MANUAL ON TECHNICAL GUIDELINES

FOR HOSPITAL PLANNING AND DESIGN


250-BED HOSPITAL
(LEVEL 3)

List of Volumes

Volume 1 – INTRODUCTION AND INSTRUCTIONS FOR USE

Volume 2 – STANDARD PLANS OF A 250-BED HOSPITAL (LEVEL 3)

Volume 3 – DEPARTMENTAL PLANS AND TECHNICAL REQUIREMENTS

OF A 250-BED HOSPTAL (LEVEL 3)

Volume 4 – APPENDICES

First Edition
DEPARTMENT OF HEALTH
Manila
2017
MANUAL ON TECHNICAL GUIDELINES
FOR HOSPITAL PLANNING AND DESIGN
250-BED HOSPITAL
(LEVEL 3)

VOLUMES

Volume 1 – INTRODUCTION AND INSTRUCTIONS FOR USE

Volume 2 – STANDARD PLANS OF A 250-BED HOSPITAL (LEVEL 3)

Volume 3 – DEPARTMENTAL PLANS AND TECHNICAL REQUIREMENTS

OF A 250-BED HOSPTAL (LEVEL 3)

Volume 4 – APPENDICES

First Edition
DEPARTMENT OF HEALTH
Manila
2017
MANUAL on TECHNICAL GUIDELINES for
HOSPITAL PLANNING and DESIGN
250-BED HOSPITAL
(LEVEL 3)

VOLUME 1
INTRODUCTION and INSTRUCTIONS FOR USE

First Edition
DEPARTMENT OF HEALTH
Manila
2017
VOLUME 1
INTRODUCTION and INSTRUCTIONS FOR USE

TABLE OF CONTENTS

PAGE
1.0 INTRODUCTION
1.1. Purpose of the Manual on Technical Guidelines 1
1.2. Format of the Technical Guidelines 1
1.3. Functions of the Technical Guidelines 1
1.4. Updating of the Technical Guidelines 1
1.5. Need for Technical Guidelines 2
1.6. Limitation of the Manual on Technical Guidelines 2

2.0 INSTRUCTIONS FOR USE


2.1. Room Data Sheet A : 5
FUNCTIONAL DESIGN REQUIREMENTS

2.2. Room Data Sheet B : 6


TECHNICAL DESIGN DATA

2.3. Room Data Sheet C : 12


TECHNICAL DESIGN DATA and LAYOUT OF
ROOM and SPACE REQUIREMENTS
1.0 INTRODUCTION
It is the policy of the Department of Health (DOH) to provide both preventing and curative
healthcare that are available, accessible, acceptable, and affordable to the people. Such policy
determines to a large extent the provisions of hospitals and other healthcare facilities.
The provision of hospitals and other healthcare facilities involves a significant amount of capital
investment and operational expenditure. It is then imperative to give utmost attention and concern
to hospital planning and design, considering the country’s socio-economic, cultural, political, and
technological conditions; the rapid advance in medical and design technology; and the country’s
limited resources.
1.1 Purpose of the Guidelines
The primary objective of the technical guidelines is to serve as a tool for hospital planning
and design.
1.2 Format of the Technical Guidelines
The technical guidelines are presented on a per room basis. Every room is discussed in
three (3) different types of Room Data Sheet (RDS). The Room Data Sheet A:
FUNCTIONAL DESIGN REQUIREMENTS provides information on functional design
requirements, stating the facilities (equipment, furniture, engineering terminals, etc.)
needed to support the activities of the room user. The Room Data Sheet B: TECHNICAL
DESIGN DATA states the ideal environmental conditions that must be maintained in a
room. The Room Data Sheet C: TECHNICAL DESIGN DATA and LAYOUT OF ROOM
AND SPACE COMPONENTS gives additional technical design data specifying direct
services provided in the room and direct demand on floor and wall, that shall help designers
identify appropriate finishing materials. Further, a room layout and area requirement is also
provided.
1.3 Function of the Technical Guidelines
These technical guidelines and prototypes shall serve as tools and reference guide for
hospital planning and design and not as dogmatic documents to be used for specific
projects.
It is the intention of the guidelines to provide users with basic information on the functional
and technical requirements for the planning and design of a 250-Bed Hospital, Level 3
Classification.
Along with this technical guidelines manual is a catalogue of operational and management
manuals, also prepared by the Health Facility Development Bureau (DOH-HFDB), which
should be used as cross-references for this Technical Manual. (See List of Manuals under
Cross-References)
1.4 Updating the Technical Guidelines
It is envisioned that the further improvement of the technical guidelines shall emanate from
the result of its continued use and cross-referencing against any hospital design brief.

1
Comments and results from test-case application of the technical guidelines shall be
evaluated. The final outcome of the evaluation will determine the corresponding revisions
to be made in the guidelines. These shall be the inputs used in the updating the guidelines.
1.5 Need for Technical Guidelines
In writing about using a selection of existing techniques and tools for planning health
facilities, Dr. Montoya Aguilar of the SHA/WHO Headquarters says, “Subject to an
understandable range of nuances, people agree that rigid standards are to be excluded and
that typical plans and modules are useful, but only as references or examples of
approaches. Indeed, along with alternative reference plans designed for typical situations,
planners should also formulate guidelines on how to adapt them for more specific
circumstances. Certain technical norms are, of course, necessary and statutory. But, even
these must be revised from time to time.” Truly, there are a lot of these guidelines and
typical plans but these are however scattered and not thoroughly explained nor set in the
proper context of our environment. There is therefore a need for selecting and if possible
formulating a set of tools for health facility planning design appropriate for our milieu.
It is generally perceived that the licensing requirements set by the Health Facilities and
Services Regulatory Bureau (DOH-BHFS) is a large effort to readily meet the “norms and
standards which are necessary and statutory.” What this technical guideline manual seeks
to achieve is to address the challenge of hospital planning and go beyond what is required
by the BHFS. Because in the final analysis, each hospital project will and shall remain
novel and unique in its adaption of the socio-cultural, physical and other characteristics of
the community it seeks to serve.
1.6 Limitation of the Technical Guidelines
This Manual of Technical Guidelines is limited to a 250-Bed Hospital, Level 3
Classification only.
Typical, Redundant and Special Rooms/Spaces
In the use of these Technical Guidelines, there will be some rooms/spaces/areas shown on
the floor plans that do not have Room Data Sheets --- this is due to several reasons: 1) they
are “typical” in nature and thus can be referenced through other Room Data Sheets (i.e.
Office, Clinic, etc.); 2) they are redundant, meaning previous Room Data Sheets have
already been presented (i.e. Conference/Meeting Room, Storage Room, Pantry, etc.); or 3)
they are specialty layouts which are beyond the scope of this Manual (i.e. Auditorium,
etc.).
For all cases, it is recommended that the users of this Manual perform due diligence in
executing their work: hospital administrators to properly brief designers, and designers to
consult hospital end-users regarding the specific and unique requirements of their
rooms/spaces/areas.
Refer to the tabulation below for rooms/spaces/areas shown on the floor plans that do not
have Room Data Sheets:

Room / Space Remarks


 Administrative (Executive)

2
 Infection Control Office Refer to Typical Office; shown in Manual as
ADMINISTRATIVE – Office (Typical):
250B-AD-RDS-22
 Legal Office
 Public Health Office

Room / Space Remarks


 Auditorium The Auditorium is shown on the floor plan to
indicate requirements of space and location.
The size of the space shown also indicates
scale and proportion for a Level 3 Hospital.
The Auditorium design, however, depends on
several end-user requirements (e.g. seating
form and type, acoustics, lighting, sound, etc.)
which fall under the scope of a specialty
designer/architect.
 Emergency Service
 Waste Holding Room May be cross-referenced with NUTRITION
AND DIETETICS – Waste Holding Area:
250B-DIET-RDS-13
 Supply Room Room/space is an open plan; cabinets and/or
shelving to depend on end-user requirements
 Equipment Storage Room Room/space is an open plan; cabinets and/or
shelving to depend on end-user requirements
 Affiliates’ Room Room/space is an open plan; seating, desks
and/or tables to depend on end-user
requirements
 Conference Room May be cross-referenced with
ADMINISTRATIVE – Conference Room:
250B-AD-RDS-12
 Electrical Room Room/space is an open plan; electrical
equipment/components (e.g. UPS,
transformers, panel boards, etc.) to depend on
electrical designer’s requirements
 Outpatient Service
 Affiliates’ Room Please see above (ER-Affiliates’ Room)
 Psychiatric Clinic Refer to Typical Office; shown in Manual as
 Animal Bite Clinic OUTPATIENT – Clinic (Typical): 250B-
 STD/HIV Clinic OPD-RDS-16
 Various OPD Clinic
 Lactation Room May be cross-referenced with NEONATAL
INTENSIVE CARE UNIT – Breastfeeding
Room: 250B-NICU-RDS-03
 Electrical Room Please see previous
 Ambulatory Surgery Clinic
 Sub-Waiting Area Room/space is an open plan ; type of seating
to depend on end-user requirements
 Staff Dress Area Room/space is an open plan
 Laboratory
3
 Storage Room Room/space is an open plan; cabinets and/or
shelving to depend on end-user requirements
 CMT Office Please see previous (Admin-Typical Office)
 Affiliates’ Room Please see previous (ER-Affiliates’ Room)
 Records Room May be cross-referenced with
ADMINISTRATIVE – Records Room:
250B-HIMS-RDS-06

Room / Space Remarks


 Blood Station
 Blood Issuance Area Room/space is an open plan
 Records Room May be cross-referenced with
ADMINISTRATIVE – Records Room:
250B-HIMS-RDS-06
 Radiology
 Supply Room Please see above (ER-Supply Room)
 Ultrasound 1 & 2 Typical with Ultrasound 3; shown in Manual
as Ultrasound Room; please refer to
RADIOLOGY – Ultrasound Room: 250B-
RAD-RDS-07
 Patient Dress Area Please see previous (Ambulatory Surgery
Clinic-Staff Dress Area)
 Nursing Service
 Visitors’/Caretakers’ Pantry May be cross-referenced with
ADMINISTRATIVE – Pantry: 250B-HIMS-
RDS-08
 Affiliates’ Room Please see previous (ER-Affiliates’ Room)
 Storage Room Please see previous (Laboratory-Storage)
 Operating Room Complex
 Affiliates’ Room Please see previous (ER-Affiliates’ Room)
 Conference Room/Library Please see previous (ER-Conference Room)
 Intensive Care Unit (ICU) and similar
 Equipment Storage Please see previous (ER-Equipment Storage
Room)
 Medical Intensive Care Unit Typical; shown in Manual as Intensive Care
Unit – Patient Bay: 250B-ICU-RDS-02
 Surgical Intensive Care Unit Typical; shown in Manual as Intensive Care
Unit – Patient Bay: 250B-ICU-RDS-02
 Delivery Room and Nursery Complex
 Septic Labor Room Room/space same as Labor Room, with septic
cases physically separated from regular cases
to avoid infection
 Septic Delivery Room Room/space same as Delivery Room, with
septic cases physically separated from regular
cases to avoid infection

4
 Isolation Room May be cross-referenced with NURSING
WARDS – Isolation Room: 250B-NU-RDS-
07
 Releasing Area Room/space is an open plan
 Neo-Natal Intensive Care Unit (NICU)
 On-Call Room May be cross-referenced with ER – On-Call
Room: 250B-ER-RDS-18
 Receiving Area Room/space is an open plan
 Linen and Laundry
 Pantry May be cross-referenced with
ADMINISTRATIVE – Pantry: 250B-HIMS-
RDS-08

Room / Space Remarks


 Property and Supply
 Issuing Area Room/space is an open plan
 Hazardous Items Storage Room/space same as typical Storage Room,
with special storage, cabinets, shelving, etc. to
depend on end-user requirements
 Temp-controlled Storage Room/space same as typical Storage Room,
with special storage, cabinets, shelving, etc.,
including necessary temperature and other
related considerations to depend on end-user
requirements
 Meeting Room May be cross-referenced with
ADMINISTRATIVE – Conference Room:
250B-AD-RDS-12

2.0 INSTRUCTIONS FOR USE


The Technical Guidelines is presented in the following Room Data Sheet format:
2.1 Room Data Sheet A: FUNCTIONAL DESIGN REQUIREMENTS
This pertains to the essential design considerations which include listing of facilities
required and user-related data involved to support and achieve the intended function of the
room. These essential design considerations are the following:
2.1.1 Activities Involved: a listing that provides a clearer understanding of the activities
performed within the designated area. The specific description of the activities
involved gives information on the type and number of furniture and equipment
needed to support the listed activities. As these essential information are converted
into spatial dimensions, area quantification can now be derived.
2.1.2 People Involved: a listing that provides the number of occupants or users of the
room at any time. This refers to the specific regular office period/hour or any other

5
work period or shift. Through anthropometrics, space quantification can be done
to identify the size of work areas to be provided to support the activities of the
room occupants. This shall also help in determining the number of particular
furniture and equipment needed.
This listing varies in accordance with existing official and projected plantilla or
organizational set-up in any particular hospital.
2.1.3 Planning Relationship: indicates the areas and services that are to be located
adjacent/close to one another, and easily accessible to the room being discussed or
referred to in the manual.
2.1.4 Equipment and Accessory Checklist: indicates any of the following: tools,
implements, apparatus, appliances, devices, accessories, attachments, and gadgets.
2.1.5 Furniture and Fixture Checklist: indicates either movable or non-movable
articles and fixtures found in a room that may or may not significantly occupy floor
areas.
2.1.6 Additional Equipment and Engineering Terminals: indicates other accessories
and fixtures that do not necessarily occupy a particular floor area within the room
but must be recognized for their functional importance. These fixtures are usually
wall- or ceiling-mounted.
2.2 Room Data Sheet B: TECHNICAL DESIGN DATA
This pertains to the essential technical data that must be considered in establishing and
maintaining quality and the ideal environment for any hospital in relation to the following
four (4) conditions:
2.2.1 Air
2.2.1.1 Outdoor Air Temperature (deg. C) – the average prevailing atmosphere
temperature of a locality in degrees Centigrade. As the outdoor
temperature increases, the desirable room temperature in an air-
conditioned space increases.
Temperature Ranges:
Cold - below 10 deg. C
Cool - 10 deg. C to 15 deg. C
Temperate - 15 deg. C to 27 deg. C
Hot - 27 deg. C to 38 deg. C
Very Hot - above 38 deg. C
2.2.1.2 Room Temperature (deg. C) – the ideal temperature of an air-
conditioned space for employees or hospital staff to work with ease or for
a patient to be comfortable. This is sometimes referred to as the effective
temperature. Effective temperature is an empirically determined index
which combines into a single value the effect of temperature, humidity,
and air movement on the sensation of warmth or coolness felt by the
human body. The numerical value is that of the temperature of still

6
saturated air which could induce an identical sensation. The wide range of
effective temperature is indicated in graphical representation of comfort
zone.
2.2.1.3 Mechanical Ventilation – the process of supplying air or removing air by
mechanical means for or from any space. Such air may or may not have
been conditioned. To minimize odors and to maintain freshness of the air,
a quantity of outdoor air should be required to control body odors. Odors
satisfactorily decreases as the volume space per occupant increase.
2.2.1.3.1 Volume (cu.m./hr.-person) – the quantity of outside air
ventilation requirement in cubic meter per hour per person
2.2.1.3.2 Velocity (m./min.) – the speed of outside air ventilation
requirement in meter per minute
2.2.1.4 Pressure Differential – in all infectious rooms, bacteriology laboratory
and rooms using toxic chemicals, the following are required:
2.2.1.4.1 Negative Pressure (Pa) – amount of pressure required for an
exhaust fan to force the contaminated air out of the room
2.2.1.4.2 Positive Pressure (Pa) – amount of pressure required for an
equivalent inlet fan to normalize the room air pressure
2.2.1.5 % Dust Filtration – the quality of indoor air should be clean and dust
free. Dust and other heavily contaminated tiny particles of pollutants
should be removed from the air to prevent respiratory ailments and other
diseases.
2.2.1.6 Humidity (% RH) – unless otherwise stated will mean the relative
humidity in percent (%RH). This is the ratio of the actual (measured)
partial pressure of the water vapour in the air mixture to its saturation
pressure at the same dry bulb temperature. This is also the ratio of the
actual weight of moisture per cubic meter of mixture to the weight of the
saturated water vapour per cubic meter of mixture at the same dry bulb
temperature.
Relative Humidity Ranges (%RH)
Very Dry - 0-25%
Dry - 25-50%
Humid - 50-75%
Very Humid - 75-100%
2.2.1.7 Cooling Load (TR) – the total calculated heat and moisture of a room in
Tons of Refrigeration (TR) equivalent to 12,660 KJ/Hr.
The following are the major sources of cooling load:
a. Product load in cooling and maintaining low temperature of a product;
b. Solar transmission through walls, ceilings, floors, doors, ducts, and pipes --- a
process of conduction;
7
c. Radiation and conduction through windows;
d. Occupants - sensible heat given-off by people;
e. Electrical equipment - heat from lights, motors, and other appliances;
f. Infiltration - exchange of conditioned air with outdoor air through door
openings and cracks;
g. Ventilation - the controlled replacement of conditioned air with outdoor air;
and
h. Latent load - condensation by the air-conditioner or moisture from such
sources as people, cooking appliances, and outdoor air.
2.2.2 Sound
2.2.2.1 Acceptable Sound Level (db) – the level that must be observed in a
particular area to achieve the acoustical requirements in order that the
activities involved may proceed unhampered.
The following tables provide information on the acceptable sound level
(db) for a particular area:
2.2.2.1.1 Table I – Recommended Category Classification for
Background Noise Levels
Acceptable
Acoustical Equivalent
Type of Space
Requirements
Noise Level
Range in
decibels (db)
 Intensive care areas,  Quiet surrounding 20 - 30
recovery areas must be maintained
 For listening to faint
musical sound
 Large meeting and  For good listening 35 - 40
conference rooms,
executive offices and
conference rooms for
50 people
 Bedrooms, sleeping  For sleeping, resting, 35 – 45
quarters and relaxing
 Private and semi-  For good listening 40 – 45
private offices, small conditions
conference rooms,
classrooms, libraries
 Lounging areas and  For conversing or 45 – 55
similar spaces listening to radio or
TV
 Large office, reception  For moderately good 45 – 60
areas, waiting areas, listening conditions
dining areas, cafeterias
 Lobbies, laboratory  For fair listening 50 – 55
work spaces, general conditions
secretarial areas
 Light maintenance  For moderately fair 55 – 70
shops, offices, and listening conditions
computer equipment

