Appendix B DIgSILENT®PowerFactory Model

Version 6.01a

August 5, 2019

Prepared for: GE Renewable Energy

Prepared by: GE Energy Consulting


Forward
This report was prepared by General Electric International, Inc. (GEII), acting through GE Energy Consulting
and sponsored by GE Renewable Energy, both based in Schenectady, New York. Questions and any
correspondence concerning this document should be referred to:

Su Pei Fei
Principal Engineer
GE Energy Consulting
General Electric International, Inc.
1 River Road, Bldg. 40,
Schenectady, NY 12345 USA
Office: +55 (11) 3612-7211
Mobile: +55 (11) 99940-7772
su.fei@ge.com
Legal Notices
This report was prepared by GE Energy Consulting as an account of work sponsored by GE Renewable
Energy, Neither GE Energy Consulting nor GE Renewable Energy nor any person acting on their behalf:
1) Makes any warranty or representation, expressed or implied, with respect to the use of any
information contained in this report, or that the use of any information, apparatus, method, or
process disclosed in the report may not infringe privately owned rights.
2) Assumes any liabilities with respect to the use of or for damage resulting from the use of any
information, apparatus, method, or process disclosed in this report.
CONTENTS
1  GE WTG PowerFactory files description 1 
1.1  Adding GE WTG template to a simulation database 1 
1.2  Settings Update Script 2 
1.3  Wind Turbine rating 4 
1.4  Wind Plant rating 6 
1.5  Grid rating 8 
1.6  Controls updates 8 

2  Model Description 15 


2.1  Frame 15 
2.2  Block definitions 17 

3  Control functions for RMS simulations 18 


3.1  Voltage and Reactive Power control setup 18 
3.1.1  Fault Ride Through 18 
3.1.2  Wind Control Emulator 18 
3.1.3  WindFREE reactive power 19 
3.2  Voltage and Reactive Power control behavior 20 
3.3  Wind control 24 
3.4  Protection Settings 26 

4  RMS Initialization 28 


4.1  Coordination with load flow solution 28 
4.2  Droop on Load Flow 28 

5  RMS simulations of setpoint changes 29 


5.1  Voltage setpoint 29 
5.2  Power reference 29 

6  REFERENCES 30 
1 GE WTG PowerFactory files description
This section of the document includes wind turbine model information and user instructions to 
perform engineering studies in PowerFactory of wind plants equipped with GE WTGs.   
GE’s  WTG  PowerFactory  model  reflects  the  control  design  criteria  of  the  GE  WTGs  and  was 
validated against the high fidelity electromagnetic model of the WTG in WindTRAP software. This 
model can be used for balanced and unbalanced simulations. 
The GE DFG WTG model is provided using PowerFactory’s templates and it is assumed that the 
model  user  is  familiar  with  PowerFactory  software.    The  file  name  is  “GE_WTG_DFG_vX 
(template).pfd”,  where  “X”  stands  for  the  model  version.  Additionally,  a  wind  farm  example 
project is provided, named “Project with GE WTG DFG_vX.pfd”. Please contact GE to make sure 
the latest version is provided. The file was created in PowerFactory version 2017. 
Please contact GE for advice on modeling any GE WTGs not currently included in this document.  
Dissemination of the associated files in whole or in part to a third party is subject to the written 
approval from GE. 
 
1.1 Adding GE WTG template to a simulation database
Please refer to PowerFactory user’s manual for instructions to import templates.  
To complement PowerFactory user’s manual information, this is a summary of the required steps 
to incorporate a GE WTG model to a pre‐existing PowerFactory project: 
1. Import  “GE_WTG_DFG_vX  (template)”  to  the  “Templates”  folder  in  the  PowerFactory 
project where the GE WTG model is to be incorporated. 
2. Activate the relevant study case in the PowerFactory project where the GE WTG model is 
to be incorporated. 
3. Open  a  grid  representation  (one‐line  diagram)  including  the  equivalent  690V  terminal 
where  the  WTG  will  connect  (low  voltage  terminal  connecting  to  aggregated  unit 
transformer) 
4. Apply a template copy in the grid representation.  To do this,  

a. Select the symbol   
b. Select the template “GE_WTG_DFG_vX (template)” from the browser 
c. Left  click  on  the  grid  representation  (canvas)    to  show  a  ghost  image  of  the
template grid elements 
d. Drop the ghost image with another left click at the desired GE WTG position 
 
The GE template representation includes the following grid elements: 
1. Static generator 
2. Low voltage 690V terminal  
3. Breaker (the breaker is connected only on one side) 

