Beskrivning/Description
Approved by Reg. No.
Raptor-DE-0041
Issued by Date Issue Page
ESa-PA Pär Abrahamsson 2017-09-04 20 1(409)
Öte To Copy
1 DOCUMENT DEFINITION
1.1 Identification
This document is the description of the Tank Hub SW Holding and Input registers. This description
is only meant for Rosemount internal use and should not be distributed outside Rosemount Tank
Radar AB. A description of how the registers shall be used is included in Ref. 1 Rosemount 2410,
Function and Configuration Description. NOTE: The registers in this document is available in a
HTML file for each 2410 Release.
Registers.
14 2013-10-16 ESa-PA Updated for the 1.B7 release with L&J and Varec
Registers.
Document template: C:\Users\aronnvall\AppData\Roaming\Microsoft\Templates\Normal.dotm
15 2014-11-25 ESa-PA Updated for the 1.C4 release. Only a few minor
changes.
16 2015-02-06 ESa-PA Updated for the 1.C6 release.
17 2015-11-13 ESa-PA Updated for the 1.D1 release.
18 2016-05-16 ESa-PA Updated for the 1.E0 release.
19 2016-12-06 ESa-PA Updated for the 1.E2 release.
20 2017-09-04 ESa-PA Updated for the 1.G0 release.
1.3 References
Ref. 1 Rosemount 2410, Function and Configuration Description
Raptor-DE-0053, Latest Issue
No Name Unit
0: TMV LEVEL m
1: TMV ULLAGE m
2: TMV LEVEL RATE m/s
3: TMV SIGNAL STRENGTH mV
4: TMV FREE WATER LEVEL m
5: TMV VAPOR PRESSURE Bar
6: TMV LIQUID PRESSURE Bar
7: TMV AIR PRESSURE Bar
8: TMV AMBIENT TEMP ºC
9: TMV VAPOR AVG TEMP ºC
10: TMV LIQUID AVG TEMP ºC
11: TMV TANK AVG TEMP ºC
12: TMV TEMP 1 ºC
13: TMV TEMP 2 ºC
14: TMV TEMP 3 ºC
15: TMV TEMP 4 ºC
16: TMV TEMP 5 ºC
17: TMV TEMP 6 ºC
18: TMV TEMP 7 ºC
19: TMV TEMP 8 ºC
20: TMV TEMP 9 ºC
21: TMV TEMP 10 ºC
22: TMV TEMP 11 ºC
23: TMV TEMP 12 ºC
24: TMV TEMP 13 ºC
25: TMV TEMP 14 ºC
26: TMV TEMP 15 ºC
27: TMV TEMP 16 ºC
Issue 1
3 SPECIAL CONSIDERATIONS
4 REGISTERS
0: No Device
1604: Rosemount 644
1874: Rosemount 752
2120: Rosemount 848T
8273: Rosemount 2051
8752: Rosemount 2230
8768: Rosemount 2240
12369: Rosemount 3051
12612: Rosemount 3144
12625: Rosemount 3151
21248: Rosemount 5300
21504: Rosemount 5400
22784: Rosemount 5900
43520: Rosemount 3051ITK6
43776: Rosemount 3051SMV
44032: Rosemount X051
21264: Wika T53 10
33111: Siemens TH400
12: Yokogawa EJX
17: Yokogawa EJA
Issue 1
3: Honeywell ST800
4: Honeywell ST700
16786945: Rosemount 3051 HART
16786950: Rosemount 3051C HART
16786959: Rosemount 3051C LP HART
16787011: Rosemount 5400 HART
16787012: Rosemount 3051S SIS HART
16787018: Rosemount 3051S Diag HART
16787019: Rosemount 3051 SMV HART
16787025: Rosemount 5300 HART
16787029: Rosemount 2051 HART
16787030: Rosemount 2051 LP HART
33554432: Generic Ain
50331648: Enraf Unknown
54014002: Enraf 802 GPP
54014257: Enraf 811
54014259: Enraf 813
54015284: Enraf 854
54015795: Enraf 873
54016308: Enraf 894
Issue 1
10: Tank 10
Dev2_DevType 108 ENUM 0 - na 0.A0 Device 2, see device 1.
Dev3_DevType 116 ENUM 0 - na 0.A0 Device 3, see device 1.
Dev4_DevType 124 ENUM 0 - na 0.A0 Device 4, see device 1.
Dev5_DevType 132 ENUM 0 - na 0.A0 Device 5, see device 1.
Dev6_DevType 140 ENUM 0 - na 0.A0 Device 6, see device 1.
Dev7_DevType 148 ENUM 0 - na 0.A0 Device 7, see device 1.
Dev8_DevType 156 ENUM 0 - na 0.A0 Device 8, see device 1.
Dev9_DevType 164 ENUM 0 - na 0.A0 Device 9, see device 1.
Dev10_DevType 172 ENUM 0 - na 0.A0 Device 10, see device 1.
Dev11_DevType 180 ENUM 0 - na 0.A0 Device 11, see device 1.
Dev12_DevType 188 ENUM 0 - na 0.A0 Device 12, see device 1.
Dev13_DevType 196 ENUM 0 - na 0.A0 Device 13, see device 1.
Dev14_DevType 204 ENUM 0 - na 0.A0 Device 14, see device 1.
Dev15_DevType 212 ENUM 0 - na 0.A0 Device 15, see device 1.
Dev16_DevType 220 ENUM 0 - na 0.A0 Device 16, see device 1.
Dev17_DevType 228 ENUM 0 - na 1.B1 Device 17, see device 1.
Dev18_DevType 236 ENUM 0 - na 1.B1 Device 18, see device 1.
Dev19_DevType 244 ENUM 0 - na 1.B1 Device 19, see device 1.
Dev20_DevType 252 ENUM 0 - na 1.B1 Device 20, see device 1.
Issue 1
6: Whessoe
9: GPE
11: GSI ASCII
NonStandardConf 701 SENUM 0 0-1 na 0.A0 Use standard configuration or non standard configuration.
If non standard configuration is selected the configuration
will be setup according to the registers below.
0: UseStandard
1: UseNonStandard
Baudrate 702 WORD 4800 70 - # 0.A0 Baud rate (Nonstandard config has to be selected)
57600
DataBits 703 WORD 8 7-8 # 0.A0 Data bits (Nonstandard config has to be selected)
Parity 704 SENUM 0 0-2 na 0.A0 Parity (Nonstandard config has to be selected)
0: None
1: Odd
2: Even
StopBits 705 WORD 1 1-2 # 0.A0 Stop bits (Nonstandard config has to be selected)
MiscConfigPri 706 SBT 0x2 - na 0.B0 Miscellaneous configuration
Bit0: Reserved
Bit1: EnaAutoModbusDetect
Issue 1
ResponseTimeout 707 WORD 0 - ms 0.E0 Maximum time from the request to the reply has to be
transmitted by the Tank Hub. If set to 0 the default
response time for the used protocol will be used.
GapTimeout 708 WORD 0 - ms 0.E0 Maximum time between characters in a request. If set to 0
an appropriate gap timeout will be calculated from the
used baud rate.
RxToTxTime 709 WORD 0 - ms 0.E0 Minimum time from the request to the response. If set to 0
the default response time for the used protocol will be
used.
TxToRxTime 710 WORD 0 - ms 0.E0 Minimum time from the response to the request. If set to 0
the default response time for the used protocol will be
used.
ActiveBeforeTx 711 WORD 0 - ms 0.E0 Active RTS before start of transmission. If set to 0 the
default response time for the used protocol will be used.
ActiveAfterTx 712 WORD 0 - ms 0.E0 Active RTS after start of transmission. If set to 0 the
default response time for the used protocol will be used.
0: NoProtocol
1: AutoDetect
2: Modbus
3: Enraf
6: Whessoe
9: GPE
11: GSI ASCII
NonStandardConf 751 SENUM 0 0-1 na 0.A0 Use standard configuration or non standard configuration.
If non standard configuration is selected the configuration
will be setup according to the registers below.
0: UseStandard
1: UseNonStandard
Baudrate 752 WORD 4800 70 - # 0.A0 Baud rate (Nonstandard config has to be selected)
57600
DataBits 753 WORD 8 7-8 # 0.A0 Data bits (Nonstandard config has to be selected)
Parity 754 SENUM 0 0-2 na 0.A0 Parity (Nonstandard config has to be selected)
0: None
1: Odd
2: Even
StopBits 755 WORD 1 1-2 # 0.A0 Stop bits (Nonstandard config has to be selected)
MiscConfigSec 756 SBT 0x2 - na 0.B0 Miscellaneous configuration
Issue 1
Bit0: Reserved
Bit1: EnaAutoModbusDetect
ResponseTimeout 757 WORD 0 - ms 0.E0 Maximum time from the request to the reply has to be
transmitted by the Tank Hub. If set to 0 the default
response time for the used protocol will be used.
GapTimeout 758 WORD 0 - ms 0.E0 Maximum time between characters in a request. If set to 0
an appropriate gap timeout will be calculated from the
used baud rate.
RxToTxTime 759 WORD 0 - ms 0.E0 Minimum time from the request to the response. If set to 0
the default response time for the used protocol will be
used.
TxToRxTime 760 WORD 0 - ms 0.E0 Minimum time from the response to the request. If set to 0
the default response time for the used protocol will be
used.
ActiveBeforeTx 761 WORD 0 - ms 0.E0 Active RTS before start of transmission. If set to 0 the
default response time for the used protocol will be used.
ActiveAfterTx 762 WORD 0 - ms 0.E0 Active RTS after start of transmission. If set to 0 the
default response time for the used protocol will be used.
MbAddress_1 800 WORD 247 1 - 255 # 0.A0 R2410 Modbus address for Tank Position 1. This address shall
be used to configure the Rosemount 2410 and to collect
specific tank data for Tank Position 1. It is also used for
tunneling modbus queries to the 2230 and 2240 connected to
the Tank Position 1.
MbAddress_2 801 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 2. This address is
used by the Host or FCU to collect the values in the TRL2
Standard Input registers area (Ireg 0-50) for tank 2. Address 0
means that the 2410 will not answer (this function is disabled).
It is also used to tunneled Modbus queries to Rosemount 2240
and Rosemount 2230 that are connected to tank position 2.
MbAddress_3 802 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 3. See description
for tank position 2.
MbAddress_4 803 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 4. See description
for tank position 2.
MbAddress_5 804 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 5. See description
for tank position 2.
MbAddress_6 805 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 6. See description
for tank position 2.
MbAddress_7 806 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 7. See description
for tank position 2.
MbAddress_8 807 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 8. See description
for tank position 2.
Issue 1
MbAddress_9 808 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 9. See description
for tank position 2.
MbAddress_10 809 WORD 0 0 - 255 # 0.A0 R2410 Modbus address for Tank Position 10. See description
for tank position 2.
MbLevelAddress_6 855 WORD 0 0 - 255 # 0.B0 Modbus level address for Tank 6. See description for
tank position 1.
MbLevelAddress_7 856 WORD 0 0 - 255 # 0.B0 Modbus level address for Tank 7. See description for
tank position 1.
MbLevelAddress_8 857 WORD 0 0 - 255 # 0.B0 Modbus level address for Tank 8. See description for
tank position 1.
MbLevelAddress_9 858 WORD 0 0 - 255 # 0.B0 Modbus level address for Tank 9. See description for
tank position 1.
MbLevelAddress_10 859 WORD 0 0 - 255 # 0.B0 Modbus level address for Tank 10. See description for
tank position 1.
EmulAddress_6 905 WORD 65535 - na 0.A0 Emulation address for 2410 Tank Position 6.
EmulAddress_7 906 WORD 65535 - na 0.A0 Emulation address for 2410 Tank Position 7.
EmulAddress_8 907 WORD 65535 - na 0.A0 Emulation address for 2410 Tank Position 8.
EmulAddress_9 908 WORD 65535 - na 0.A0 Emulation address for 2410 Tank Position 9.
EmulAddress_10 909 WORD 65535 - na 0.A0 Emulation address for 2410 Tank Position 10.
LengthUnit 910 SENUM 0 - na 0.B0 Selected length unit. The unit for the Emulated Slave
response if supported by the Emulation Protocol. See
the description for each Emulation Protocol. For the
Enraf and Varec Master Function, this register should
be configured to match the Unit used by the Slave.
0: Auto
44: Feet
45: Meters
47: Inches
49: MilliMeters
556: Feet Inches 1 16Inches
812: Feet 1 100
TemperatureUnit 911 SENUM 0 - na 0.B0 Selected temperature unit. See Length Unit above for
more descriptions.
0: Auto
32: Deg C
33: Deg F
Issue 1
DensityUnit 912 SENUM 0 - na 0.B0 Selected density unit. See Length Unit above for more
descriptions.
0: Auto
92: kg per m3
104: Deg API
PressureUnit 913 SENUM 0 - na 0.B0 Selected pressure unit. See Length Unit above for more
descriptions.
0: Auto
6: Psi
7: Bar
11: Pa
EmulMasterAddr_1 930 WORD 65535 - na 1.B3 Emulation address for Slave 1. This address is used by
the Emulation Master to collect the measurement
values from Slave 1.
EmulMasterAddr_2 931 WORD 65535 - na 1.B3 Emulation address for Slave 2. This address is used by
the Emulation Master to collect the measurement
values from Slave 2.
EmulMasterAddr_3 932 WORD 65535 - na 1.B3 Emulation address for Slave 3. This address is used by
the Emulation Master to collect the measurement
values from Slave 3.
EmulMasterAddr_4 933 WORD 65535 - na 1.B3 Emulation address for Slave 4. This address is used by
the Emulation Master to collect the measurement
values from Slave 4.
Issue 1
EmulMasterAddr_5 934 WORD 65535 - na 1.B3 Emulation address for Slave 5. This address is used by
the Emulation Master to collect the measurement
values from Slave 5.
EmulMasterAddr_6 935 WORD 65535 - na 1.B3 Emulation address for Slave 6. This address is used by
the Emulation Master to collect the measurement
values from Slave 6.
EmulMasterAddr_7 936 WORD 65535 - na 1.B3 Emulation address for Slave 7. This address is used by
the Emulation Master to collect the measurement
values from Slave 7.
EmulMasterAddr_8 937 WORD 65535 - na 1.B3 Emulation address for Slave 8. This address is used by
the Emulation Master to collect the measurement
values from Slave 8.
EmulMasterAddr_9 938 WORD 65535 - na 1.B3 Emulation address for Slave 9. This address is used by
the Emulation Master to collect the measurement
values from Slave 9.
EmulMasterAddr_10 939 WORD 65535 - na 1.B3 Emulation address for Slave 10. This address is used by
the Emulation Master to collect the measurement
values from Slave 10.
Bit3: RELAY K2
WhessoeM_MiscCtrl 1048 SBT 0x0 - na 1.D0 Whessoe 550 Master, miscellaneous
control register.
Bit0: EnableWhessoeMaster
Bit5: MAP TO LIQUID PRESSURE
Bit6: CONVERT FROM HIGHRES
PRESSURE
WhessoeM1_Task 1050 SBT 0x4 - na 1.D0 Whessoe Master 1, Type Of Task. These
Tasks are used in the request to the
Whessoe 550 Slave. Note 4 should not be
combined with 30 (select only one request
for Level and Avg Temp).
Bit2: Task 04 Level AvgTemp
Bit10: Task 30 Level AvgTemp
Pressure
WhessoeM2_Task 1051 SBT 0x4 - na 1.D0 Whessoe Master 2, see Whessoe Master 1.
WhessoeM3_Task 1052 SBT 0x4 - na 1.D0 Whessoe Master 3, see Whessoe Master 1.
WhessoeM4_Task 1053 SBT 0x4 - na 1.D0 Whessoe Master 4, see Whessoe Master 1.
WhessoeM5_Task 1054 SBT 0x4 - na 1.D0 Whessoe Master 5, see Whessoe Master 1.
WhessoeM6_Task 1055 SBT 0x4 - na 1.D0 Whessoe Master 6, see Whessoe Master 1.
WhessoeM7_Task 1056 SBT 0x4 - na 1.D0 Whessoe Master 7, see Whessoe Master 1.
WhessoeM8_Task 1057 SBT 0x4 - na 1.D0 Whessoe Master 8, see Whessoe Master 1.
Issue 1
WhessoeM9_Task 1058 SBT 0x4 - na 1.D0 Whessoe Master 9, see Whessoe Master 1.
WhessoeM10_Task 1059 SBT 0x4 - na 1.D0 Whessoe Master 10, see Whessoe Master
1.
EnrafM_MiscCtrl 1060 SBT 0x0 - na 1.B1 Enraf Master, miscellaneous control
register.
Bit0: EnableEnrafMaster
Bit1: Enable GPP Protocol
Bit4: Enable Background TORX Poll
Bit5: Enable AlarmStatus Check
Bit8: Set InvLevel In Servo Test Mode
Bit9: Set ValidLevel When Drum Wrap
Around
EnrafM_BusTimeout 1061 WORD 2000 600 - ms 1.B1 Enraf, L&J and Whessoe 550 Master,
2000 timeout waiting for complete response.
EnrafM_PollTime 1062 WORD 1000 500 - ms 1.B1 Enraf, L&J and Whessoe 550 Master, time
5000 between each query.
EnrafM_Retries 1063 WORD 2 0 - 10 # 1.B1 Enraf, L&J and Whessoe 550 Master,
number of retries in case of no response.
EnrafM_Drum_WrapLim_m 1064 WORD 0 - m 1.F0 Limit for Drum Wrap Around Correction.
This can typically happen for Enraf 811
and 813 when close to the bottom. The
output will normally be 99.999 m. If the
Issue 1
EnrafM2_TOR_Z 1076 SBT 0x0 - na 1.C4 Enraf Master 2, see Enraf Master 1.
EnrafM3_TOI 1078 SENUM 0 - na 1.B1 Enraf Master 3, see Enraf Master 1.
EnrafM3_TOR 1079 SBT 0x3 - na 1.B1 Enraf Master 3, see Enraf Master 1.
EnrafM3_TOR_Z 1080 SBT 0x0 - na 1.C4 Enraf Master 3, see Enraf Master 1.
EnrafM4_TOI 1082 SENUM 0 - na 1.B1 Enraf Master 4, see Enraf Master 1.
EnrafM4_TOR 1083 SBT 0x3 - na 1.B1 Enraf Master 4, see Enraf Master 1.
EnrafM4_TOR_Z 1084 SBT 0x0 - na 1.C4 Enraf Master 4, see Enraf Master 1.
EnrafM5_TOI 1086 SENUM 0 - na 1.B1 Enraf Master 5, see Enraf Master 1.
EnrafM5_TOR 1087 SBT 0x3 - na 1.B1 Enraf Master 5, see Enraf Master 1.
EnrafM5_TOR_Z 1088 SBT 0x0 - na 1.C4 Enraf Master 5, see Enraf Master 1.