8
rooms, kitchen and
laundry areas
 Shops, garages, power  For acceptable speech 70 – 110
plant control rooms and telephone
communications

2.2.2.1.2 Table II – Common Noise Levels

Sound
Subjective
Type of Sound Level
Impression
(db)
 Siren at 30,480mm  Deafening, threshold 120
of pain
 Wood working shop,  Threshold of 110
accelerating discomfort
motorcycle
 Loud street noise  Very loud 90
 Power lawn mower
 Car/truck unmuffled
 Kitchen blender
 Noisy office  Loud, intolerable 80
 Average street noise  For phone use 70
 Quiet typewriter
 Average radio
 Average office  Usual background 60
 Normal conversation
 General office
 Quiet radio
 Quiet street
 Private office  Noticeably quiet 40
 Quiet bedroom 30
 Quiet conversation
 Whisper  Very quiet 20
 Human breathing 10
 Complete silence  Intolerably quiet 0
threshold of audibility

2.2.2.1.3 Table III – Average Ambient Noise Levels of Interior


Spaces

Average Ambient
Area
Noise Level (db)
 Television or radio station, church, 20-34
synagogue
 Office, residence, night school 26-30
 Library, reception or reading 31-36
room, school study hall
 Noisy office, doctor’s or dentist’s 37-42
office, classroom
 Store and factory 43-49

2.2.2.2 Speech Privacy – levels that indicate extent of acoustical limits and
identify areas where application of acoustical provisions is necessary

9
2.2.2.3 Quality Which Cannot be Tolerated – the presence of noise
characterized as tonal impacts which are incompatible with the required
acceptable sound/noise level and may also hinder achieving and
performing the desired activities involved in a particular area
2.2.3 Lighting and Visual
2.2.3.1 General Illumination (lux) – is a method of illumination that provides an
approximately uniform level of illumination on the work plane over the
entire area. The luminaries are usually arranged in a symmetrical plan
fitted into the physical characteristics of the area and blend well with the
room architecture. They are relatively simple to install and does not
require coordination with furniture or machinery that may not be in place
at the time of the installation. Perhaps the greatest advantage of using this
system of illumination is that it permits complete flexibility in task
location.
In this system of illumination, lighting units are supported fairly close to
the ceiling or at least at a considerable distance above the working plane.
They are spaced uniformly throughout the area without special regard to
the location of equipment, machinery, furniture, etc., and at such a distance
from one another as to give nearly uniform illumination.
2.2.3.2 Night Illumination (lux) – reduced lighting levels for period of low or
minimal activity usually observed during night time
2.2.3.3 Task Illumination (lux) – provides lighting only over a relatively small
area occupied by the task and its immediate surrounding. The illumination
may be from lamps mounted near the task or from remote spotlights. This
system is also called local lighting. It is an economical means of providing
higher illumination levels over a small area, and it usually permits some
adjustment of the lighting to suit the requirements of the individual.
Improper adjustment may, however, cause annoying glare for nearby
workers. Local lighting by itself, is seldom desirable. To prevent excessive
changes in adaptation, it should be used in conjunction with general
lighting or illumination that is at least 20% of the local lighting level; it
then becomes supplementary lighting.
2.2.3.4 Color Rendering – is a general expression for the effect of a light source
on the color appearance of objects in conscious or subconscious
comparison with their color appearance under a reference light source. For
example, a case of the fish looking red or fresh under pink light. It is
defined as the degree to which perceived colors of objects as illuminated
by a test source conform to the colors of the same objects as illuminated
by a standard source. The standard is always daylight as that color
temperature. Therefore, the color rendering index of a light is really a
measure of how closely it approximates daylight of the same color
temperature.

10
2.2.3.5 Standby Light – the installed reserve lighting equipment in excess of that
required which is a reliable support or source to carry peak load
2.2.3.6 Emergency Light – lighting designed to supply illumination essential to
the safety of life and property in the event of failure of the normal supply.
It is required when the normal source is interrupted for any of the
following reasons:
a. Interruption of current flow through operation of a circuit disconnect.
For example, inadvertent de-energizing of a circuit at a panel or
switchboard;
b. Failure of the building’s electrical system; or
c. General power failure.
2.2.3.7 Daylight – the cheapest (insofar as energy is concerned), most abundant
and in many ways, most desirable form of lighting available. The presence
of daylight in interior spaces is made possible by windows and other
similar openings. When daylight enters through windows (side lighting, as
opposed to top lighting), its horizontal directivity provides good modelling
shadows, minimal veiling reflections and excellent vertical surface
illumination. Further, the continual variation of daylight, which is one of
its prominent characteristics, provides a constantly changing pattern of
space illumination; that is unattainable with artificial light. Since these
changes are gradual, the eyes adapt easily and the effect is one of visual
restfulness and interest.
On the other hand, no ill effects have conclusively been demonstrated to
have been caused by lack of daylight; that is by working in an artificially
lighted space. An artificial lighting system must be installed in any event,
to furnish interior illumination during periods when daylight is
insufficient.
Since daylight is variable, it creates special problems of glare control,
direct sunlight control and heat gain limitation in large measure. The
science and art of daylighting is not so much how to provide daylight but
how to do so without the attendant undesirable effects. It is thus imperative
to adopt the technique of permanent supplementary artificial lighting in
interiors. This design approach/technique views artificial lighting as
supplementary to daylight and not vice versa. For structures that are
extracted to be in use at night, artificial lighting must be designed to
furnish all of the required lighting.
2.2.3.8 View Out – the provision of openings, like windows, in interior spaces
that will create visual contact with the outside and the resultant effect
providing a bright, pleasant and airy ambiance to the room
2.2.3.9 Privacy – as opposed to being public, not exposed; not open; seclusion;
isolation; separateness

11
2.2.3.10 Black Out – deliberated exclusion of unwanted light necessary in the
performance of specific activities involving special procedures that may
require special low level lighting or the complete absence of some specific
type of lighting
2.2.4 Safety
2.2.4.1 Accessible Hot Surface – identifies heat generating equipment whose
surfaces may reach temperatures of dangerous levels that users may
possibly come in contact with
2.2.4.2 Accessible Hot Water – identifies the sources and location of accessible
hot water with its allowable maximum temperature for safe use
2.2.4.3 Access Limit – identifies the authorized room or facility users in order to
identify the proper security measures to be adopted
2.2.4.4 Fire Risk – identifies the level (quantity and quality) of fire hazards
present in the space being discussed in order that proper fire prevention
measures may be applied
2.2.4.5 Other Risks – identifies other health hazards that may be present in the
room other than what it previously listed that may pose as some danger to
room users
2.3 Room Data Sheet C: TECHNICAL DESIGN DATA ON DIRECT SERVICES AND
DEMANDS ON FLOOR AND WALL and LAYOUT OF ROOM AND SPACE
COMPONENTS
2.3.1 Direct Services – this refers to the required basic utilities and other convenient
necessities that must be provided in a specific area
2.3.1.1 Disposal – identifies the type of waste generated in an area, treatment of
which must conform with the approved operational programs for solid
waste management as established by the Department of Health (DOH)
2.3.1.2 Hot Water – identifies fixture source and location of this particular utility
2.3.1.3 Cold Water – identifies fixture source and location of this particular
utility
2.3.1.4 Drainage – identifies fixtures and areas to be provided with this utility.
Treatment of sewage material must also conform with the approved
operational programs for liquid waste management as established by the
Department of Health (DOH)
2.3.1.5 Gas – identifies areas to be provided with this utility (may either refer to
medical or non-medical); the types of which, whether supplied in portable
cylinders or through wall outlets, must be determined according to the
capacity to supply and to safely maintain such as system
2.3.1.6 Compressed Air – see 2.3.1.5

12
2.3.1.7 Steam – identifies location where required
2.3.1.8 Others – indicates other necessary utilities not previously listed
2.3.2 Direct Demands on Floor and Wall – the extent of usage and other factors, such
as the activities involved, affecting the performance of materials to be used as
finishing for floors and walls
2.3.2.1 Loading – type of loads, whether light moving loads or heavy stationary
loads that will be taken into consideration so that ample structural support
can be provided
2.3.2.2 Spillage – the type and frequency of accidental or unintentional falling or
throwing of items and materials in the area, that the floor and finishing
materials must conform with
2.3.2.3 Foot Traffic – the expected maximum level of the traffic that can be
observed in a particular area that the floor finishing materials must be able
to support. The finishing material must be durable enough to withstand the
movement with the least need for maintenance and upkeep
2.3.2.4 Wheel Traffic – see 2.3.2.3
2.3.2.5 Impact – the force or collision where either floor or wall is subjected to
when equipment or other bulky items are being moved or transported
2.3.2.6 Abrasion – scraping or wearing away by friction in either floor or wall
brought about by foot and wheel traffic and the movement and
transportation of equipment and other load-bearing items
2.3.2.7 Easy Maintenance – where the practice and observance of cleanliness or
sanitation can be carried out with a minimum involvement of work and
effort
2.3.2.8 Vibration Free – maintaining the constant absence of quivering or
trembling disturbances both physical and auditory, that may originate from
machines, equipment, and other obvious sources. The absence of these
disturbances may be necessary to maintain a safe and secure room
atmosphere
2.3.2.9 Door Sets – identifies the type of door, its size and material finish, so that
equipment and other listed items may be provided easy access, smooth
transfer and movement from one area to another
2.3.2.10Windows – determine the type, size, and material finish of the windows
in order to meet the quality of the interior atmosphere that must be
maintained in a room
2.3.2.11Internal Glazing – identifies the type of glass finishes to be used, whether
clear, opaque, etc.

13
2.3.3 Layout of Room and Space Components – indicative rooms plans showing the
space components, dimensions, and the required equipment and furnishings to be
installed in the room
2.3.4 Space Demands – the quantity or the number of each space component and its
standard minimum area requirement that shall comprise the total minimum area
requirements of the room (To be filled out by the Designer, in most cases; since
this is based on End-Users’ specific needs; in addition to licensing and minimum
requirements)
2.3.5 Regulations and Notes – special rules, regulations, and directives that must be
applied during the design process to improve and standardize the hospital design
and plan (To be filled out by the Designer, in most cases; for local laws and
ordinances in addition to national rules and regulations)

14
MANUAL on TECHNICAL GUIDELINES for
HOSPITAL PLANNING and DESIGN
250-BED HOSPITAL
(LEVEL 3)

VOLUME 2
STANDARD PLANS and TECHNICAL
REQUIREMENTS of a 250-BED HOSPITAL (LEVEL 3)

First Edition
DEPARTMENT OF HEALTH
Manila
2017
VOLUME 2
STANDARD PLANS and TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

TABLE OF CONTENTS

PAGE
2.A 250-BED HOSPITAL (LEVEL 3)
FOUR-STOREY MODEL

Site Development Plan 15


19
Ground Floor Plan 16
20
Second Floor Plan 17
21
Third and Fourth Floor Plans 18
22
Ground Floor Zonal Plan 19
23
Second Floor Zonal Plan 20
24
Third and Fourth Floor Zonal Plans 21
25
Perspectives 22
26

17
MORGUE

HEALTH ENGINEERING
INFORMATION MAINTENANCE
MANAGEMENT PROPERTY SUPPLY LAUNDRY & SECURITY
SYSTEM & MANAGEMENT LINEN HOUSEKEEPING
DIETETICS

250-BED
HOSPITAL

CENTRAL
WASTE
STORAGE

GRAPHICAL SCALE (METERS)


5 4321 0 5 10 20

250-BED HOSPITAL
SITE DEVELOPMENT PLAN
SCALE 1:1200M

19
20
MORGUE

SERVICE
YARD

LAUNDRY
& LINEN
UP UP UP

PROPERTY SUPPLY &


DIETETICS DEPARTMENT
MANAGEMENT OFFICE
HEALTH
INFORMATION ENGINEERING,
MAINTENANCE,
MANAGEMENT
UP
HOUSEKEEPING &
SYSTEMS
SECURITY

RAMP
UP

UP

UP UP
LABORATORY DEPARTMENT

IMAGING DEPARTMENT
UP UP UP UP
UP

PHYSICAL
REHABILITATION UP

DEPARTMENT BLOOD OPEN


STATION COURT
MRI OPEN OPEN OPEN
OPEN RAMP
COURT UP COURT
COURT PRAYER COURT
ROOM

RAMP UP UP UP

OPD LOBBY MAIN EMERGENCY


UP UP

HOSPITAL DEPARTMENT
LOBBY

OPD HEMODIALYSIS
OPEN
TB DOTS COURT OPEN
RAMP RAMP RAMP RAMP COURT
UP UP UP UP
CLINIC

CENTRAL WASTE
STORAGE
UP UP UP UP

RAMP
UP

GRAPHICAL SCALE (METERS)


5 4321 0 5 10 20

250-BED HOSPITAL
GROUND FLOOR PLAN
SCALE 1:1000M
HEALTH
INFORMATION
DN UP DN UP UP DN
MANAGEMENT
SYSTEMS SURGERY WARD OBSTETRICS WARD

SOLARIUM
DN

RAMP
UP

RAMP
DN

UP DN

DN UP DN
CENTRAL
STERILE
SICU PICU SUPPLY
BURN UNIT
DN
ROOM
DN DN DN DN

MICU

OPEN
DN
BELOW
RAMP
DN
OPEN NICU
OPEN OPEN OPEN
BELOW BELOW
BELOW BELOW
AUDITORIUM

DN DN

RAMP DN

OPD OR COMPLEX DR COMPLEX OFFICES


DN DN

OPEN
BELOW

OPEN OPEN
BELOW BELOW

DN DN DN DN

GRAPHICAL SCALE (METERS)


54 32 1 0 5 10 20

250-BED HOSPITAL

21
SECOND FLOOR PLAN
SCALE 1:1000M
22
DN UP DN UP UP DN

MEDICINE WARD PEDIATRIC WARD

RAMP
UP

RAMP
DN

UP DN

GRAPHICAL SCALE (METERS)


54 32 1 0 5 10 20

250-BED HOSPITAL
THIRD FLOOR PLAN
SCALE 1:1000M

DN DN DN

SOLARIUM PRIVATE ROOMS PRIVATE ROOMS SOLARIUM

RAMP
DN

DN

GRAPHICAL SCALE (METERS)


54 32 1 0 5 10 20

250-BED HOSPITAL
FOURTH FLOOR PLAN
SCALE 1:1000M
MORGUE

UNASSIGNED

ENGINEERING,
MAINTENANCE,
TOILETS UP UP UP
HOUSEKEEPING &
DIETETICS PROPERTY SUPPLY and LINEN & LAUNDRY
DINING HALL SECURITY
DEPARTMENT MANAGEMENT OFFICE DEPARTMENT
HEALTH WATER
INFORMATION POWER
PUMP
MANAGEMENT HOUSE
ROOM
SYSTEMS

RAMP E
UP
EE
ELEVATOR ROOM
LOBBY
E

UP

TOILETS
UP UP

IMAGING DEPARTMENT

UP UP UP UP
UP

TOILETS
EE ROOM
UP
DRUG
CANTEEN GARDEN
E TESTING
EE ELEVATOR
ROOM LOBBY OPEN
OPEN E
COURT MRI RAMP
GARDEN COURT
UP PRAYER
BLOOD
STATION ROOM
PHYSICAL TOILETS GARDEN
REHABILITATION
DEPARTMENT
E
EMERGENCY
UP
RAMP UP
TOILETS MAIN UP

DEPARTMENT
OPD ADMINISTRATIVE HOSPITAL
PHARMACY EMERGENCY
UP
OFFICES LOBBY UP

TOILETS TOILETS DEPARTMENT DEPARTMENT


TOILETS

TB DOTS
CLINIC OPD HEMODIALYSIS OPEN
OPEN COURT
RAMP RAMP RAMP RAMP
UP UP UP UP
COURT
OPD MAIN HOSPITAL EMERGENCY
ENTRANCE ENTRANCE ENTRANCE
CENTRAL WASTE
STORAGE TOILETS
UP UP UP UP

RAMP
UP

GRAPHICAL SCALE (METERS)


5 4321 0 5 10 20

250-BED HOSPITAL

23
GROUND FLOOR ZONAL PLAN
SCALE 1:1000M
24
HEALTH
DN UP DN UP UP DN
INFORMATION
MANAGEMENT
SYSTEM SURGERY WARD OB-GYNE WARD