Figure 2‐1. Grid Elements. 
The  pre‐existing  PowerFactory  project  should  include  an  aggregated  or  individual  unit 
transformer and the associated low voltage (690 V) terminal or medium voltage (6 kV) terminal. 
To connect the GE WTG model to the rest of the system, simply connect the disconnected side 
of the template breaker (“Breaker/Switch”) to the desired low voltage terminal in the pre‐existing 
system. 
The template also includes measurement elements and DSL elements.  The DSL elements may 
need parameter adjustments based on the specific characteristics of a project. The measurement 
elements and Station Control need to be connected to the correct measurement points. Normally 
the measurement elements of “WGenT” 690V terminal are connected, but the measurements 
elements “VPOI” and “Q for droop”, and the Station Control need to be connected to the chosen 
POI (Point of Interconnection) in case the user wants to test the wind plant level controller. 
The library of models “GE DFG Library” and script “Project Setup” are part of the template.  Once 
the template is imported, the user can move (not copy) the library to the desired location in the 
existing project database, and move the script file to folder “Script”. 
The simulation timestep should be 1.0 ms or less for proper model response.  Fixed timestep is 
recommended. 
 
1.2 Settings Update Script
Ratings and control parameter adjustments need to be done in the provided files according to 
the  specific  project  to  be  simulated.  This  can  be  done  manually  by  adjusting  each  element.  
Alternatively, the user can update parameters and ratings automatically using the provided file 
“Project Setup.txt” (Figure 2‐2) and the script with the same name located in folder “Script” inside 
PowerFactory project or inside the GE WTG template imported. The script updates the relevant 
rating and control parameters when executed.  
 
Figure 2‐2. Project Setup.txt file. 
The appropriate path to file “Project Setup.txt” has to be updated inside the script, line 75, prior 
to execution.  
When using the txt‐file, the user shall update the 2nd line according to the project file selected as 
shown in next table. This parameter enables updates to elements of the specific file used.  
Table 2‐1. 2nd line of Project Setup.txt. 

Parameter  Acceptable values  Applicable to file: 


nTmplt  1  Project with GE WTG DFG_vX.pfd 
2  GE_WTG_DFG_vX (template).pfd 
If  the  wind  turbine  only  template  is  chosen  (option  2)  the  user  shall  connect  manually  the 
Measurement elements and Station Control to the points of measurement and control of the 
specific project. 
 
1.3 Wind Turbine rating
The Project Setup.txt file can be used to automatically update the static generator "GE WTG" 
ratings. The user shall update the 4th line of the text‐file according to the specifications shown in 
the next table.  
 
Table 2‐2. 4th line of Project Setup.txt. 

Parameter Description Unit Possible values


WTGmw  MW rating of the individual WTG  MW  1.X, 2.X, 3.X, 4.X 
and 5.X series 
nWTG  Number of WTGs in parallel  ‐  ‐ 
pf  Static power factor  ‐  0.95, 0.9 
 
Alternatively, the user may manually update of the static generator "GE WTG”. The following 
equations can be used to calculate the rated values of GE DFG WTG series. The control design 
criteria are the same for these WTGs.   
In order to adapt the model to represent a specific WTG, set in the static generator "GE WTG", 
the “Nominal Apparent Power” to the WTG MW rating, “Power Factor” to 1, “Min. and Max. 
Reactive Power Limits”, “Min. and Max. Active Power” according to the equations 1 and 2: 
 
(1)
1  

(2)
1  

Where: 
P= Rated Active Power (MW) 
Q= Reactive Power (MVAr) 
PF= Power Factor (‐) (0.95 or 0.9) 
The  PQ  and  VQ  capability  curves  of  each  GE  WTG  are  available  on  the  WTG  specific 
documentation. The user shall input the correspondent data in the Capability Curve of Reactive 
Power Operation Limits inside the Static Generator. 
Additionally, there is a DPL available in PowerFactory website that automatically generates these 
curves for the wind plant, called “Wind Farm PQ Diagram” and “Wind Farm VQ Diagram”.  
The following figures show the updated parameters of the static generator "GE WTG". 
 
 

 
Figure 2‐3. Static Generator, Basic Data. 
Figure 2‐4. Static Generator, Load Flow. 
 
1.4 Wind Plant rating
The  Project  Setup.txt  file  can  also  be  used  to  automatically  update  the  unit  transformer, 
aggregated collector system, LV, MV and HV terminals, and wind farm main transformer data of 
the file “Project with GE WTG DFG_vX.pfd”. The user shall update the following parameters of 
the txt file according to the specifications shown in the next table. 
 