EnrafM6_TOI 1090 SENUM 0 - na 1.B1 Enraf Master 6, see Enraf Master 1.
EnrafM6_TOR 1091 SBT 0x3 - na 1.B1 Enraf Master 6, see Enraf Master 1.
EnrafM6_TOR_Z 1092 SBT 0x0 - na 1.C4 Enraf Master 6, see Enraf Master 1.
EnrafM7_TOI 1094 SENUM 0 - na 1.B1 Enraf Master 7, see Enraf Master 1.
EnrafM7_TOR 1095 SBT 0x3 - na 1.B1 Enraf Master 7, see Enraf Master 1.
EnrafM7_TOR_Z 1096 SBT 0x0 - na 1.C4 Enraf Master 7, see Enraf Master 1.
EnrafM8_TOI 1098 SENUM 0 - na 1.B1 Enraf Master 8, see Enraf Master 1.
EnrafM8_TOR 1099 SBT 0x3 - na 1.B1 Enraf Master 8, see Enraf Master 1.
EnrafM8_TOR_Z 1100 SBT 0x0 - na 1.C4 Enraf Master 8, see Enraf Master 1.
EnrafM9_TOI 1102 SENUM 0 - na 1.B1 Enraf Master 9, see Enraf Master 1.
EnrafM9_TOR 1103 SBT 0x3 - na 1.B1 Enraf Master 9, see Enraf Master 1.
Issue 1
EnrafM9_TOR_Z 1104 SBT 0x0 - na 1.C4 Enraf Master 9, see Enraf Master 1.
EnrafM10_TOI 1106 SENUM 0 - na 1.B1 Enraf Master 10, see Enraf Master 1.
EnrafM10_TOR 1107 SBT 0x3 - na 1.B1 Enraf Master 10, see Enraf Master 1.
EnrafM10_TOR_Z 1108 SBT 0x0 - na 1.C4 Enraf Master 10, see Enraf Master 1.
LnJGaugeType 1120 SENUM 3 0-3 # 1.B7 Specifies the emulated gauge type for the
L&J Slave protocol
0: Undefined 0
1: Undefined 1
2: MCG 2000
3: MCG 1500
LnJMiscCtrl 1121 SBT 0x0 - na 1.B7 L&J Slave miscellaneous control register.
See Raptor-DE-0140 for details.
Bit0: Positive Temp Negative Sign
Bit1: Reserved1
Bit2: No Response if Invalid Level
Bit3: Set All Bits Invalid Temp
Bit6: Shift Use Liquid Pressure
Bit7: Shift Pressure and Interface
Bit9: Enable Modbus Alarm Bits
Bit10: Invert Modbus Alarm Bits
Bit12: Enable Modbus FC4
Issue 1
MultTestByte1 1122 WORD 23 - na 1.B7 The value returned for byte 1 in the L&J
multi variable request (60 Hex).
MultTestByte2 1123 WORD 0 - na 1.B7 The value returned for byte 2 in the L&J
multi variable request (60 Hex).
MultTestByte9 1124 WORD 0 - na 1.B7 The value returned for byte 9 in the L&J
multi variable request (60 Hex).
MultTestByte10 1125 WORD 0 - na 1.B7 The value returned for byte 10 in the L&J
multi variable request (60 Hex).
MultTestByte11 1126 WORD 255 - na 1.B7 The value returned for byte 11 in the L&J
multi variable request (60 Hex).
MultTestByte12 1127 WORD 0 - na 1.B7 The value returned for byte 12 in the L&J
multi variable request (60 Hex).
MultTestByte13 1128 WORD 0 - na 1.B7 The value returned for byte 13 in the L&J
multi variable request (60 Hex).
MultTestByte14 1129 WORD 0 - na 1.B7 The value returned for byte 14 in the L&J
multi variable request (60 Hex).
Varec_GaugeType 1140 SENUM 1 0-1 # 1.B7 Specifies the emulated gauge type for the
Varec Slave protocol
0: GT 1800
1: GT 1900
Varec_MiscCtrl 1141 SBT 0x0 - na 1.B7 Varec miscellaneous control register. See
Raptor-DE-0141 for details.
Bit0: UsePositiveTempOffset
Issue 1
LnJM6_DataReq 1167 SBT 0x1 - na 1.D1 L&J Master Data Request selection
register for Tank position 6.
LnJM7_DataReq 1168 SBT 0x1 - na 1.D1 L&J Master Data Request selection
register for Tank position 7.
LnJM8_DataReq 1169 SBT 0x1 - na 1.D1 L&J Master Data Request selection
register for Tank position 8.
LnJM9_DataReq 1170 SBT 0x1 - na 1.D1 L&J Master Data Request selection
register for Tank position 9.
LnJM10_DataReq 1171 SBT 0x1 - na 1.D1 L&J Master Data Request selection
register for Tank position 10.
VarecMaster_MiscCtrl 1180 SBT 0x0 - na 1.D1 Varec Master Function miscellaneous
control register. See Raptor-DE-0141 for
details.
Bit0: Enable Varec Master
VM1_MiscCtrl 1182 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 1. See Raptor-
DE-0141 for details.
Bit0: Resp Level
Bit1: Resp Level AvgTemp
Bit8: Enable 0 20m
Bit9: Subtract Temp Offset
Bit10: Use GT 1800 Temp
Issue 1
VM2_MiscCtrl 1183 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 2.
VM3_MiscCtrl 1184 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 3.
VM4_MiscCtrl 1185 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 4.
VM5_MiscCtrl 1186 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 5.
VM6_MiscCtrl 1187 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 6.
VM7_MiscCtrl 1188 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 7.
VM8_MiscCtrl 1189 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 8.
VM9_MiscCtrl 1190 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 9.
VM10_MiscCtrl 1191 SBT 0x1 - na 1.D1 Varec Master Data Request selection
register for Tank position 10.
Tic_MiscCtrl 1200 SBT 0x0 - na 1.E0 TIC Slave Emulation miscellaneous
control register. See Raptor-DE-0171 for
details.
Bit2: Use Ullage
Bit4: Normal Temp Stat NC
Issue 1
0: Default
1: Last Valid
2: Invalid Value
3: User Defined Error Set
Sakura_AlarmConf 1213 SBT 0x0 - na 1.F0 Sakura V1 Alarm Configuration. The
Alarm limits are configured in TMVAlarm
Hregs, starting at Hreg 2400.
Bit0: Alarm1 High
Bit1: Alarm1 Low
Bit2: Alarm2 High
Bit3: Alarm2 Low
Bit4: Alarm1 K1
Bit5: Alarm1 K2
Bit6: Alarm2 K1
Bit7: Alarm2 K2
Sakura_PressConf 1214 SBT 0x0 - na 1.F0 Sakura Slave Emulation miscellaneous
control register. See Raptor-DE-0183 for
details.
Bit0: P1 Liquid
Bit1: P2 Liquid
Bit2: P3 Liquid
Issue 1
Sakura_DisplConf 1215 SBT 0x8002 - na 1.F0 Sakura MDP Displacer Status bits
configuration. See Raptor-DE-0183 for
details.
Bit0: TC4 Bit0
Bit1: TC4 Bit1
Bit2: TC4 Bit2
Bit3: TC4 Bit3
Bit14: Use Nothing But Hreg Status Bits
Bit15: Indicate Valid Level as Balance
Sakura_StatusConf 1216 SBT 0x800 - na 1.F0 Sakura MPD Status bits.Slave Emulation
miscellaneous control register. See Raptor-
DE-0183 for details.
Bit0: S1
Bit1: S2
Bit2: S3
Bit3: S4
Bit4: S5
Bit5: MS
Bit6: C1
Bit7: C2
Bit8: C3
Issue 1
Bit9: P1
Bit10: P2
Bit11: P3
Bit12: P4
Sakura_BaudRate 1217 WORD 0 - # 1.F0 Sakura bus baud rate. If 0, auto baud rate is
used.
Sakura_DutyCycle 1218 WORD 0 - % 1.F0 Sakura bus signal duty cycle. if 0 auto is
used else the pulse duty cycle in %.
Bit1: Tank 2
Bit2: Tank 3
Bit3: Tank 4
Bit4: Tank 5
Bit5: Tank 6
Bit6: Tank 7
Bit7: Tank 8
Bit8: Tank 9
Bit9: Tank 10
ToggVar1_General 2302 BITFIELD 0x801 - na 0.B0 Selected TMV's to be displayed for all selected Tanks.
Bit0: LEVEL
Bit1: ULLAGE
Bit2: LEVEL RATE
Bit3: SIGNAL STRENGTH
Bit4: FREE WATER LEVEL
Bit5: VAPOR PRESSURE
Bit6: MIDDLE PRESSURE
Bit7: LIQUID PRESSURE
Bit8: AIR PRESSURE
Bit9: AMBIENT TEMPERATURE
Issue 1
MiscConfig 2308 BITFIELD 0x1 - na 0.B0 Miscellaneous control register. Note that bit 1 only is
used if only one tank is selected in the Tanks register
above.
Bit0: LIGHT ON IF LCD
Bit1: EXCLUDE TANK NAME
Bit2: HIGH RESOLUTION
Bit3: ALWAYS LIGHT ON
Language 2310 ENUM 0 0-0 na 0.B0 Language selection.
0: English
LenUnit 2312 ENUM 0 0 - 999 na 0.B0 Unit for length variables.
0: Auto
44: Feet
45: Meter
49: MilliMeter
556: Imp16
VolUnit 2314 ENUM 0 0 - 999 na 0.B0 Unit for volume variables.
0: Auto
40: US Gallons
41: Liter
42: UK Gallons
43: Cubic Meters
Issue 1
46: Barrels
TempUnit 2316 ENUM 0 0 - 999 na 0.B0 Unit for temperature variables
0: Auto
32: Deg C
33: Deg F
35: Kelvin
LRUnit 2318 ENUM 0 0 - 999 na 0.B0 Unit for velocity variables.
0: Auto
20: Feet per second
21: Meters per second
120: Meters per hour
247: Feet per hour
PressureUnit 2320 ENUM 0 0 - 999 na 0.B0 Unit for pressure variables.
0: Auto
6: Psi
7: Bar
8: mBar
11: Pa
12: KPa
14: Atm
Issue 1
263: Bar A
519: Bar G
262: PSI A
518: PSI G
DensityUnit 2322 ENUM 0 0 - 999 na 0.B0 Unit for density variables.
0: Auto
92: kg/m3
104: degAPI
FlowRateUnit 2324 ENUM 0 0 - 999 na 0.F0 Unit for volume flow rate variables.
0: Auto
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
ToggVar1_Tank1 2330 BITFIELD 0x0 - na 1.A8 TMV selection for Tank 1.
Bit0: LEVEL
Bit1: ULLAGE
Bit2: LEVEL RATE
Bit3: SIGNAL STRENGTH
Bit4: FREE WATER LEVEL
Issue 1
Bit25: TEMP 13
Bit26: TEMP 14
Bit27: TEMP 15
Bit28: TEMP 16
Bit29: OBSERVED DENSITY
Bit30: REFERENCE DENSITY
Bit31: TANK VOLUME
ToggVar2_Tank1 2332 BITFIELD 0x0 - na 1.A8 TMV selection for Tank 1.
Bit0: USER DEF 1
Bit1: USER DEF 2
Bit2: USER DEF 3
Bit3: USER DEF 4
Bit4: USER DEF 5
Bit5: FLOW RATE
Bit6: TANK HEIGHT
Bit7: DELTA LEVEL
Bit8: FWV
Bit9: NSV
Bit10: HTG LEVEL
Bit11: MASS
Issue 1
AlarmLevelLimitLL_5 2436 FLOAT -200.0 - m 0.A0 Tank 5 alarm level low low. See Tank 1.
AlarmLevelLimitHH_5 2438 FLOAT 200.0 - m 0.A0 Tank 5 alarm level high high. See Tank 1.
AlarmLevelLimitLo_6 2440 FLOAT -100.0 - m 0.A0 Tank 6 alarm level low. See Tank 1.
AlarmLevelLimitHi_6 2442 FLOAT 100.0 - m 0.A0 Tank 6 alarm level high. See Tank 1.
AlarmLevelLimitLL_6 2444 FLOAT -200.0 - m 0.A0 Tank 6 alarm level low low. See Tank 1.
AlarmLevelLimitHH_6 2446 FLOAT 200.0 - m 0.A0 Tank 6 alarm level high high. See Tank 1.
AlarmLevelLimitLo_7 2448 FLOAT -100.0 - m 0.A0 Tank 7 alarm level low. See Tank 1.
AlarmLevelLimitHi_7 2450 FLOAT 100.0 - m 0.A0 Tank 7 alarm level high. See Tank 1.
AlarmLevelLimitLL_7 2452 FLOAT -200.0 - m 0.A0 Tank 7 alarm level low low. See Tank 1.
AlarmLevelLimitHH_7 2454 FLOAT 200.0 - m 0.A0 Tank 7 alarm level high high. See Tank 1.
AlarmLevelLimitLo_8 2456 FLOAT -100.0 - m 0.A0 Tank 8 alarm level low. See Tank 1.
AlarmLevelLimitHi_8 2458 FLOAT 100.0 - m 0.A0 Tank 8 alarm level high. See Tank 1.
AlarmLevelLimitLL_8 2460 FLOAT -200.0 - m 0.A0 Tank 8 alarm level low low. See Tank 1.
AlarmLevelLimitHH_8 2462 FLOAT 200.0 - m 0.A0 Tank 8 alarm level high high. See Tank 1.
AlarmLevelLimitLo_9 2464 FLOAT -100.0 - m 0.A0 Tank 9 alarm level low. See Tank 1.
AlarmLevelLimitHi_9 2466 FLOAT 100.0 - m 0.A0 Tank 9 alarm level high. See Tank 1.
AlarmLevelLimitLL_9 2468 FLOAT -200.0 - m 0.A0 Tank 9 alarm level low low. See Tank 1.
AlarmLevelLimitHH_9 2470 FLOAT 200.0 - m 0.A0 Tank 9 alarm level high high. See Tank 1.
AlarmLevelLimitLo_10 2472 FLOAT -100.0 - m 0.A0 Tank 10 alarm level low. See Tank 1.
AlarmLevelLimitHi_10 2474 FLOAT 100.0 - m 0.A0 Tank 10 alarm level high. See Tank 1.
AlarmLevelLimitLL_10 2476 FLOAT -200.0 - m 0.A0 Tank 10 alarm level low low. See Tank 1.
Issue 1
AlarmLevelLimitHH_10 2478 FLOAT 200.0 - m 0.A0 Tank 10 alarm level high high. See Tank 1.
Bit0: SPOT 1
Bit1: SPOT 2
Bit2: SPOT 3
Bit3: SPOT 4
Bit4: SPOT 5
Bit5: SPOT 6
Bit6: SPOT 7
Bit7: SPOT 8
Bit8: SPOT 9
Bit9: SPOT 10
Bit10: SPOT 11
Bit11: SPOT 12
Bit12: SPOT 13
Bit13: SPOT 14
Bit14: SPOT 15
Bit15: SPOT 16
TempSensPosition_1_1 2512 FLOAT -1000.0 - m 0.A0 Position for temperature sensor 1 measured from
the dipping datum point (zero level). Positive
value if the sensor is placed above the dipping
datum point.
TempSensPosition_1_2 2514 FLOAT -1000.0 - m 0.A0 See above.
Issue 1
WeightFactor_1_3 2548 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 3 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_4 2550 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 4 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_5 2552 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 5 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_6 2554 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 6 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_7 2556 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 7 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_8 2558 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 8 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_9 2560 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 9 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_10 2562 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 10 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_11 2564 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 11 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_12 2566 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 12 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_13 2568 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 13 in Average
100.0 Calculation, see WeightFactor_1_1.
Issue 1
WeightFactor_1_14 2570 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 14 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_15 2572 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 15 in Average
100.0 Calculation, see WeightFactor_1_1.
WeightFactor_1_16 2574 FLOAT 1.0 1.0 - na 0.A0 Weight Factor for element 16 in Average
100.0 Calculation, see WeightFactor_1_1.
NrOfsensors_2 2576 DWORD 16 0 - 16 # 0.A0 Average Temperature configuration for Tank
Position 2, see the description for Tank Position
1.
NrOfsensors_3 2652 DWORD 16 0 - 16 # 0.A0 Average Temperature configuration for Tank
Position 3, see the description for Tank Position
1.
NrOfsensors_4 2728 DWORD 16 0 - 16 # 0.A0 Average Temperature configuration for Tank
Position 4, see the description for Tank Position
1.
NrOfsensors_5 2804 DWORD 16 0 - 16 # 0.A0 Average Temperature configuration for Tank
Position 5, see the description for Tank Position
1.
NrOfsensors_6 2880 DWORD 16 0 - 16 # 0.A0 Average Temperature configuration for Tank
Position 6, see the description for Tank Position
1.
NrOfsensors_7 2956 DWORD 16 0 - 16 # 0.A0 Average Temperature configuration for Tank
Position 7, see the description for Tank Position
1.
Issue 1
7: Tank 7
8: Tank 8
9: Tank 9
10: Tank 10
Hybrid2_Config 3322 BITFIELD 0x0 - na 0.B0 Hybrid 2 function configuration register.
Bit0: Enable HTG Calc
Bit1: Enable Manual HTG Density
Bit4: Enable Manual Pressure Type
Bit5: Manual Pressure Type Absolute
Hybrid2_Reserved 3324 DWORD 0 - na 0.B0
Hybrid2_P1_Level 3326 FLOAT 0.0 - m 0.B0 Pressure sensor P1 (Liquid Pressure)
position.
Hybrid2_P3_Level 3328 FLOAT 0.0 - m 0.B0 Pressure sensor P3 (Vapor Pressure)
position.
Hybrid2_MinimumLevel 3330 FLOAT 0.0 - m 0.B0 Minimum liquid level for valid density
measurement. Measured from Zero Level
Reference point.
Hybrid2_VaporDensity 3332 FLOAT 1.21 - kg/m3 0.B0 Estimated tank vapor density.
Hybrid2_LowerDensityLimit 3334 FLOAT 0.0 - kg/m3 0.B0 Lower Density Limit for valid Density
measurement (alarm limit).
Hybrid2_UpperDensityLimit 3336 FLOAT 10000.0 - kg/m3 0.B0 Upper Density Limit for valid Density
measurement (alarm limit).
Issue 1
1147: IN H2O 4C
1148: IN H2O 68F
1150: MM H2O 4C
1151: MM H2O 68F
1153: FT H2O 4C
1154: FT H2O 68F
1156: IN HG 0C
1158: MM HG 0C
1590: BARG
1597: BARA
1243: mV
1349: CUBIC METER PER HOUR
1352: LITER PER MINUTE
1358: CUBIC FEET PER HOUR
1364: US GALLON PER HOUR
1369: UK GALLON PER HOUR
1373: BARREL PER HOUR
Manual2_Value 3404 FLOAT 0.0 - na 0.C4 Manula TV Value.