RAMP E
UP
EE
ELEVATOR ROOM
LOBBY
RAMP E
DN

UP DN

DN UP
CENTRAL DN

COUNSELING PEDIA STERILE


SURGICAL BURN ROOMS ICU SUPPLY
DN

DN DN
MEDICAL ICU UNIT ROOM DN DN

ICU NICU

O P E N
DN B E L O W
O P E N
E B E L O W
ELEVATOR RAMP
EE DN
O P E N LOBBY
ROOM
B E L O W O P E N O P E N
E
B E L O W B E L O W
OPD CLINICS OPD CLINICS EXECUTIVE
AUDITORIUM
OFFICES

R O O F
DN
G A R D E N DN

RAMP DN

OPERATING ROOM DELIVERY ROOM


COMPLEX COMPLEX
DN DN

O P E N
B E L O W

AMBULATORY O P E N
OPD CLINICS OFFICES B E L O W OFFICES
SURGERY

DN
DN DN DN

GRAPHICAL SCALE (METERS)


54 32 1 0 5 10 20

250-BED HOSPITAL
SECOND FLOOR ZONAL PLAN
SCALE 1:1000M
DN UP DN UP UP DN

MEDICINE WARD PEDIATRIC WARD

RAMP E
UP
EE
ELEVATOR ROOM
LOBBY
RAMP E
DN

UP DN

GRAPHICAL SCALE (METERS)


54 32 1 0 5 10 20

250-BED HOSPITAL
THIRD FLOOR ZONAL PLAN
SCALE 1:1000M

DN DN DN

SOLARIUM PRIVATE ROOMS PRIVATE ROOMS SOLARIUM

E
EE
ELEVATOR ROOM
LOBBY
RAMP E
DN

DN

GRAPHICAL SCALE (METERS)


54 32 1 0 5 10 20

250-BED HOSPITAL

25
FOURTH FLOOR ZONAL PLAN
SCALE 1:1000M
26
250-BED HOSPITAL
AERIAL PERSPECTIVE
250-BED HOSPITAL
MAIN ENTRANCE
PERSPECTIVE

250-BED HOSPITAL
SITE ENTRANCE
PERSPECTIVE

27
MANUAL on TECHNICAL GUIDELINES for
HOSPITAL PLANNING and DESIGN
250-BED HOSPITAL
(LEVEL 3)

VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

First Edition
DEPARTMENT OF HEALTH
Manila
2017
VOLUME 3
DEPARTMENTAL PLANS and TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

TABLE OF CONTENTS

PAGE
3.1 ADMINISTRATIVE SERVICE FACILITIES 33
3.2 EMERGENCY SERVICE FACILITIES 131
3.3 OUTPATIENT SERVICE FACILITIES 195
3.3.1 OUTPATIENT CLINICS 199
3.3.2 AMBULATORY SURGERY CLINIC 249
3.3.3 PHYSICAL REHABILITATION 279
3.3.4 DIALYSIS 292
3.4 ANCILLARY SERVICE FACILITIES 315
3.4.1 PHARMACY 319
3.4.2 LABORATORY 344
3.4.3 BLOOD STATION 396
3.4.4 RADIOLOGY 418
3.5 NURSING SERVICE FACILITIES 473
3.6 BURN UNIT SERVICE FACILITIES 499
3.7 OPERATING ROOM & ICU SERVICE FACILITIES 513
3.7.1 OR & ICU 516
3.7.2 CSSR 590
3.8 DELIVERY and NICU SERVICE FACILITIES 603
3.9 NUTRITION and DIETETICS SERVICE FACILITIES 675
3.10 ENGINEERING, MAINTENANCE and
HOUSEKEEPING FACILITIES
731

3.11 SUPPORT SERVICE FACILITIES 781


3.10.1 LINEN and LAUNDRY 784
3.10.2 PROPERTY and SUPPLY 803
3.10.3 MORGUE 819
3.10.4 CENTRAL WASTE STORAGE 829

31
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.1 ADMINISTRATIVE SERVICE FACILITIES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

33
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE 250B-AD-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
ADMINISTRATIVE 1,086.00
ADMINISTRATIVE (FRONTLINE) 422.00 250B-AD-DDS-01A 37
Main Lobby 180.00 250B-AD-RDS-01 38
Info/ Reception & Communication Area 19.00 250B-AD-RDS-02 41
Admitting Office 27.00 250B-AD-RDS-03 44
Billing & Claims Office 36.00 250B-AD-RDS-04 47
Cashier's Office 36.00 250B-AD-RDS-05 50
Medical Social Work Office 43.00 250B-AD-RDS-06 53
Public/ PWD Toilets 45.00 250B-AD-RDS-07 56
Staff Toilets 36.00 250B-AD-RDS-08 59

ADMINISTRATIVE (EXECUTIVE) 664.00 250B-AD-DDS-01B 62


Budget & Accounting Offices/ 108.00 250B-AD-RDS-09 63
Finance Manager's Office
Office of the Chief of Hospital 66.00 250B-AD-RDS-10 66
IHOMP (Integrated Hospital Operations 36.00 250B-AD-RDS-11 69
& Management Program)
Conference Room 22.00 250B-AD-RDS-12 72
Office of the Administrative Officer 30.00 250B-AD-RDS-13 75
Office of the Chief of Clinics 42.00 250B-AD-RDS-14 78
Human Resource Development Head 90.00 250B-AD-RDS-15 81
& Staff Offices
Office of the Chief Nurse & Nursing Office 90.00 250B-AD-RDS-16 84
Auditing Office 36.00 250B-AD-RDS-17 87
Library 48.00 250B-AD-RDS-18 90
Staff Lounge 18.00 250B-AD-RDS-19 93
Public Toilets 36.00 250B-AD-RDS-20 96
Office (Typical) 18.00 250B-AD-RDS-21 99
Procurement Department/ BAC Office 24.00 250B-AD-RDS-22 102

35
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE 250B-AD-SFSI-02
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
HEALTH INFORMATION MANAGEMENT 785.00 250B-HIMS-DDS-01 105
MANAGEMENT SYSTEMS
Waiting Area 90.00 250B-HIMS-RDS-01 106
Staff Office and Releasing/Receiving 54.00 250B-HIMS-RDS-02 109
Completion Room 27.00 250B-HIMS-RDS-03 112
Head's Office 11.00 250B-HIMS-RDS-04 115
Admin Records 45.00 250B-HIMS-RDS-05 118
Records Room 36.00 250B-HIMS-RDS-06 121
Files Storage Area 486.00 250B-HIMS-RDS-07 124
Staff Pantry, Lockers and Toilets 36.00 250B-HIMS-RDS-08 127

36
SCALE 1:300 M

15000

TO ER
12000

12000
MAIN
LOBBY

MAIN
ENTRANCE
3000

MALE PABX
INFORMATION
STAFF T ROOM

ADMITTING
3000

9000
MALE OFFICE
PHILHEALTH
STAFF
OFFICE

36000
LOCKERS

FEMALE
STAFF
6000

LOCKERS
BILLING &
WAITING
CLAIMS
AREA

FEMALE
24000

STAFF T

CASHIER WAITING
6000

AREA
15000

FEMALE T
6000

JAN PWD
CLO T

MEDICAL
SOCIAL
MALE T
SERVICE

TO
OPD

3050 6000 6000 3000

37
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE MAIN LOBBY 250B-AD-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Reception/ Waiting area for patients, relatives Glass board w/ directory 1
and visitors Waste bin w/ black or colorless 1
lining

People Involved:
Patients, Relatives and Visitors

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
2- Seater Sofa 4
Center Table, 900mmX900mm 1
Side Table 400mmX400mm 4

Planning Relationships:
a. Within the frontline service building

ADDITIONAL EQUIPMENT & QUANTITY REMARKS


ENGINEERING TERMINALS
Window curtain rail 4
Outlet, 10A, 2P, 240V, duplex 8 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1
Smoke Detector 4

38
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE MAIN LOBBY 250B-AD-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit general public

Fire risk LOW: medium: high

Other risks NA

39
15000

4 2 3 2 5

3 3
1

SD SD 2

12000
2

SD SD

DT

KEY SCALE 1:200 M

1 Table, center, 900 x 900mm 3 2-Seater sofa


2 Table, side, 400 x 400mm 4 Hospital directory
5 Waste bin

40
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-02A
INFORMATION/ RECEPTION &
April 2016 ADMINISTRATIVE COMMUNICATIONS ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Receives queries from clients, patients and guests Computer w/ internet connection 1
b. Gives direction to hospital clients Waste bin w/ black or 2
colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


2 x Computer Operators FIXTURE CHECKLIST
Patients and Guests Counter, 2-Level 1
Computer Table 1
Swivel Chair 5
Work Counter 1
File Cabinet 2
Communication System Console 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Lobby
Outlet, 10A, 2P, 240V, duplex 9 grounding type
universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Outlet, DATA 2
Outlet, Telephone 2
Smoke Detector 2

41
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-02B
INFORMATION/ RECEPTION &
April 2016 ADMINISTRATIVE COMMUNICATIONS ROOM

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit general public

Fire risk LOW: medium: high

Other risks NA

42
2100 4000

2
9 CH 9 DT CH
7
4 5
4 4
CH

3000
SD SD
5 4
D
8 6 1 T
4 3
8 CH

KEY SCALE 1:100 M

1 INFORMATION 6 PABX ROOM


2 Counter, 2-level 7 Counter, work
3 Table, computer 8 Cabinet, file
4 Chair, swivel, with casters 9 Communication system console
5 Waste bin

43
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE ADMITTING OFFICE 250B-AD-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Admitting of patients Computer w/ internet connection 1
b. Conduct interviews with clients to determine service Printer 1
needed Waste bin w/ black or 3
c. Assignment of room/bed where patient is to be colorless lining
admitted (private, pay medicare or service)
d. Encoding of demographic data of inpatient records

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Administrative Officer I FIXTURE CHECKLIST
4 x Computer Operator II Desk, 600mmX1200mm 1
Patients and Companion/s Desk extension, 400mmX900mm 4
Swivel Chair 3
Counter w/ low partitions 2
Cabinet, 500mmX700mm 3
Steel Filing Cabinet 6
Visitor's chair 6
Chair, gang-type 2
Wheelchair park 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Lobby Window curtain rail 4
Outlet, 10A, 2P, 240V, duplex 11 grounding type
universal
Outlet, 10A, 2P, 240V, single 2 emergency light
Outlet, DATA 3 wall-mounted
Outlet, Telephone 3 desktop
Smoke Detector 2
Airconditioning Unit 1 split type

44
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE ADMITTING OFFICE 250B-AD-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit general public

Fire risk LOW: medium: high

Other risks NA

45
3000

7 8

9 7

7000
SD

6 6

9000
6 6
T T
1 D 1 D
5 5

8 4 4 4

4
2000

SD
2 5 3
6 6 TD 8

KEY SCALE 1:100 M

1 Counter, with low partition 6 Chair, visitor


2 Desk, 600 x 1200mm 7 Chair, gang-type
3 Cabinet, 450 x 1200mm 8 Waste bin
4 Cabinet, filing, 500 x 700mm 9 Wheelchair park
5 Chair, swivel, with casters

46
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE BILLING AND CLAIMS 250B-AD-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Chief Billing Officer and Clerks read, write and use Computer 7
telephone in their work stations Printer 7
b. Chief Billing Officer and Clerks compute billing charges ACU 1
c. Chief Billing Officer and Clerks sort charge slips, store Telephone 3
file and retrieve billing records Waste bin w/ black or 2
colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Chief Billing Officer FIXTURE CHECKLIST
6 x Clerks Transaction counter 1 w/ glass panel
Desk, 750mmX1200mm 1
Desk, 600mmX1200mm 6
Swivel Chair 7
Desk extension, 400mmX900mm 7
Steel Filing Cabinet 5
Visitor's chair 2
Stool, adjustable height 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accessible to the Office of the Administrative Officer
b. Accessible to Business and Accounting Office Outlet, 10A, 2P, 240V, duplex 13 grounding type
universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Outlet, DATA 7 wall-mounted
Outlet, Telephone 3 desktop
Smoke Detector 1

47
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE BILLING AND CLAIMS 250B-AD-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit PhilHealth staff/ patient/ visitors

Fire risk LOW: medium: high

Other risks NA

48
6000

4 D 4 D 4 DT
6 3 6 3 6 3

9
CH

9 9
8

6000
SD 1 10
6 3 6 3 6 3
D D DT
4 4 4
8
5
CH
5
9
6 2
DT 5 5 5
9 4 7 7

KEY SCALE 1:100 M

1 Counter, transaction, with glass 6 Chair, swivel, with casters


front panel 7 Chair, visitor
2 Desk, 750 x 1200mm 8 Stool, adjustable height
3 Desk, 600 x 1200mm 9 Waste bin
4 Desk, extension, 400 x 900mm 10 Waiting area
5 Cabinet, filing, 500 x 700mm

49
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE CASHIER'S OFFICE 250B-AD-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Prepares checks and statement of collection Computer 7
and disbursement Printer 3
b. Maintains record of collection and deposit CCTV 2 if funds are available
c. Collects payments Check Writer 1
d. Issues check to suppliers and other claimants Money Verifier (Scanner) 1
e. Prepares Monthly Report of Collection and Deposit Typewriter 1
and other Reports Waste bin w/ black or 4
colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Chief Cashier Officer FIXTURE CHECKLIST
4 x Collecting and Disbursement Clerks Desk, 600mmX1200mm 4
Swivel Chair 4
Desk extension, 300mmX500mm 3
Desk extension, 400mmX900mm 4
Transaction Counter 1 w/ glass panel
Cork/ White board 1
Safe/ Cash box 1
Stool, adjustable height 3
Filing cabinet 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Billing and PhilHealth Section
b. Adjacent to Medical Social Worker Outlet, 10A, 2P, 240V, duplex 14 grounding type
universal
Outlet, 10A, 2P, 240V, single 2 emergency light
Outlet, DATA 5 wall-mounted
Outlet, Telephone 1 desktop
Smoke Detector 2

50
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE CASHIER'S OFFICE 250B-AD-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Chief Cashier, Clerks

Fire risk LOW: medium: high

Other risks NA

51
6000
2900 3100

3 3 4
D 10 DT D
8 2 8 2 9
CH

3900
9 1
SD CH

6000
8 2 8 2 9
3 D 10 3 D CH

2100

6 SD

7 10 5 5 10

KEY SCALE 1:100 M

1 Counter, transaction, with glass 6 Vault


front panel 7 Safe/cash box
2 Desk, 600 x 1200mm 8 Chair, swivel, with casters
3 Desk, extension, 400 x 900mm 9 Stool, adjustable height
4 Desk, extension, 300 x 500mm 10 Waste bin
5 Cabinet, filing, 500 x 700mm

52
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
MEDICAL SOCIAL
April 2016 ADMINISTRATIVE WORK OFFICE 250B-AD-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. MSW conducts psychosocial assessment to determine Computer W/ internet 6
financial capacity of patient to defray expenses and Telefax 1
diagnose psychosocial condition as it interacts with Queuing System 1
physical condition and treatment. This involves Copying machine 1
interviewing the patient, family and significant others. Safety Alarm 1
b. MSW has referral system and maintains coordination Local Telephone 6
with medical team, other stakeholders, patient, Waste bin w/ black or 2
family and significant others colorless lining
c. MSW provides case management and therapeutic services
that includes pre-admission and discharge planning
group therapy
d. MSW documents, maintains reports, conducts research
and studies.
e. Clerk receives visitors, requests communication,
documents and maintains reports and filing system
f. MSW validates PhilHealth membership and NHTS listing FURNITURE AND QUANTITY REMARKS
of indigent patients from computer program provided FIXTURE CHECKLIST
g. Provide supervisory service for both administrative and Desk 600mmX1200mm 6 room should be
clinical services of the MSWD staff Upright chair 6 sound proof to
h. Attend to the reference patients with special needs such Visitor's Chair 7 afford privacy
as pay patients requesting for transfer to service ward Steel filing cabinet 1 but with glass
or political reference Cabinet 1 windows for security
i. Conducts resource development and networking Chair, gang-type 2 purpose and with
j. Develop plans and policies for the unit emergency buzzer

People Involved:
1 x Head Medical Social Worker
5 x Clerks
Patient, family and significant others
Medical team
NGO's, GO's, other stakeholders
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Admitting Office Window curtain rail 5
b. Accessible to Emergency Room and Outpatient Dept. Outlet, 10A, 2P, 240V, duplex 12 grounding type
c. Accessible to the Office of the Administrative Officer universal
d. Close to Business and Finance Office Outlet, 10A, 2P, 240V, single 3 emergency light
Outlet, DATA 6 wall-mounted
Outlet, Telephone 6 desktop
Smoke Detector 4

53
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
MEDICAL SOCIAL
April 2016 ADMINISTRATIVE WORK OFFICE 250B-AD-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA


Medical Social Service Staff,
Access limit
patients & visitors
Fire risk LOW: medium: high

Other risks NA

54
3000

4 4
DT

2000
3 6
1 SD
7 2
3

2000
1 DT
4

SD 3

2000
1 D
T
4
3

2000
1 D

15000
T
4
3

2000
1 D
T
SD 4
3

2000
1 D
T
4

3000
SD
5

7 5

KEY SCALE 1:200 M

1 Desk, 600 x 1200mm


2 Cabinet, steel, filing
3 Chair, upright
4 Chair, visitor
5 Chair, gang-type
6 Cabinet
7 Waste bin

55
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE PUBLIC/ PWD TOILETS 250B-AD-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hospital patients, relatives and visitors make use of Exhaust Fan 3
public/PWD toilet facilities Waste bin w/ black or 3
b. Janitorial services do clean-up activities colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