 
 
 
 
 
 
Table 2‐3. 6th and 8th lines of Project Setup.txt. 

Parameter Description Unit Possible values


freq  System frequency  Hz  50, 60 
TRFmva  Unit transformer MVA rating  MVA  ‐ 
LVside  Voltage level at low side of the unit  kV  ‐ 
transformer 
MVside  Voltage level at high side of the unit  kV  ‐ 
transformer 
uk  Short circuit voltage of unit transformer  %  ‐ 
XR  X/R ratio of unit transformer  ‐  ‐ 
vLV  Vector group LV‐side of unit transformer  ‐  Y, YN, Z, ZN, D 
vMV  Vector group HV‐side of unit transformer  ‐  Y, YN, Z, ZN, D 
PHshift  Phase shift of unit transformer  *30deg  1 to 11 
Iline  Rated current of aggregated collector system  kA  ‐ 
cables 
Rline  Resistance of aggregated collector system  Ω  ‐ 
cables 
Xline  Reactance of aggregated collector system  Ω  ‐ 
cables 
Bline  Susceptance of aggregated collector system  uS  ‐ 
cables 
mTRFmva  Main transformer MVA rating  MVA  ‐ 
HVside  Voltage level at high side of the unit  kV  ‐ 
transformer 
muk  Short circuit voltage of main transformer  %  ‐ 
mXR  X/R ratio of main transformer  ‐  ‐ 
mvMV  Vector group LV‐side of main transformer  ‐  Y, YN, Z, ZN, D 
mvHV  Vector group HV‐side of main transformer  ‐  Y, YN, Z, ZN, D 
mPHshift  Phase shift of main transformer  *30deg  ‐ 
 
Alternatively, these updates can be done manually at each element.   
 
1.5 Grid rating
The Project Setup.txt file can also be used to automatically update of the OH line, HV terminal, 
external grid and AC voltage source of the file “Project with GE WTG DFG_vX.pfd”. The user shall 
update the following parameters of the txt‐file according to the specifications shown in the next 
table.  
Table 2‐4. 10th line of Project Setup.txt. 

Parameter Description Unit


IOHline  Rated current of overhead line  kA 
ROHline  Resistance of overhead line  Ω 
XOHline  Reactance of overhead line  Ω 
BOHline  Susceptance of overhead line  uS 
Skmax  Maximum external grid short circuit power  MVA 
RXmax  R/X ratio of maximum external grid short  ‐ 
circuit 
Skmin  Minimum external grid short circuit power  MVA 
RXmin  R/X ratio of minimum external grid short  ‐ 
circuit 
 
Alternatively,  these  updates  can  be  done  manually  at  each  element  according  to  the 
specifications of the project.  
 
1.6 Controls updates
Details  of  the  GE  WTG  controls  parameters  are  explained  in  the  main  body  of  the  modeling 
document and in other sections of this Appendix. This section shows how to update automatically 
key parameters using Project Setup.txt file.   
The  text  file  has  parameters  from  the  DSL  elements  “Converter  Control  (GEWTE  v601a)”, 
“Generator/Converter (GEWTG v601a)” and “Fault Ride Through”.  These parameters shall be 
determined and update by the GE team.  The parameters from the DSL elements “Reactive Power 
Control” and “Turbine Control (GEWTA v601a)”.  These parameters may also be updated by the 
user based on the descriptions shown in the next table.  
Table 2‐5. Setup of Turbine Control DSL 

Parameter Description Value/Unit DSL element


USIZE WTG unit size MW Turbine Control
MBASE Generator Rated Power MW Turbine Control
Plant and drive train parameters

FBASE Rated Frequency Hz Turbine Control


MASSFLAG Flag to indicate which mass model to 1 or 2 Turbine Control
be used: Rotor 1-mass or Rotor 2-
Mass
Turbine Control
WBASE Nominal generator rotor speed rad/s
Turbine Control
Hg Generator inertia MW-s/MW
Turbine Control
Ht Turbine inertia MW-s/MW
Turbine Control
Ktg Shat stiffness coefficient -
Turbine Control
Dtg Shaft damping coefficient -
- Turbine Control
Kibr Below rated integral gain
- Turbine Control
Kpbr Below rated proportional gain
- Turbine Control
Kiar1 Above rated integral gain
MBC Model Parameters