Manual2_Unit 3406 ENUM 0 - na 0.C4 Manual TV Unit, see above.
Manual3_Value 3408 FLOAT 0.0 - na 0.C4 Manula TV Value.
Issue 1
8: TV TANK HEIGHT
9: TV WATER LEVEL
10: TV HOUSING TEMP
11: TV LIQUID TEMP
12: TV VAPOR TEMP
13: TV TANK TEMP
14: TV FLOW RATE
51: TV TEMP 1
52: TV TEMP 2
53: TV TEMP 3
54: TV TEMP 4
55: TV TEMP 5
56: TV TEMP 6
57: TV TEMP 7
58: TV TEMP 8
59: TV TEMP 9
60: TV TEMP 10
61: TV TEMP 11
62: TV TEMP 12
63: TV TEMP 13
Issue 1
64: TV TEMP 14
65: TV TEMP 15
66: TV TEMP 16
67: TV TEMP POS 1
68: TV TEMP POS 2
69: TV TEMP POS 3
70: TV TEMP POS 4
71: TV TEMP POS 5
72: TV TEMP POS 6
73: TV TEMP POS 7
74: TV TEMP POS 8
75: TV TEMP POS 9
76: TV TEMP POS 10
77: TV TEMP POS 11
78: TV TEMP POS 12
79: TV TEMP POS 13
80: TV TEMP POS 14
81: TV TEMP POS 15
82: TV TEMP POS 16
100: TV HART PV
Issue 1
101: TV HART SV
102: TV HART TV
103: TV HART QV
150: TV AIN 1
151: TV AIN 2
152: TV AIN 3
200: TV PRESSURE 1
201: TV PRESSURE 2
202: TV PRESSURE 3
1000: TV MAN VALUE 1
1001: TV MAN VALUE 2
1002: TV MAN VALUE 3
1003: TV MAN VALUE 4
1004: TV MAN VALUE 5
1005: TV MAN VALUE 6
1006: TV MAN VALUE 7
1007: TV MAN VALUE 8
1008: TV MAN VALUE 9
1009: TV MAN VALUE 10
1010: TV MAN VALUE 11
Issue 1
9: FF Device 9
10: FF Device 10
11: FF Device 11
12: FF Device 12
13: FF Device 13
14: FF Device 14
15: FF Device 15
16: FF Device 16
21: HART Device 1
22: HART Device 2
23: HART Device 3
24: HART Device 4
25: HART Device 5
31: AIN Device 1
41: TankHub Device
50: Emul Device 1
51: Emul Device 2
52: Emul Device 3
53: Emul Device 4
54: Emul Device 5
Issue 1
1: TMV ULLAGE
2: TMV LEVEL RATE
3: TMV SIGNAL STRENGTH
4: TMV FREE WATER LEVEL
5: TMV VAPOR PRESSURE
6: TMV LIQUID PRESSURE
7: TMV AIR PRESSURE
8: TMV AMBIENT TEMP
9: TMV VAPOR AVG TEMP
10: TMV LIQUID AVG TEMP
11: TMV TANK AVG TEMP
12: TMV TEMP 1
13: TMV TEMP 2
14: TMV TEMP 3
15: TMV TEMP 4
16: TMV TEMP 5
17: TMV TEMP 6
18: TMV TEMP 7
19: TMV TEMP 8
20: TMV TEMP 9
Issue 1
3: TANK 3
4: TANK 4
5: TANK 5
6: TANK 6
7: TANK 7
8: TANK 8
9: TANK 9
10: TANK 10
SimTime 3804 DWORD 10 0 - 6000 min 0.A0 Simulation duration.
SimConfig 3806 BITFIELD 0x0 - na 0.C5 Simulation Configuration.
Bit0: CALCULATE AVG TEMP
Bit1: CALCULATE VOLUME
Bit2: CALCULATE DENSITY
Level 3808 FLOAT 10.0 - m 0.A0 Simulated value.
Level_Status 3810 BITFIELD 0x0 - na 0.A0 Simulated status.
Bit0: DataError
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: SaturatedLow
Bit4: SaturatedHigh
Issue 1
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit24: MaintAlert
Level_Offset 3812 FLOAT 0.0 - m 0.A0 Value offset used in SimMode SIM_MODE_ALL to get
different values for all tanks.
Ullage 3814 FLOAT 5.0 - m 0.A0 Simulated value, status and offset, see level for register
definitions.
LevelRate 3820 FLOAT 0.0123 - m/s 0.A0 Simulated value, status and offset, see level for register
definitions.
SignalStrength 3826 FLOAT 12345.0 - mV 0.A0 Simulated value, status and offset, see level for register
definitions.
FreeWaterLevel 3832 FLOAT 1.0 - m 0.A0 Simulated value, status and offset, see level for register
definitions.
VaporPressure 3838 FLOAT 1.0 - bar 0.A0 Simulated value, status and offset, see level for register
definitions.
LiquidPressure 3844 FLOAT 2.0 - bar 0.A0 Simulated value, status and offset, see level for register
definitions.
Issue 1
AirPressure 3850 FLOAT 1.21 - bar 0.A0 Simulated value, status and offset, see level for register
definitions.
AmbientTemp 3856 FLOAT 23.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
VaporAvgTemp 3862 FLOAT 11.1 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
LiquidAvgTemp 3868 FLOAT 22.2 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
TankAvgTemp 3874 FLOAT 33.3 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_1 3880 FLOAT 1.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_2 3886 FLOAT 2.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_3 3892 FLOAT 3.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_4 3898 FLOAT 4.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_5 3904 FLOAT 5.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_6 3910 FLOAT 6.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Issue 1
Temp_7 3916 FLOAT 7.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_8 3922 FLOAT 8.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_9 3928 FLOAT 9.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_10 3934 FLOAT 10.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_11 3940 FLOAT 11.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_12 3946 FLOAT 12.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_13 3952 FLOAT 13.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_14 3958 FLOAT 14.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_15 3964 FLOAT 15.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
Temp_16 3970 FLOAT 16.0 - C 0.A0 Simulated value, status and offset, see level for register
definitions.
ObservedDensity 3976 FLOAT 1234.57 - kg/m3 0.A0 Simulated value, status and offset, see level for register
definitions.
Issue 1
ReferenceDensity 3982 FLOAT 1000.0 - kg/m3 0.A0 Simulated value, status and offset, see level for register
definitions.
FlowRate 3988 FLOAT 1.0 - m/s 0.A0 Simulated value, status and offset, see level for register
definitions.
Volume 3994 FLOAT 7.0 - m3 0.A0 Simulated value, status and offset, see level for register
definitions.
UserDef_1 4000 FLOAT 1.0 - na 0.A0 Simulated value, status and offset, see level for register
definitions.
UserDef_2 4006 FLOAT 2.0 - na 0.A0 Simulated value, status and offset, see level for register
definitions.
UserDef_3 4012 FLOAT 3.0 - na 0.A0 Simulated value, status and offset, see level for register
definitions.
UserDef_4 4018 FLOAT 4.0 - na 0.A0 Simulated value, status and offset, see level for register
definitions.
UserDef_5 4024 FLOAT 5.0 - na 0.A0 Simulated value, status and offset, see level for register
definitions.
TankHeight 4030 FLOAT 15.0 - m 0.A0 Simulated value, status and offset, see level for register
definitions.
MiddlePressure 4036 FLOAT 1.5 - bar 0.F0 Simulated value, status and offset, see level for register
definitions.
StrapTableLength 4304 DWORD 0 0 - 100 # 0.B0 Number of strap table points used.
ZeroLevelToBottom 4306 FLOAT 0.0 - m 0.B0 Distance from zero level to the tanks physical
bottom.
L1 4308 FLOAT 0.0 - m 0.B0 Geometry parameter #1. The tank diameter.
L2 4310 FLOAT 0.0 - m 0.B0 Geometry parameter #2. The length. Only
applicable for horizontal cylinder.
Reserved_L3 4312 FLOAT 0.0 - m 0.B0 Geometry parameter #3.
InterpolateMethod 4314 ENUM 0 - na 0.B0 Interpolation method.
0: Linear Interpolation
1: Quadratic Interpolation
LevelOffs 4316 FLOAT 0.0 - m 0.B0 Strapping table offset. This offset will be added to
the measured Level and then used to find the
corresponding volume value in the strapping table.
A positive LevelOffs value will increase the
displayed volume.
VolumeOffs 4318 FLOAT 0.0 - m3 0.B0 Strapping table volume offset. Note this offset is
also added when predefined tank shapes are used.
This offset will be added to the calculated volume.
VolumeUnitCode 4320 ENUM 43 - na 0.B0 Strapping table Volume Unit Code.
40: UsGallons
41: Liter
42: UkGallons
Issue 1
43: CubicMeter
46: Barrels
112: CubicFeet
TankNo 4322 ENUM 0 - # 0.B0 Tank number for the volume calculation.
0: Not active
1: Tank 1
2: Tank 2
3: Tank 3
4: Tank 4
5: Tank 5
6: Tank 6
7: Tank 7
8: Tank 8
9: Tank 9
10: Tank 10
NetVol_VCT_Table 4324 ENUM 0 - # 1.B6 VCT Table used for the Net Standard Volume
Calculation. 54A, 54B, 54D, 6A, 6B and 6D of the
API Standard 2540 from 2004 are supported.
0: Net Volume Disabled
50: API 2540 54A 2004
51: API 2540 54B 2004
Issue 1
0: Not active
1: Tank 1
2: Tank 2
3: Tank 3
4: Tank 4
5: Tank 5
6: Tank 6
7: Tank 7
8: Tank 8
9: Tank 9
10: Tank 10
Arithm1_A_TmvType 4804 SENUM 0 - na 0.E0 TMV Type for the arithmetic operation parameter
A.
Arithm1_A_TankNo 4805 SENUM 1 - na 0.E0 TMV Tank for the arithmetic operation parameter
A.
Arithm1_B_TmvType 4806 SENUM 0 - na 0.E0 TMV Type for the arithmetic operation parameter B.
Arithm1_B_TankNo 4807 SENUM 2 - na 0.E0 TMV Tank for the arithmetic operation parameter
A.
Arithm2_Operation 4808 SENUM 0 - na 0.E0 Arithm 2, see Arithm 1.
Arithm3_Operation 4816 SENUM 0 - na 0.E0 Arithm 3, see Arithm 1.
Arithm4_Operation 4824 SENUM 0 - na 0.E0 Arithm 4, see Arithm 1.
Issue 1
Dev1_VfdIndex 5005 WORD 0 - na 0.D1 Virtual Field Device index. It can be found in the
*.CFF file, See Rosemount 2410 Function and
Configuration Description.
Dev1_MiscConfig 5006 SBT 0x0 - na 0.D1 Miscellaneous configuration of Generic Device 1.
This register should normally not be changed.
Bit0: RmCmdSupported
Bit1: LevelDevice
Dev1_MiscData1 5007 WORD 1 - na 0.D1 This register can be used for several purposes.
If bit 1 is set in MiscConfig this register will be
used as RM_CMD index.
Dev1_MiscData2 5008 WORD 0 - na 0.D1 This register can be used for several purposes.
If bit 1 is set in MiscConfig this register will be
used as RM_DATA index.
Dev1_MiscData3 5009 WORD 0 - na 0.D1 This register can be used for several purposes.
If bit 1 is set in MiscConfig this register will be
used as RM_STATUS index.
Dev2_ManufacturerIdHi 5012 WORD 0 - na 0.E2 Generic device 2, see Generic device 1.
Dev3_ManufacturerIdHi 5024 WORD 0 - na 0.E2 Generic device 3, see Generic device 1.
Dev4_ManufacturerIdHi 5036 WORD 0 - na 0.E2 Generic device 4, see Generic device 1.
View1_GenDevNo 5048 SENUM 0 0-4 na 0.D1 Selected generic device for view 1.
0: NotUsed
1: GenericDevice1
Issue 1
2: GenericDevice2
3: GenericDevice3
4: GenericDevice4
View1_ParamNo 5049 WORD 0 - na 0.D1 Parameter number for view 1.
View1_ParamSize 5050 WORD 0 0 - 128 na 0.D1 Number of bytes in view 1.
View1_MiscConfig 5051 SBT 0x0 - na 0.D1 Miscellaneous configuration of Generic Device
View 1.
Bit0: StaticView
Bit1: TbModeBlk
View2_GenDevNo 5054 SENUM 0 0-4 na 0.D1 View 2, see view 1.
View3_GenDevNo 5060 SENUM 0 0-4 na 0.D1 View 3, see view 1.
View4_GenDevNo 5066 SENUM 0 0-4 na 0.D1 View 4, see view 1.
View5_GenDevNo 5072 SENUM 0 0-4 na 0.D1 View 5, see view 1.
View6_GenDevNo 5078 SENUM 0 0-4 na 0.D1 View 6, see view 1.
View7_GenDevNo 5084 SENUM 0 0-4 na 0.D1 View 7, see view 1.
View8_GenDevNo 5090 SENUM 0 0-4 na 0.D1 View 8, see view 1.
Val1_ValueViewNo 5096 SENUM 0 0-8 na 0.D1 Selected view where to find the value for value 1.
0: NotUsed
1: View1
2: View2
Issue 1
3: View3
4: View4
5: View5
6: View6
7: View7
8: View8
Val1_ValueViewOffset 5097 WORD 0 0 - 128 na 0.D1 Byte offset to the variable value within the view.
Val1_ValueType 5098 SENUM 0 - na 0.D1 Type of the value variable. Note that if other type
than DS_65 is used the status of the value will not
be present.
0: DS 65 TYPE
1: FLOAT TYPE
Val1_UnitViewNo 5099 SENUM 0 0-8 na 0.D1 Selected view where to find the unit for value 1.
0: NotUsed
1: View1
2: View2
3: View3
4: View4
5: View5
6: View6
7: View7
Issue 1
8: View8
Val1_UnitViewOffset 5100 WORD 0 0 - 128 na 0.D1 Byte offset to the variable unit whithin the view.
Val1_UnitType 5101 SENUM 0 - na 0.D1 Type of the unit variable.
0: DS 68 TYPE
1: U16 TYPE
2: U32 TYPE
Val1_TvNo 5102 SENUM 0 0 - 24 na 0.D1 TV number that the value will be copied to.
0: NotUsed
1: TV1
2: TV2
3: TV3
4: TV4
5: TV5
6: TV6
7: TV7
8: TV8
9: TV9
10: TV10
11: TV11
12: TV12
Issue 1
13: TV13
14: TV14
15: TV15
16: TV16
17: TV17
18: TV18
19: TV19
20: TV20
21: TV21
22: TV22
23: TV23
24: TV24
Val1_TvType 5103 SENUM 0 0 - 9999 na 0.D1 TV type of the value.
0: TV LEVEL
1: TV ULLAGE
2: TV LEVEL RATE
3: TV SIGNAL STRENGTH
4: TV VOLUME
5: TV GAIN
6: TV SIGNAL QUALITY
Issue 1
7: TV OBSERVED DENSITY
8: TV TANK HEIGHT
9: TV WATER LEVEL
10: TV HOUSING TEMP
11: TV LIQUID TEMP
12: TV VAPOR TEMP
13: TV TANK TEMP
14: TV FLOW RATE
51: TV TEMP 1
52: TV TEMP 2
53: TV TEMP 3
54: TV TEMP 4
55: TV TEMP 5
56: TV TEMP 6
57: TV TEMP 7
58: TV TEMP 8
59: TV TEMP 9
60: TV TEMP 10
61: TV TEMP 11
62: TV TEMP 12
Issue 1
63: TV TEMP 13
64: TV TEMP 14
65: TV TEMP 15
66: TV TEMP 16
67: TV TEMP POS 1
68: TV TEMP POS 2
69: TV TEMP POS 3
70: TV TEMP POS 4
71: TV TEMP POS 5
72: TV TEMP POS 6
73: TV TEMP POS 7
74: TV TEMP POS 8
75: TV TEMP POS 9
76: TV TEMP POS 10
77: TV TEMP POS 11
78: TV TEMP POS 12
79: TV TEMP POS 13
80: TV TEMP POS 14
81: TV TEMP POS 15
82: TV TEMP POS 16
Issue 1
100: TV HART PV
101: TV HART SV
102: TV HART TV
103: TV HART QV
150: TV AIN 1
151: TV AIN 2
152: TV AIN 3
200: TV PRESSURE 1
201: TV PRESSURE 2
202: TV PRESSURE 3
1000: TV MAN VALUE 1
1001: TV MAN VALUE 2
1002: TV MAN VALUE 3
1003: TV MAN VALUE 4
1004: TV MAN VALUE 5
1005: TV MAN VALUE 6
1006: TV MAN VALUE 7
1007: TV MAN VALUE 8
1008: TV MAN VALUE 9
1009: TV MAN VALUE 10
Issue 1
Tank_6_MiLowerLevelLimit 6044 FLOAT 0.0 - m 0.D1 MI limits for Tank 6, see Tank 1 for
register definitions.
Tank_7_MiLowerLevelLimit 6052 FLOAT 0.0 - m 0.D1 MI limits for Tank 7, see Tank 1 for
register definitions.
Tank_8_MiLowerLevelLimit 6060 FLOAT 0.0 - m 0.D1 MI limits for Tank 8, see Tank 1 for
register definitions.
Tank_9_MiLowerLevelLimit 6068 FLOAT 0.0 - m 0.D1 MI limits for Tank 9, see Tank 1 for
register definitions.
Tank_10_MiLowerLevelLimit 6076 FLOAT 0.0 - m 0.D1 MI limits for Tank 10, see Tank 1 for
register definitions.
MultTempSourceConfig 6092 BITFIELD 0x0 - na 1.G0 Source selection for the Multi Average
Temperature calculation. This function
supports the AvgTemp calculation based
on more than one Tank Position. See
Raptor-DE-0187 for more details.
Bit0: TankPos 1
Bit1: TankPos 2
Bit2: TankPos 3
Bit3: TankPos 4
Bit4: TankPos 5
Bit5: TankPos 6
Bit6: TankPos 7
Issue 1
Bit7: TankPos 8
Bit8: TankPos 9
Bit9: TankPos 10
MultTempDestConfig 6094 BITFIELD 0x0 - na 1.G0 Source selection for the Multi Average
Temperature calculation. The
AvgLiqTemp, AvgVaporTemp and
AvgTankTemp will be replaced with the
Multi Avg Temperatures in the
Destination Tank Positions.
Bit0: TankPos 1
Bit1: TankPos 2
Bit2: TankPos 3
Bit3: TankPos 4
Bit4: TankPos 5
Bit5: TankPos 6
Bit6: TankPos 7
Bit7: TankPos 8
Bit8: TankPos 9
Bit9: TankPos 10
TmvErrorCtrl 6096 BITFIELD 0x0 - na 1.B0 TMV error indication control. See also
HREG 6098.
