   Rk
2r j 1   
(9) To maintain vp constant even under grid voltage sag and
swell conditions an appropriate amount of reactive power is
Rk is the measurement error covariance matrix. The cross required. The equivalent amplitude of the PCC voltage VE is at
regulated its reference VE* by the PI controller. The reactive grid
covariance between xˆk and yˆ k is estimated as
current component Iq accounts for the reactive power essential
1 2r   j     ˆ j 
T
to maintain vp at its rated value.
Pxy    ˆ
x
2r j 1  k
 ˆ
x k  
 k
y  ˆ
y k 

(10)
I q  K PE *VeE  K IE  VeE dt (18)
The states are updated using the following equations [11] where VeE  VE*  VE
xˆk  xˆk  Kk *  yk  yˆ k  ; Kk  Pxy Py ; Hence, the per phase reactive grid current component is
Iq
Pk  Pk  Kk * Py * KkT (11) IQ  (19)
3
The Kalman gain Kk is updated such that the major diagonal
terms of error covariance matrix Pk are minimized. Using the D. Estimation of Reference of Reference Grid Current
nonlinear state space model of single sinusoid, the fundamental The reference grid currents are obtained by sum of product
component of vp is estimated by updating the using UKF. A of IP with the in-phase unit vector template of PCC voltage and
signal sk of a single sinusoid is represented as IQ with the quadrature unit vector template of PCC voltage.
sk  a1cos  k1Ts  1  k  1, 2,3...... N (12) *
iga  I P . uia  I Q . uqa ; igb
*
 I P . uib  IQ . uqb ;
where ω1 is the fundamental frequency, TS is the sampling *
igc  I P . uic  I Q . uqc (20)
time ϕ1 phase shift. It may be noted that the three consecutive
Hysteresis current controller is used for tracking ig
samples of this single sinusoid satisfy eq (13)
sk - 2cos 1Ts sk 1  sk 2  0 (13)
IV. RESULTS AND DISCUSSION
The state space vector is given by
To analyze the performance of the proposed UKF-PI based

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
4

Table I Parameters for Simulation and Experimental Study harmonics. A 800 W PV array is used which consists of 4 PV
Symbols Parameters Values modules, with irradiation of 500 W/m2. The Maximum Power
Point (MPP) is at Vmp = 105.5 V and Pmax = 386 W. All the
PPV PV array Power 800W parameters of PV module are chosen as in [15]. Parameters used
vg Grid Voltage 62 V for simulation study are given in Table I.
f Grid Frequency 50 Hz
RL,LL Load Impedance 40Ω, 20 mH To analyze the effectiveness of the proposed UKF-PI control
Lg Grid Inductance 5 mH, scheme, the responses (PCC voltage (vpa), grid current (iga),
Cdc DC-link Capacitance 2350 µF DC-link capacitor voltage (Vdc)) after compensation are
Lf Filter Inductance 7.5 mH, presented in Fig.3 The control action is provided at time t = 0.3
fsw Switching frequency 20 kHz
KPdc, KIdc Proportional and Integral Gain for regulating Vdc 0.419, 5.95. s. iga settles at t = 0.34s (two cycles) and in phase with vpa. The
KPE, KIE Proportional and Integral Gain for regulating VE 2, 82. compensation of iga using UKF-PI is faster as compared to KF-
VE * Ref. Equivalent amplitude of vp 51.04 V PI and STF-PI. Maximum PV power is extracted using InC
K STF Gain 100 MPPT which estimates the Vmp. Fig.3 (a) shows the Vdc which
ωc Cut-off Frequency 314 rad/sec
Qk Process error covariance matrix 10^-3*eye(3) is effectively regulated at Vmp with reduced steady state
Rk Measurement error covariance matrix 1.5 oscillation. The waveform of iga under unbalanced grid voltage
P0 Initial error covariance matrix 10*eye(3) (Fig.3 (b)). The unbalanced grid voltage makes the load current
x0 Initial state variables [0 ; 0 ; 0 ] unbalanced. ig becomes balanced at around time t = 0.34 s using
UKF-PI which is faster as compared to KF-PI and STF- PI.
control scheme, the results obtained using simulation and
Fig. 4 shows the active power analysis with waveforms of the
experimental analysis of the PV system are presented here.
inverter active power (PI) and grid active power (Pg) using the
A. Simulation Results UKF-PI, KF-PI and STF-PI control scheme. The settling times
Results obtained from the Simulink model of a single-stage of PI and Pg obtained using UKF-PI are faster as compared to
three phase grid-connected PV system using the proposed the respective values in case of KF-PI and STF-PI. The residual
UKF-PI control scheme, KF-PI and STF-PI scheme are shown PV power obtained after suppling the nonlinear load and the
in Fig. 3 and Fig.4. For realizing a practical distorted grid losses of the system is injected into the utility grid at UPF.
condition, 5th and 7th order voltage harmonics are introduced Negative Pg signifies that the surplus PPV is sunk into the grid.
into the grid. A nonlinear load comprising of a diode rectifier Table II shows the FFT analysis of vga and iga using UKF-PI,
with a series RL load is connected at the PCC. The load current KF-PI and STF-PI control schemes. THD of vga and iga are
and the grid voltage are both nonlinear due to the presence of found to be 5.91% and 26.97% respectively when compensated.