Turbine Control
Temax Maximum electrical torque pu
Turbine Control
Temin Minimum electrical torque pu
- Turbine Control
Kiar2 Second integral gain for above rated
mode
- Turbine Control
Kpar2 Second proportional gain for above
rated mode
Turbine Control
Pmmin Minimum mechanical torque pu
Turbine Control
Pres Power reserve pu
spdrrl Speed rate limit
rpm Turbine Control
SPD1 Speed 1 in power speed curve
Wind Inertia

Turbine Control
Parameters

SPD2 Speed 2 in power speed curve rpm


Turbine Control
PWR1 Power 1 in power speed curve kW
Turbine Control
PWR2 Power 2 in power speed curve kW
Turbine Control
Tm1 Time constant 1 in power shaper s
Parameter Description Value/Unit DSL element
Turbine Control
Ulim Upper ramp rate limit in power pu/s
shaper
Turbine Control
Llim Lower ramp rate limit in power pu/s
shaper
Turbine Control
Kwsi Input whashout gain -
Turbine Control
Twi Input washout time constant s
Turbine Control
DBL Deadband lower limit pu
Turbine Control
DBU Deadband upper limit pu
Turbine Control
Kwi Wind inertia gain pu
Turbine Control
Tm2 Time constant 2 in wind inertia s
Turbine Control
Ulim1 Upper wind inertia ramp rate pu/s
Turbine Control
Llim1 Lower wind inertia ramp rate pu/s
Turbine Control
Kwso Output washout gain -
Turbine Control
Two Output washout time constant s
Turbine Control
Pwimax Maximum wind inertia power output pu
pu Turbine Control
P0 Speed Curve Parameter P0
pu Turbine Control
P1 Speed Curve Parameter P1
pu Turbine Control
Speed Power Curve

P2 Speed Curve Parameter P2


pu Turbine Control
P3 Speed Curve Parameter P3
pu Turbine Control
W0 Speed Curve Parameter W0
pu Turbine Control
W1 Speed Curve ParameterW1
pu Turbine Control
W2 Speed Curve Parameter W2
pu Turbine Control
W3 Speed Curve Parameter W3
pu Turbine Control
PMIN Minimum wind plant power
Turbine Control
APCFLAG Active Power Flag 0 or 1
Turbine Control
Kipw Power regulator integral gain -
Wind control
parameters

Turbine Control
Kppw Power regulator proportional gain -
Turbine Control
Td Power regulator proportianl delay s
Turbine Control
Tdl Power command delay s
Turbine Control
Tpr Time constant in pref command s
Parameter Description Value/Unit DSL element
Turbine Control
Prrup Upper rr limit on pref pu/s
Turbine Control
Prrdw Lower rr limit on pref pu/s
Turbine Control
VFRZ Voltage freeze threshold for MBC pu
regulators
Turbine Control
Trqrup Up ramp rate on electrical torque pu/s
command
Turbine Control
Trqrdn Down ramp rate on electrical torque pu/s
command
Turbine Control
Tpref Time constant on Pref command s
Turbine Control
Prefrup Upper ramp rate on Pref signal pu/s
Turbine Control
Prefrdw Lower ramp rate on Pref signal pu/s
 
Table 2‐6. Setup of Reactive Power Control DSL 

Parameter Description Value/Unit DSL element


Rc Compensating resistance for ohms Reactive Power Control
voltage control
Reactive Power Control
Xc Compensating reactance for ohms
voltage control
Reactive Power Control
Xqd Compensating reactance for ohms
Q Droop function
Reactive Power Control
Vermn Minimum limit on pu
WindCONTROL regulated bus
voltage error
Reactive Power Control
Vermx Maximum limit on pu
WindCONTROL regulated bus
voltage error
Reactive Power Control
Tr Time constant s
Kqd Reactive power droop gain pu on MW Reactive Power Control
base
Tlpqd Response time of reactive s Reactive Power Control
power droop feedback signal
Tpwr Time constant s Reactive Power Control
Kiv Voltage control integral gain pu on MW Reactive Power Control
base
Tc Time constant s Reactive Power Control
FN Fraction of WTGs on wind - Reactive Power Control
farm that are on-line
Kvp Washout 1 gain - Reactive Power Control
Kvp2 Washout 2 gain - Reactive Power Control
Tv Time constant s Reactive Power Control
Tv2 Time constant s Reactive Power Control
Tld Lead time constant s Reactive Power Control
Tlg Lag time constant s Reactive Power Control
DBLL Deadband threshold pu Reactive Power Control
pu Reactive Power Control
Qmn1 Qmn1 Limit in Windfree
pu Reactive Power Control
Qmn2 Qmn 2 Limit in Windfree
pu Reactive Power Control
Qmn3 Qmn 3 Limit in Windfree
pu Reactive Power Control
Qmx1 Qmx1 Limit in Windfree
pu Reactive Power Control
Qmx2 Qmx 2 Limit in Windfree
pu Reactive Power Control
Qmx3 Qmx 3 Limit in Windfree
pu Reactive Power Control
PG1 PG1 Limit in Windfree
pu Reactive Power Control
PG2 PG2 Limit in Windfree
pu Reactive Power Control
Vermn Minimum limit on
WindCONTROL regulated bus
voltage error
Reactive Power Control
Vermx Maximum limit on pu
WindCONTROL regulated bus
voltage error
 