Bit0: AvgTemp KeepLastValid
Issue 1
TmvErrorValueAvgTemp 6098 FLOAT -300.0 - C 1B0 Used error value for average temperatures
in case if invalid value. Note that the value
is always given in Deg C. See also HREG
6096.
TmvFrozenLimit 6100 DWORD 20000 1000 - ms 0.E0 The maximum allowed time between
180000 TMV updates. If the value not is updated
within this time the TMV status bit frozen
will be set.
HregLockTime 6102 DWORD 60000 - ms 0.E0 The time that HREG writes will be locked
if a HREG write has been performed on
one bus, i.e. configuration can only be
performed from one bus at a time.
Trl2_PresCtrl 6104 ENUM 1 - na 0.E2 Selects unit for TRL2 IREG Integer
Length and integer temperatures.
1: Metric And Celsius
2: Imperial And Fahrenheit
3: Imperial And Celsius
4: Metric And Fahrenheit
Trl2_AnalogIn_1_TmvType 6106 ENUM 4 0 - 9999 na 0.E2 TMV Type that is used as Analog_In_1 in
TRL2 IREG. Note this register must have
the value 4 (FWL) if used in a Tank
Master System including a FCU.
0: TMV LEVEL
Issue 1
1: TMV ULLAGE
2: TMV LEVEL RATE
3: TMV SIGNAL STRENGTH
4: TMV FREE WATER LEVEL
5: TMV VAPOR PRESSURE
6: TMV LIQUID PRESSURE
7: TMV AIR PRESSURE
8: TMV AMBIENT TEMP
9: TMV VAPOR AVG TEMP
10: TMV LIQUID AVG TEMP
11: TMV TANK AVG TEMP
12: TMV TEMP 1
13: TMV TEMP 2
14: TMV TEMP 3
15: TMV TEMP 4
16: TMV TEMP 5
17: TMV TEMP 6
18: TMV TEMP 7
19: TMV TEMP 8
20: TMV TEMP 9
Issue 1
Trl2_HartSlave_1_TmvType 6114 ENUM 5 0 - 9999 na 0.E2 TMV Type that is used as HART_1 in
TRL2 IREG. Note this register must have
the value 5 (Vapor Pressure) if used in a
Tank Master System including a FCU. See
Analog In 1 for enumeration.
Trl2_HartSlave_2_TmvType 6116 ENUM 6 0 - 9999 na 0.E2 TMV Type that is used as HART_2 in
TRL2 IREG. Note this register must have
the value 6 (Liquid Pressure) if used in a
Tank Master System including a FCU. See
Analog In 1 for enumeration.
Trl2_HartSlave_3_TmvType 6118 ENUM 60 0 - 9999 na 0.E2 TMV Type that is used as HART_3 in
TRL2 IREG. See Analog In 1 for
enumeration. This input is not used by
tank Master.
Trl2_Reserved 6120 DWORD 0 0-0 na 0.E2 Reserved.
Trl2_HartSlave_1_LoRange 6122 FLOAT 0.0 - na 0.E2 Low range value for HART slave 1 in
TRL2 IREG. The HART1 float value is
scaled to a signed integer value using the
following formula IntVal = 10000 *
(H1_float_Value – LoRange) / (HiRange –
LoRange)
Trl2_HartSlave_1_HiRange 6124 FLOAT 0.0 - na 0.E2 High range value for HART slave 1 in
TRL2 IREG.
Issue 1
LoRangeMisc 6126 FLOAT 0.0 - na 1.B1 Multi purpose register used used in
emulation protocols.
[Whessoe] Lo Pressure range [Bar], Taks
30.
HiRangeMisc 6128 FLOAT 0.0 - na 1.B1 Multi purpose register used used in
emulation protocols.
[Whessoe] Hi Pressure range [Bar], Taks
30.
MaxAutoBlockedTempSensors 6134 DWORD 0 - na 1.A6 Defines the maximum number of failing
temperature sensors that will be
automatically blocked from the average
liquid temperature calculation.
BlockAutoMap1 6136 BITFIELD 0x0 - na 1.A6 The selected TMV will not be
automatically mapped from a Device TV.
For example, if the FWL bit is raised in
this register, the FWL value will not be
automatically fetched from a 2240.
Bit0: LEVEL
Bit1: ULLAGE
Bit2: LEVEL RATE
Bit3: SIGNAL STRENGTH
Bit4: FREE WATER LEVEL
Bit5: VAPOR PRESSURE
Issue 1
Bit26: TEMP 14
Bit27: TEMP 15
Bit28: TEMP 16
Bit29: OBSERVED DENSITY
Bit30: REFERENCE DENSITY
Bit31: TANK VOLUME
BlockAutoMap2 6138 BITFIELD 0x0 - na 1.A6 See the register above.
Bit0: USER DEF 1
Bit1: USER DEF 2
Bit2: USER DEF 3
Bit3: USER DEF 4
Bit4: USER DEF 5
Bit5: FLOW RATE
Bit6: TANK HEIGHT
Bit7: DELTA LEVEL
Bit8: FWV
Bit9: NSV
StdQ_LevelUnit 6140 ENUM 0 - na 0.F3 Selects Length unit for StdQ area.
0: Auto
44: Feet
Issue 1
45: Meter
49: MilliMeter
StdQ_LevelRateUnit 6142 ENUM 0 - na 0.F3 Selects Level Rate unit for StdQ area.
0: Auto
20: Feet per second
21: Meters per second
120: Meters per hour
247: Feet per hour
StdQ_TempElementUnit 6144 BITFIELD 0x0 - na 0.F3 Selects element Temperature unit and
resolution for StdQ area.
Bit0: Tank1 Fahrenheit
Bit1: Tank1 HighRes
Bit3: Tank2 Fahrenheit
Bit4: Tank2 HighRes
Bit6: Tank3 Fahrenheit
Bit7: Tank3 HighRes
Bit9: Tank4 Fahrenheit
Bit10: Tank4 HighRes
Bit12: Tank5 Fahrenheit
Bit13: Tank5 HighRes
Issue 1
7: Bar
11: Pa
12: KPa
14: Atm
263: Bar A
519: Bar G
262: PSI A
518: PSI G
StdQ_DensityUnit 6152 ENUM 0 - na 0.F3 Selects Density unit for StdQ area and
TRL2 IREG HART variables.
0: Auto
92: kg/m3
93: lbPerUsGallon
104: degAPI
StdQ_VolumeUnit 6154 ENUM 0 - na 0.F3 Selects Volume unit for StdQ area and
TRL2 IREG HART variables.
0: Auto
40: US Gallons
41: Liter
43: Cubic Meters
46: Barrels
Issue 1
StdQ_FlowRateUnit 6156 ENUM 0 - na 0.F3 Selects Flow Rate unit for StdQ area and
TRL2 IREG HART variables.
0: Auto
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
StdQ_TK1_UserDef1Unit 6176 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 1 within the StdQ area. NOTE
Not used in the TRL2 IREG area.
0: NotUsed
32: Deg C
33: Deg F
35: Kelvin
44: Feet
45: Meter
49: MilliMeter
20: Feet per second
21: Meters per second
120: Meters per hour
247: Feet per hour
Issue 1
6: Psi
7: Bar
11: Pa
12: KPa
14: Atm
263: Bar A
519: Bar G
262: PSI A
518: PSI G
40: US Gallons
41: Liter
43: Cubic Meters
46: Barrels
61: Kilograms
62: Metric tons
63: Pounds
64: Short tons
65: Long tons
17: LiterPerMinute
19: CubicMeterPerHour
Issue 1
134: BarrelPerHour
136: UsGallonPerHour
92: kg/m3
93: lbPerUsGallon
104: degAPI
36: mV
StdQ_TK1_UserDef2Unit 6178 ENUM 0 - na 0.F3 Selects unit for the User Defined 2 value
for Tank 1 within the StdQ area. NOTE
Not used in the TRL2 IREG area.
StdQ_TK1_UserDef3Unit 6180 ENUM 0 - na 0.F3 Selects unit for the User Defined 3 value
for Tank 1 within the StdQ area. NOTE
Not used in the TRL2 IREG area.
StdQ_TK1_UserDef4Unit 6182 ENUM 0 - na 0.F3 Selects unit for the User Defined 4 value
for Tank 1 within the StdQ area. NOTE
Not used in the TRL2 IREG area.
StdQ_TK1_UserDef5Unit 6184 ENUM 0 - na 0.F3 Selects unit for the User Defined 5 value
for Tank 1 within the StdQ area. NOTE
Not used in the TRL2 IREG area.
StdQ_TK2_UserDef1Unit 6186 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_TK3_UserDef1Unit 6196 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
Issue 1
StdQ_TK4_UserDef1Unit 6206 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_TK5_UserDef1Unit 6216 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_TK6_UserDef1Unit 6226 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_TK7_UserDef1Unit 6236 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_TK8_UserDef1Unit 6246 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_TK9_UserDef1Unit 6256 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_TK10_UserDef1Unit 6266 ENUM 0 - na 0.F3 Selects unit for the User Defined 1 value
for Tank 2 within the StdQ area.
StdQ_UserCfg1_TmvType 6280 ENUM 0 - na 0.F3 Selects source TMV-type for User Config
1 value within the StdQ area.
0: TMV LEVEL
1: TMV ULLAGE
2: TMV LEVEL RATE
3: TMV SIGNAL STRENGTH
4: TMV FREE WATER LEVEL
5: TMV VAPOR PRESSURE
Issue 1
1: Tank 1
2: Tank 2
3: Tank 3
4: Tank 4
5: Tank 5
6: Tank 6
7: Tank 7
8: Tank 8
9: Tank 9
10: Tank 10
StdQ_UserCfg1_Unit 6284 ENUM 0 - na 0.F3 Selects unit for the User Config 1 value.
0: NotUsed
32: Deg C
33: Deg F
35: Kelvin
44: Feet
45: Meter
49: MilliMeter
20: Feet per second
21: Meters per second
Issue 1
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
92: kg/m3
93: lbPerUsGallon
104: degAPI
36: mV
StdQ_UserCfg2_TmvType 6286 ENUM 0 - na 0.F3 User Config 2 configuration.
StdQ_UserCfg3_TmvType 6292 ENUM 0 - na 0.F3 User Config 3 configuration.
StdQ_UserCfg4_TmvType 6298 ENUM 0 - na 0.F3 User Config 4 configuration.
StdQ_UserCfg5_TmvType 6304 ENUM 0 - na 0.F3 User Config 5 configuration.
StdQ_UserCfg6_TmvType 6310 ENUM 0 - na 0.F3 User Config 6 configuration.
StdQ_UserCfg7_TmvType 6316 ENUM 0 - na 0.F3 User Config 7 configuration.
StdQ_UserCfg8_TmvType 6322 ENUM 0 - na 0.F3 User Config 8 configuration.
StdQ_UserCfg9_TmvType 6328 ENUM 0 - na 0.F3 User Config 9 configuration.
StdQ_UserCfg10_TmvType 6334 ENUM 0 - na 0.F3 User Config 10 configuration.
StdQ_UserCfg11_TmvType 6340 ENUM 0 - na 0.F3 User Config 11 configuration.
StdQ_UserCfg12_TmvType 6346 ENUM 0 - na 0.F3 User Config 12 configuration.
StdQ_UserCfg13_TmvType 6352 ENUM 0 - na 0.F3 User Config 13 configuration.
Issue 1
Bit7: GaugePressureTank8
Bit8: GaugePressureTank9
Bit9: GaugePressureTank10
TankMidPressCtrl 6402 BITFIELD 0x3FF - na 1.B0 Configuration of Middle Pressure sensor
type. If bit is set the pressure sensor
measures gauge pressure (relative). If bit is
cleared the pressure sensor measures
absolute pressure. Note that this setting
not will override any pressure device
setting, e.g. Primary Value Type or
specific absoulte/gauge pressure unit. See
TankVapPressCtrl for bit definition.
TankLiqPressCtrl 6404 BITFIELD 0x3FF - na 1.B0 Configuration of Liquid Pressure sensor
type. If bit is set the pressure sensor
measures gauge pressure (relative). If bit is
cleared the pressure sensor measures
absolute pressure. Note that this setting
not will override any pressure device
setting, e.g. Primary Value Type or
specific absoulte/gauge pressure unit. See
TankVapPressCtrl for bit definition.
TankAirPress 6406 FLOAT 1.01325 - bar 1.B0 Air pressure (Atmospheric pressure) used
when converting to/from
absolute/gauge(relative) pressure. Note
Issue 1
16: FF Device 16
21: HART Device 1
22: HART Device 2
23: HART Device 3
24: HART Device 4
25: HART Device 5
31: AIN Device 1
41: TankHub Device
50: Emul Device 1
51: Emul Device 2
52: Emul Device 3
53: Emul Device 4
54: Emul Device 5
55: Emul Device 6
56: Emul Device 7
57: Emul Device 8
58: Emul Device 9
59: Emul Device 10
TmvDevMap1_ParamNo 7001 SENUM 0 - na 0.E0 FF Parameter number to write TMV value to.
0: Disabled
Issue 1
1: Parameter 1
2: Parameter 2
3: Parameter 3
4: Parameter 4
5: Parameter 5
6: Parameter 6
7: Parameter 7
8: Parameter 8
TmvDevMap1_TankNo 7002 SENUM 0 - na 0.E0 TMV Tank number to get value from.
0: Not active
1: Tank 1
2: Tank 2
3: Tank 3
4: Tank 4
5: Tank 5
6: Tank 6
7: Tank 7
8: Tank 8
9: Tank 9
10: Tank 10
Issue 1
TmvDevMap22_DeviceNo 7210 SENUM 0 - na 0.E0 TMV Devicemap 22,see TMV Device Map 1.
TmvDevMap23_DeviceNo 7220 SENUM 0 - na 0.E0 TMV Devicemap 23,see TMV Device Map 1.
TmvDevMap24_DeviceNo 7230 SENUM 0 - na 0.E0 TMV Devicemap 24,see TMV Device Map 1.
TmvDevMap25_DeviceNo 7240 SENUM 0 - na 0.E0 TMV Devicemap 25,see TMV Device Map 1.
TmvDevMap26_DeviceNo 7250 SENUM 0 - na 0.E0 TMV Devicemap 26,see TMV Device Map 1.
TmvDevMap27_DeviceNo 7260 SENUM 0 - na 0.E0 TMV Devicemap 27,see TMV Device Map 1.
TmvDevMap28_DeviceNo 7270 SENUM 0 - na 0.E0 TMV Devicemap 28,see TMV Device Map 1.
TmvDevMap29_DeviceNo 7280 SENUM 0 - na 0.E0 TMV Devicemap 29,see TMV Device Map 1.
TmvDevMap30_DeviceNo 7290 SENUM 0 - na 0.E0 TMV Devicemap 30,see TMV Device Map 1.
46: Barrel
TempUnit 9076 SENUM 32 - na 1.B0 Hart Slave temperature unit.
32: Deg C
33: Deg F
35: Kelvin
VelocityUnit 9077 SENUM 120 - na 1.B0 Hart Slave velocity unit.
20: FeetPerSecond
21: MeterPerSecond
120: MeterPerHour
247: FeetPerHour
PressureUnit 9078 SENUM 7 - na 1.B0 Hart Slave pressure unit.
6: Psi
7: Bar
11: Pa
12: KPa
14: Atm
DensityUnit 9079 SENUM 92 - na 1.B0 Hart Slave density unit.
92: kg per m3
104: Deg API
FlowRateUnit 9080 SENUM 19 - na 1.B0 Hart Slave volumetric flowrate unit.
Issue 1
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
MassUnit 9081 SENUM 61 - na 1.C6 Hart Slave mass unit. Only used for User Defined
unit conversion.
61: Kilograms
62: Metric Tons
63: Pounds
64: Short Tons
65: Long Tons
WirelessAoutCurr 9090 FLOAT 18.0 4.0 - mA 1.B0 Analog output current applied when Wireless HART
18.0 is used.
WirelessShortAddress 9092 WORD 15 0 - 63 na 1.B0 HART short address of the 2410 when Wireless
HART is used.
WirelessHartVersion 9093 WORD 7 5-7 # 1.B0 HART revision used when Wireless HART is used.
R2410_Date 9102 WORD 257 - na 1.B0 Date code, R2410.
R2410_AssemblyNo 9104 WORD 0 - na 1.B0 Assembly code, R2410. See also HREG 9001.
R2410_Message 9110 WORD 2178 - na 1.B0 Message (packed), R2410.
R2410_Descriptor 9122 WORD 2178 - na 1.B0 Descriptor (Packed), R2410.
R2410_Tag 9128 WORD 11595 - na 1.B0 Tag (Packed), R2410.
Issue 1
DevRev5400 9651 WORD 0 - na 1.B1 Used Device Revision for 5400 devices. 0 will give
default Device Revision, i.e. DR=2 (HART5) and
DR=3 (HART7).
DevRev5900 9652 WORD 0 - na 1.B1 Used Device Revision for 5900 devices. 0 will give
default Device Revision, i.e. DR=1 (HART5) and
DR=2 (HART7).
DevRev2240 9653 WORD 0 - na 1.B1 Used Device Revision for 2240 devices. 0 will give
default Device Revision, i.e. DR=1 (HART5) and
DR=2 (HART7).
49: MilliMeter
20: Feet per second
21: Meters per second
120: Meters per hour
247: Feet per hour
6: Psi
7: Bar
11: Pa
12: KPa
14: Atm
263: Bar A
519: Bar G
262: PSI A
518: PSI G
40: US Gallons
41: Liter
43: Cubic Meters
46: Barrels
61: Kilograms
62: Metric tons
Issue 1
63: Pounds
64: Short tons
65: Long tons
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
92: kg/m3
93: lbPerUsGallon
104: degAPI
36: mV
Ain_LowerRange 9804 FLOAT 0.0 - na 1.B0 Value that corresponds to 4.0 mA imput
current.
Ain_UpperRange 9806 FLOAT 10000.0 - na 1.B0 Value that corresponds to 20.0 mA input
current.
Ain_LoCurrLimit 9814 FLOAT 3.8 - mA 1.B0 Current below this limit will set the Error
Status for Ain.
Ain_HiCurrLimit 9816 FLOAT 20.8 - mA 1.B0 Current above this limit will set the Error
Status for Ain.
Ain_FilterFactor 9818 FLOAT 0.1 0.0 - 1.0 na 1.B0 LP-Filter factor for Analog Input. High value
gives low filtering.
Issue 1
7: Tank 7
8: Tank 8
9: Tank 9
10: Tank 10
Aout_TmvType 9914 ENUM 0 - na 1.B0 Analog Output source TmvType.