Patients, relatives and visitors FIXTURE CHECKLIST
Water closet w/ spray hose 10
Lavatory 7
Urinal 4
Slop Sink 1
Shelf, open 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to the Main Lobby
Outlet, 10A, 2P, 240V, single 1 emergency light

56
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE PUBLIC/ PWD TOILETS 250B-AD-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) required Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privac ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit: Visitors/Patients

Fire risk LOW: medium: high

Other risks NA

57
6000 3000

3
1

3000
7 6 3

2200
5 4

3000
2
3

KEY SCALE 1:150 M

1 FEMALE TOILET 4 PWD TOILET

2 MALE TOILET 5 JANITOR'S CLOSET


3 Waste bin 6 Slop sink, with faucet
7 Shelf, open

58
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE STAFF TOILETS 250B-AD-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hospital administrative staff make use of personnel Exhaust Fan 2
toilet facilities Waste bin w/ black or 4
b. Janitorial services do clean-up activities colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


Male and Female Employees FIXTURE CHECKLIST
Water closet w/ spray hose 4
Lavatory 4
Urinal 2
Steel Lockers, 300 x 500mm 18

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Billing and Claims Office Outlet, 10A, 2P, 240V, duplex 4

Outlet, 10A, 2P, 240V, single 2 emergency light


Smoke Detector 2

59
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE STAFF TOILETS 250B-AD-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) applicable Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit: Administrative Staff

Fire risk LOW: medium: high

Other risks NA

60
3000

3000
1
3

3000
4 SD

12000
3
3
5

3000
4 SD

3 2

3000
KEY SCALE 1:150 M

1 MALE TOILET 4 LOCKER ROOM (MALE &


FEMALE)
2 FEMALE TOILET 5 Locker, steel, 300 x 500mm
3 Waste bin

61
SCALE 1:300 M

45000

1600 19400 3000 3000 3000 4100 1900 9000

6000
CHIEF NURSE PANTRY NURSING SERVICES
OFFICE OFFICE
FEMALE MALE
PUBLIC PUBLIC
TOILET TOILET

3000
A U D I T O R I U M

6000
INFECTION LOUNGE
PROCUREMENT LIBRARY
ELECTRICAL CONTROL
DEPT. / COA
ROOM BAC OFFICE OFFICE

ROOF
O P E N B E L O W O P E N B E L O W
GARDEN

6000
INT. HOSPITAL CHIEF OF PUBLIC
CONFERENCE HRD HEAD'S HRD STAFF
LEGAL OPERATIONS & MGT. SECRETARY PANTRY HOSPITAL PANTRY HEALTH FEMALE MALE
ROOM OFFICE OFFICE
OFFICE PROGRAM OFFICE STAFF STAFF
TOILET TOILET

3000
PANTRY
6000
CHIEF OF
BUDGET & FINANCE AO CPMT
BUDGET & OPET SEC CLINICS
ACCOUNTING MANAGER'S OFFICE OFFICE
ACCOUNTING DEPARTMENT OFFICE
HEADS' OFFICE OFFICE

5502 4100 3500 1900 3000 3000 1900 5100 4000 3000 4000

45000

62
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-09A
BUDGET AND ACCOUNTING/
April 2016 ADMINISTRATIVE FINANCE MANAGER'S OFFICE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Processes funding & payments of vouchers, payroll, Computer 13
contract and other financial transactions of the hospital Printer with scanner 1
b. Maintains and ensures that the financial transaction Printer for payroll 1
is in accordance with the generally accepted Tape recorder 1
accounting and auditing rules and regulations Waste bin w/ black or 9
c. Prepares and submits accurate and timely financial colorless lining
statements and reports
d. Maintains book of accounts, equipment and supplies,
and accounts receivables
e. Provides periodic financial analysis

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Transaction counter 1
Desk, 750mmX1200mm 3
Desk, 600mmX1200mm 10
Desk Extensions, 400mmX900mm 3
People Involved: Counter w/ cabinets above & below 1
Chief Accountant Sink, stainless steel 1
Chief Budget Officer Steel filing cabinet 20
Bookkeeper Stool, adjustable height 1
Budget Clerk Visitor's chair 5
Accounting Clerk Junior Executive chair 3
Swivel chair 10
Chair, gang-type 1
2-Seater Sofa 3
Water closet 1
Urinal 1
Lavatory 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Office of the Chief of Hospital Window curtain rail 1
b. Close to Office of the Administrative Officer Outlet, 10A,2P,240V, duplex 28 grounding type
universal
Outlet, 10A, 2P, 240V, single 2 emergency light
Outlet, DATA 13
Outlet, Telephone 6
Smoke Detector 6

63
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-09B
BUDGET AND ACCOUNTING/
April 2016 ADMINISTRATIVE FINANCE MANAGER'S OFFICE

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Accounting & Administrative staff

Fire risk LOW: medium: high

Other risks NA

64
18000
5500 4100 3500 1900 3000

7 14 7 7 11 14 4 D T 10 10 T D
D DT D 5 6 CH
3 9
9 3 9 3 9 3 SD 8 14
2
13 13 SD 7
14 1
7
7 12 7 7 7

6000
7 SD
14 7 SD SD
10
7 7 13 10
2 DT
SD

13
9 3 9 3 9 3 9 3 9 3
9 8 2 8
7 4
D DT D D D D 14 4 D T 10
7 14 7 7 7 14 7 3 7 14

KEY SCALE 1:200 M

1 Counter, transaction 7 Cabinet, filing, 500 x 700mm


2 Desk, 750 x 1200mm 8 Chair, junior executive
3 Desk, 600 x 1200mm 9 Chair, swivel, with casters
4 Desk, extension, 400 x 900mm 10 Chair, visitor
5 Counter, with cabinets above 11 Chair, gang-type
and below 12 Stool, adjustable height
6 Sink, stainless steel 13 Sofa, 2-seater
14 Waste bin

65
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
OFFICE OF THE CHIEF OF
April 2016 ADMINISTRATIVE HOSPITAL 250B-AD-RDS-10A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Chief of Hospital reads, writes and uses telephone in Computer and printer 2
his desk Fax Machine 1
b. Chief of Hospital receives visitors Telephone 1
c. Chief of Hospital stores, files and retrieves records Intercom/ PABX 1
d. COH's secretary reads, writes and uses telephone in Waste bin w/ black or 3 non-biodegradable
her desk colorless lining
e. COH's secretary receives visitors Waste bin w/ green lining 1 biodegradable
f. COH's secretary stores, files and retrieves records
g. Use of toilet facilities

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Executive desk, 900mmX1800mm 1
Desk extension, 400mmX1200mm 1
Desk, 600mmX1200mm 1
Desk extension, 400mmX900mm 1
Executive chair 1
People Involved: Swivel chair 1
1 x Chief of Hospital Visitor's chair 6
1 x Secretary Sofa, two-seater 2
2 x Visitors Side table, 400mmX400mm 3
Cabinet, 400mmX800mm 1
Conference table 1
Conference chair 5
Counter, w/ cabinets above & below 1
Sink, stainless steel 1
Steel filing cabinet 4
Water closet 1
Urinal 1
Lavatory 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to the Office of the Administrative Officer Window curtain rail 4
b. Close to Conference Room Outlet, 10A,2P,240V, duplex 13 grounding type
c. Close to Business and Accounting universal
Outlet, 10A, 2P, 240V, single 3 emergency light
Outlet, DATA 2 wall-mounted
Outlet, Telephone 2 desktop
Smoke Detector 4
Airconditioning Unit 1 window/ split type
Water heater, 6kw 1

66
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
OFFICE OF THE CHIEF OF
April 2016 ADMINISTRATIVE HOSPITAL 250B-AD-RDS-10B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 3.6

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit COH, Hospital & Visitors

Fire risk LOW: medium: high

Other risks NA

67
11000
3000 2000 6000

13 7 7 2 16
D T

2100
13 1 5
16 SD
13
4 12
13 7 7
6
T
9
D 3 15 14

6000
CH

2200
7 SD SD 11
8 SD 16 11
7
11 10
11
11

1700
9 8 9

KEY SCALE 1:150 M

1 Desk, executive, 900 x 1800mm 9 Table, side, 400 x 400mm


2 Desk, extension, 400 x 1200mm 10 Table, conference
3 Desk, 600 x 1200mm 11 Chair, conference
4 Desk, extension, 400 x 900mm 12 Cabinet, 400 x 1800mm
5 Chair, executive 13 Cabinet, filing 500 x 700mm
6 Chair, swivel, with casters 14 Counter, with cabinets above
7 Chair, visitor and below
8 Sofa, two-seater 15 Sink, stainless steel
16 Waste bin

68
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
INTEGRATED HOSPITAL OPERATIONS &
April 2016 ADMINISTRATIVE MANAGEMENT PROGRAM (IHOMP) 250B-AD-RDS-11A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. System Administrator prepares program, enhances system,Database Server 2
builds libraries of diseases, drugs and medicines Computers 2
hospital staff, personnel directories of doctors and UPS (Uninterrupted Power Supply) 3
specialists AVR (Automatic Voltage Regulator) 2
Printers 1
Airconditioning Unit 1 hp stand-by ACU
Electric fan 1
Hub 1
Waste bin w/ black or 3
colorless lining

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Desk, 600mmX1200mm 5
People Involved: Desk Extensions, 400mmX900mm 5
Information Technologist Clerical Chair 5
Computer Engineer Visitor's Chair 2
Systems Administrator Cabinet 450mmX1500mm 2
Server Cabinet, 1000mmX1000mm 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near or adjacent to the Chief of Hospital's Office Window curtain rail 2
b. Close to other Executive Offices (Administrative Service) Outlet, 10A,2P,240V, duplex 10 grounding type
universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1 desktop
Smoke Detector 1
Airconditioning Unit 1 window/ split type

69
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE IHOMP 250B-AD-RDS-11B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.8

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Systems Administrator Maximum temperature (°C) NA

Access limit IHOMP Staff/ Visitors

Fire risk LOW: medium: high

Other risks NA

70
6000

7 2 2 5
3 1 3 1

7
2
3
2
1 3
1

6000
SD
5 4
4

6 3 1
7 DT
2

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 5 Cabinet, with shelves,


2 Desk extension, 400 x 900mm 450 x 1500mm
3 Chair, clerical 6 Server, 1000 x 1000mm
4 Chair, visitor 7 Waste bin

71
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE CONFERENCE ROOM 250B-AD-RDS-12A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hospital staff/ Hospital Services Personnel & Visitors White board 1
hold meetings and special lectures Glass board 1
LCD Screen 1
Opaque Projector 1
Microphone 1
Sound System 1 set
Voice Recorder 1
Waste bin w/ black or 1
colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


Hospital Staff FIXTURE CHECKLIST
Hospital Services Personnel Conference table, 500mmX1500mm 6
Visitors Cabinet, 400mmX1800mm 1
Conference chair 12

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to the Office of the Administrative Officer Outlet, 10A,2P,240V, duplex 6 grounding type
b. Close to Office of the Chief of Hospital universal
c. Close to Office of the Chief Nurse Outlet, 10A, 2P, 240V, single 1 emergency light
d. Close to the Office of the Chief of Clinics Outlet, Laptop 1 floor type
Smoke Detector 1

72
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE CONFERENCE ROOM 250B-AD-RDS-12B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 70 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 5

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Hospital Staff, clients & visiotrs

Fire risk low: medium:HIGH

Other risks NA

73
3600

3 3 2
4 1
5
3 3
1 1
3 FO 3

6000
SD
3 3
1 1
3 3

1
3 3
2

KEY SCALE 1:100 M

1 Table, conference, 500 x 1500mm


2 Cabinet, 400 x 1800mm
3 Chair, conference
4 Whiteboard
5 Waste bin

74
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
OFFICE OF THE
April 2016 ADMINISTRATIVE ADMINISTRATIVE OFFICER 250B-AD-RDS-13A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Administrative Officer reads, writes and uses telephone in Computer and printer 1
his desk Printer w/ scanner 1
b. Administrative Officer receives visitors Calculating machine 1
c. Administrative Officer plans, directs, controls and Telephone 1
organizers workplace system Intercom/ PABX 1
d. Clerk acts as secretary, prepares plans and schedule Waste bin w/ black or 2
of CAO colorless lining
e. Clerk stores, files and retrieves records Airconditioning unit 1
f. Clerk updates records Electric fan 1
g. Use toilet facilities

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Desk, 750mmx1200mm 1
Desk extension, 400mmX1800mm 1
People Involved: Junior executive chair 1
1 x Hospital Administrative Officer Visitor's chair 2
1 x Clerk Sofa, two-seater 1
Visitor/s
Steel filing cabinet 3
Cabinet, 400mmX1200mm 1
Counter w/ cabinets above & below 1
Sink, stainless steel 1
Water Closet 1
Urinal 1
Lavatory 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Budget and Accounting office Window curtain rail 2
b. Close to Office of the Chief of Hospital Outlet, 10A,2P,240V, duplex 8 grounding type
c. Close to Human Resource Development & universal
Property and Supply Outlet, 10A, 2P, 240V, single 1 emergency light
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1 desktop
Smoke Detector 2
Airconditioning Unit 1 window/ split type

75
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-13B
OFFICE OF THE
April 2016 ADMINISTRATIVE ADMINISTRATIVE OFFICER
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70


Administrative Officer, Hospital
Access limit
staff and visitors
Fire risk LOW: medium: high

Other risks NA

76
4900
3000 1900

6 CH 11 10
12
1 9

3900
5 SD

5
T

6000
D 2 SD

4 8
3

12 7

2100
7
7

KEY SCALE 1:100 M

1 AO OFFICE 9 PANTRY
2 Desk, 750 x 1200mm 10 Counter, with cabinet above
3 Desk, extension, 400 x 1800mm and below
4 Chair, junior executive 11 Sink, stainless steel
5 Chair, visitor 12 Waste bin
6 Sofa, two-seater
7 Cabinet, filing, 500 x 700mm 13 TOILET
8 Cabinet, with shelves,
400 x 1200mm

77
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE OFFICE OF THE CHIEF OF CLINICS 250B-AD-RDS-14A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Chief of Clinics reads and writes in his work station Computer 2
b. Chief of Clinics receives visitors Printer w/ scanner 1
c. Chief of Clinics stores, files and retrieves records Airconditioning unit 1
d. Clerk receives visitors Telephone/ Intercom 1
e. Clerk stores, files and retrieves records Waste bin w/ black or 2
f. Clerk updates records colorless lining
g. Use of toilet facilities

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Desk, 900mmX1500mm 1
Desk, 600mmX1200mm 1
Desk extension, 400mmX900mm 1
Junior executive chair 1
Clerical chair 1
People Involved: Visitor's chair 4
1 x Chief of Clinics Single-seater sofa 1
1 x Clerk Two-seater sofa 2
Visitors Side table, 400mmX400mm 2
Cabinet, 400mmX900mm 1
Steel filing cabinet 3
Lavatory 1
Water Closet 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to the Office of the Chief of Hospital Window curtain rail 2
Outlet, 10A,2P,240V, duplex 11 grounding type
universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Outlet, DATA 2
Outlet, Telephone 2
Smoke Detector 2

78
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-14B
OFFICE OF THE CHIEF OF
April 2016 ADMINISTRATIVE CLINICS
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit COC, Hospital & Visitors

Fire risk LOW: medium: high

Other risks NA

79
7000
3000 1500 2500

9 7 11 11 11

1900
8

6000
SD SD
6
4100 6 1 4
9
6 T
T 6 D
D
2 8 12
5
3 10
12

KEY SCALE 1:100 M

1 Desk, 900 x 1500mm 7 Sofa, single-seater


2 Desk, 600 x 1200mm 8 Sofa, two-seater
3 Desk, extension, 400 x 900mm 9 Table, side, 400 x 400mm
4 Chair, junior executive 10 Cabinet, with shelves,
5 Chair, clerical 400 x 900mm
6 Chair, visitor 11 Cabinet, filing, 500 x 700mm
12 Waste bin

80
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-15A
HUMAN RESOURCE
April 2016 ADMINISTRATIVE DEVELOPMENT OFFICE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Prepares comprehensive manpower development Computer 3
program from selection to separation Printer with scanner 1
b. Maintains and ensures the confidentiality of personnel Printer for payroll 1
records Telephone 1
c. Prepares payroll and other personnel records per Intercom/ PABX 1
employee Copier 1
d. Acts on personnel actions and transactions Waste bin w/ black or 4
e. Acts as secretary of the hospital training committee, PSB colorless lining
and Accreditation committee

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Transaction Counter 1
Desk, 750mmX1200mm 1
Desk, 600mmX1200mm 11
Desk Extensions, 400mmX900mm 1
Shelves, wall-mounted 1
People Involved: Steel filing cabinet 15
Personnel Officer Side table 1
10 x Administrative Clerks Visitor's chair 5
Applicants/ Employees Junior Executive chair 1
Swivel chair 11
Chair, Visitor 2
Chair, gang-type 1
2-Seater Sofa 1
Counter, w/ cabinets above & below 1
Sink, stainless steel 1
Stool, adjustable height 1
Water closet 1
Lavatory 1
Urinal 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Lobby within the Administrative Window curtain rail 1
Service Office Outlet, 10A,2P,240V, duplex 25 grounding type
universal
Outlet, 10A, 240V, single 2 emergency light
Outlet, DATA 11 wall-mounted
Outlet, Telephone 2 desktop
Smoke Detector 5
Airconditioning Unit 1 window/ split type