This  list  comprises  parameters  that  may  change  between  applications.    The  remainder  of 
parameters would normally not need to be modified but can be manually modified in the DSL 
elements. 
If chosen to not run the script, the remaining manual updates have to be done in the Station 
Control “GE Wind Control” and measurement element “Q for Droop”.  
 Set the total rated Reactive Power at the Station Control element “GE Wind Control”> 
Load Flow > Rated Reactive Power. The desired droop setting should be set in the same 
element.  Note that droop value is set in Qrange base in %.  
 

= Number of WTGs x 
WTG Rated Reactive 
Power

 
Figure 2‐5. Station Control “GE Wind Control”, Load Flow. 
 
 Set the Power Rating field in the in the PQ measurement element “Q for droop” to the 
rated Apparent Power of all GE WTGs.   
 

= Number of WTGs x 
WTG Rated Power 

 
Figure 2‐6. PQ Measurement "Q for Droop", Basic Data. 
 
 
2 Model Description
The GE wind turbine generator model in the provided PowerFactory template comprises of: 
 Network  elements:  GE  WTG  (Static  Generator  and  Composite  model),  WGenT  690V 
terminal, Breaker/Switch element, static measurement elements 
 Composite model and DSL elements associated to GE WTG controls 
 Library folder “GE DFG WTG” (Frame and block definitions) 
 Script “Project Setup” 
2.1 Frame
The composite frame of the GE wind turbine generator model is presented in next figure. The 
colored boxes represent: 
1. GENERATOR/CONVERTER MODEL (red box)  
2. ELECTRICAL (CONVERTER) CONTROL MODEL (green box)  
3. WIND TURBINE AND TURBINE CONTROL MODEL (dark blue box)  
Several additional blocks on the light blue box are associated to PowerFactory measurement 
elements. 
 
 
DIgSILENT
GE Wind Turbine Model v601:

WIND TURBINE AND TURBINE ELECTRICAL(CONVERTER)


GENERATOR/CONVERTER MODEL
MEASUREMENT CONTROL MODEL CONTROL MODEL
DEVICES

Pgen
0 0
Meas PQ Gen
StaPqmea* Qgen
1
Pord IPcmd
Wind Turbine Model 0 0 0
ElmWtm*
u1r_in;u1i_in Generator(network)
0
fe ElmGenstat*
0 1
IQcmd
1 1
u
1 2
Meas VTRM
StaVmea* ur;ui
2
1 2

2
Converter Control 2
Generator/Converter
ElmWec* ElmDsl*
Qcmd
0 3

1
Iplv
1
Qbranch
0 2
Meas Qbranch ir;ii
4 3
StaPqmea*
1 Reactive Power Control
Vreg ElmWrc*
3

5 4
Im
4
Meas VREG
StaVmea*
5

Meas IBranch
StaImea*

Meas Igen
StaImea*
0

Fault Ride Through


ElmVpr*
1

 
Figure 2‐1: PowerFactory composite frame of GE wind turbine generator model  
2.2 Block definitions
The  table  below  provides  a  short  description  of  each  block  and  the  associated  section  of 
reference with detailed description.  
Table 2‐1. Block Definition. 