0: TMV LEVEL
1: TMV ULLAGE
2: TMV LEVEL RATE
3: TMV SIGNAL STRENGTH
4: TMV FREE WATER LEVEL
5: TMV VAPOR PRESSURE
6: TMV LIQUID PRESSURE
7: TMV AIR PRESSURE
8: TMV AMBIENT TEMP
9: TMV VAPOR AVG TEMP
10: TMV LIQUID AVG TEMP
11: TMV TANK AVG TEMP
12: TMV TEMP 1
13: TMV TEMP 2
14: TMV TEMP 3
Issue 1
SB_FieldCalibOffs_4mA 9936 FLOAT 0.0 -0.5 - mA 1.C3 Field calibration offset from 4.0 mA for the
0.5 Secondary Bus. This register is updated by the
Rosemount 2410 when receiving a HART
Command 45,46,66 and 67 (or Modbus cmd) to
perform a Analog Out field calibration.
SB_FieldCalibOffs_20mA 9938 FLOAT 0.0 -0.5 - mA 1.C3 Field calibration offset from 20.0 mA for the
0.5 Secondary Bus. This register is updated by the
Rosemount 2410 when receiving a HART
Command 45,46,66 and 68 (or Modbus cmd) to
perform a Analog Out field calibration.
LevelRate 3 INT na 0.A0 Level rate. The unit is selected in HREG 7, cm/h or foot/h.
Level 4 INT na 0.A0 Level. The unit is selected in HREG 7, mm or 1/16 inch.
Ullage 5 WORD na 0.A0 Ullage. The unit is selected in HREG 7, mm or 1/16 inch.
AnalogInput_1 6 INT na 0.A0 The Analog Input 1 value. Note that if the measured value is outside the
range of -32768 to +32767 the endpoint will be used and the status bit in
DeviceStatus will be raised (see Ireg 2). FWL must be mapped (default
mapping) her in a Tank Master FCU System, mm or 1/16 inch.
AnalogInput_2 7 INT na 0.A0 The Analog Input 2 value. Note that if the measured value is outside the
range of -32768 to +32767 the endpoint will be used and the status bit in
DeviceStatus will be raised (see Ireg 2). Vapor Temperature must be
mapped her (default mapping) in a Tank Master FCU System, 1/10 °C or
1/10 °F. See Analog Input 1.
HartSlave_1 8 INT na 0.A0 The HART slave sensor 1 measured Primary Variable in percent of range *
100.
Temp_14 11 INT na 0.A0 Temperature value from temperature sensor 14. The unit is selected in
HREG 7, 1/10 °C or 1/10 °F.
Temp_13 12 INT na 0.A0 Temperature value from temperature sensor 13.
Temp_12 13 INT na 0.A0 Temperature value from temperature sensor 12.
Temp_11 14 INT na 0.A0 Temperature value from temperature sensor 11.
Temp_10 15 INT na 0.A0 Temperature value from temperature sensor 10.
Temp_9 16 INT na 0.A0 Temperature value from temperature sensor 9.
Temp_8 17 INT na 0.A0 Temperature value from temperature sensor 8.
Temp_7 18 INT na 0.A0 Temperature value from temperature sensor 7.
Issue 1
Bit14: DeviceError
BlockedStatus 26 SBT na 0.A0 Bit0: Sens1Blocked
Bit1: Sens2Blocked
Bit2: Sens3Blocked
Bit3: Sens4Blocked
Bit4: Sens5Blocked
Bit5: Sens6Blocked
Bit6: Sens7Blocked
Bit7: Sens8Blocked
Bit8: Sens9Blocked
Bit9: Sens10Blocked
Bit10: Sens11Blocked
Bit11: Sens12Blocked
Bit12: Sens13Blocked
Bit13: Sens14Blocked
Bit14: MILegalTemp
Bit15: MIApproved
TempStatus 27 SBT na 0.A0 Bit0: Sens1Error
Bit1: Sens2Error
Bit2: Sens3Error
Issue 1
Bit3: Sens4Error
Bit4: Sens5Error
Bit5: Sens6Error
Bit6: Sens7Error
Bit7: Sens8Error
Bit8: Sens9Error
Bit9: Sens10Error
Bit10: Sens11Error
Bit11: Sens12Error
Bit12: Sens13Error
Bit13: Sens14Error
Bit15: AvgLiqTempError
AverageTemp 28 INT na 0.A0 The Average Liquid Temperature. The unit is selected in HREG 7, 1/10 °C
or 1/10 °F.
AnalogInputStatus 29 SBT na 0.A0 Bit0: Analog1Error
Bit2: Analog2Error
AnalogIn_1_float 30 FLOAT na 0.A0 The floating point value of Analog In 1, see IREG 6. Note this variable is
not stored in the FCU memory.
AnalogIn_2_float 32 FLOAT na 0.A0 The floating point value of Analog In 2, see IREG 7. Note this variable is
not stored in the FCU memory.
Issue 1
HartSlave_3_float 36 FLOAT na 0.A0 Contains the Value of a TMV selected with HREG 6118. Tank Master is
not using this variable. All TMV’s except UserDefined will be converted
to the units configured in the Holding register block SysCtrl.
HartSlave_2_float 38 FLOAT na 0.A0 Contains the Value of a TMV selected with HREG 6116. In a Tank Master
FCU System the TMV Liquid Pressure must be mapped here Default
mapping). All TMV’s except UserDefined will be converted to the units
configured in the Holding register block SysCtrl.
HartSlave_1_float 40 FLOAT na 0.A0 Contains the Value of a TMV selected with HREG 6114. In a Tank Master
FCU System the TMV Vapor Pressure must be mapped here Default
mapping). All TMV’s except UserDefined will be converted to the units
configured in the Holding register block SysCtrl.
HartSlaveStatus 42 SBT na 0.A0 Bit0: HartSlave1ValueInvalid
Bit1: HartSlave2ValueInvalid
Bit2: HartSlave3ValueInvalid
RelayStatus 43 SBT na 0.A0 Bit0: Relay K1 Energized
Bit1: Relay K1 Deenergized
Bit2: Relay K2 Energized
Bit3: Relay K2 Deenergized
Bit6: Relay SIL Energized
Bit7: Relay SIL Deenergized
Bit8: Relay K1 Error
Bit9: Relay K2 Error
Issue 1
9: GPE
10: Sakura
11: GSI ASCII
12: TIC
16: HART
255: Unknown Protocol
Baudrate 1201 WORD # 0.A0 Used baud rate.
DataBits 1202 WORD # 0.A0 Used data bit count.
StopBits 1203 WORD # 0.A0 Used stop bit count.
Parity 1204 SENUM na 0.A0 Used parity.
0: None
1: Odd
2: Even
ExtBaudrate 1205 WORD # 1.B7 Used Baud-rate on the external Primary bus.
RecMessages 1206 DWORD # 0.A0 Received message count.
MessagesToMe 1208 DWORD # 0.A0 Received message count to configured address.
SentMessages 1210 DWORD # 0.A0 Sent message count.
FramingErrors 1212 DWORD # 0.A0 Framing error count.
CrcErrors 1214 DWORD # 0.A0 CRC error count.
UartErrors 1216 DWORD # 0.A0 Uart error count.
Issue 1
6: Whessoe 550
7: Whessoe 660
9: GPE
10: Sakura
11: GSI ASCII
12: TIC
16: HART
255: Unknown Protocol
Baudrate 1251 WORD # 0.A0 Used baud-rate between CB and Modem.
DataBits 1252 WORD # 0.A0 Used data bit count.
StopBits 1253 WORD # 0.A0 Used stop bit count.
Parity 1254 SENUM na 0.A0 Used parity.
0: None
1: Odd
2: Even
ExtBaudrate 1255 WORD # 1.B7 Used Baud-rate on the external Secondary bus.
RecMessages 1256 DWORD # 0.A0 Received message count.
MessagesToMe 1258 DWORD # 0.A0 Received message count to configured address.
SentMessages 1260 DWORD # 0.A0 Sent message count.
FramingErrors 1262 DWORD # 0.A0 Framing error count.
Issue 1
Dev1_NoOfOpenFailures 1342 DWORD # 0.C5 Number of times that the device has failed to be opened.
Dev1_NoOfReads 1344 DWORD # 0.A0 Number of reads from device 1.
Dev1_NoOfReadErrors 1346 DWORD # 0.A0 Number of read errors for device 1.
Dev1_NoOfReadTimeOuts 1348 DWORD # 0.A0 Number of read timeouts for device 1.
Dev1_AvgReadTime 1350 DWORD ms 0.C1 Average read time for device 1.
Dev1_NoOfWrites 1352 DWORD # 0.A0 Number of writes to device 1.
Dev1_NoOfWritesErrors 1354 DWORD # 0.A0 Number of write errors for device 1.
Dev1_NoOfWritesTimeOuts 1356 DWORD # 0.A0 Number of write timeouts for device 1.
Dev1_AvgWriteTime 1358 DWORD ms 0.C1 Average write time for device 1.
Dev2_NoOfOpenings 1360 DWORD # 0.C5 Diagnostics device 2. See device 1.
Dev3_NoOfOpenings 1380 DWORD # 0.C5 Diagnostics device 3. See device 1.
Dev4_NoOfOpenings 1400 DWORD # 0.C5 Diagnostics device 4. See device 1.
Dev5_NoOfOpenings 1420 DWORD # 0.C5 Diagnostics device 5. See device 1.
Dev6_NoOfOpenings 1440 DWORD # 0.C5 Diagnostics device 6. See device 1.
Dev7_NoOfOpenings 1460 DWORD # 0.C5 Diagnostics device 7. See device 1.
Dev8_NoOfOpenings 1480 DWORD # 0.C5 Diagnostics device 8. See device 1.
Dev9_NoOfOpenings 1500 DWORD # 0.C5 Diagnostics device 9. See device 1.
Dev10_NoOfOpenings 1520 DWORD # 0.C5 Diagnostics device 10. See device 1.
Dev11_NoOfOpenings 1540 DWORD # 0.C5 Diagnostics device 11. See device 1.
Dev12_NoOfOpenings 1560 DWORD # 0.C5 Diagnostics device 12. See device 1.
Dev13_NoOfOpenings 1580 DWORD # 0.C5 Diagnostics device 13. See device 1.
Issue 1
Bit0: DeviceHandled
Bit1: DeviceOpened
Bit2: DeviceConnected
Bit3: DeviceConfigured
Bit4: DeviceModeAuto
Row2_DeviceType 1714 ENUM na 0.A0 Device 2, see device 1.
Row3_DeviceType 1728 ENUM na 0.A0 Device 3, see device 1.
Row4_DeviceType 1742 ENUM na 0.A0 Device 4, see device 1.
Row5_DeviceType 1756 ENUM na 0.A0 Device 5, see device 1.
Row6_DeviceType 1770 ENUM na 0.A0 Device 6, see device 1.
Row7_DeviceType 1784 ENUM na 0.A0 Device 7, see device 1.
Row8_DeviceType 1798 ENUM na 0.A0 Device 8, see device 1.
Row9_DeviceType 1812 ENUM na 0.A0 Device 9, see device 1.
Row10_DeviceType 1826 ENUM na 0.A0 Device 10, see device 1.
Row11_DeviceType 1840 ENUM na 0.A0 Device 11, see device 1.
Row12_DeviceType 1854 ENUM na 0.A0 Device 12, see device 1.
Row13_DeviceType 1868 ENUM na 0.A0 Device 13, see device 1.
Row14_DeviceType 1882 ENUM na 0.A0 Device 14, see device 1.
Row15_DeviceType 1896 ENUM na 0.A0 Device 15, see device 1.
Row16_DeviceType 1910 ENUM na 0.A0 Device 16, see device 1.
Issue 1
Bit13: R4 Error
Bit14: R5 Error
Bit15: R6 Error
Bit16: R7 Error
Bit17: R8 Error
Bit18: R9 Error
Bit19: R10 Error
Bit20: R1 Disabled
Bit21: R2 Disabled
Bit22: R3 Disabled
Bit23: R4 Disabled
Bit24: R5 Disabled
Bit25: R6 Disabled
Bit26: R7 Disabled
Bit27: R8 Disabled
Bit28: R9 Disabled
Bit29: R10 Disabled
DeviceStatus 1994 BITFIELD na 0.F0 Device Status for the Tank Hub.
Bit1: DeviceWarning
Bit7: DeviceError
Issue 1
Bit3: SW Warning
Bit4: Other Mem Warning
Bit5: Sys Warning
Bit6: Display Warning
Bit7: Aux Warning
Bit8: Ff Stack Warning
Bit9: Tankbus Com Warning
Bit10: Host Com Warning
Bit11: Data Manager Warning
Bit12: Config Warning
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidLevel
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
Bit30: InvalidLevelRate
Bit31: InvalidUllage
TK1_UpdateCounter 2008 WORD # 0.F0 No of updates for the level value for Tank 1.
TK1_SignalStrength 2009 WORD mV 0.F0 Signal strength value.
TK2_Level 2010 FLOAT na 0.F0 See Tank 1.
TK3_Level 2020 FLOAT na 0.F0 See Tank 1.
Issue 1
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidLiquidTemp
Bit24: MaintAlert
Bit31: InvalidVaporTemp
TK1_UpdateCounter 2106 WORD # 0.F0 No of updates for the Average temperature value for Tank 1.
TK2_AverageProductTemp 2108 FLOAT na 0.F0 See Tank 1.
TK3_AverageProductTemp 2116 FLOAT na 0.F0 See Tank 1.
TK4_AverageProductTemp 2124 FLOAT na 0.F0 See Tank 1.
TK5_AverageProductTemp 2132 FLOAT na 0.F0 See Tank 1.
TK6_AverageProductTemp 2140 FLOAT na 0.F0 See Tank 1.
TK7_AverageProductTemp 2148 FLOAT na 0.F0 See Tank 1.
TK8_AverageProductTemp 2156 FLOAT na 0.F0 See Tank 1.
TK9_AverageProductTemp 2164 FLOAT na 0.F0 See Tank 1.
TK10_AverageProductTemp 2172 FLOAT na 0.F0 See Tank 1.
Issue 1
Bit17: Cfail E2
Bit18: Cfail E3
Bit19: Cfail E4
Bit20: Cfail E5
Bit21: Cfail E6
Bit22: Cfail E7
Bit23: Cfail E8
Bit24: Cfail E9
Bit25: Cfail E10
Bit26: Cfail E11
Bit27: Cfail E12
Bit28: Cfail E13
Bit29: Cfail E14
Bit30: Cfail E15
Bit31: Cfail E16
TK1_ElementInProductStatus 2202 SBT na 0.F0 Bit is set if Element is in product for Tank 1.
Bit0: E1
Bit1: E2
Bit2: E3
Bit3: E4
Issue 1
Bit4: E5
Bit5: E6
Bit6: E7
Bit7: E8
Bit8: E9
Bit9: E10
Bit10: E11
Bit11: E12
Bit12: E13
Bit13: E14
Bit14: E15
Bit15: E16
TK1_ElementInVaporStatus 2203 SBT na 0.F0 Bit is set if Element is in vapor for Tank 1. See Element in product
status for bit definitions.
TK1_ElementBlockedStatus 2204 SBT na 0.F3 Bit is set if Element is blocked for Tank 1. See Element in product
status for bit definitions.
TK1_TempEmenentValue1 2208 INT na 0.F0 Element 1 Temperature value for Tank 1. For unit information see
standard unit area.
TK1_TempEmenentValue2 2209 INT na 0.F0 Element 2.
TK1_TempEmenentValue3 2210 INT na 0.F0 Element 3.
TK1_TempEmenentValue4 2211 INT na 0.F0 Element 4.
Issue 1
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK1_FreeWaterLevelUpdateCounter 2504 WORD # 0.F0 No of Ambient Air temperature updates for Tank 1.
TK2_FreeWaterLevel 2506 FLOAT na 0.F0 See Tank 1.
TK3_FreeWaterLevel 2512 FLOAT na 0.F0 See Tank 1.
TK4_FreeWaterLevel 2518 FLOAT na 0.F0 See Tank 1.
Issue 1
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK1_AmbAirPressureUpdateCounter 2704 WORD # 0.F0 No of Ambient Air temperature updates for Tank 1.
TK2_AmbAirPressure 2706 FLOAT na 0.F0 See Tank 1.
TK3_AmbAirPressure 2712 FLOAT na 0.F0 See Tank 1.
TK4_AmbAirPressure 2718 FLOAT na 0.F0 See Tank 1.
TK5_AmbAirPressure 2724 FLOAT na 0.F0 See Tank 1.
TK6_AmbAirPressure 2730 FLOAT na 0.F0 See Tank 1.
TK7_AmbAirPressure 2736 FLOAT na 0.F0 See Tank 1.
TK8_AmbAirPressure 2742 FLOAT na 0.F0 See Tank 1.
TK9_AmbAirPressure 2748 FLOAT na 0.F0 See Tank 1.
TK10_AmbAirPressure 2754 FLOAT na 0.F0 See Tank 1.
Issue 1
Bit2: DataFrozen
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK1_MiddlePressureUpdateCounter 2904 WORD # 0.F0 No of Middle Pressure updates for Tank 1.
TK2_MiddlePressure 2906 FLOAT na 0.F0 See Tank 1.
TK3_MiddlePressure 2912 FLOAT na 0.F0 See Tank 1.
TK4_MiddlePressure 2918 FLOAT na 0.F0 See Tank 1.
TK5_MiddlePressure 2924 FLOAT na 0.F0 See Tank 1.
Issue 1
56: TV TEMP 6
57: TV TEMP 7
58: TV TEMP 8
59: TV TEMP 9
60: TV TEMP 10
61: TV TEMP 11
62: TV TEMP 12
63: TV TEMP 13
64: TV TEMP 14
65: TV TEMP 15
66: TV TEMP 16
67: TV TEMP POS 1
68: TV TEMP POS 2
69: TV TEMP POS 3
70: TV TEMP POS 4
71: TV TEMP POS 5
72: TV TEMP POS 6
73: TV TEMP POS 7
74: TV TEMP POS 8
75: TV TEMP POS 9
Issue 1
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK1_UserDef2Type 3164 SENUM na 0.F0 User Defined 2 type for Tank 1.
TK1_UserDef2UpdateCounter 3165 WORD # 0.F0 No of User Defined 2 updates for Tank 1.
TK2_UserDef2Value 3166 FLOAT na 0.F0 See Tank 1.
TK3_UserDef2Value 3172 FLOAT na 0.F0 See Tank 1.
TK4_UserDef2Value 3178 FLOAT na 0.F0 See Tank 1.
TK5_UserDef2Value 3184 FLOAT na 0.F0 See Tank 1.
TK6_UserDef2Value 3190 FLOAT na 0.F0 See Tank 1.
TK7_UserDef2Value 3196 FLOAT na 0.F0 See Tank 1.
TK8_UserDef2Value 3202 FLOAT na 0.F0 See Tank 1.
Issue 1
TK1_UserDef4Value 3280 FLOAT na 0.F0 User Defined 4 value for Tank 1. For unit information see
standard unit area.