Table II FFT analysis of PCC Voltage and Grid Current


Controller PCC Voltage (vpa) Grid Current (iga)
Fundamental %3rd %5th %7th %11th %13th %THD Fundamental %3rd %5th %7th %11th %13th %THD
Uncontrolled 51.05 V 0.00 3.19 2.39 1.95 1.67 5.95 1.219 A 0.11 18.45 9.56 5.84 3.42 26.49
STF-PI 51.05 V 0.04 0.64 0.61 0.33 0.20 2.82 1.647 A 0.11 1.09 1.13 0.58 0.47 3.90
KF-PI 51.05 V 0.04 0.61 0.61 0.32 0.18 2.81 1.652 A 0.06 1.01 1.15 0.42 0.41 3.71
UKF-PI 51.05 V 0.04 0.59 0.63 0.30 0.19 2.81 1.660 A 0.05 0.91 1.01 0.35 0.40 3.35

Uncompensated Compensated Uncompensated Compensated


50 UKF-PI 2 Phase'a'
v pa (kV)

KF-PI Phase'b'
ig (A)

0 STF-PI Phase'c'
-50 -2 STF-PI
2 0.3 0.35 0.4 0.45 UKF-PI 2 0.3 0.35 0.4Phase'a'
iga (A)

KF-PI
ig (A)

Phase'b'
STF-PI Phase'c'
-2 -2 KF-PI
130 0.3 0.35 0.4 0.45 UKF-PI 2 0.3 0.35 0.4Phase'a'
ig (A)

KF-PI Phase'b'
Vdc (V)

115 STF-PI Phase'c'


-2 UKF-PI
100
0.25 0.3 0.35 0.4 0.45 0.5 0.25 0.3 0.35 0.4
Time in Sec Time in Sec
(a) (b)

Fig.3. Waveforms after compensation using UKF-PI, KF-PI and STF-PI under (a) Distorted grid voltage condition; (b) Unbalanced grid voltage condition [PCC
voltage (vpa), Grid current (iga), DC-link capacitor voltage (Vdc)]
Uncompensated Compensated Uncompensated Compensated
400 200
UKF-PI
-180
Pg (W)
PI (W)

UKF-PI 0 KF-PI
200 360 KF-PI 0.45 STF-PI
STF-PI -200
0 0.45
0.25 0.3 0.35 0.4 0.45 0.5 0.25 0.3 0.35 0.4 0.45 0.5
Time in Sec Time in Sec
(a) (b)

Fig.4. Power analysis using UKF-PI, KF-PI and STF-PI for (a) Inverter active power (PI); (b) Grid active power (Pg)

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
5

Uncompensated Compensated Uncompensated Compensated


50 Phase'a' 50 Phase'a'
vga (V)

vga (V)
0 Phase'b' 0 Phase'b'
Phase'c' Phase'c'
-50 -50
50 .50 .55 .60 50 .50 .55 .60
v pa (V)

v pa (V)
0 0
-50 -50
4 0.5 0.55 0.6 4 .80 .85 .90
iga (A)

iga (A)
0 0

-4 -4
55 .50 .55 .60 55 .80 .85 .90
VE (A)

VE (A)
50 50
45 45
-180 .50 .55 .60 -160 .80 .85 .90
Pg (W)

Pg (W)
-200 -180

.50 .55 .60 .80 .85 .90


PI (W)