Category Block name Description or dedicated section in


GENERATOR/CONVERTER  Generator/Converter  Refer to section 5.1 in main body 
MODEL 
Generator (network)  Static  generator  element  in 
PowerFactory network 
Fault Ride Through  Refer to section 5.1.3 in main body 
Interface  Additional  block  to  improve  PF 
numerical behavior 
ELECTRICAL  (CONVERTER)  Converter Control  Refer to section 5.2.1 in main body 
CONTROL MODEL 
Reactive  Power  Refer to section 5.2.2.1 in main body 
Control 
WIND TURBINE AND TURBINE  Turbine Control  Refer to section 5.3.1 in main body 
CONTROL MODEL 
Rotor  Refer to section 5.3.2 in main body 
Wind Control  Refer to section 5.3.3 in main body 
Wind Inertia  Refer to section 5.3.4 in main body 

The  “Generator(network)”  block  is  assigned  as  “Main  Slot”.    That  is,  if  the  static  generator 
element is set out‐of‐service, the composite model will be automatically be set out‐of‐service. 
 
3 Control functions for RMS simulations
3.1 Voltage and Reactive Power control setup
Section 5.2.2.1 in the main body of this document describes the options of voltage and reactive 
power control in the model. The associated parameters should be set in the “Reactive Power 
Control” and “Converter Control” DSL elements. 
In order to perform voltage control of the point of interconnection (Settings in provided models), 
the StaVmea element called "VPOI" located inside the composite model should be set to measure 
the appropriate bus bar in the system.   
3.1.1 Fault Ride Through
The generator model also includes over/under voltage protective functions to reflect conditions 
when the WTG may disconnect.  In particular, the low voltage tripping can be set to meet so‐
called “low‐voltage ride through‐LVRT” or “zero‐voltage ride through‐ZVRT” requirements.  
3.1.2 Wind Control Emulator
In case the user wants to verify wind plant level voltage and reactive power control behavior, the 
Reactive  Power  Control  DSL  element  must  be  activated.  This  DSL  represents  a  simplified 
equivalent of the supervisory VAr controller portion of the entire wind farm management system, 
commercially called WindCONTROL. 
Qcmd can come from the WindCONTROL voltage and reactive power control emulator (varflg to 
1) or from the WTG power factor control emulator (pfaflg to 1 and varflg to 0). It can also be held 
constant (pfaflg to 0 and varflg to 0) or come from a separate model (varflg to ‐1). The varflg and 
pfaflg flags will determine the configuration chosen. 
The WindCONTROL emulator function represents a simplified equivalent of the supervisory VAr 
controller portion of the entire wind farm management system (WindCONTROL). The function 
monitors a specified bus voltage and compares it against the reference voltage. The regulator 
itself is a PI controller, with gains Kpv and Kiv.  The time constant, Tc, reflects the delays associated 
with cycle time, communication delay to the individual WTGs, and additional filtering in the WTG 
controls.  The voltage measurement lag is represented by the time constant Tr.  
3.1.2.1 Droop and Line Drop Compensation
In case the user needs to consider reactive power droop at the plant level, the parameter Xqd 
(droop gain) must be set to a value different than 0 for dynamic simulations.  This parameter is 
set on a 100MVA base.  
The  Q  Droop  function  is  a  relatively  slow‐acting  function  that  reduces  the  effective  voltage 
reference  for  the  plant  level  voltage  control  as  reactive  power  changes.    This  improves 
coordination  between  multiple  integral  controllers  regulating  the  same  point  in  the  system. 
There are three options for the reactive power input to this function: reactive power generated 
by  the  WTG  (Droop_selector  to  0),  reactive  power  flow  in  a  user‐specified  branch 
(Droop_selector to 1), or a synthesized reactive power (Droop_selector to 2).  The latter is the 
reactive power flow in the user‐specified branch plus a secondary term, Xqd*Im2, where Im is the 
magnitude of the current flowing in that branch (“I for Droop” measurement element).  The Xqd 
refers to the electrical distance between the measurement point and the point of desired voltage 
regulation. Commercially this function is called “Line Drop Compensation”, and may be enabled 
setting Xqd to a value different than 0.  
“I for Droop” and “Q for Droop” measurement elements must be set to the point of measurement 
of the Wind Control. The rated power of the wind plant must be set in the PQ measurement 
element. 
 

= Number of WTGs x 
WTG Rated Power 

 
Figure 3‐1. PQ Measurement "Q for Droop", Basic Data. 

3.1.2.2 Common WindCONTROL for N‐aggregated models


In case the user wants to simulate a project with N‐aggregated models of the GE WTG, however 
representing a single WindCONTROL at the POI, it must set the measurement elements of the 
Reactive Power Control DSL elements of each aggregated WTG to read the same point, the POI.  
One station control, “GE Wind Control”, can be adjusted to control the N‐aggregated or single 
static generators, and the remaining station controls shall be set out of service.  