TK1_UserDef4Status 3282 BITFIELD na 0.F0 User Defined 4 status for Tank 1.
Bit0: DataError
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK1_UserDef4Type 3284 SENUM na 0.F0 User Defined 4 type for Tank 1.
Issue 1
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK1_UserDef5Type 3344 SENUM na 0.F0 User Defined 5 type for Tank 1.
TK1_UserDef5UpdateCounter 3345 WORD # 0.F0 No of User Defined 5 updates for Tank 1.
TK2_UserDef5Value 3346 FLOAT na 0.F0 See Tank 1.
TK3_UserDef5Value 3352 FLOAT na 0.F0 See Tank 1.
TK4_UserDef5Value 3358 FLOAT na 0.F0 See Tank 1.
TK5_UserDef5Value 3364 FLOAT na 0.F0 See Tank 1.
TK6_UserDef5Value 3370 FLOAT na 0.F0 See Tank 1.
Issue 1
Bit14: DeviceError
Bit15: InvalidVolume
Bit24: MaintAlert
Bit31: InvalidFlowRate
TK2_Volume 3406 FLOAT na 0.F0 See Tank 1.
TK3_Volume 3412 FLOAT na 0.F0 See Tank 1.
TK4_Volume 3418 FLOAT na 0.F0 See Tank 1.
TK5_Volume 3424 FLOAT na 0.F0 See Tank 1.
TK6_Volume 3430 FLOAT na 0.F0 See Tank 1.
TK7_Volume 3436 FLOAT na 0.F0 See Tank 1.
TK8_Volume 3442 FLOAT na 0.F0 See Tank 1.
TK9_Volume 3448 FLOAT na 0.F0 See Tank 1.
TK10_Volume 3454 FLOAT na 0.F0 See Tank 1.
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK2_ObsDensity 3504 FLOAT na 0.F0 See Tank 1.
TK3_ObsDensity 3508 FLOAT na 0.F0 See Tank 1.
TK4_ObsDensity 3512 FLOAT na 0.F0 See Tank 1.
TK5_ObsDensity 3516 FLOAT na 0.F0 See Tank 1.
Issue 1
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK2_RefDensity 3546 FLOAT na 0.F0 See Tank 1.
TK3_RefDensity 3552 FLOAT na 0.F0 See Tank 1.
TK4_RefDensity 3558 FLOAT na 0.F0 See Tank 1.
TK5_RefDensity 3564 FLOAT na 0.F0 See Tank 1.
TK6_RefDensity 3570 FLOAT na 0.F0 See Tank 1.
TK7_RefDensity 3576 FLOAT na 0.F0 See Tank 1.
TK8_RefDensity 3582 FLOAT na 0.F0 See Tank 1.
TK9_RefDensity 3588 FLOAT na 0.F0 See Tank 1.
TK10_RefDensity 3594 FLOAT na 0.F0 See Tank 1.
TK9_LevelDeviceStatus 3632 BITFIELD na 0.F0 Level Device status for Tank 9. See Tank 1 for bit definition.
TK9_TempDeviceStatus 3634 BITFIELD na 0.F0 Temperature Device status for Tank 9. See Tank 1 for bit definition.
TK10_LevelDeviceStatus 3636 BITFIELD na 0.F0 Level Device status for Tank 10. See Tank 1 for bit definition.
TK10_TempDeviceStatus 3638 BITFIELD na 0.F0 Temperature Device status for Tank 10. See Tank 1 for bit definition.
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
TK2_LevelDeltaValue 3804 FLOAT na 0.F0 See Tank 1.
TK3_LevelDeltaValue 3808 FLOAT na 0.F0 See Tank 1.
TK4_LevelDeltaValue 3812 FLOAT na 0.F0 See Tank 1.
TK5_LevelDeltaValue 3816 FLOAT na 0.F0 See Tank 1.
TK6_LevelDeltaValue 3820 FLOAT na 0.F0 See Tank 1.
TK7_LevelDeltaValue 3824 FLOAT na 0.F0 See Tank 1.
TK8_LevelDeltaValue 3828 FLOAT na 0.F0 See Tank 1.
TK9_LevelDeltaValue 3832 FLOAT na 0.F0 See Tank 1.
TK10_LevelDeltaValue 3836 FLOAT na 0.F0 See Tank 1.
44: Feet
45: Meter
49: MilliMeter
LevelRateUnit 3901 SENUM na 0.F0 Level Rate unit used in the standard questions.
20: Feet per second
21: Meter per second
120: Meter per hour
247: Feet per hour
TempElementUnit 3902 BITFIELD na 0.F0 Temperature Element unit used in the standard questions. If bit not is set for
the unit selection DegC is used. If bit not is set for the accuracy selection 1/10
will be used.
Bit0: Tank1 Fahrenheit
Bit1: Tank1 HighRes
Bit3: Tank2 Fahrenheit
Bit4: Tank2 HighRes
Bit6: Tank3 Fahrenheit
Bit7: Tank3 HighRes
Bit9: Tank4 Fahrenheit
Bit10: Tank4 HighRes
Bit12: Tank5 Fahrenheit
Bit13: Tank5 HighRes
Issue 1
14: Atm
263: Bar A
519: Bar G
262: PSI A
518: PSI G
DensityUnit 3907 SENUM na 0.F0 Density unit used in the standard questions.
92: KgPerCubicMeter
93: lbPerUsGallon
104: Deg API
VolumeUnit 3908 SENUM na 0.F0 Volume unit used in the standard questions.
40: UsGallon
41: Liter
43: CubicMeter
46: Barrels
112: CubicFeet
FlowRateUnit 3909 SENUM na 0.F0 Flow Rate unit used in the standard questions.
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
Issue 1
21: MeterPerSecond
120: MeterPerHour
247: FeetPerHour
6: Psi
7: Bar
11: Pa
12: kPa
14: Atm
263: Bar A
519: Bar G
262: PSI A
518: PSI G
92: KgPerCubicMeter
93: lbPerUsGallon
104: DegAPI
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
36: mV
Issue 1
65535: Unknown
TK1_UserDef2Unit 3921 SENUM na 0.F0 See User Defined 1 unit.
TK1_UserDef3Unit 3922 SENUM na 0.F0 See User Defined 1 unit.
TK1_UserDef4Unit 3923 SENUM na 0.F0 See User Defined 1 unit.
TK1_UserDef5Unit 3924 SENUM na 0.F0 See User Defined 1 unit.
TK2_UserDef1Unit 3925 SENUM na 0.F0 See Tank 1.
TK3_UserDef1Unit 3930 SENUM na 0.F0 See Tank 1.
TK4_UserDef1Unit 3935 SENUM na 0.F0 See Tank 1.
TK5_UserDef1Unit 3940 SENUM na 0.F0 See Tank 1.
TK6_UserDef1Unit 3945 SENUM na 0.F0 See Tank 1.
TK7_UserDef1Unit 3950 SENUM na 0.F0 See Tank 1.
TK8_UserDef1Unit 3955 SENUM na 0.F0 See Tank 1.
TK9_UserDef1Unit 3960 SENUM na 0.F0 See Tank 1.
TK10_UserDef1Unit 3965 SENUM na 0.F0 See Tank 1.
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
UserCfg1_Type 4004 SENUM na 0.F0 TMV Type of User Configurable value.
UserCfg1_Unit 4005 SENUM na 0.F0 Unit of User Configurable value.
32: Deg C
33: Deg F
Issue 1
35: Kelvin
44: Feet
45: Meter
49: MilliMeter
20: Feet per second
21: Meters per second
120: Meters per hour
247: Feet per hour
6: Psi
7: Bar
11: Pa
12: KPa
14: Atm
263: Bar A
519: Bar G
262: PSI A
518: PSI G
40: US Gallons
41: Liter
43: Cubic Meters
Issue 1
46: Barrels
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
92: kg per m3
93: lbPerUsGallon
104: degAPI
36: mV
UserCfg2_Value 4006 FLOAT na 0.F0 See User Configurable value 1.
UserCfg3_Value 4012 FLOAT na 0.F0 See User Configurable value 1.
UserCfg4_Value 4018 FLOAT na 0.F0 See User Configurable value 1.
UserCfg5_Value 4024 FLOAT na 0.F0 See User Configurable value 1.
UserCfg6_Value 4030 FLOAT na 0.F0 See User Configurable value 1.
UserCfg7_Value 4036 FLOAT na 0.F0 See User Configurable value 1.
UserCfg8_Value 4042 FLOAT na 0.F0 See User Configurable value 1.
UserCfg9_Value 4048 FLOAT na 0.F0 See User Configurable value 1.
UserCfg10_Value 4054 FLOAT na 0.F0 See User Configurable value 1.
UserCfg11_Value 4060 FLOAT na 0.F0 See User Configurable value 1.
UserCfg12_Value 4066 FLOAT na 0.F0 See User Configurable value 1.
Issue 1
Bit4: Sensor 5
Bit5: Sensor 6
Bit6: Sensor 7
Bit7: Sensor 8
Bit8: Sensor 9
Bit9: Sensor 10
Bit10: Sensor 11
Bit11: Sensor 12
Bit12: Sensor 13
Bit13: Sensor 14
Bit14: Sensor 15
Bit15: Sensor 16
Tk1_AvgInVapStatus 4214 BITFIELD na 0.C7 Sensor in Vapor status. See Sensor in Liquid status for bit definitions.
Tk1_AvgBlockedStatus 4216 BITFIELD na 0.C7 Sensor block status. See Sensor in Liquid status for bit definitions.
Tk1_LevelValue 4218 FLOAT m 0.E2 Used Level value in the average temperature calculation.
Tk1_LevelStatus 4220 BITFIELD na 0.E2 Current Level status for the Level value.
Bit0: DataError
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: SaturatedLow
Issue 1
Bit4: SaturatedHigh
Bit7: UnsupportedUnit
Bit14: DeviceError
Bit15: InvalidValue
Tk1_LoLevelLimit 4222 FLOAT m 0.E2 Used low level limit.
Tk1_HiLevelLimit 4224 FLOAT m 0.E2 Used high level limit.
Tk2_AvgLiqTemp 4230 FLOAT C 0.C7 See Tank 1.
Tk3_AvgLiqTemp 4260 FLOAT C 0.C7 See Tank 1.
Tk3_AvgLiqStatus 4262 BITFIELD na 0.C7 Status of the average Liquid temperature.
Tk3_AvgVapTemp 4264 FLOAT C 0.C7 Average measured Vapor temperature.
Tk3_AvgVapStatus 4266 BITFIELD na 0.C7 Status of the average Vapor temperature.
Tk3_AvgTankTemp 4268 FLOAT C 0.C7 Average measured Tank temperature.
Tk3_AvgTankStatus 4270 BITFIELD na 0.C7 Status of the average Tank temperature.
Tk3_AvgInLiqStatus 4272 BITFIELD na 0.C7 Sensor in Liquid status.
Tk3_AvgInVapStatus 4274 BITFIELD na 0.C7 Sensor in Vapor status.
Tk3_AvgBlockedStatus 4276 BITFIELD na 0.C7 Sensor block status.
Tk3_LevelValue 4278 FLOAT m 0.E2 Used Level value in the average temperature calculation.
Tk3_LevelStatus 4280 BITFIELD na 0.E2 Current Level status for the Level value.
Tk3_LoLevelLimit 4282 FLOAT m 0.E2 Used low level limit.
Tk3_HiLevelLimit 4284 FLOAT m 0.E2 Used high level limit.
Issue 1
Bit5: ManualPressureTypeUsed
Bit6: AbsolutePressureUsed
Bit7: P3 ConvertedToRelativePressure
Bit8: HTG DensityCalcActive
Bit9: Simulation
Bit15: Level Is Under MinLevel
ObservedDensity_1 4506 FLOAT kg/m3 0.A0 Observed density.
P2_Value_1 4510 FLOAT bar 1.C6 Used P2 pressure value in HTG calculation.
P1_Value_1 4512 FLOAT bar 0.A0 Used P1 pressure value.
P3_Value_1 4514 FLOAT bar 0.A0 Used P3 pressure value.
Level_1 4516 FLOAT m 0.A0 Used liquid level value.
DensityErrorStatus_2 4518 BITFIELD na 0.A0 If this register is nonzero, then the calculated density is not valid (old
value is frozen). See above.
DensityWarningStatus_2 4522 BITFIELD na 0.A0 This register is only for information about the status of the Hybrid
module. See above.
ObservedDensity_2 4524 FLOAT kg/m3 0.A0 Observed density.
P2_Value_2 4528 FLOAT bar 1.C6 Used P2 pressure value in HTG Calculation.
P1_Value_2 4530 FLOAT bar 0.A0 Used P1 pressure value.
P3_Value_2 4532 FLOAT bar 0.A0 Used P3 pressure value.
Level_2 4534 FLOAT m 0.A0 Used liquid level value.
Issue 1
DensityErrorStatus_3 4536 BITFIELD na 0.A0 If this register is nonzero, then the calculated density is not valid (old
value is frozen). See above.
DensityWarningStatus_3 4540 BITFIELD na 0.A0 This register is only for information about the status of the Hybrid
module. See above.
ObservedDensity_3 4542 FLOAT kg/m3 0.A0 Observed density.
P2_Value_3 4546 FLOAT bar 1.C6 Used P2 pressure value in HTG Calculation.
P1_Value_3 4548 FLOAT bar 0.A0 Used P1 pressure value.
P3_Value_3 4550 FLOAT bar 0.A0 Used P3 pressure value.
Level_3 4552 FLOAT m 0.A0 Used liquid level value.
Bit7: VirtRel 8
Bit8: VirtRel 9
Bit9: VirtRel 10
Relay_K2_Connection 4644 BITFIELD na 1.A6 Bitfield to indicate the Virtual Relays connection to the physical
Relay K2.
Bit0: VirtRel 1
Bit1: VirtRel 2
Bit2: VirtRel 3
Bit3: VirtRel 4
Bit4: VirtRel 5
Bit5: VirtRel 6
Bit6: VirtRel 7
Bit7: VirtRel 8
Bit8: VirtRel 9
Bit9: VirtRel 10
AlarmRelay_Status 4650 BITFIELD na 1.A8 Status for the AR option (SIL relay).
Bit0: Alarm
Bit1: HW Error
Bit2: SIL3
Bit3: NotConnected
Issue 1
Bit8: Alarm R1
Bit9: Alarm R2
Bit4: NoLowPosFound
Bit5: NoHighPosFound
Bit6: LevelIsOutOfRange
Bit7: StrapTableNotAllowed
Bit8: VCBIsNotChecked
Bit12: InvalidWaterLevel
Bit13: InvalidLevel
Bit15: InvalidFreeWaterVolume
Bit16: InvalidVolume
UsedTankGeometry 4708 ENUM na 0.C7 Currently selected tank geometry for the volume calculation, see HREG
for configuration.
0: GeometryNotDefined
1: StrapTable
2: Sphere
3: CylinderHorizontel
4: CylinderVertical
UsedInterpolateFunction 4710 ENUM na 0.C7 Currently selected interpolate function.
0: Linear
1: Quadratic
NetVolStatus 4720 BITFIELD na 1.B6 Status indication for the following Net Volume values.
Issue 1
Bit0: FunctionNotEnabled
Bit1: CtrlBlockNotValid
Bit12: InvalidWaterVolume
Bit13: InvalidAvgTemp
Bit14: Invalid TOV
Bit16: InvalidNetStandardVolume
FWV 4722 FLOAT m3 1.B6 Free Water Volume. Calculated with the same geometry asthe VTotal
Observed Volume (TOV)
GOV 4724 FLOAT m3 1.B6 Gross Observed Volume. Calculated as TOV - FWV. Note there is no
support for tank shell temperature correction factor or compensation for
floating roof.
GSV 4726 FLOAT m3 1.B6 Gross Standard Volume. Calculated as GOV * VCF.
VCF 4728 FLOAT # 1.B6 The Volume Correction Factor, calculated accoding to the Holding
Register VCF_Table (API 2540).
NSV 4730 FLOAT m3 1.B6 Net Standard Volume. Calculated as GSV * (1 - SW/100). SW is the
volume of dissolved sediment and water in percent. There is no support
for liguid equivalent of vapour (for LPG/LNG).
Bit0: DataError
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
Arithm1_ValueB 4810 FLOAT na 0.E0 Used B value in the operation.
Arithm1_StatusB 4812 BITFIELD na 0.E0 Used B status in the operation.
Bit0: DataError
Issue 1
Bit1: DeviceOutOfService
Bit2: DataFrozen
Bit3: LowSaturated
Bit4: HighSaturated
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
Arithm2_Value 4814 FLOAT na 0.E0 Arithmetic 2, see arithmetic 1.
Arithm3_Value 4828 FLOAT na 0.E0 Arithmetic 3, see arithmetic 1.
Arithm4_Value 4842 FLOAT na 0.E0 Arithmetic 4, see arithmetic 1.
Arithm5_Value 4856 FLOAT na 0.E0 Arithmetic 5, see arithmetic 1.
Issue 1
Bit1: AoutIsActive
Bit2: LowCurrent
Bit3: HighCurrent
Bit4: AdSaturated
Bit12: DisabledByConfiguration
Bit14: ColdStart
Bit15: InvalidValue
Current 5102 FLOAT mA 1.B0 Measured Analog Input current.
PercentOfRange 5104 FLOAT % 1.B0 Measured Analog Input current in percent of range. 0% for 4.0 mA and
100% for 20 mA.
Value 5106 FLOAT na 1.B0 Measured Analog Input value converted according to HREG LowerRange
and UpperRange.
RawUpdateCounter 5108 DWORD # 1.B0 AD-Converter update counter.
UpdateCounter 5110 DWORD # 1.B0 Update counter for the converted value.
Bit2: Saturated
Bit3: InMultidrop
Bit4: InFixedCurrMode
Bit5: OutOfLimits
Bit8: InCalibrationMode
Bit9: InvalidCalibration
Bit10: HwError
Bit11: OpenCurrLoop
Bit12: WirelessHART
Bit14: InvalidTmv
Bit15: InvalidLimits
Current 5202 FLOAT mA 1.B0 Analog Output current, including alarm conditions etc.
PercentOfRange 5204 FLOAT % 1.B0 Source value in percent of the Analog Output range.
Value 5206 FLOAT na 1.B0 Source value.
Unit 5208 ENUM na 1.B0 Source unit.
0: Not applicable
32: degC
33: degF
35: degK
44: Feet
Issue 1
45: Meter
49: Millimeter
40: UsGallon
41: Liter
43: CubicMeter
46: Barrels
61: Kilogram
62: Metric ton
63: Pound
64: Short ton
65: Long ton
20: FeetPerSecond
21: MeterPerSecond
120: MeterPerHour
247: FeetPerHour
6: Psi
7: Bar
11: Pa
12: kPa
14: Atm
Issue 1
263: Bar A
519: Bar G
262: PSI A
518: PSI G
92: KgPerCubicMeter
93: lbPerUsGallon
104: DegAPI
17: LiterPerMinute
19: CubicMeterPerHour
134: BarrelPerHour
136: UsGallonPerHour
36: mV
65535: Unknown
TankNo 5210 DWORD # 1.B0 Source TankNo.