PI (W)
350 350

0 .50 .55 .60 .80 .85 .90

Qg (Var)
200
Qg (Var)

-100 100
-200 0
.50 .55 .60 .80 .85 .90
QI (Var)

200

QI (Var)
0
100 -100
0 -200
.45 .50 .55 .60 .65 .75 .80 .85 .90 .95
Time in Sec Time in Sec
(a) (b)

Fig.5. Waveforms after compensation using UKF-PI under grid voltage (a) Sag Condition (b) Swell Condition [Grid voltage (vg), PCC voltage (vpa), Grid current
(iga), PCC Amplitude (VE), Grid active power (Pg), Inverter active power (PI), Inverter reactive power (QI), Grid reactive power (Qg),] From top to bottom

The THD of vga after compensation is reduced to 2.81%, 2.81% reverse action with respect to Qg. Inverter active power (PI) grid
and 2.82% using UKF-PI, KF-PI and STF-PI respectively. The active power (Pg) settle at around two cycles of the grid voltage.
harmonic contents in the grid current are effectively minimized During the transient period, there is a slight decrease and
using UKF-PI as compared to both KF-PI and STF-PI. The increase of Pg due to sag and swell. Lower SCR results in
THD of iga is reduced to a minimum value of 3.35% using UKF- fluctuation of vp while higher SCR produces a high rise in ig.
PI as compared to the THD values of 3.71% and 3.90% Although for higher and lower values of SCR limits the voltage
obtained using KF-PI and STF-PI respectively. regulation capabilities of the PV system but in case of UKF-PI,
The response of the proposed scheme under grid sag and ig is maintained as a sinusoidal waveform. Hence, for safety
swell conditions is presented in Fig. 5. The Short Circuit Ratio point of view the reactive grid current component is limited
(SCR) at the PCC is 5.87. During the grid voltage sag and swell, such that the inverter current maintained within its rated value.
iga amplitude increases due to the presence of the reactive
B. Experimental Study
current component which is required to maintain the equivalent
PCC voltage (VE) constant. UPF operation is lost while For the experimental study, a 600W, Agilent make solar
regulating VE. A corresponding decrease and increase in the array simulator (E4360A) is used as a virtual PV array. The
grid reactive power (Qg) is observed for the grid voltage sag and maximum power is set as 0.39 kW. The parameters for
swell respectively. The inverter reactive power (QI) has a experimental study of the SPV system are given in Table I. The

(a) (b)
Fig. 6. (a) Prototype of three phase single stage Grid connected PV system; (b) Power-Voltage and Current-Voltage Curves of PV array with InC MPPT

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
6

(a) (b) (c) (d)


Fig. 7. Uncompensated Waveforms of (a) PCC Voltage (vga) and Grid Current (iga); (b) Inverter Power ;(c) Grid Power;(d) THD of iga

photograph of the prototype of single stage three phase grid- obtained after compensation using STF-PI, KF-PI, and the
connected PV system developed in the laboratory is shown in proposed UKF-PI control schemes respectively are shown in
Fig. 6(a). A 320-AMX ac power source is considered as the Fig. 8(a-c). The grid current waveforms become sinusoidal with
grid. The current and voltage are sensed using the Hall Effect reduced harmonic content using UKF-PI as compared to the
current (LEM LA 55-P) and voltage (LEM LV 25-P) sensor. grid current waveforms obtained using KF-PI and STF-PI. The
UKF-PI control algorithm is implemented in real-time using a excess PV power of 179 W is added into the grid with UPF
dSPACE 1104 which generates the required gate signal of the using the proposed UKF-PI control scheme. The negative active
VSI. grid power signifies that the excess power of the PV array is
From Fig. 6(b), it is seen that InC MPPT efficiently tracks inserted into the utility grid. From Fig. 8(a-c) it is analyzed that
the maximum PV power of 385.18 W. Fig. 7 (a-d) show the THD of the grid current is reduced to a lower value of 3.4%
waveforms before the VSI is triggered i.e. zero inverter power. using UKF-PI as compared to 3.8% and 4% using KF-PI and
The nonlinear load draws 0.168 kW power from the grid with a STF-PI respectively. Fig. 9 shows the grid current waveform
current THD of 26.7%.The waveforms of PCC Voltage vpa, under unbalanced voltage condition. The grid current is almost
Grid Current iga, inverter power, grid power and THD of iga balanced using UKF-PI with reduced distortion as compared to
vpa and iga Inverter Power Grid Power THD of iga
(a)