81
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-15B
HUMAN RESOURCE
April 2016 ADMINISTRATIVE DEVELOPMENT OFFICE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Personnel Staff

Fire risk LOW: medium: high

Other risks NA

82
15000
3000 1900 10100

7 3 D 7D T 7D 7D 7D
T 15
7D 7D

2100
15 7 15
9
7 3 9 3 9 3 9 3 9 3 9 3 9

3600
4
T 8 SD

D 2 15

6000
7
10 SD SD
7 7 12
10 7

3900
1
SD
15 15
3 9

2400
3 9 3 9 SD SD
9 14
13 5 CH 6 3 D7D 7
D
11

KEY SCALE 1:200 M

1 Counter, transaction 8 Chair, junior executive


2 Desk, 750 x 1200mm 9 Chair, swivel, with casters
3 Desk, 600 x 1200mm 10 Chair, visitor
4 Desk, extension, 400 x 900mm 11 Chair, gang-type
5 Counter, with cabinets above 12 Stool, adjustable height
and below 13 Sofa, 2-seater
6 Sink, stainless steel 14 Shelf, open
7 Cabinet, filing, 500 x 700mm 15 Waste bin

83
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE OFFICE OF THE CHIEF NURSE 250B-AD-RDS-16A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Chief Nurse reads, writes and uses telephone in his desk Computer 1
b. Chief Nurse receives visitors Calculating Machine 1
c. Chief Nurse stores, files and retrieves records Whiteboard/Glassboard 1
d. Clerk receives visitors Waste bin w/ black or 5
e. Clerk stores, files and retrieves records colorless lining
f. Clerk updates records
g. Use of toilet facilities

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Desk, 750mmX1200mm 1
Desk, 600mmX1200mm 8
Desk Extensions, 400mmX900mm 1
Counter w/ cabinets above and below 1
Sink, Stainless steel 1
People Involved: Steel filing cabinet 11
1 x Chief Nurse Side table 1
8 x Clerks Visitor's chair 4
Visitors Junior Executive chair 1
Swivel chair 8
Cabinet, 300mmX900mm 1
2-Seater Sofa 1
Water Closet 1
Urinal 1
Lavatory 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to the Office of the Chief of Hospital Window curtain rail 5
Outlet, 10A,2P,240V, duplex 17 grounding type
universal
Outlet, 10A, 2P, 240V, single 2 emergency light
Outlet, DATA 9 wall-mounted
Outlet, Telephone 3 desktop
Smoke Detector 4
Airconditioning Unit 1 Window/ Split type

84
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-AD-RDS-16B
OFFICE OF THE CHIEF
April 2016 ADMINISTRATIVE NURSE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.8

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit CN, Hospital & Visitors

Fire risk LOW: medium: high

Other risks NA

85
15000
4100 1900 9000

7 13
DT
7 13 D
7 1111 1111 7 D 13 7 D

2100
13 7 10 2 10 2 2 10 2 10
3 7
9
T
1

6000
D 8
11 11 SD SD SD

11 11 8

3900
SD

13 10 2 10 2 2 10 2 10
12 6 CH DT D D D
4 5 7 13 7 7 13 7

KEY SCALE 1:200 M

1 Desk, 750 x 1200mm 7 Cabinet, filing, 500 x 700mm


2 Desk, 600 x 1200mm 8 Cabinet, with shelves,
3 Desk, extension, 400 x 900mm 300 x 900mm
4 Counter, with cabinets above 9 Chair, junior executive
and below 10 Chair, swivel, with casters
5 Sink, stainless steel 11 Chair, visitor
6 Table, side, 400 x 400mm 12 Sofa, 2-seater
13 Waste bin

86
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE AUDITING OFFICE 250B-AD-RDS-17A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Commission on Audit personnel reads, writes and Computer 5
uses telephone in his work Printer 1
b. Commision on Audit personnel receives visitors Calculating machine 1
c. Commission on Audit personnel stores, and retrieves Waste bin w/ black or 3
records colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


1 x COA Auditor FIXTURE CHECKLIST
1 x Clerk Desk, 750mmX1200mm 1
10 x Visitors Desk, 600mmX1200mm 4
Desk Extensions, 400mmX900mm 2
Conference table 1
Steel filing cabinet 4
Chair, upright, stacking 5
Visitor's chair 5
Conference chair 6

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Budget and Accounting Office Window curtain rail 2
b. Close to Office of the Administrative Officer Outlet, 10A,2P,240V, duplex 12 grounding type
universal
Outlet, 10A, 2P, 240V, single 2 emergency light
Outlet, DATA 5
Outlet, Telephone 2
Smoke Detector 3

87
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE AUDITING OFFICE 250B-AD-RDS-17B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.8

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit COA staff

Fire risk LOW: medium: high

Other risks NA

88
6000
2300 3700

7 8 8
7

2500
D 8 SD 4 8
2
6 8 8

6000
D SD
2 7
6 7
7 1 D

3500
T
D D SD
2 2 T
6
6 6 3
3
5 5 5 5 9

KEY SCALE 1:100 M

1 Desk, 750 x 1200mm 6 Chair, upright, stacking


2 Desk, 600 x 1200mm 7 Chair, visitor
3 Desk extension, 400 x 900mm 8 Chair, conference
4 Table, conference 9 Waste bin
5 Cabinet, steel, filing

89
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE LIBRARY 250B-AD-RDS-18A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hospital staff and affiliates make use of the Computer 4
library and its amenities Printer 1

People Involved: FURNITURE AND QUANTITY REMARKS


Hospital staff FIXTURE CHECKLIST
Medical staff Counter 1
Affiliates Desk 2
Cart, book 1
Cart, for computer & printer 1
Shelf, for books 10
Rack, for magazines etc. 2
Chair, swivel 2
Chair, upright 4
Stool, adjustable 2
Study desk/carrel 4
Waste bin 3

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near offices (not public)
Outlet, 10A,2P,240V, duplex 12 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light

90
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE LIBRARY 250B-AD-RDS-18B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.5 - 3

SOUND SAFETY

Acceptable sound level (db) 30 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit none

Fire risk low: MEDIUM : high

Other risks NA

91
8000

13 4 4 13

10

5
4 4
12
13 4 4

6000
12 SD
1 4 4
2 10 4 4

3
9 11 11 11 11
6
9 8 8 8 8

KEY SCALE 1:100 M

1 Counter, 1000mm high 8 Study desk/carrel


2 Desk, 600 x 1200mm 9 Periodical/magazine rack
3 Cabinet, filing, 500 x 700mm 10 Chair, swivel, with casters
4 Shelf, 400 x 1600mm, open 11 Chair, upright, stacking
5 Shelf, 300mm deep, overhead 12 Stool, adjustable height
6 Cart, book 13 Waste bin
7 Table, with computer and printer

92
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE STAFF LOUNGE 250B-AD-RDS-19A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hospital Administrative Staff makes use of the pantry Refrigerator 1
b. Hospital Administrative Staff do clean-up activities Water Dispenser 1
Waste bin w/ black or 2
colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


Male and Female Employees FIXTURE CHECKLIST
Dining table, 6-seater 1
Dining chairs 6
Sofa, two-seater 1
Counter w/cabinets above & below 1
Sink, stainless steel 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accessible to Administrative Offices Window curtain rail 1
Outlet, 10A, 2P, 240V, duplex 7 grounding type
universal
Outlet, 10A, 2P, 240V, single 1 emergency light

Smoke Detector 1

93
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE STAFF LOUNGE 250B-AD-RDS-19B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit Administrative Staff

Fire risk LOW: medium: high

Other risks NA

94
3000

2 1 2

6000
SD
2 2

8
7 9
4 5 CH 6

KEY SCALE 1:100 M

1 Table, dining, 6-seater 6 Refrigerator


2 Chair, dining 7 Water dispenser, hot and cold
3 Sofa, two-seater 8 Waste bin
4 Counter, with cabinets above 9 Concealed floor drain
and below
5 Sink, stainless steel

95
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:

April 2016 ADMINISTRATIVE PUBLIC TOILETS 250B-AD-RDS-20A


FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hospital patients, relatives and visitors make use of Exhaust Fan 2
public/PWD toilet facilities Waste bin w/ black or 2
b. Janitorial services do clean-up activities colorless lining

People Involved: FURNITURE AND QUANTITY REMARKS


Patients, relatives and visitors FIXTURE CHECKLIST
Water closet w/ spray hose 5
Lavatory 4
Urinal 2
Slop sink w/ faucet 2
Floor strainer 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accesible to all Administrative Offices
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 2

96
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE PUBLIC TOILETS 250B-AD-RDS-20B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 85 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit: Visitors/ Patients

Fire risk LOW: medium: high

Other risks NA

97
3000 3000

2 2

6000
3
1 4
3

KEY SCALE 1:100 M

1 FEMALE TOILET
2 Slop sink
3 Waste bin
4 MALE TOILET

98
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE OFFICE (TYPICAL) 250B-AD-RDS-21A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hospital office workers read, write and use Computer 3-5
telephone and/or computer in their work stations Printer 2-3
b. Performance of clerical, filing and office work ACU 1
c. Use of office equipment Telephone 1-3
d. Office worker attends to visitor/client , patient Waste bin 2 with black lining
and/or other hospital office worker/medical staff Note:
1) provide other equipment and accessories necessary to
specific office type
2) number of equipment and accessories depend on requirement
and not necessarily 1:1 ratio per staff
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Desk, 600 x 1200mm 5
Chair, swivel 5
Chair, visitor 2
Cabinet, steel, filing 2
People Involved: Note:
5 x Hospital office workers 1) provide other furniture and fixture necessary to
2 x Visitors specific office type
2) number of furniture and fixture depend on requirement
and not necessarily 1:1 ratio per staff
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, data 7
Planning Relationships: Outlet, telephone 4
a. May be close to or adjacent to hospital area being Smoke detector 1
served Cubicle curtain rail 1
b. May be grouped with other administrative offices Note:
1) provide additional equipment and engineering terminals
necessary to specific office type
2) number of additional equipment and engineering terminals
depend on requirement and not necessarily 1:1 ratio per staff

99
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE OFFICE (TYPICAL) 250B-AD-RDS-21B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.75

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit office staff, patients, visitors

Fire risk LOW: medium : high

Other risks NA

100
3000

4
4
T
1 D
2 3
2

6000
SD
T
1 1 D
3
T 3
D

5
1 1
3 3
TD D
5

KEY

1 Desk, 600 x 1200mm


2 Cabinet, filing; 500 x 700mm
3 Chair, swivel; with casters
4 Chair, visitor
5 Waste bin

101
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE BAC OFFICE 250B-AD-RDS-22A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Procurement Department - Bids and Awards Computer 3-5
Committee (BAC) office workers read, write and use Printer 2-3
telephone and/or computer in their work stations ACU 1
b. Performance of clerical, filing and office work Telephone 1-3
c. Use of office equipment Waste bin 2 with black lining
d. Office worker attends to bidder/visitor/client Note:
and/or other hospital office worker/medical staff 1) provide other equipment and accessories as required by
BAC end-user
2) number of equipment and accessories depend on requirement
and not necessarily 1:1 ratio per staff
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Desk, 600 x 1200mm 5
Chair, swivel 5
Chair, visitor 2
Cabinet, steel, filing 2
People Involved: Note:
5 x BAC office workers 1) provide other furniture and fixture as required by
5 x Visitors BAC end-user
2) number of furniture and fixture depend on requirement
and not necessarily 1:1 ratio per staff
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, data 7
Planning Relationships: Outlet, telephone 4
a. May be grouped with other administrative offices Smoke detector 1
Cubicle curtain rail 1
Note:
1) provide additional equipment and engineering terminals
as required by BAC end-user
2) number of additional equipment and engineering terminals
depend on requirement and not necessarily 1:1 ratio per staff

102
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 ADMINISTRATIVE BAC OFFICE 250B-AD-RDS-22B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.75

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit office staff, visitors

Fire risk LOW: medium : high

Other risks NA

103
4000

5 9
8
SD
10

1
2
6
T 4
D

6000
2
3
4
D SD 3

7
2 2 2
4 4 4
TD D D
7

KEY

1 Counter, transaction, with glass 7 Waste bin


front panel 8 Door, glass; with full windows
2 Desk, 600 x 1200mm 9 Window, glass
3 Cabinet, filing; 500 x 700mm 10 Waiting area
4 Chair, swivel; with casters
5 Chair, 5-seater gang style
6 Stool, adjustable height

104
SCALE 1:300 M

15800

3000 3800 3000 6000

2300
FT MT STAFF
PANTRY
3700

LOCKERS DUMB
WAITER
JAN UP
CLO
2100

15000
WAITING AREA
4400

STAFF
ADMIN COMPLETION OFFICE
RECORDS ROOM
2500

HEAD'S RECEIVING/
OFFICE RELEASING

4900 4100 6000 6000

21000

36000

27000 3000 6000


6000

RECORDS
DUMB ROOM
WAITER
DN
15000

F I L E S
S T O R A G E A R E A
9000

105
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
WAITING AREA 250B-HIMS-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Visitors wait for receiving and issuance of medical/ Emergency light 1
medico-legal certificates, birth and death certificates Queuing numbering system 1
Waste bin - black or colorless 1
lining

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Chair, gang-type, waiting 3 4-seater
People Involved: 3 5-seater
Client / Visitor 3 7-seater

Planning Relationships:
a. Adjacent to Administrative Department
b. Accessible to Out Patient Department ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
c. Accessible to Receiving/Releasing Area ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 2

106
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
WAITING AREA 250-HIMS-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 70 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 5

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit HIMS staff, clients, and visitors

Fire risk LOW: medium: high

Other risks NA

107
6000

2 2 2

SD

1 1 1

15000
3 3 3

SD

KEY SCALE 1: 200 M

1 Chair, gang-type, 4-seater


2 Chair, gang-type, 5-seater
3 Chair, gang-type, 7-seater

108
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION STAFF OFFICE &
April 2016
MANAGEMENT SYSTEMS RELEASING/ RECEIVING 250B-HIMS-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. HIMS staff and other authorized users conduct Computer 1 w/ printer & scanner
medical studies, read, write, and retrieve Calculator 1
records Photocopier machine 1
b. Processing and filing of OPD, ER, and OR records Risograph machine 1
c. Transcription of birth and death certificates Emergency light 1
d. HIMS staff assemble/input inpatient charts Facsimile machine 1
and updated death registry UPS and AVR 1
e. Receiving and issuance of medical/medico- Waste bin - black or colorless 1
legal certificates, birth and death certificates lining
PA & BGM system 1
Airconditioning unit 1 window/split type
LCD optional
Electric typewriter 1
People Involved: Paper shredder 1
1 x Statistician
1 x Data Controller
2 x HIMS Clerks FURNITURE AND
QUANTITY REMARKS
Researchers / Doctors FIXTURE CHECKLIST
Desk, 600 x 1200mm 12
Chair, clerical 12
Counter, transaction 1
Cabinet, steel, filing 5
Stool, adjustable 3

Planning Relationships: ADDITIONAL EQUIPMENT & REMARKS


QUANTITY
a. Accessible to Filing Area ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 15 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Smoke detector 1
Outlet, airconditioning unit window/split type
Window curtain rail 1

109
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION STAFF OFFICE &
April 2016
MANAGEMENT SYSTEMS RELEASING/ RECEIVING
250-HIMS-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 70 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit researchers/doctors, HIMS staff

Fire risk low: medium: HIGH

Other risks NA

110
6000

SD

3
FO
2
3 2 2 3
2
FO
6
FO 3
3 2 2 3
3

9000
FO
2T
SD 2
7
FO 3
3 2 2 3
FO 4
FO
3 3 CH
2 2
4
FO 1
CH
4
5 5 5 8 9 5 5

KEY SCALE 1:150 M

1 Counter, transaction 6 Photocopier machine


2 Desk, 600 x 1200mm 7 Risograph machine
3 Chair, clerical 8 Paper shredder
4 Stool, adjustable 9 Waste bin
5 Cabinet, filing, 500 x 700mm

111
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
COMPLETION AREA 250B-HIMS-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Researchers / Doctors and other authorized users Computer 1 w/ printer & scanner

discuss and finalize pertinent papers/documents Whiteboard, 1200 x 2400mm 1


related to medical records as requested by Airconditioning unit 1 window type
patients/relatives Waste bin - black or colorless 1
b. HIMS officer assists researchers/doctors by lining
providing data on specific research topics
c. Researchers/Doctors protect confidentiality of
medical records

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x HIMS Officer (Administrative Officer V) FIXTURE CHECKLIST
1 x Clinical Coder (Administrative Officer IV) Table, conference 1
Researchers / Doctors Chair, conference 6
Counter, 900mm high 2
w/ shelves below

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Staff Office ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Outlet, data 1
Smoke detector 1
Outlet, airconditioning unit 1 window/split type
Window curtain rail 2

112
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
COMPLETION AREA 250-HIMS-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.6

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit researchers/doctors, medical

records staff & authorized users

Fire risk low: medium: HIGH

Other risks NA

113
4100

2 2
4

4400
2 1 2
SD

2 2

CH
3 3 DT

KEY SCALE 1:100 M

1 Table, conference
2 Chair, conference
3 Counter, 900mm high, with
shelves below
4 White board, 1200 x 2400mm
5 Waste bin