TmvType 5212 ENUM na 1.B0 Source TmvType.
0: TMV LEVEL
1: TMV ULLAGE
2: TMV LEVEL RATE
3: TMV SIGNAL STRENGTH
4: TMV FREE WATER LEVEL
Issue 1
CurrentDiff 5220 FLOAT mA 1.B0 Difference in requested current and actual measured current. Note that this
difference not is updated for every DA-Conversion.
35: Kelvin
36: Millivolt
37: Ohm
38: Hertz
39: Milliampere
40: Gallon
41: Liter
42: Imperial gallon
43: Cubic meter
44: Feet
45: Meter
46: Barrel
47: Inche
48: Centimeter
49: Millimeter
58: Volt
59: PH
60: Gram
61: Kilogram
62: Metric ton
Issue 1
63: Pound
64: Short ton
65: Long ton
68: Newton
69: Newton meter
70: Gram per second
71: Gram per minute
72: Gram per hour
73: Kilogram per second
74: Kilogram per minute
75: Kilogram per hour
76: Kilogram per day
77: Metric ton per minute
78: Metric ton per hour
79: Metric ton per day
80: Pound per second
81: Pound per minute
82: Pound per hour
83: Pound per day
84: Short ton per minute
Issue 1
36: Millivolt
37: Ohm
38: Hertz
39: Milliampere
40: Gallon
41: Liter
42: Imperial gallon
43: Cubic meter
44: Feet
45: Meter
46: Barrel
47: Inche
48: Centimeter
49: Millimeter
58: Volt
59: PH
60: Gram
61: Kilogram
62: Metric ton
63: Pound
Issue 1
Bit0: Checksum
Bit1: Appl Version
Bit2: Appl Checksum
HREG_Error 6104 BITFIELD na 0.A0 Detailed HREG error information.
Bit0: Checksum
Bit1: Limit
Bit2: Version
Bit3: Read
Bit4: Write
SW_Error 6106 BITFIELD na 0.A0 Detailed SW error information.
Bit0: Undefined SW Error
Bit1: Task Not Running
Bit2: Out of stack space
Bit3: Unused RAM access
Bit4: Divide by zero
Bit5: Reset Counter Overflow
Bit15: Simulated SW Error
Other_Mem_Error 6108 BITFIELD na 0.A0 Detailed otehr memory error information.
Bit0: CheckSum
Bit1: Stack
Issue 1
0: Level
1: Ullage
2: Level Rate
3: Signal Strength
4: Volume
5: Gain
6: Signal Quality
7: Observed Density
8: Tank Height
9: Water Level
10: Housing Temp
11: Liquid Temp
12: Vapor Temp
13: Tank Temp
14: Flow Rate
51: Temp 1
52: Temp 2
53: Temp 3
54: Temp 4
55: Temp 5
Issue 1
56: Temp 6
57: Temp 7
58: Temp 8
59: Temp 9
60: Temp 10
61: Temp 11
62: Temp 12
63: Temp 13
64: Temp 14
65: Temp 15
66: Temp 16
67: Temp pos 1
68: Temp pos 2
69: Temp pos 3
70: Temp pos 4
71: Temp pos 5
72: Temp pos 6
73: Temp pos 7
74: Temp pos 8
75: Temp pos 9
Issue 1
0: Level
1: Ullage
2: Level Rate
3: Signal Strength
4: Volume
5: Gain
6: Signal Quality
7: Observed Density
8: Tank Height
9: Water Level
10: Housing Temp
11: Liquid Temp
12: Vapor Temp
13: Tank Temp
14: Flow Rate
51: Temp 1
52: Temp 2
53: Temp 3
54: Temp 4
55: Temp 5
Issue 1
56: Temp 6
57: Temp 7
58: Temp 8
59: Temp 9
60: Temp 10
61: Temp 11
62: Temp 12
63: Temp 13
64: Temp 14
65: Temp 15
66: Temp 16
67: Temp pos 1
68: Temp pos 2
69: Temp pos 3
70: Temp pos 4
71: Temp pos 5
72: Temp pos 6
73: Temp pos 7
74: Temp pos 8
75: Temp pos 9
Issue 1
FileNo_1 6320 DWORD # 0.A0 Identification number for the module where the exception was detected.
LineNo_1 6322 DWORD # 0.A0 Line number in module where exception where detected.
ExcCode_1 6324 DWORD na 0.A0 Exception Code describing the Exception Type.
Info_1 6326 DWORD na 0.A0 Additional exception information.
TimeLo_1 6328 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
TimeHi_1 6330 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
FileNo_2 6340 DWORD # 0.A0 Identification number for the module where the exception was detected.
LineNo_2 6342 DWORD # 0.A0 Line number in module where exception where detected.
ExcCode_2 6344 DWORD na 0.A0 Exception Code describing the Exception Type.
Info_2 6346 DWORD na 0.A0 Additional exception information.
TimeLo_2 6348 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
TimeHi_2 6350 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
FileNo_3 6360 DWORD # 0.A0 Identification number for the module where the exception was detected.
LineNo_3 6362 DWORD # 0.A0 Line number in module where exception where detected.
ExcCode_3 6364 DWORD na 0.A0 Exception Code describing the Exception Type.
Info_3 6366 DWORD na 0.A0 Additional exception information.
TimeLo_3 6368 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
TimeHi_3 6370 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
FileNo_4 6380 DWORD # 0.A0 Identification number for the module where the exception was detected.
LineNo_4 6382 DWORD # 0.A0 Line number in module where exception where detected.
ExcCode_4 6384 DWORD na 0.A0 Exception Code describing the Exception Type.
Issue 1
FileNo_8 6456 DWORD # 0.A0 Identification number for the module where the exception was detected.
LineNo_8 6458 DWORD # 0.A0 Line number in module where exception where detected.
ExcCode_8 6460 DWORD na 0.A0 Exception Code describing the Exception Type.
Info_8 6462 DWORD na 0.A0 Additional exception information.
TimeLo_8 6464 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
TimeHi_8 6466 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
FileNo_9 6476 DWORD # 0.A0 Identification number for the module where the exception was detected.
LineNo_9 6478 DWORD # 0.A0 Line number in module where exception where detected.
ExcCode_9 6480 DWORD na 0.A0 Exception Code describing the Exception Type.
Info_9 6482 DWORD na 0.A0 Additional exception information.
TimeLo_9 6484 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
TimeHi_9 6486 DWORD ms 0.A0 Time in ms when exception occurred, relative last reset/start-up of system.
2: VRelay 2
3: VRelay 3
4: VRelay 4
5: VRelay 5
6: VRelay 6
7: VRelay 7
8: VRelay 8
9: VRelay 9
10: VRelay 10
Status_0 6606 BITFIELD na 1.G0 Virtual Ralay Status causing the event.
Bit0: NotConnected
Bit1: RelayManSetInResetState
Bit2: RelayManSetInActiveState
Bit3: RelayManSetInToggleState
Bit4: LimitsAlarm
Bit5: InvalidTmvValueAlarm
Bit8: InToggleState
Bit9: DelayActivated
Bit12: DisabledByConfiguration
Bit13: InvalidLimits
Issue 1
Bit14: Deenergized
TMV_Value_0 6608 FLOAT na 1.G0 TMV Value when event occured.
TimeLo_0 6610 DWORD ms 1.G0 Time from startup in ms when event occured (Low word).
TimeHi_0 6612 DWORD ms 1.G0 Time from startup in ms when event occured (High word)
VirtRelayNum_2 6632 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_3 6646 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_4 6660 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_5 6674 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_6 6688 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_7 6702 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_8 6716 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_9 6730 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_10 6744 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
Issue 1
VirtRelayNum_11 6758 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_12 6772 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_13 6786 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_14 6800 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_15 6814 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_16 6828 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_17 6842 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_18 6856 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
VirtRelayNum_19 6870 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more
information.
AoutId_1 6918 ENUM # 1.G0 Start of next block with event data. See event 0 aboce for more information.
AoutId_2 6932 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
AoutId_3 6946 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
AoutId_4 6960 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
AoutId_5 6974 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
AoutId_6 6988 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
AoutId_7 7002 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
AoutId_8 7016 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
AoutId_9 7030 ENUM # 1.G0 Start of the next block with event data. See event 0 above for more information.
6: FF Device 6
7: FF Device 7
8: FF Device 8
9: FF Device 9
10: FF Device 10
11: FF Device 11
12: FF Device 12
13: FF Device 13
14: FF Device 14
15: FF Device 15
16: FF Device 16
21: HART Device 1
22: HART Device 2
23: HART Device 3
24: HART Device 4
25: HART Device 5
31: AIN Device 1
41: TankHub Device
50: Emul Device 1
51: Emul Device 2
Issue 1
Note The DeviceTag area was updated in R2410 version 1.B1. Bofore 1.B1 and after 0.C1 the area included 16 devices and each device had 32 registers. From
1.B1 the area include 24 devices and each device has 16 registers.
Row18_DeviceTag_1 9272 WORD na 1.B1 Start of the device tag string for device 18. See Device 1.
Row19_DeviceTag_1 9288 WORD na 1.B1 Start of the device tag string for device 19. See Device 1.
Row20_DeviceTag_1 9304 WORD na 1.B1 Start of the device tag string for device 20. See Device 1.
Row21_DeviceTag_1 9320 WORD na 1.B1 Start of the device tag string for device 21. See Device 1.
Row22_DeviceTag_1 9336 WORD na 1.B1 Start of the device tag string for device 22. See Device 1.
Row23_DeviceTag_1 9352 WORD na 1.B1 Start of the device tag string for device 23. See Device 1.
Row24_DeviceTag_1 9368 WORD na 1.B1 Start of the device tag string for device 24. See Device 1.
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Bit24: MaintAlert
Ullage_Value 30004 FLOAT m 0.A0 Ullage value.
Ullage_Status 30006 BITFIELD na 0.A0 Ullage status, see above.
LevelRate_Value 30008 FLOAT m/s 0.A0 Level rate value.
LevelRate_Status 30010 BITFIELD na 0.A0 Level rate status, see above.
SignalStrength_Value 30012 FLOAT mV 0.A0 Signal strength value.
SignalStrength_Status 30014 BITFIELD na 0.A0 Signal strength status, see above.
FreeWaterLevel_Value 30016 FLOAT m 0.A0 Free water level value.
FreeWaterLevel_Status 30018 BITFIELD na 0.A0 Free water level status, see above.
VaporPressure_Value 30020 FLOAT bar 0.A0 Vapor pressure value.
VaporPressure_Status 30022 BITFIELD na 0.A0 Vapor pressure status, see above.
MiddlePressure_Value 30024 FLOAT bar 0.F0 Middle pressure value.
Issue 1
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: InLiquid
Bit17: InVapor
Bit18: Blocked
Bit19: NotConnected
Bit20: ShortCircuit
Bit21: ShortCircuitToGnd
Bit22: OpenCircuit
Bit23: ReferenceResistor
Bit24: MaintAlert
Temp2_Value 30056 FLOAT C 0.A0 Temperature sensor 2 value.
Temp2_Status 30058 BITFIELD na 0.A0 Temperature sensor 2 status, see above.
Temp3_Value 30060 FLOAT C 0.A0 Temperature sensor 3 value.
Temp3_Status 30062 BITFIELD na 0.A0 Temperature sensor 3 status, see above.
Issue 1
Bit26: TempValueWrongUnit
Bit27: TempDeviceNotProtected
Bit28: TempDeviceValueNotApproved
TK2_MiStatus 33002 BITFIELD na 0.F1 MI status information for Tank 2. For bit definitions see Tank 1.
TK3_MiStatus 33004 BITFIELD na 0.F1 MI status information for Tank 3. For bit definitions see Tank 1.
TK4_MiStatus 33006 BITFIELD na 0.F1 MI status information for Tank 4. For bit definitions see Tank 1.
TK5_MiStatus 33008 BITFIELD na 0.F1 MI status information for Tank 5. For bit definitions see Tank 1.
TK6_MiStatus 33010 BITFIELD na 0.F1 MI status information for Tank 6. For bit definitions see Tank 1.
TK7_MiStatus 33012 BITFIELD na 0.F1 MI status information for Tank 7. For bit definitions see Tank 1.
TK8_MiStatus 33014 BITFIELD na 0.F1 MI status information for Tank 8. For bit definitions see Tank 1.
TK9_MiStatus 33016 BITFIELD na 0.F1 MI status information for Tank 9. For bit definitions see Tank 1.
TK10_MiStatus 33018 BITFIELD na 0.F1 MI status information for Tank 10. For bit definitions see Tank 1.
8274: TRL2
8276: Tokyo Keiso TIC
8277: Sakura
8278: Varec Mark Space
8279: HART Wireless
8280: CustomerSpecific
SecondaryBus 39907 SENUM na 1.A6 8224: Undefined
8240: NONE
8245: RS485 Isolated
8246: HARTM AinAct
8247: HARTM AinPass
8248: HARTM AinAct IS
8249: HARTM AinPass IS
8257: HARTS AoutAct
8258: HARTS AoutPass
8259: HARTS AoutAct IS
8260: HARTS AoutPass IS
8261: Enraf GPU
8262: Ready for Upgrade
8263: GPE DCL
Issue 1
8257: K2
8262: Ready for Upgrade
8280: CustomerSpecific
LCD 39910 SENUM na 1.A6 8224: Undefined
8240: NO LCD
8241: LCD
8280: CustomerSpecific
PowerSupply 39911 SENUM na 1.A6 8224: Undefined
8272: Extended Input
8280: CustomerSpecific
Firmware 39912 SENUM na 1.A6 8224: Undefined
8275: Standard
8280: CustomerSpecific
ExCert 39913 SENUM na 1.A6 8224: Undefined
17483: None Demo Unit
17713: ATEX Flameproof
17714: Brazil Flameproof
17715: China NEPSI Flameproof
17716: Japan TIIS Flameproof
Issue 1
17717: FM US ExplosionProof
17718: FM Canada ExplosionProof
17719: IECEx FlameProof
17744: South Korea FlameProof
19249: ATEX FM US Flameproof
19250: ATEX FM Canada Flameproof
19251: ATEX IECEx Flameproof
19252: FM US FM Canada Flameproof
19253: FM US IECEx Flameproof
19254: FM Canada IECEx Flameproof
20033: NO ExCert
22616: CustomerSpecific
CT_Cert 39914 SENUM na 1.A6 8224: Undefined
8240: NONE
8257: CMI
8258: NMI Australia
8259: PTB
8261: TJA
8262: None ReadyForUpgrade
8263: GUM
Issue 1
8265: Ministero
8267: GOST
8268: LNE
8269: BMS
8270: NMI
8273: IPQ
8274: OIML
8275: GOSSandard
8279: METAS
8280: CustomerSpecific
8281: Justervesenet
Housing 39915 SENUM na 1.A6 8224: Undefined
8257: StandardAluminum
8280: CustomerSpecific
8275: SST
Conduit 39916 SENUM na 1.A6 8224: Undefined
8241: NPT
8242: M20 M25
8260: Demo Kit
8261: Eurofast
Issue 1
Bit1: TankConfig
Bit2: TankName
Bit3: Tankbus
Bit4: PrimaryBus
Bit5: SecondaryBus
Bit6: Modbus
Bit7: ModbusLevel
Bit8: Emul
Bit9: EmulProt
Bit10: Relay
Bit11: Display
Bit12: TmvAlarm
Bit13: AvgTemp
Bit14: Hybrid
Bit15: TvManualValues
Bit16: TmvMapping
Bit17: TmvSimulation
Bit18: InternalScratch
Bit19: Vol
Bit20: TmvArithmetic
Issue 1
Bit21: GenDev
Bit22: SysCtrl
Bit23: TmvToDevMap
Bit24: FactoryModelCode
Bit25: HartCtrl
Bit26: AnalogCtrl
HREG_SegLimitStatus 40006 BITFIELD na 0.A0 Segment limit status. See HREG_SegChSumStatus for bit definition.
HREG_NoDefaultWrites 40008 DWORD # 0.A0 Counter for the number of default writes performed.
HREG_SegNonDefault 40010 BITFIELD na 0.A0 Segments that are non default. See HREG_SegChSumStatus for bit
definition.
E2PROM_BytesWritten 40012 DWORD # 1.B1 Number of bytes written to non volatile memory since last restart.
E2PROM_NumWrites 40014 DWORD # 1.B1 Number performed writes to non volatile memory since last restart.
Ees_RejData7 40687 WORD # 1.F0 Received Emulation byte 7 when message was rejected.
Ees_RejData8 40688 WORD # 1.F0 Received Emulation byte 8 when message was rejected.
Ees_RejData9 40689 WORD # 1.F0 Received Emulation byte 9 when message was rejected.
Ees_RejData10 40690 WORD # 1.F0 Received Emulation byte 10 when message was rejected.
Ees_RejData11 40691 WORD # 1.F0 Received Emulation byte 11 when message was rejected.
Ees_RejData12 40692 WORD # 1.F0 Received Emulation byte 12 when message was rejected.
Ees_RejData13 40693 WORD # 1.F0 Received Emulation byte 13 when message was rejected.
Ees_RejData14 40694 WORD # 1.F0 Received Emulation byte 14 when message was rejected.
Ees_RejData15 40695 WORD # 1.F0 Received Emulation byte 15 when message was rejected.
Ees_RejData16 40696 WORD # 1.F0 Received Emulation byte 16 when message was rejected.
Ees_RejData17 40697 WORD # 1.F0 Received Emulation byte 17 when message was rejected.
Ees_RejData18 40698 WORD # 1.F0 Received Emulation byte 18 when message was rejected.
Ees_RejDataNumber 40699 WORD # 1.F0 Number of rejected Emulation messages.
NoCmdRespFromUsBusy 40706 DWORD # 1.B1 Number of Busy responses sent from the TankHub.
NoCmdForOther 40708 DWORD # 1.B1 Number of HART commands sent to address NOT handled by the
TankHub.
NoCmdRespFromOther 40710 DWORD # 1.B1 Number of HART responses sent by other HART slave.
NoCmdCrcError 40712 DWORD # 1.B1 HART command checksum error counter.
NoCmdFramingError 40714 DWORD # 1.B1 HART command framing error counter.
NoCmdGapTimeout 40716 DWORD # 1.B1 HART command gap timeout counter.