1. 2.
(b)

1.
(c)

Fig. 8. Compensated Waveform Analysis (a) STF-PI; (b) KF-PI; (c) UKF-PI; [vpa and iga; Inverter Power; Grid Power ; THD of iga] From left to right

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
7

Uncompensated STF-PI KF-PI UKF-PI


vpa
iga
igb
igc

(a) (b) (c) (d)


Fig. 9. Waveform Analysis of Grid Current under unbalanced voltage (a) Uncompensated; (b) STF-PI; (c) KF-PI; (d) UKF-PI
2.

KF-PI and STF-PI. Fig. 10 shows that the ig under fault The waveforms of vpa, iga, inverter power, grid power, THD
condition where the line ‘c’ of the nonlinear load is of iga after compensation under grid sag and swell conditions
disconnected from the PCC. The grid current is almost balanced are shown in Fig.12 (a)-(b). iga increases due to presence of the
using UKF-PI (Fig. 10.(b)). As phase ‘C’ of the load is reactive current component. The reactive current component of
disconnected the overall load power is reduced and hence there ig are intorduced to maintain VE constant at its rated value. Due
is a corresponding increase in the grid current. Fig.11. shows to presence of reactive power, UPF operation is lost but vp is
waveforms of load current ila, iga; grid power; THD of iga. The maintained under sag and swell conditions is accomplished.
load current is increased from 1.622 A to 4.77 A (Fig.11.(a)). The THD of iga is reduced to 3.5%.
The proposed UKF-PI control scheme maintains iga sinusoidal
(Fig. 11.(b)). Due the increase in load power the entire extracted V. CONCLUSIONS
PV power is feeds the load and the excess power needed for the In this research work, a new UKF-PI based control scheme
load is supplied by grid (Fig.11.(c)) and hence the direction of is proposed for a single stage three phase grid-connected PV
iga is reversed, but the UKF-PI control scheme has maintained system. From the simulation and experimental results obtained,
the sinusoidal nature of the grid current by reducing THD of iga it is confirmed that the proposed UKF-PI control scheme
to 3.3% (Fig.11.(b)). provides more effective grid synchronization of PV system as
vpa
iga

(a) (b)
igb

3.
igc

(c) (d)
(a) (b)
Fig. 10. Waveform Analysis of Grid Current under Fault condition (a) Fig. 11. Load Change condition: Waveforms of (a) Load Current (ila) (b)
Uncompensated; (b) UKF-PI; [vga; (iga, igb, igc) ] From top to bottom Compensated Grid Current (iga);(c) Grid Power;(d) THD of iga

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSTE.2018.2864822, IEEE
Transactions on Sustainable Energy
8

(a)

4. 5. 6.
(b)

1.
Fig. 12. Results under grid voltage (a) Sag Condition; (b) Swell Condition; [vpa and iga; Inverter Power; Grid Power ; THD of iga] From left to right