114
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
HEAD'S OFFICE 250B-HIMS-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Health Information Management (HIM) Officer reads, Computer 1 w/ printer & scanner

transcribes, and updates disease and operation Calculating machine 1


coding and indexing Airconditioning unit 1 window type
b. HIM Officer prepares communications and other Telephone 1
pertinent papers related to medical records as Intercom 1
requested by patients Whiteboard 1
c. HIM Officer protects confidentiality of medical records Waste bin - black or colorless 1
d. HIM Officer performs statistical and other reports lining
required by DOH and other institutions
e. HIM Officer performs qualitative and quantitative
analysis of hospital health records

FURNITURE AND
QUANTITY REMARKS
People Involved: FIXTURE CHECKLIST
1 x HIMS Officer (Administrative Officer V) Desk, 750 x 1200mm 1
Researchers Desk extension, 400 x 850mm 1
Clients/Visitors Cabinet, filing, 500 x 700mm 2
Chair, junior executive 1
Chair, visitor 2
Sofa, two-seater 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Staff Office ENGINEERING TERMINALS
b. Accessible to Receiving/Releasing Area Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Outlet, data 1
Smoke detector 1
Outlet, airconditioning unit 1 window/split type
Window curtain rail 1

115
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
HEAD'S OFFICE 250-HIMS-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.6

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical records staff &

authorized users

Fire risk low: medium: HIGH

Other risks possible termite infestation

116
4100

8 2 T D 5
7 4
1

2500
SD

3 3 6

KEY SCALE 1:100 M

1 Desk, 750 x 1200mm 5 Chair, visitor


2 Desk, extension, 400 x 850mm 6 Sofa, two-seater
3 Cabinet, filing, 500 x 700mm 7 White board
4 Chair, junior executive 8 Waste bin

117
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
ADMIN RECORDS 250B-HIMS-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. HIMS staff stores/files administative records Calculator 1
for easy access PA & BGM system 1
b. HIMS staff retrieves records on file Exhaust fan 2

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
People Involved: Shelving, steel, open 8
HIMS staff Cabinet, with shelves 2
Researchers / Doctors Ladder, aluminum or wooden 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Staff Office ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 2
Water sprinkler system
Window curtain rail 3

118
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
ADMIN RECORDS 250-HIMS-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit authorized HIMS staff

Fire risk low: medium: HIGH

Other risks possible termite infestation

119
4900

1
1

SD

1
1

13500
1
1

SD

1
1

3
2

KEY SCALE 1:150 M

1 Shelving, steel, open


2 Cabinet, with shelves
3 Ladder, movable

Note : provide 1000mm clear distance from


ceiling to topmost shelf

120
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
RECORDS ROOM 250B-HIMS-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. HIMS staff stores/files OPD, ER, and OR/DR records, Calculator 1
birth and death certificates for easy access PA & BGM system 1
b. HIMS staff retrieves records on file for request/ Exhaust fan 2
follow-up of patients/relatives and researchers/
doctors and refiles them
c. HIMS staff records individual charts by patient's
data for complete inventory control

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
People Involved: Shelving, steel, open 4
HIMS staff Cabinet, with shelves 2
Researchers / Doctors Ladder, aluminum or wooden 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Accessible to Staff Office ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 8 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1
Water sprinkler system
Window curtain rail 1

121
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
RECORDS ROOM 250-HIMS-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit authorized HIMS staff

Fire risk low: medium: HIGH

Other risks possible termite infestation

122
6000

6000
2 SD

1 1 1 1 2

KEY SCALE 1:100 M

1 Shelving, steel, open


2 Cabinet, with shelves
3 Ladder, movable

Note : provide 1000mm clear distance from


ceiling to topmost shelf

123
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
FILES STORAGE AREA 250B-HIMS-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of inactive files that have passed the
ten- to thirty-year filing period PA & BGM system 1
b. Storage of files to ensure protection from fire, Exhaust fan 3
flood and theft
c. Periodic evaluation of inactive health
records/files
d. To keep medical records accessible as many
years as possible

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
People Involved: Shelving, steel, open 102
HIMS staff Ladder, aluminum or wooden 5

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to HIMS Department ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 14 grounding type,
universal slots
Outlet, 10A,2P,240V, single 3 emergency light
Smoke detector 7
Water sprinkler system

124
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION
April 2016
MANAGEMENT SYSTEMS
FILES STORAGE AREA 250-HIMS-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit authorized HIMS staff

Fire risk low: medium: HIGH

Other risks possible rodents and termite

infestation; moisture

125
27000

2 2

6000
1
1 1 SD1 1 1 1 1 SD1 1 1 1 1 SD1
1
DN

15000
2
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1

SD SD SD SD

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2 2

36000

KEY SCALE 1:400 M

1 Shelving, steel, open


2 Ladder, movable

Note : provide 1000mm clear distance from


ceiling to topmost shelf

126
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION STAFF PANTRY, LOCKERS
April 2016
MANAGEMENT SYSTEMS AND TOILETS
250B-HIMS-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Lounging area for HIMS staff Refrigerator 1
b. HIMS staff stores personal belongings Water dispenser 1
c. HIMS staff uses toilet facilities Waste bin 1

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Table, dining 1
Chair, dining 4
Counter, with cabinets above 1
and below
People Involved: Sink, stainless steel 1
HIMS staff Concealed floor drain 1
Locker, steel, 300 x 500 mm 7
Slop sink with faucet 1
Shelf, open 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to HIMS Department ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 3
Water sprinkler system

127
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH INFORMATION STAFF PANTRY, LOCKERS
April 2016
MANAGEMENT SYSTEMS AND TOILETS 250-HIMS-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Cooling load (TR) NA Black out essential:desirable:UNNECESSARY

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Emergency Staff

Fire risk LOW: medium : high

Other risks NA

128
6800

1500 1500 3800

9 9 8

3 3 5

2300
15 9 16
CH
2 SD
4
3 3
7

4750
1
6
6000
2100 SD

11
10
12
1600

13 SD

14

KEY SCALE 1:100 M

1 STAFF PANTRY 10 LOCKERS


2 Table, dining 11 Locker, steel, 300 x 500 mm
3 Chair, dining
4 Counter, with cabinets above 12 JANITOR'S CLOSET
and below 13 Slop sink with faucet
5 Sink, stainless steel 14 Shelf, open
6 Refrigerator
7 Water dispenser 15 FEMALE TOILET
8 Concealed floor drain
9 Waste bin 16 MALE TOILET

129
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.2 EMERGENCY SERVICE FACILITIES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

131
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 EMERGENCY 250B-ER-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
EMERGENCY 566.00 250B-ER-DDS-01 134
Waiting Area & Triage 138.00 250B-ER-RDS-01 135
Decontamination Room 19.00 250B-ER-RDS-02 138
Resuscitation Bay 41.00 250B-ER-RDS-03 141
Respiratory Unit 16.00 250B-ER-RDS-04 144
Staff Pantry/Lockers, T&B 38.00 250B-ER-RDS-05 147
Isolation Room 20.00 250B-ER-RDS-06 150
VAWC Room 23.00 250B-ER-RDS-07 153
Treatment Cubicle (PEDIA) 10.00 250B-ER-RDS-08 156
Treatment Cubicle (MEDICAL) 10.00 250B-ER-RDS-09 159
Treatment Cubicle (OB-GYNE) 10.00 250B-ER-RDS-10 162
Treatment Cubicle (SURGERY) 10.00 250B-ER-RDS-11 165
Nurse Station 21.00 250B-ER-RDS-12 168
Delivery Room 24.00 250B-ER-RDS-13 171
Scrub-Up / Sub-Sterile 9.00 250B-ER-RDS-14 174
Minor Operating Room 31.00 250B-ER-RDS-15 177
HEM Office and Supply Room 44.00 250B-ER-RDS-16 180
ER Head Office 28.00 250B-ER-RDS-17 183
Doctors' On Call Room 36.00 250B-ER-RDS-18 186
Ambulatory Care 29.00 250B-ER-RDS-19 189
Observation Bay 9.00 250B-ER-RDS-20 192

133
SCALE 1:400 M
51000

3000 2100 18900 3000 2600 2100 2100 4000 4300 5900 3000

CLEAN WASTE
4300

LINEN HOLDING DOCTORS'


ROOM
ROOM SUP EQPT AFFILIATES' CONF

6000
MT ON-CALL
STO ROOM ROOM
DIRTY RM ROOM
ROOM
LINEN
UP

UP
3000

FT ROOM
OBSERVATION BAY

3000
NURSE
STATION
4500

STAFF
HEMS PANTRY

6000
AMBULATORY ER HEAD HEMS OPCEN /
CARE OFFICE OFFICE SUPPLY
3200

ELECTRICAL
DIRTY ROOM
ROOM STAFF
T JANLINEN
CLO
5000
36000

OPERATING

6000
NURSE
ROOM
OPEN COURT STATION OPEN COURT
2000

6000
5900

SURGICAL MEDICINE

3000
2100

UP
UP

UP
OB-GYNE PEDIA
6000

6000
DELIVERY ISOLATION VAWC
ROOM ROOM ROOM

EQPT
STORAGE
6000

ROOM
13900 3300 3800 3000
UP

3000
3100
5100

RESPIRATORY
UNIT
8100

RESCUSCITATION
BAY
4100
33000

SUPPLY
ROOM

TRIAGE
4100

RECORDS
ROOM
12800

WAITING
7500

AREA

DECONTAMINATION
3100

3100

ROOM

3000 3000 6000

12000

134
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY WAITING AREA & TRIAGE 250B-ER-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot Sphygmomanometer/ Stethoscope 1
b. Patient may arrive in a wheelchair/ stretcher for Pedia/ Adult
c. Patients arriving at ER are evaluated at the counter Computer 1
d. Patients await their turns to be interviewed and Adult/ Pediatric Scale 1
their cases to be assessed at the triage Spine board 1
e. Transfer of patient to/ from stretcher trolley or Printer 1
wheelchair to examining table Fire Extinguisher 1
Whiteboard 1
Thermometer, digital 1
Wheelchair & stretcher park 1
Waste bin w/ black lining 3

FURNITURE AND QUANTITY REMARKS


People Involved: FIXTURE CHECKLIST
1 x Medical Doctor Counter, 2-level 1
1 x Nurse Counter, 1200mm high; with 1
1 x Nursing Attendant window
2 x Clerks Desk, 500mm x 300mm 1
Chair, swivel 5
Stool, adjustable 1
Chair, gang-type, 3-, 4- & 5-seater 20

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to OPD Waiting Area ENGINEERING TERMINALS
b. Close to entrance to OPD Outlet, 10A,2P,240V, duplex 10 grounding type,
c. Close to the Office of the OPD chief universal slots
d. Close to Consultation Rooms Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 2
Outlet, DATA 1
Outlet, Telephone 1
Window Curtain Rail 2

135
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY WAITING AREA & TRIAGE 250B-ER-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER staff, patients, and visitors

Fire risk LOW: medium: high

Other risks NA

136
9000

8
T D3 7 2
6 4 5
6
4 4

5300
1
SD

6 6 6
6 6

8 6 6
7500
SD 6 SD 6

6 6 6

6 6 6
9

6 6

12000

KEY SCALE 1:200 M

1 Counter, 2-level 7 Whiteboard


2 Counter, 1200mm high; with 8 Waste bin
window 9 Wheelchair & stretcher park
3 Desk, with computer and printer
4 Chair, swivel
5 Stool, adjustable
6 Chair, gang-type, 3-, 4- & 5-seater

137
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY DECONTAMINATION ROOM 250B-ER-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Ambulatory patient may arrive Exhaust fan 1
b. Patient may arrive on wheelchair/ stretcher Electric fan 1
c. Patient is decontaminated with chemical solutions Airconditioning unit 1
d. Patient undergoes screening for possible or suspected Thermometer 1
with any biological or chemical contamintion Sphygmomanometer 1
Weighing scale 1
Stethoscope 1
IV stand 1
Suction machine 1
Gooseneck lamp 1
Linen Hamper 1
People Involved: Stretcher 1
1 x Resident Physician Waste bin 1
Patient

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Water closet w/ spray hose 1
Lavatory 1
Shower 1
Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to ambulance or emergency vehicle drop-off ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1

138
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
DECONTAMINATION
April 2016 EMERGENCY ROOM 250B-ER-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit ER staff and patient

Fire risk low:MEDIUM:high

Other risks NA

139
6000

TD

3100
SD 4
2 6
1
3 5

KEY SCALE 1:100 M

1 Stretcher

2 DRESS CUBICLE

3 Hamper, soiled linen


4 Cubicle curtain and rod
5 Waste bin

6 TOILET WITH SHOWER

140
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY RESUSCITATION BAY 250B-ER-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot Defibrillator 1
b. Patient may arrive on wheelchair/ stretcher E-cart w/ complete emergency 1
c. Use of diagnostic equipment medicines
ECG or cardiac monitor 1
Pulse oxymeter 1
Sphygmomanometer 1
Stethoscope 1
Thermometer, digital 1
Suction machine 1
Cardiac board 1
IV stand w/ IV fluid 1
People Involved: Laryngoscope w/ endotracheal tube 1
1 x Resident Physician Indwelling poly catheter 1
1 x Patient Bag valve mask or respirator 1
1 x Nurse Nebulizer 1
1 x Nursing Attendant Waste bin 1
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Examination table 1
Table, instrument 1
Resuscitating apparatus 1
Counter, with cabinets below 1
Sink, stainless steel 1
Examination light 1
Medical gas console 1
Cubicle curtain and rod 1
Concealed floor drain 1
Portable X-Ray Machine 1
Planning Relationships ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
a. Close to Emergency suite entrance ENGINEERING TERMINALS
b. Adjacent to Nurse Station and Minor Operating room Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1
Outlet, Aircon 1
Outlet for various equipment

141
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY RESUSCITATION BAY 250B-ER-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patients

Fire risk LOW:medium:high

Other risks NA

142
5050

11 3
4
1

2750
5
7
CH
2
8 6 10 9

2700

8200
SD

CH

2750
CH
TD

KEY SCALE 1:100 M


1 Examination table 7 Medical gas console (Air, Oxgyen,
2 Table, instrument Vaccum)
3 Resuscitating apparatus 8 Cubicle curtain and rod
4 Counter, with cabinets below 9 Concealed floor drain
5 Sink, stainless steel 10 Waste bin
6 Examination light
11 Portable X-Ray Machine

143
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY RESPIRATORY UNIT 250B-ER-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Ambulatory patient may arrive Waste bin w/ yellow lining 1
b. Patient may arrive on wheelchair/ stretcher Bed 1
c. Patient is triaged and brought to the Respiratory unit Stethoscope 1
d. Holding area of patient prior to admission or referral for Sphygmomanometer 1
laboratory tests Thermometer, non-medical 1
e. Collection of specimen by nasopharyngeal swab Nebulizer 1
IV stand 1
Suction machine 1
Pulse Oxymeter 1
Ventilator 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician FIXTURE CHECKLIST
1 x Patient Examination table 1
1 x Nurse Medical gas console 1
Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to emergency exit and accessible to the ENGINEERING TERMINALS
Nursing wards Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1

144
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY RESPIRATORY UNIT 250B-ER-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.65

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER staff, patients and companions

Fire risk LOW:medium:high

Other risks NA

145
3050

7 2
TD
4
1
5

3
6

5100
SD

KEY SCALE 1:100 M


1 Examination table 5 Medical gas console (Air, Oxgyen,
2 Suction apparatus Vaccum)
3 Ventilator 6 Cubicle curtain and rod
4 IV stand 7 Waste bin

146
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY STAFF PANTRY/ LOCKERS, T&B 250B-ER-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Lounging area for Emergency Room staff Waste bin w/ black lining 2
b. Emergency Room staff stores personal belongings
c. Emergency Room staff uses toilet facilities

People Involved: FURNITURE AND


QUANTITY REMARKS
Emergency Room Staff FIXTURE CHECKLIST
Table, dining 1
Chair; dining 4
Counter, with cabinets above 1
and below
Sink, stainless steel 1
Refrigerator 1
Water dispenser 1
Locker, steel, 300 x 500mm 8
Concealed floor drain 1
Slop sink 1
Shelf, open 1
Water closet 1
Lavatory 1
Urinal 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Accessible from all ER facilities ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
1 GFCI
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 2

147
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
STAFF PANTRY/
April 2016 EMERGENCY LOCKERS, T&B 250B-ER-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Emergency Staff

Fire risk LOW: medium : high

Other risks NA

148
6200
1700 4500

1300
12 11
13 3 3
2

3900
1 SD
3 3

6000
8
9 4

4700
6 7 CH
5
GFCI
10
14

2100
SD

KEY SCALE 1:100 M


1 STAFF PANTRY 8 Concealed floor drain
2 Table, dining 9 Waste bin
3 Chair; dining 10 Locker, steel, 300 x 500mm
4 Counter, with cabinets above
and below 11 JANITOR'S CLOSET
5 Sink, stainless steel 12 Slop sink with faucet
6 Refrigerator 13 Shelf, open
7 Water dispenser
14 STAFF TOILET & BATH