3.1.3 WindFREE reactive power


The WindFREE option can be enabled in the GE WTG model.  There are two ways of simulating 
the operation of this feature: 
1. Initial operation above cut‐in wind speed.  If the turbine trips on extreme rotor speed or 
low  wind  speed  during  the  simulation,  the  generator  model  in  Power  Factory  (Static 
Generator) stays connected providing reactive power and zero active power.  The provided 
model includes a logic that disconnects the Turbine Control common  model and sets the 
power command to zero.  
2. Initial operation below cut‐in wind speed.  The user should also set the load flow dispatch 
power of the static generator to zero (note to have the minimum active power operation 
limit set to zero). The simulation performed in this way would represent the voltage and 
reactive power control features of the GE WTGs. 
 
3.2 Voltage and Reactive Power control behavior
The GE WTGs are capable of producing Reactive current above its static limits for a short period 
of time under voltage control mode, with the aim of keeping the voltage stable.  
The 0.95 PF and 0.9 PF static limits are applicable at steady state condition, but dynamically the 
reactive current of the WTGs can be increased.  
The  reactive  power  control  behavior  can  be  configured  to  meet  the  different  grid  code 
requirement.  This  is  achieved  by  setting  the  parameter  “VCONTROLFLAG”  according  to  table 
below: 
 
Table 3‐1. Voltage control mode 
 
Parameter name Parameter value Description Grid Code
VCONTROLFLAG  0  Conventional Control  (Most countries 
VCONTROLFLAG  1  Proportional Control  Germany 
VCONTROLFLAG  2  Proportional  VDE  SPAIN,  
Control  VDE (Germany) 
 
Conventional Control:
 
The maximum and minimum dynamic limits of Reactive Current are defined in the graph below: 
Figure 3‐2. WTG Reactive Current dynamic limits. 
The WTG inner loop voltage controller reacts faster to the voltage variations at its terminals, and 
will contribute with up to the reactive current of the figure above. Subsequently it follows the 
reactive  power  command  from  the  voltage  controller  of  the  WindCONTROL.  This  speed  of 
response depends of the parameters set in the converter and in the WindCONTROL, additionally 
to communication delays. 
The WTG Reactive Current dynamic limits can be configured using two look‐up tables shown in 
the figure below. 
 
 
Figure 3‐3. WTG Reactive Current dynamic limits input table. 
The text file has also the lookup table parameters that can be modified shown in the figure below. 

 
Figure 3‐4. WTG Reactive Current dynamic limits look‐up tables. 
 
 
Proportional Control:
In proportional control mode, the turbine provides additional reactive current in proportional to 
change in voltage as shown in Figure 3-5. In this mode of operation, the proportional control 
becomes active when the voltage during disturbance falls outside of the +‐10% of the nominal 
voltage.  
The proportionality factor (K_HV and K_LV), dead‐band (DB_HV and DB_LV) and  reactive current 
limits (Iqmax and Iqmin) can be configured based on Table 3-2. 
Additional reactive current required 1.0
Δi1 

K_HV

0.5

DB_HV
DB_LV
‐0.5 ‐0.3 ‐0.1 0.1 0.3 Δu1 
Voltage drop or increase

‐0.5
Δu1 = voltage change in the positive sequence system  
Δi1 = reactive current change in the positive sequence system  

K_LV ‐1.0

Figure 3‐5. Proportional control. 

Table 3‐2. Parameters for proportional control & proportional VDE control 

Recommended
Variable Name Description
Value (SPAIN)
K_LV  Reactive current deviation /voltage deviation for 
3.5 
voltage reductions   
K_HV  Reactive current deviation /voltage deviation for over 
3.5 
voltages 
DB_LV  0  Dead‐band around initial voltage (voltage reductions) 

DB_HV  0  Dead‐band around initial voltage (overvoltages) 

DeltaV  0.1  Abrupt voltage change detection threshold  

Iqmax  0.9  Maximum reactive current limit 

Iqmin  ‐0.9  Minimum reactive current limit 


 
Proportional VDE Control:
In this control mode, the turbine provides additional reactive current in proportional to change 
in voltage as shown in Figure 3-5. In this mode of operation, the proportional control becomes 
active when ; 
 
(i) the  voltage  during  disturbance  falls  outside  of  the  +‐10%  of  the  nominal 
voltage.  
OR 
(ii) there is an abrupt change in voltage that exceeds the specified threshold. The 
threshold voltage (DeltaV) can be configured. 
 