compared to KF-PI and STF-PI. The proposed controller generalized averaging method,” IEEE Tran. on Power Electronics, vol.
31, no. 2, pp.1064-1073, 2016.
effectively extracts the fundamental components of the [8] S. Swain, and B. Subudhi, “A new grid synchronization scheme for a
distorted PCC voltage and the nonlinear load current by three phase PV system employing Kalman filtering,” IEEE Region 10
mitigating the harmonics. Pmp is extracted by regulating the Vdc Sym.(TENSYMP), pp. 1-5, Kochi, July 2017
[9] M. A. Khanesar, E. Kayacan, M. Teshnehlab, and O. Kaynak, “Extended
at Vmp. ig becomes sinusoidal and in phase with the vp ensuring
Kalman filter based learning algorithm for type-2 fuzzy l.ogic systems
UPF operation. The FFT analysis shows that by using the UKF- and its experimental evaluation,” IEEE Trans. Ind. Electron., vol. 59, no.
PI approach, THD of ig is reduced to 3.4% as compared to KF- 11, pp. 4443–4455, Nov. 2012.
PI and STF-PI, which is well within the prescribed standards of [10] X. Wang, and E. E. Yaz, “Smart power grid synchronization with fault
tolerant nonlinear estimation,” IEEE Trans. on Power Systems, vol.31,
IEEE 519 .Under unbalanced grid voltage condition and load no. 6, pp.4806-4816, 2016.
fault condition, the proposed UKF-PI scheme effectively [11] D. Simon, “Optimal state estimation: Kalman, H∞ and nonlinear
maintains ig balanced. With increase in the load current, the approaches”, John Wiley & Sons, New Jersey, 2006.
[12] E. Ghahremani and I. Kamwa, "Online State Estimation of a
overall direction of ig is reversed but using UKF-PI, the THD Synchronous Generator Using Unscented Kalman Filter From Phasor
of ig is maintained at 3.3%. An appropriate amount of reactive Measurements Units," IEEE Trans. Energy Conversion, vol. 26, no. 4,
power is provided to the utility grid in order to maintain vp pp. 1099-1108, Dec. 2011.
[13] A. N. Vargas, H. M. T. Menegaz, J. Y. Ishihara and L. Acho, "Unscented
constant for grid sag and swell. Although vp regulation is limited Kalman Filters for Estimating the Position of an Automotive Electronic
for higher and lower value of SCR, but UKF-PI maintains the Throttle Valve," IEEE Trans. Veh. Tech., vol. 65, no. 6, pp. 4627-4632,
sinusoidal waveform of ig by reducing the THD to 3.5%. June 2016.
[14] S. Jafarzadeh, C. Lascu and M. S. Fadali, "State Estimation of Induction
Motor Drives Using the Unscented Kalman Filter," IEEE Trans.
REFERENCES Industrial Electronics, vol. 59, no. 11, pp. 4207-4216, Nov. 2012.
[1] M.Azrik, K. H. Ahmed, S. J. Finney, and B. W. Williams, “Voltage [15] S. Swain and B. Subudhi, "A New grid synchronization scheme for a
synchronization scheme based on zero crossing detection for parallel three-phase PV system using self-tuning filtering approach," IET Gen.,
connected inverters in AC microgrids,” Proc. 2012 IEEE Int. Symp. Tran. & Dist., vol. 11, no. 14, pp. 3557-3567, Sept. 2017
Industrial Electronics, pp. 588–593. May 2012 [16] R. Faraji, A. Rouholamini, H.R. Naji, Fadaeinedjad, R., Chavoshian,
[2] B. Singh, C. Jain and S. Goel , "ILST Control Algorithm of Single-Stage M.R.: ‘FPGA-based real time incremental conductance maximum
Dual Purpose Grid Connected Solar PV System," IEEE Trans. Power power point tracking controller for photovoltaic systems’, IET Power
Electronics, vol.29, no.10, pp.5347-5357, Oct. 2014. Electronics, vol. 7, no. 5, pp. 1294-1304, May 2014
[3] A. Pigazo, M. Liserre, R. A. Mastromauro, V. M. Moreno and A.
Dell'Aquila, "Wavelet-Based Islanding Detection in Grid-Connected PV Sudarshan Swain is currently working towards the
Systems," IEEE Trans. IE, vol. 56, no. 11, pp. 4445-4455, Nov. 2009. Ph.D. degree in electrical engineering at National
[4] D. Dong, B. Wen, D. Boroyevich, P. Mattavelli, and Y. Xue, “Analysis
of phase-locked loop low-frequency stability in three-phase grid- Institute of Technology (NIT) Rourkela. His
connected power converters considering impedance interactions,” IEEE research interest include control of PV system.
Trans. Ind. Electron., vol. 62, no. 1, pp. 310–321, Jan. 2015.
[5] A. Abur and A. G. Exposito, Power System State Estimation: Theory Bidyadhar Subudhi (M’94–SM’08) is currently
and Implementation. New York, NY, USA: Marcel Dekker, 2004.
[6] I. Sadinezhad and V. G. Agelidis, "Frequency Adaptive Least-Squares- working as Professor in the Department of Electrical
Kalman Technique for Real-Time Voltage Envelope and Flicker Engineering, NIT Rourkela. His research interest
Estimation," IEEE Trans. IE., vol. 59, no. 8, pp. 3330-3341, Aug. 2012. include control of PV system and micro-grid.
[7] A. Bagheri, M. Mardaneh, A. Rajaei, and A. Rahideh, “Detection of grid
voltage fundamental and harmonic components using Kalman filter and

1949-3029 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like