149
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY ISOLATION ROOM 250B-ER-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. ER patient is triaged and brought to Isolation Room Exhaust fan 1
b. ER attendant bathes patient Electric fan 1
c. Patient is decontaminated with chemical solutions Airconditioning unit 1
d. Patient undergoes screening for possible or suspected Thermometer 1
biological or chemical contamination Sphygmomanometer 1
e. Consultation/ examination/ treatment of patients Weighing scale 1
f. Holding area of patients prior to admission or referral Stethoscope 1
to other hospitals IV stand 1
Suction machine 1
Gooseneck lamp 1
Linen Hamper 1
People Involved: Stretcher 1
1 x Medical Doctor Waste bin w/ black lining 1
1 x Nurse Waste bin w/ yellow lining 1
Patient
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Examination table/bed 1
Table, side, 400 x 400mm 1
Footstool 1
Cabinet, for PPE; with PPE 1
Lavatory, wall-hung 1
Hamper, for soiled linen 1
Concealed floor drain w/ 1
waterless trap

Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS


a. Close to Emergency Department exit ENGINEERING TERMINALS
b. Adjacent to ambulance entrance Outlet, 10A,2P,240V, duplex 7 grounding type,
c. Accessible to Nursing Wards universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1

150
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY ISOLATION ROOM 250B-ER-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 10 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 30 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER staff and patient

Fire risk low:MEDIUM:high

Other risks NA

151
3300
1800 1500

8
11

2500
7 SD 9 12

10
6 6

6000
TD

1
3

3500
SD
2
4

5 6

KEY SCALE 1:100 M

1 ISOLATION ROOM 7 ANTE ROOM


2 Examination table/bed 8 Cabinet, for PPE; with PPE
3 Table, side, 400 x 400mm 9 Lavatory, wall-hung
4 Footstool 10 Hamper, for soiled linen
5 Waste bin, general 11 Concealed floor drain
6 Waste bin, infectious
12 TOILET

152
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY VAWC ROOM 250B-ER-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
Examination table/bed 1
VAWC - Violence Against Women & Children Speculum set 1
a. Patient arrives on foot, wheelchair, or stretcher Examination light 1
b. Social Worker/Family Physician interviews and Waste bin, w/ black or 2
records information from/about patient colorless lining
c. Family Physician examines patient and/or
refers patient to diagnostic/laboratory service

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Family Physician FIXTURE CHECKLIST
1 x Nurse Desk, 600 x 1200mm 1
1 x Social Worker Desk, extension 1
Patient Chair, swivel 1
Patient's companion Chair, upright, stacking 4
Table, side 1
Footstool 1
Cart, instrument 1
Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Preferably with exterior access ENGINEERING TERMINALS
Window curtain rail 1
Outlet, 10A, 2P, 240V, duplex 6 grounding type,
universal slots
Outlet, intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, Data 1
Smoke Detector 1 Ionization type

153
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY VAWC ROOM 250B-ER-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.5

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER staff, patient, companion

Fire risk LOW: medium: high

Other risks NA

154
3800
1500 2300

10 11
T

2500
D 9
13
7
6
8
7 6
12

6000
SD 6
6
3

3500
2 1

5 7

KEY SCALE 1:100 M

1 PATIENT ROOM 8 INTERVIEW AREA


2 Examination table/bed 9 Desk, 600 x 1200mm
3 Table, side, 400 x 400mm 10 Desk, extension
4 Footstool 11 Chair, swivel
5 Instrument cart 12 Cubicle curtain and rod
6 Chair, upright
7 Waste bin, general 13 TOILET

155
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY TREATMENT CUBICLE (PEDIA) 250B-ER-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Ambulatory patient may arrive on foot Laryngoscope w/ endotracheal tube 1
b. Patient may arrive on wheelchair/ stretcher (different sizes)
c. Use of diagnostic equipment Examining light 1
d. Patient is treated for minor injuries and illness Nebulizer 1
e. Transfer of patient from examining table to stretcher Sphygmomanometer w/ pediatric 1
cuffs
trolley, to go to observation rooms or pediatric wards Weighing scale, infant 1
f. Patient is assisted by Nurse/ Nursing Attendant to Heavy-duty weighing scale 1
move out from examining table and be discharged Stethoscope 1
IV stand 1
Suction machine 1
Gooseneck lamp 1
People Involved: Waste bin w/ black lining 1
1 x Resident Physician Oxygen tank set 1
1 x Patient Bag valve mask 1
1 x Nurse Cervical collar 1
1 x Nursing Attendant
FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Examination table/bed 1
Table, side, 400 x 400mm 1
Footstool 1
Chair, upright 1
Lavatory, wall-hung 1
Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Emergency suite entrance ENGINEERING TERMINALS
b. Adjacent to Nurse Station and Minor Operating room Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1 for entire area
Cubicle curtain rail 1

156
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
TREATMENT CUBICLE
April 2016 EMERGENCY (PEDIA) 250B-ER-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Medical staff and patient

Fire risk LOW:medium:high

Other risks NA

157
2350

7
4

3650
3 1

5
6 2

KEY SCALE 1:100 M

1 Examination table/bed 5 Waste bin, general


2 Table, side, 400 x 400mm 6 Lavatory, wall-hung
3 Footstool 7 Cubicle curtain and rod
4 Chair, upright
Note : provide smoke detectors
at entire area of pedia
treatment

158
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
TREATMENT CUBICLE
April 2016 EMERGENCY (MEDICAL) 250B-ER-RDS-09A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Ambulatory patient may arrive on foot Laryngoscope w/ endotracheal tube 1
b. Patient may arrive on wheelchair/ stretcher Pulse Oxymeter 1
c. Use of diagnostic equipment Examining light 1
d. Patient is treated for minor injuries and illness Nebulizer 1
e. Transfer of patient from examining table to stretcher Sphygmomanometer 1
trolley, to go to observation rooms or medical wards Weighing scale 1
f. Patient is assisted by Nurse/ Nursing Attendant to Stethoscope 1
move out from examining table and be discharged IV stand w/ IV fluid 1
Suction machine 1
ECG cardiac monitor 1
Waste bin w/ black lining 1
People Involved: Oxygen tank set 1
1 x Resident Physician Bag valve mask 1
1 x Patient Cervical collar 1
1 x Nurse E-cart w/ complete ER meds 1
1 x Nursing Attendant Thermometer, digital 1
Electric fan 1
Glucometer 1

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Examination table/bed 1
Table, side, 400 x 400mm 1
Footstool 1
Chair, upright 1
Lavatory, wall-hung 1
Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Emergency suite entrance ENGINEERING TERMINALS
b. Adjacent to Nurse Station and Minor Operating room Cubicle curtain rail 1
c. Accessible to the Nursing Wards Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1 for entire area

159
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
TREATMENT CUBICLE
April 2016 EMERGENCY (MEDICAL) 250B-ER-RDS-09B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 3.6

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Medical staff and patient

Fire risk LOW:medium:high

Other risks NA

160
2650

2 6
5

3 1

3650
4
7

KEY SCALE 1:100 M

1 Examination table/bed 5 Waste bin, general


2 Table, side, 400 x 400mm 6 Lavatory, wall-hung
3 Footstool 7 Cubicle curtain and rod
4 Chair, upright
Note : provide smoke detectors
at entire area of pedia
treatment

161
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
TREATMENT CUBICLE
April 2016 EMERGENCY (OB-GYNE) 250B-ER-RDS-10A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Ambulatory patient may arrive on foot IV stand w/ IV fluid 1
b. Patient may arrive on wheelchair/ stretcher Examining light 1
c. Use of diagnostic equipment Oxygen tank set 1
d. Patient is treated for minor injuries and illness Sphygmomanometer 1
e. Transfer of patient from examining table to stretcher Stethoscope 1
trolley, to go to observation rooms or ob-gyne wards Weighing scale 1
f. Patient is assisted by Nurse/ Nursing Attendant to Ortho Set 1
move out from examining table and be discharged Thermometer, digital 1
Suction apparatus 1
EENT diagnostic set 1
Neurological hammer 1
People Involved: Glucometer 1
1 x Resident Physician Pulse Oxymeter 1
1 x Patient Cervical collar 1
1 x Nurse Laryngoscope w/ ET tube 1
1 x Nursing Attendant E-cart w/ complete ER meds 1 set
ECG cardiac monitor 1
Bag valve mask 1
Electric fan 1
Waste bin w/ black lining 1
FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Examination table/bed 1
Table, side, 400 x 400mm 1
Footstool 1
Chair, upright 1
Lavatory, wall-hung 1
Cubicle curtain and rod 1
Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS
a. Close to Emergency suite entrance ENGINEERING TERMINALS
b. Adjacent to Nurse Station and Minor Operating room Cubicle curtain rail 1
Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1 for entire area

162
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
TREATMENT CUBICLE
April 2016 EMERGENCY (OB-GYNE) 250B-ER-RDS-10B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Medical staff and patient

Fire risk LOW:medium:high

Other risks NA

163
2350

7
4

3650
3 1

5
6 2

KEY SCALE 1:100 M

1 Examination table/bed 5 Waste bin, general


2 Table, side, 400 x 400mm 6 Lavatory, wall-hung
3 Footstool 7 Cubicle curtain and rod
4 Chair, upright
Note : provide smoke detectors
at entire area of pedia
treatment

164
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
TREATMENT CUBICLE
April 2016 EMERGENCY (SURGERY) 250B-ER-RDS-11A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Ambulatory patient may arrive on foot IV stand w/ IV fluid 1
b. Patient may arrive on wheelchair/ stretcher Examining light 1
c. Use of diagnostic equipment Oxygen tank set 1
d. Patient is treated for minor injuries and illness Sphygmomanometer 1
e. Transfer of patient from examining table to stretcher Stethoscope 1
trolley, to go to observation rooms or surgery wards Weighing scale 1
f. Patient is assisted by Nurse/ Nursing Attendant to Ortho Set 1
move out from examining table and be discharged Thermometer, digital 1
g. Patient is given initial treatment and brought to the Suction apparatus 1
Minor Operating Room EENT diagnostic set 1
Neurological hammer 1
Glucometer 1
Pulse Oxymeter 1
People Involved: Cervical collar 1
1 x Resident Physician Laryngoscope w/ ET tube 1
1 x Patient Surgical set (minor) 1 set
1 x Nurse Waste bin w/ black lining 1
1 x Nursing Attendant
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Examination table/bed 1
Table, side, 400 x 400mm 1
Footstool 1
Chair, upright 1
Lavatory, wall-hung 1
Cubicle curtain and rod 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships ENGINEERING TERMINALS
a. Close to Emergency suite entrance Cubicle curtain rail 1
b. Adjacent to Nurse Station and Minor Operating room Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1 for entire area

165
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
TREATMENT CUBICLE
April 2016 EMERGENCY (SURGERY) 250B-ER-RDS-11B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 3.6

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Medical staff and patient

Fire risk LOW:medium:high

Other risks NA

166
2650

2 6
5

3 1

3650
4
7

KEY SCALE 1:100 M

1 Examination table/bed 5 Waste bin, general


2 Table, side, 400 x 400mm 6 Lavatory, wall-hung
3 Footstool 7 Cubicle curtain and rod
4 Chair, upright
Note : provide smoke detectors
at entire area of pedia
treatment

167
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY NURSE STATION 250B-ER-RDS-12A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse receives patient Instrument sterilizer 1
b. Nurse makes inquiries and records necessary information Waste bin w/ yellow lining 3
from/about patients rushed to ER Cart, supply 1
c. Nurse performs other medical monitoring activities Cart, emergency 1
d. Physician aided by nurses and nursing attendants, Lockers for staff 4
monitor and perform diagnostic activities and administers Filing cabinet 1
proper treatment to patient rushed to ER Cabinet for dangerous medicines 1
Whiteboard 1
Electric fan 1
Exhaust fan 1
GENT diagnostic set 1
People Involved: Weighing scale 1
1 x Nurse Defribrillator 1
1 x Nursing Attendant Ambu bag (Adult/Pedia) 1
Suction machine 1
Puncture-proof container 1
Clock 1
Refrigerator 1

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Counter, 2-level 2
Counter, with cabinets above 1
& below
Sink, stainless steel 2
Chair, stacking, upright 1
Stool, adjustable 1
Concealed floor drain 1
Planning Relationships Shelf, open 2
a. Close to Emergency entrance Water closet w/ spray hose 1
b. Adjacent to Treatment and Minor Operating Room Lavatory 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 15 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 2
Outlet, DATA 1
Outlet, Telephone 1
Water heater, 3.5kw 1
Paging System 1

168
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY NURSE STATION 250B-ER-RDS-12B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit nursing staff

Fire risk LOW: medium: high

Other risks NA

169
4033
1267 2767

12 10 11
4 3 6

1265
20 2

1412 1
3

3998
4 SD T
8 9 D
13

2733
SD D5 12

9 2
16
15
17

1270
18 7

2473
17
6

1203 19

2008
KEY SCALE 1:100 M
1 NURSE STATION 12 Waste bin
2 Counter, 2-level
3 Counter, with cabinets above 13 MEDICINE PREP. ROOM
and below 14 Concealed floor drain
4 Sink, stainless steel 15 Refrigerator, for medicine
5 Desk
6 Cart, supply 16 SUPPLY ROOM
7 Cart, emergency 17 Shelf, open
8 Chair, stacking, upright
9 Stool, adjustable 18 CLEAN LINEN ROOM
10 Whiteboard 19 DIRTY LINEN ROOM
11 Clock 20 STAFF TOILET

170
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY DELIVERY ROOM 250B-ER-RDS-13A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a wheelchair or stretcher Delivery table 1
b. Patient is transferred to delivery table Adjustable stool 1
c. Clinical handwashing Shelf 1
d. Administering of anesthesia
e. Preparation of patient for childbirth
f. Normal delivery of baby by patient

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician FIXTURE CHECKLIST
1 x Nurse or Nursing Attendant Delivery table 1
Patient Adjustable stool 1
Shelf 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS
b. Adjacent to Scrub-Up Window curtain rail 1
c. Near Ob-Gyne Treatment Area Outlet, 10A, 2P, 240V, duplex 8 grounding type,
universal slots
Outlet, intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, Data 1
Smoke Detector 1 Ionization type

171
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY DELIVERY ROOM 250B-ER-RDS-13B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000-20,000

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Exhaust (Pa) NA Daylight essential:desirable:UNNECESSARY

Inlet (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.5-3

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIALl:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER staff, patient

Fire risk low : medium: HIGH

Other risks NA

172
3900

13 6
14

T
D
11
7
5 8
7

6000
9 1 SD 2 12

3 16

15
10
4

KEY SCALE 1:100 M


1 Delivery table 9 Kick bucket
2 Obstetrical lamp 10 Heated bassinet/warmer
3 Mayo table 11 Aspirator
4 Emergency light, fixed 12 Clock
5 Instrument table 13 Isolation monitor
6 Emergency light, portable 14 Floor clean-out
7 Single basin stand 15 Shelving; adjustable, 500mm
8 Adjustable stool deep
16 Ground terminal

173
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY SCRUB-UP/SUB-STERILE 250B-ER-RDS-14A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
SCRUB-UP Clock 1
a. Physician and nurses rinse arms and hands with water Soap Dispenser 1
and soap prior to and/or after surgical operation Hand Dryer 1
SUB-STERILE Small instrument sterilizer 1
a. Preparation of packed and surgical instruments from cabinets Waste bin w/ yellow lining 2
b. Storing and retrieving of instruments from cabinets Airconditioning unit 1
c. Minor sterilizing works
d. Handwashing and other clean-up activities

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician FIXTURE CHECKLIST
1 x Nurse 2-Station Scrub sink, with 1
1 x Nursing Attendant gooseneck spout & foot control,
sensor type
Shelves, overhead 1
Concealed floor drain 2
Counter, 900mm high 1
Sink, with drainboard 1
Door, with vision panel 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS
b. Adjacent to Scrub-Up Outlet, 10A,2P,240V, duplex 5 grounding type,
c. Close to Treatment cubicles universal slots
d. Close to Nurse Station Outlet, 15A,2P,240V, single 1 for emergency light
e. Adjacent to Minor Operating Room Smoke detector 2
Outlet, Aircon 1

174
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY SCRUB-UP/SUB-STERILE 250B-ER-RDS-14B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER staff

Fire risk low:MEDIUM:high

Other risks NA

175
2300 1500

6 7 4
13
9

2000
SD 5

2600
8 SD
10 11 CH 12 2
1
86
3

KEY SCALE 1:100 M

1 SCRUB-UP AREA 9 SUB-STERILE ROOM


2 2-Station Scrub sink, with 10 Counter, 900mm high
gooseneck spout & foot control, 11 Sink, with drainboard
sensor type 12 Instrument sterilizer, small
3 Soap dispenser 13 Door, with vision panel
4 Hand dryer
5 Shelves, overhead
6 Waste bin, infectious
7 Clock
8 Concealed floor drain

176
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY MINOR OPERATING ROOM 250B-ER-RDS-15A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley IV Stand 1
b. Patient is transferred from a stretcher trolley to Operating light 1
operating table Oxygen tank set 1
c. Clinical Handwashing Sphygmomanometer 1
d. Anesthesia is administered Stethoscope 1
e. Use of diagnostic equipment Suction apparatus 1
f. Patient is surgically operated EENT diagnostic & surgical set 1
Surgical set 1
Clock 1
Double-film Negatoscope 1
Double X-ray film illuminator 1
UV Light 1
Telephone 1
People Involved: Airconditioning Unit 1
2 x Resident Physician Anesthesia Unit 1
1 x Patient Puncture-proof container 1
1 x Nurse Waste bin w/ yellow lining 1
1 x Nursing Attendant FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Aspirator 1
Footstool 2
Instrument table 1
Double basin stand 1
Single basin stand 1
Anesthetist's stool 1
Anesthetist's table 1
Kick bucket 1
Concealed floor drain 1
Planning Relationships Shelving; adjustable, 500mm deep 1
a. Adjacent to Sub-sterilizing Room Door with vision panel 1
b. Adjacent to Scrub-Up ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
c. Close to treatment cubicles ENGINEERING TERMINALS
d. Close to Nurse station Outlet, 10A,2P,240V, duplex 9 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, Telephone 1
Outlet, DATA 1
Grounding terminal 3