The proportionality factor (K_HV and K_LV), dead‐band (DB_HV and DB_LV), threshold voltage 
for  abrupt  voltage  change  (DeltaV)  and    reactive  current  limits  (Iqmax  and  Iqmin)  can  be 
configured based on Table 3-2. 
 
 
3.3 Wind control
Active Power Control options are described in section 5.3.3 of the main document and associated 
parameters can be set in the "Turbine Control" DSL element.   
The frequency droop control function is enabled by setting the parameter “APCFLAG” inside DSL 
element  “Turbine  Control”  to  1.  The  graph  below  shows  the  steady‐state  frequency  x  power 
curve set in the GE DFG wind turbine and can be configured using the look‐up table in "Turbine 
Control" DSL element. 
 
Figure 3‐6. Power droop curve. 

 
Figure 3‐7. Power droop curve setting table 
The text file has also the lookup table parameters that can be modified shown in the figure below. 
 
Figure 3‐8. Power droop curve look‐up table 
 
3.4 Protection Settings
Table 3-3 presents the parameters describing the WTG tolerance during under/overvoltage (“Zero Voltage
Ride Through”) and under/over frequency events.

Table 3‐3  Voltage and frequency ride through parameters 

Protection Function Parameter Default value

Undervoltage (Level 1) GE31 0.90 p.u.

Undervoltage (Level 2) GE32 0.85 p.u.

Undervoltage (Level 3) GE33 0.75 p.u.

Undervoltage (Level 4) GE34 0.20 p.u.

Undervoltage (Level 0) GE43 0.00 p.u.

Undervoltage (Time 1) GE37 600 sec

Undervoltage (Time 2) GE38 10.0 sec

Undervoltage (Time 3) GE39 3.0 sec

Undervoltage (Time 4) GE40 1.0 sec

Undervoltage (Time 0) GE46 1.0 sec

Overvoltage (Level 1) GE35 1.10 p.u.

Overvoltage (Level 2) GE36 1.15 p.u.

Overvoltage (Level 3) GE44 1.20 p.u.

Overvoltage (Level 4) GE45 1.25 p.u.

Overvoltage (Time 1) GE41 300.0 sec


Protection Function Parameter Default value

Overvoltage (Time 2) GE42 30.0 sec

Overvoltage (Time 3) GE47 2.0 sec

Overvoltage (Time 4) GE48 0.5 sec

Under frequency (Level 1) GE100 0.94 p.u.

Under frequency (Level 2) GE101 0.90 p.u.

Under frequency (Time 1) GE104 60.0 sec

Under frequency (Time 2) GE105 0.01 sec

Over Frequency (Level 1) GE102 1.06 p.u.

Over Frequency (Level 2) GE103 1.10 p.u.

Over frequency (Time 1) GE106 60.0 sec

Over frequency (Time 2) GE107 0.01 sec


 
4 RMS Initialization
4.1 Coordination with load flow solution
The initialization of the provided model for balanced or unbalanced RMS simulations provides no 
error messages if the load flow solution is within the model capability. 
As an example, if an RMS simulation is initialized from a load flow with terminal voltages outside 
0.9 to 1.1 pu voltage range, state variables related to voltage control will be incorrectly initialized. 
The message shown below is likely to appear after such initialization.   
 
Figure 4‐1. Initialization message for terminal voltage outside acceptable range. 

4.2 Droop on Load Flow


The  droop  function  for  load  flow  simulations  is  set  at  the  Station  Control  called  “GE  Wind 
Control”. The box “Enable Droop” must be checked and the droop value set as a percentage of 
the rated reactive power, as shown in figure Figure 2‐5. 
 
5 RMS simulations of setpoint changes
5.1 Voltage setpoint
The  voltage  setpoint  of  the  plant  level  controller  (WindCONTROL)  can  be  modified  using  a 
parameter event.  The event should modify the variable Vref of the DSL element “Wind Control”.  
The figure below shows the event settings.  Vref is in per‐unit. 

Figure 5‐1. Voltage setpoint event. 
This simulation does not include the slew rate limitation applied to a modification of this setpoint 
from the WindSCADA. That is, it is assumed that the voltage regulator is affected with a step 
change. 
5.2 Power reference
A power reference modification to the plant can also be simulated using a parameter event.  The 
event should modify the variable pref of the DSL element “Turbine Control”.  The figure below 
shows the event settings, pref is in per‐unit. 
Figure 5‐2. Power ramp event. 

6 REFERENCES
[1] “Modelling of GE Wind Turbine Generator for Grid Studies”, Version 6.01, October 17, 2017 issued
by General Electrical International, Inc.