R2410_MsgCount 40720 DWORD # 1.B0 2410 message count
R2410_Command 40722 WORD na 1.B0 2410 last command number
R2410_Delimiter 40723 WORD na 1.B0 2410 response delimiter
R2410_FieldDevStatus 40724 SBT na 1.B0 2410 response Field Device Status
Bit0: PV AOUT OF LIMITS
Bit1: NON PV AOUT OF LIMITS
Bit2: PV AOUT SATUR
Bit3: PV AOUT FIXED
Bit4: MORE STATUS AVAILABLE
Bit5: COLD START
Bit6: CONFIG CHANGED
Bit7: DEVICE MALFUNC
R2410_RespCode 40725 WORD na 1.B0 2410 Response Code
Slave1_MsgCount 40730 DWORD # 1.B0 Slave 1 message count
Issue 1
SA2_NoOfSentQueries 40854 WORD # 1.B1 Number of HART Queries sent to shoart address 2.
SA2_NoOfOkResponses 40855 WORD # 1.B1 Number of HART Responses from shoart address 2.
SA3_NoOfSentQueries 40856 WORD # 1.B1 Number of HART Queries sent to shoart address 3.
SA3_NoOfOkResponses 40857 WORD # 1.B1 Number of HART Responses from shoart address 3.
SA4_NoOfSentQueries 40858 WORD # 1.B1 Number of HART Queries sent to shoart address 4.
SA4_NoOfOkResponses 40859 WORD # 1.B1 Number of HART Responses from shoart address 4.
SA5_NoOfSentQueries 40860 WORD # 1.B1 Number of HART Queries sent to shoart address 5.
SA5_NoOfOkResponses 40861 WORD # 1.B1 Number of HART Responses from shoart address 5.
EEM4_NoOfOkResponses 40907 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 4, see Enraf Master 1.
EEM5_NoOfSentQueries 40908 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 5, see Enraf Master 1.
EEM5_NoOfOkResponses 40909 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 5, see Enraf Master 1.
EEM6_NoOfSentQueries 40910 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 6, see Enraf Master 1.
EEM6_NoOfOkResponses 40911 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 6, see Enraf Master 1.
EEM7_NoOfSentQueries 40912 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 7, see Enraf Master 1.
EEM7_NoOfOkResponses 40913 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 7, see Enraf Master 1.
EEM8_NoOfSentQueries 40914 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 8, see Enraf Master 1.
EEM8_NoOfOkResponses 40915 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 8, see Enraf Master 1.
EEM9_NoOfSentQueries 40916 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 9, see Enraf Master 1.
EEM9_NoOfOkResponses 40917 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 9, see Enraf Master 1.
EEM10_NoOfSentQueries 40918 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 10, see Enraf Master 1.
EEM10_NoOfOkResponses 40919 WORD # 1.B1 Enraf, L&J, Varec and Whessoe Master 10, see Enraf Master 1.
ComLog_Address 40920 WORD na 1.B1 The ComLog includes data from the last response. LSB has been
received first, i.e. tens address.
ComLog_TOR_TOI 40921 WORD na 1.B1 TOI in LSB, TOR in MSB. For the Whessoe Master this register
contains the Task Number.For L&J it contains the Data Request
Number.
ComLog_Data_1_0 40922 WORD na 1.B1 Data in response, LSB first.
ComLog_Data_3_2 40923 WORD na 1.B1 Data in response, LSB first.
ComLog_Data_5_4 40924 WORD na 1.B1 Data in response, LSB first.
Issue 1
0: NUL
32: Space
45: MinusSign
64: ATSign
65: A
66: B
67: C
70: F
72: H
76: L
84: T
87: W
Device1_AlarmStatus 40942 SENUM na 1.B3 The raw value of the Enraf or Whessoe Alarm Status received from
Enraf Slave 1. Note ASCII value. For the Whessoe Master this byte
contains the Received Alarm Status + 0x30.
0: NUL
32: Space
45: MinusSign
64: ATSign
65: A
66: B
Issue 1
67: C
70: F
72: H
76: L
84: T
87: W
Device1_LevelStatus 40943 SENUM na 1.B3 The raw value of the Enraf or Whessoe Level Status received from
Enraf Slave 1. Note ASCII value. This Status shall be monitored when
a Operational Command has been sent to Enraf Slave 1. For L&J and
Whessoe, F is invalid and space is Valid Level.
0: NUL
32: Space
45: MinusSign
64: ATSign
65: A
66: B
67: C
70: F
72: H
76: L
84: T
Issue 1
87: W
Device1_LevelValue 40944 FLOAT m 1.B3 The Level Value received from the Enraf, L&J or Whessoe Slave 1 in
meters.
Device2_UpdateCntr 40946 WORD # 1.B3 Update Counter for Device 2, see Device 1.
Device2_ContactStatus 40947 SENUM na 1.B3 Contact Status for Device 2, see Device 1.
Device2_AlarmStatus 40948 SENUM na 1.B3 Alarm Status for Device 2, see Device 1.
Device2_LevelStatus 40949 SENUM na 1.B3 Level Status for Device 2, see Device 1.
Device2_LevelValue 40950 FLOAT m 1.B3 Level Value for Device 2, see Device 1.
Device3_UpdateCntr 40952 WORD # 1.B3 Update Counter for Device 3, see Device 1.
Device3_ContactStatus 40953 SENUM na 1.B3 Contact Status for Device 3, see Device 1.
Device3_AlarmStatus 40954 SENUM na 1.B3 Alarm Status for Device 3, see Device 1.
Device3_LevelStatus 40955 SENUM na 1.B3 Level Status for Device 3, see Device 1.
Device3_LevelValue 40956 FLOAT m 1.B3 Level Value for Device 3, see Device 1.
Device4_UpdateCntr 40958 WORD # 1.B3 Update Counter for Device 4, see Device 1.
Device4_ContactStatus 40959 SENUM na 1.B3 Contact Status for Device 4, see Device 1.
Device4_AlarmStatus 40960 SENUM na 1.B3 Alarm Status for Device 4, see Device 1.
Device4_LevelStatus 40961 SENUM na 1.B3 Level Status for Device 4, see Device 1.
Device4_LevelValue 40962 FLOAT m 1.B3 Level Value for Device 4, see Device 1.
Device5_UpdateCntr 40964 WORD # 1.B3 Update Counter for Device 5, see Device 1.
Device5_ContactStatus 40965 SENUM na 1.B3 Contact Status for Device 5, see Device 1.
Device5_AlarmStatus 40966 SENUM na 1.B3 Alarm Status for Device 5, see Device 1.
Issue 1
Device5_LevelStatus 40967 SENUM na 1.B3 Level Status for Device 5, see Device 1.
Device5_LevelValue 40968 FLOAT m 1.B3 Level Value for Device 5, see Device 1.
Device6_UpdateCntr 40970 WORD # 1.B3 Update Counter for Device 6, see Device 1.
Device6_ContactStatus 40971 SENUM na 1.B3 Contact Status for Device 6, see Device 1.
Device6_AlarmStatus 40972 SENUM na 1.B3 Alarm Status for Device 6, see Device 1.
Device6_LevelStatus 40973 SENUM na 1.B3 Level Status for Device 6, see Device 1.
Device6_LevelValue 40974 FLOAT m 1.B3 Level Value for Device 6, see Device 1.
Device7_UpdateCntr 40976 WORD # 1.B3 Update Counter for Device 7, see Device 1.
Device7_ContactStatus 40977 SENUM na 1.B3 Contact Status for Device 7, see Device 1.
Device7_AlarmStatus 40978 SENUM na 1.B3 Alarm Status for Device 7, see Device 1.
Device7_LevelStatus 40979 SENUM na 1.B3 Level Status for Device 7, see Device 1.
Device7_LevelValue 40980 FLOAT m 1.B3 Level Value for Device 7, see Device 1.
Device8_UpdateCntr 40982 WORD # 1.B3 Update Counter for Device 8, see Device 1.
Device8_ContactStatus 40983 SENUM na 1.B3 Contact Status for Device 8, see Device 1.
Device8_AlarmStatus 40984 SENUM na 1.B3 Alarm Status for Device 8, see Device 1.
Device8_LevelStatus 40985 SENUM na 1.B3 Level Status for Device 8, see Device 1.
Device8_LevelValue 40986 FLOAT m 1.B3 Level Value for Device 8, see Device 1.
Device9_UpdateCntr 40988 WORD # 1.B3 Update Counter for Device 9, see Device 1.
Device9_ContactStatus 40989 SENUM na 1.B3 Contact Status for Device 9, see Device 1.
Device9_AlarmStatus 40990 SENUM na 1.B3 Alarm Status for Device 9, see Device 1.
Device9_LevelStatus 40991 SENUM na 1.B3 Level Status for Device 9, see Device 1.
Issue 1
Device9_LevelValue 40992 FLOAT m 1.B3 Level Value for Device 9, see Device 1.
Device10_UpdateCntr 40994 WORD # 1.B3 Update Counter for Device 10, see Device 1.
Device10_ContactStatus 40995 SENUM na 1.B3 Contact Status for Device 10, see Device 1.
Device10_AlarmStatus 40996 SENUM na 1.B3 Alarm Status for Device 10, see Device 1.
Device10_LevelStatus 40997 SENUM na 1.B3 Level Status for Device 10, see Device 1.
Device10_LevelValue 40998 FLOAT m 1.B3 Level Value for Device 10, see Device 1.
9: Water Level
10: Housing Temp
11: Liquid Temp
12: Vapor Temp
13: Tank Temp
14: Flow Rate
51: Temp 1
52: Temp 2
53: Temp 3
54: Temp 4
55: Temp 5
56: Temp 6
57: Temp 7
58: Temp 8
59: Temp 9
60: Temp 10
61: Temp 11
62: Temp 12
63: Temp 13
64: Temp 14
Issue 1
65: Temp 15
66: Temp 16
67: Temp pos 1
68: Temp pos 2
69: Temp pos 3
70: Temp pos 4
71: Temp pos 5
72: Temp pos 6
73: Temp pos 7
74: Temp pos 8
75: Temp pos 9
76: Temp pos 10
77: Temp pos 11
78: Temp pos 12
79: Temp pos 13
80: Temp pos 14
81: Temp pos 15
82: Temp pos 16
100: Hart PV
101: Hart SV
Issue 1
102: Hart TV
103: Hart QV
150: Ain 1
151: Ain 2
153: Ain 3
200: Pressure 1
201: Pressure 2
202: Pressure 3
1000: Manual value 1
1001: Manual value 2
1002: Manual value 3
1003: Manual value 4
1004: Manual value 5
1005: Manual value 6
1006: Manual value 7
1007: Manual value 8
1008: Manual value 9
1009: Manual value 10
1010: Manual value 11
1011: Manual value 12
Issue 1
1038: Liter
1043: CubicFeet
1048: UsGallon
1049: UkGallon
1051: Barrel
1061: MeterPerSecond
1062: MilliMeterPerSecond
1063: MeterPerHour
1066: InchPerSecond
1067: FeetPerSecond
1069: InchPerMinute
1070: FeetPerMinute
1072: InchPerHour
1073: FeetPerHour
1088: Kilogram
1092: MetricTon
1094: Pound
1095: ShortTon
1096: LongTon
1130: Pa
Issue 1
1132: MPa
1133: kPa
1137: Bar
1138: mBar
1139: torr
1140: atm
1141: Psi
1142: PsiA
1143: PsiG
1144: gPerCm2
1145: kgPerCm2
1146: inH2O
1147: inH2O4C
1148: inH2O68F
1149: mmH2O
1150: mmH204C
1151: mmH2068F
1152: ftH2O
1153: ftH204C
1154: ftH2068F
Issue 1
1155: inHg
1156: inHg0C
1157: mmHg
1158: mmHg0C
1590: BarG
1591: mBarG
1597: BarA
1097: KgPerCubicMeter
1108: lbPerUsGallon
1113: DegAPI
1349: CubicMeterPerHour
1353: LiterPerHour
1358: CubicFeetPerHour
1364: UsGallonPerHour
1369: UkGallonPerHour
1373: BarrelPerHour
1209: A
1211: mA
1212: uA
1240: V
Issue 1
1243: mV
1281: Ohm
1284: kOhm
TV1_Status 41004 BITFIELD na 0.A0 Device 1 TV 1 status.
Bit0: DataError
Bit1: DeviceOOS
Bit2: DataFrozen
Bit3: SaturatedLow
Bit4: SaturatedHigh
Bit5: SimulatedValue
Bit6: ManualValue
Bit7: UnsupportedUnit
Bit12: MI Approved
Bit13: MI Legal Value
Bit14: DeviceError
Bit15: InvalidValue
Bit16: Servo CMD bit0
Bit17: Servo CMD bit1
Bit18: Servo CMD bit2
Bit19: Servo CMD bit3
Issue 1
Bit24: MaintAlert
TV1_Info 41006 SBT na 0D0 Device 1 TV 1 info.
Bit0: FFLowLimit
Bit1: FFHighLimit
Bit2: FFSubstatus b0
Bit3: FFSubstatus b1
Bit4: FFSubstatus b2
Bit5: FFSubstatus b3
Bit6: FFQuality b0
Bit7: FFQuality b1
Bit8: Relative
Bit9: Absolute
Bit10: WrongUnit
Bit11: Protected
Bit12: MiApproved
Bit13: ReferenseValue
TV1_TmvMap 41007 SENUM na 1A2 Device 1 TV 1 default map.
0: TMV LEVEL
1: TMV ULLAGE
2: TMV LEVEL RATE
Issue 1
Bit16: HW IS Approved
Bit17: HW Non IS Board
Bit18: HW Analog Output
Bit19: HW Analog Input
Bit20: HW HART Slave Modem
Bit21: HW Modbus Modem
Bit22: HW HART Master Modem
Bit23: SW Protect Factory Pwd Set
Bit24: SW Protect Config Pwd set
Bit26: SW Analog Output Active
Bit27: SW Analog Input Active
Bit28: SW HART Slave Protocol
Bit29: SW Modbus Protocol
Bit30: SW HART Master Protocol
Bit31: RMH In Boot
SecModemRMHConfig 45134 BITFIELD na 1.B0 See PriModemRMHConfig
PriModemRMIConfig 45136 BITFIELD na 1.B3 Configuration Data read from the RS-485 Modem in the Primary Slot.
Bit0: RevBit0
Bit1: RevBit1
Bit2: uP Started
Issue 1
Bit3: AutoRTS
Bit4: Termination ON
Bit5: Half Duplex
Bit7: RS232 Mode
SecModemRMIConfig 45138 BITFIELD na 1.B3 See PriModemRMIConfig
PriModemLnJConfig 45140 BITFIELD na 1.B7 Configuration Data read from the L&J Modem in the Primary Slot.
Bit0: RevBit0
Bit1: RevBit1
Bit2: uP Started
Bit3: AutoRTS
Bit4: Master Config
Bit5: Primary Cable
SecModemLnJConfig 45142 BITFIELD na 1.B7 See PriModemLnJConfig
PriModemVarecConfig 45144 BITFIELD na 1.B7 Configuration Data read from the Varec Modem in the Primary Slot.
Bit0: RevBit0
Bit1: RevBit1
Bit2: uP Started
Bit3: AutoRTS
Bit4: Not Used by 2410 Baud LOW
Bit5: Primary Cable
Issue 1
PriModemSakuraConfig 45156 BITFIELD na 1.F0 Configuration Data read from the SakuraModem in the Primary Slot.
Bit0: RevBit0
Bit1: RevBit1
Bit2: uP Started
Bit3: AutoRTS
Bit4: MasterMode
Bit5: SlavePower
Bit6: MasterPower
Bit7: MasterPower DCL
SecModemSakuraConfig 45158 BITFIELD na 1.F0 See PriModemSakuraConfig
SakuraIntUpdCntr 45170 WORD # 1.F0 Update counter for the 2410 internal MML Modem communication.
SakuraIntFailCntr 45171 WORD # 1 F0 Counter for framing errors in 2410 internal modem communication.
SakuraMeasDutyCycle 45172 WORD % 1.F0 Sakura measured bus Duty Cycle received from MML.
SakuraBaudRate 45173 WORD # 1.F0 Sakura baude rate received from MML.
MML_Warnings 45174 WORD # 1.F0 MML number of internal warnings.
MML_WarningId 45175 WORD # 1.F0 MML Warnins ID (LSB last, MSB second last ID).
MML_ComInfoCrtr1 45176 WORD # 1.F0 MML internal bus diagnostics counters (LSB checksum errors, MSB
Header Errors).
MML_ComInfoCrtr2 45177 WORD # 1.F0 MML internal bus diagnostics counters (LSB timeouts on first byte,
MSB timeouts on other bytes).
Issue 1
3: WriteHreg
4: Restart
13: Program
14: PollProgram
RmStatus1_Arg1 46228 DWORD na 0.E1 RM_STATUS Arg 1.
RmStatus1_Arg2 46230 DWORD na 0.E1 RM_STATUS Arg 2.
RmStatus1_ErrCode 46232 ENUM na 0.E1 RM_STATUS Error Code.
2: InvalidSelection
3: ParamToLarge
4: ParamToSmall
5: ToFeewBytes
6: TransSpecCmdError
7: WriteProtect
11: AccessDenied
16: AccessRestricted
32: DeviceBusy
50: PrgEraseFailure
51: PrgInvFileFormat
52: PrgWriteFailure
53: PrgInvProhibited
Issue 1
54: PrgIllegalDataAddr
55: PrgLoadedSwError
56: PrgChksumError
RmStatus2_FfAddr 46234 DWORD na 0.E1 See RMSTATUS1.
RmStatus2_CmdNo 46236 ENUM na 0.E1 See RMSTATUS1.
RmStatus2_Arg1 46238 DWORD na 0.E1 See RMSTATUS1.
RmStatus2_Arg2 46240 DWORD na 0.E1 See RMSTATUS1.
RmStatus2_ErrCode 46242 ENUM na 0.E1 See RMSTATUS1.
RmStatus3_FfAddr 46244 DWORD na 0.E1 See RMSTATUS1.
RmStatus3_CmdNo 46246 ENUM na 0.E1 See RMSTATUS1.
RmStatus3_Arg1 46248 DWORD na 0.E1 See RMSTATUS1.
RmStatus3_Arg2 46250 DWORD na 0.E1 See RMSTATUS1.
RmStatus3_ErrCode 46252 ENUM na 0.E1 See RMSTATUS1.
RmStatus4_FfAddr 46254 DWORD na 0.E1 See RMSTATUS1.
RmStatus4_CmdNo 46256 ENUM na 0.E1 See RMSTATUS1.
RmStatus4_Arg1 46258 DWORD na 0.E1 See RMSTATUS1.
RmStatus4_Arg2 46260 DWORD na 0.E1 See RMSTATUS1.
RmStatus4_ErrCode 46262 ENUM na 0.E1 See RMSTATUS1.
PollProgram1 46264 WORD na 0.F0 Last Poll Program response (Data 1).
PollProgram2 46265 WORD na 0.F0 Last Poll Program response (Data 2).
Issue 1
PollProgram3 46266 WORD na 0.F0 Last Poll Program response (Data 3).
Issue 1