177
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY MINOR OPERATING ROOM 250B-ER-RDS-15B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit ER Staff and patient

Fire risk low:medium:HIGH

Other risks NA

178
6000

5
14
4 7

10

5100
2 1 9
SD
6
4 8

T
D

11 12 15 13

KEY SCALE 1:100 M

1 Operating table 10 Kick bucket


2 Operating lamp 11 Clock
3 Aspirator 12 Double-film negatoscope
4 Footstool 13 Concealed floor drain
5 Instrument table 14 Shelving; adjustable, 500mm
6 Double basin stand deep
7 Single basin stand 15 Door with vision panel
8 Anesthetist's stool
9 Anesthetist's table

179
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH EMERGENCY MGMT.
April 2016 EMERGENCY OFFICE & SUPPLY RM. 250B-ER-RDS-16A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of supplies for public health emergency Personal Protective Equipment (PPE)
preparedness and response unit Gloves
b. Distribution of said supplies Gown
Goggles
Facial Guards
N95 Respirator or Surgical Mask
Waste bin 2

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Medical Doctor FIXTURE CHECKLIST
Desk, 600 x 1200mm 1
Desk, extension 1
Desk, 600 x 1000mm 2
Chair, upright; stacking 5
Cabinet, steel, filing 3
Shelf, open, adjustable, 8
600mm deep
Ladder, aluminum 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Emergency Department and near the ENGINEERING TERMINALS
exit/ lobby for easier distribution of supplies in cases Outlet, 10A,2P,240V, duplex 11 grounding type,
of emergency universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 2
Outlet, Telephone 1
Outlet, DATA 1

180
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HEALTH EMERGENCY MGMT.
April 2016 EMERGENCY OFFICE & SUPPLY RM. 250B-ER-RDS-16B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Medical Staff

Fire risk low:MEDIUM: high

Other risks NA

181
3200 4000

9
10
5 8
5 1
T
D 9 9 9
2

5 4
3

6000
SD
5 SD
7
9

9 9 9
7 4
6 5
6
6

KEY SCALE 1:100 M

1 HEMS OFFICE 8 HEMS SUPPLY ROOM


2 Desk, 600 x 1200mm 9 Shelf, open, adjustable,
3 Desk, extension 600mm deep
4 Desk, 600 x 1000mm 10 Ladder, aluminum
5 Chair, upright; stacking
6 Cabinet, steel, filing
7 Waste bin

182
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY ER HEAD OFFICE 250B-ER-RDS-17A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Reads, writes, and uses telephone in his work station Waste bin w/ black lining 3
b. Receives visitors
c. Consulted by patients
d. Stores, files and retrieves records
e. Supervises/ monitors clinical activities
f. Use of toilet facilities

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x ER Chief FIXTURE CHECKLIST
1 x ER staff Desk, 600 x 1200mm 1
Visitors Desk, extension 1
Desk, 600 x 1000mm 1
Chair, junior executive 1
Chair, upright, stacking 4
Cabinet, steel, filing 3
Table, 4-seater 1
Chair, with armrest 4
Lavatory 1
Urinal 1
Water closet 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to ER treatment cubicles ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 2
Outlet, Telephone 1
Outlet, DATA 1

183
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY ER HEAD OFFICE 250B-ER-RDS-17B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER chief, staff and visitors

Fire risk LOW:medium:high

Other risks NA

184
1700 4000

6 T 7
6
4 7
7
10
1

11

6000
6

1900
SD
6
2 T
9 9 D

8 5
3
9 9
10

KEY SCALE 1:100 M

1 ER HEAD'S OFFICE 7 Cabinet, steel, filing


2 Desk, 600 x 1200mm 8 Table, 4-seater
3 Desk, extension 9 Chair, with armrest
4 Desk, 600 x 1000mm 10 Waste bin
5 Chair, junior executive
6 Chair, upright, stacking 11 TOILET

185
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY DOCTORS ON CALL ROOM 250B-ER-RDS-18A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Doctor on duty reads, writes, and uses mobile Waste bin w/ black lining 1 non-bidoegradable
phone at his table Waste bin w/ green lining 1 biodegradable
b. Doctor on duty rests while awaiting emergency calls
c. Doctor on duty uses toilet facilities
d. Doctor on duty stores personal belongings

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Sofa, 2-seater 2
Desk, 600 x 1200mm 1
People Involved: Chair, swivel 1
2 x Resident Physician Cabinet, steel, filing 2
2 x Nurse Table, side, 400 x 400mm 2
2 X Nursing Attendant Table, dining, 4-seater 1
Chair, dining 4
Counter, with cabinets above 1
and below
Sink, stainless steel 1
Water dispenser 1
Refrigerator 1
Concealed floor drain 1
Closet 1
Lavatory 1
Urinal 1
Water closet 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to ER Major Operating Room ENGINEERING TERMINALS
b. Close to Nurse Station Outlet, 10A,2P,240V, duplex 8 grounding type,
c. Close to Treatment Cubicles universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 2
Outlet, Telephone 1
Outlet, DATA 1

186
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY DOCTORS ON CALL ROOM 250B-ER-RDS-18B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit ER chief, staff and visitors

Fire risk LOW:medium:high

Other risks NA

187
5900
1700 4200

11 10 CH 12 13

14
5
16 5

4300
9 8 8
7 4 3

6000
SD
8 8
9

2
1
1700

15 D
T
6 2 6

KEY SCALE 1:100 M

1 DOCTORS' ON-CALL RM 10 Counter, with cabinets above


2 Sofa, 2-seater and below
3 Desk, 600 x 1200mm 11 Sink, stainless steel
4 Chair, swivel 12 Water dispenser
5 Cabinet, steel, filing 13 Refrigerator
6 Table, side, 400 x 400mm 14 Concealed floor drain
7 Table, dining, 4-seater 15 Closet
8 Chair, dining
9 Waste bin 16 TOILET & BATH

188
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY AMBULATORY CARE 250B-ER-RDS-19A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is transferred to Ambulatory Care Examination table/bed 2
after physician declares patient fit to be Waste bin, w/ black or 2
moved from Emergency to a patient room colorless lining
b. Patient stays at Ambulatory Care until a
patient room is available

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician FIXTURE CHECKLIST
Patient Table, side 2
Footstool 2
Chair, upright, stacking 2
Cubicle curtain and rod 2

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Observation Bays ENGINEERING TERMINALS
b. Close to Treatment Area Window curtain rail 1
Outlet, 10A, 2P, 240V, duplex 6 grounding type,
universal slots
Outlet, intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, Data 1
Smoke Detector 1 Ionization type

189
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY AMBULATORY CARE 250B-ER-RDS-19B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR)

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ER staff, patient, companion

Fire risk LOW: medium: high

Other risks NA

190
3650 1700

2200
9

3000
4
1
2 6

3
5
SD
5
3

3000
7 8
4

1900
9 6

TD 6

KEY SCALE 1:100 M

1 MALE AMBULATORY CARE 8 FEMALE AMBULATORY CARE


2 Examination table/bed
3 Table, side, 400 x 400mm 9 TOILET
4 Footstool
5 Chair, upright
6 Waste bin, general
7 Cubicle curtain and rod

191
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY OBSERVATION BAY 250B-ER-RDS-20A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is transferred to ER Observation from Emergency light 1
other ER areas: either from Rescusitation Bay, Volume respirator 1
Respiratory Unit, Treatment Cubicle, VAWC Room, Pulse oximeter 1
Delivery Room, or Operating Room Nebulizer 1
b. Patient is transferred to bed and vice versa Sphygmomanometer 1
c. Nurses and nursing attendants monitor vital Stethoscope 1
signs of patient at regular intervals IV stand with IV fluid 1
Thermometer, digital 1
Electric fan 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Patient FIXTURE CHECKLIST
1 x Resident Physician Hospital bed, adjustable 1
1 x Nurse Table, side 1
1 x Nursing Attendant Footstool 1
Chair, upright 1
Cubicle curtain and rod 1

Planning Relationships: ADDITIONAL EQUIPMENT & QUANTITY REMARKS


a. Visible from Observation Area Nurse Station ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 2 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 3

192
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 EMERGENCY OBSERVATION BAY 250B-ER-RDS-20B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 3.6

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit patient and medical staff

Fire risk LOW: medium : high

Other risks NA

193
2700

3 1

3000
4
5

KEY SCALE 1:100 M

1 Hospital bed, adjustable Note :


2 Table, side - Provide smoke detectors at
3 Footstool entire area of Observation bays
4 Chair, upright - Provide handwashing sinks at
5 Cubicle curtain and rod central areas of Observation
bays for shared use

194
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.3 OUTPATIENT SERVICE FACILITIES


3.3.1 OUTPATIENT CLINICS
3.3.2 AMBULATORY SURGERY CLINIC
3.3.3 PHYSICAL REHABILITATION UNIT
3.3.4. DIALYSIS UNIT

First Edition
DEPARTMENT OF HEALTH
Manila
2017

195
Hospital: Department of Health
250-Bed (Level 3)
SERVICE FACILITY SHEET INDEX
Hospital HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 OUTPATIENT 250B-OPD-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
OUTPATIENT 839.00 250B-OPD-DDS-01 199
Lobby & Waiting Area 297.00 250B-OPD-RDS-01 201
Registration/ Admitting Area 18.00 250B-OPD-RDS-02 204
OPD Records Room 36.00 250B-OPD-RDS-03 207
Office of the Family Medicine Chief 30.00 250B-OPD-RDS-04 210
Conference Room 43.00 250B-OPD-RDS-05 213
Consultation Room (Medicine) 18.00 250B-OPD-RDS-06 216
Consultation Room (OB-GYNE) 54.00 250B-OPD-RDS-07 219
Consultation Room (Pedia/ Under Six) 36.00 250B-OPD-RDS-08 222
Consultation Room (Surgery) 18.00 250B-OPD-RDS-09 225
Consultation Room (Dental) 55.00 250B-OPD-RDS-10 228
Consultation Room (ENT) 36.00 250B-OPD-RDS-11 231
Consultation Room (Ophtha) 36.00 250B-OPD-RDS-12 234
Consultation Room (TB-DOTS) 90.00 250B-OPD-RDS-13 237
Staff Pantry & Lounge 18.00 250B-OPD-RDS-14 240
Public Toilets 36.00 250B-OPD-RDS-15 243
Clinic (Typical) 18.00 250B-OPD-RDS-16 246

AMBULATORY SURGERY CLINIC 200.00 250B-OPD-DDS-02 200


Reception 18.00 250B-ASC-RDS-01 249
Treatment Room 36.00 250B-ASC-RDS-02 252
Consult/ Exam 18.00 250B-ASC-RDS-03 255
Patient Dress/ Toilet 21.00 250B-ASC-RDS-04 258
Scrub-Up Area 7.00 250B-ASC-RDS-05 261
Clean-Up Area 9.00 250B-ASC-RDS-06 264
Recovery Room 33.00 250B-ASC-RDS-07 267
Operating Room 36.00 250B-ASC-RDS-08 270
Sterilization Room 12.00 250B-ASC-RDS-09 273
Sterile Instrument Supply & Storage Room 10.00 250B-ASC-RDS-10 276

197
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 OUTPATIENT 250B-OPD-SFSI-02
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
PHYSICAL REHABILITATION 144.00 250B-PR-DDS-01 279
Waiting & Reception 20.00 250B-PR-RDS-01 280
Consult/ Exam Room 9.00 250B-PR-RDS-02 283
Treatment/ Gym Area 94.00 250B-PR-RDS-03 286
Toilets, Dress Cubicles & Soiled Linen Area 21.00 250B-PR-RDS-04 289

DIALYSIS 213.00 250B-DIA-DDS-01 292


Information, Admitting & Waiting Area 33.00 250B-DIA-RDS-01 293
Consultation Room 12.00 250B-DIA-RDS-02 296
Dialysis Treatment Area 123.00 250B-DIA-RDS-03 299
Isolation Room 12.00 250B-DIA-RDS-04 302
Janitor's Closet, Soiled Linen & Waste 13.00 250B-DIA-RDS-05 305
Holding Area
Pantry 10.00 250B-DIA-RDS-06 308
Reprocessing Room 10.00 250B-DIA-RDS-07 311

198
15000

SCALE 1:300 M
18000

OPD LOBBY

RAMP
WAITING AREA

UP
3000

OPD
REGISTRATION/
ADMITTING
COUNTER
PUBLIC
FEMALE
TOILET
6000

OPD
RECORDS
ROOM

PUBLIC
MALE
TOILET
UP

3100 8900 3000 3000 3000 3000


6000

STD & HIV PSYCH


CLINIC CLINIC

PUBLIC FEMALE MALE


FEMALE STAFF STAFF
ANIMAL BITE CLINIC
TOILET TOILET TOILET
15000
3000

UP

PUBLIC
MALE
6000

OILET STAFF/
PANTRY/
LOUNGE

TB DOTS CLINIC

3100 14900 3000


21000

199
SCALE 1:300 M

51000
3000 3000 6000 9000 3000 3000 3000 3000 3000 2500 6000 3500 3000

STERILE
CLEAN INSTRUMENT,
UP SUPPLY,
STORAGE
6000

RECEPTION/
ELECTRICAL AFFILIATES' OB-GYNE RECORDS/ OR
ROOM ROOM CLINIC WAITING
AREA SUB- DRESS
WAITING STERILIZATION
SCRUB ROOM
AREA
DN

DN

DN
UP
3000

FEMALE MALE
STAFF STAFF
TOILET TOILET
DRESS
6000

STAFF FAMILY OB-


PANTRY/ PLANNING GYNE RECOVERY OR
CONSULT/
LOUNGE CLINIC CLINIC ROOM
EXAM TREATMENT TREATMENT
E
ROOM
RAMP DN
6000

PEDIA DENTAL X-RAY


6000

FM
CONFERENCE SURGERY/
CHIEF WELLNESS WELLNESS OPHTHA OPHTHA
ROOM MEDICINE
OFFICE
FEMALE MALE
PEDIA DENTAL STAFF STAFF
TOILET TOILET
3000

FEMALE MALE
DN

DN

PUBLIC PUBLIC
TOILET TOILET
6000

FAMILY FAMILY STAFF


NURSES' NEWBORN BREAST CHEMOTHERAPY HEARING ENT DERMA
MEDICINE MEDICINE PANTRY/
OFFICE CLINIC CLINIC CLINIC CLINIC CLINIC CLINIC
CLINIC CLINIC LOCKERS

3000 3000 6000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000

200
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT LOBBY & WAITING AREA 250B-OPD-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patients await their turns to be interviewed and their Waste bins, foot-controlled 6 General waste
cases be assessed at the triage (black & green)
b. Patients await their turns to be attended to in any of
the treatment rooms
c. Patient waits for his/ her number to be called

People Involved: FURNITURE AND QUANTITY REMARKS


72 x Outpatients and Companions FIXTURE CHECKLIST
Counter, 2-level 1
Chair, gang 14 4-seater
4 5-seater
19 6-seater

Planning Relationships: ADDITIONAL EQUIPMENT & QUANTITY REMARKS


a. Close to OPD Consultation Rooms ENGINEERING TERMINALS
b. Adjacent to OPD Registration Counter Window curtain rail 4
c. Close to other Ancillary Services Outlet, 10A,2P,240V, duplex 12 grounding type,
d. Registration Area to a location near the entrance and universal
accessible to OPD Clinics Outlet, 10A, 2P 240V, single 2 for emergency light
Smoke Detector 6

201
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT LOBBY & WAITING AREA 250B-OPD-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit general public

Fire risk LOW: medium: high

Other risks NA

202
15000

3 3 3

2 2
2 2 2 2 2
SD SD

2 2
2 2 2 2 2

18000
SD
3
2 2 2 2 2 SD
2 2 2

2 SD 2
2 2
2 2
2 2
3 2 SD 2
1
2 2
3000

2 2
3

9000

KEY SCALE 1:300 M

1 Counter, 2-level
2 Chair, gang
3 Waste bin

203
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
ADMITTING/
April 2016 OUTPATIENT REGISTRATION COUNTER 250B-OPD-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. OPD Patient Registration Printer 1
b. Data encoding of patient's information to the system Computer 1
c. Issuance of Medical/Legal certificates Telephone handset 1
d. Maintenance of OPD register Intercom handset 1
Electric fan 1
Microphone 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Administrative Officer FIXTURE CHECKLIST
2 x Data controller Counter, with transaction window 1
Cabinet, 450 x 2000mm 1
Stool, adjustable 3

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to OPD Waiting Area
b. Close to entrance to OPD Outlet, 10A,2P,240V, duplex 6 grounding type,
c. Close to the Office of the OPD chief universal slots
d. Close to Consultation Rooms Outlet, 10A, 2P 240V, single 1
e. Adjacent and accessible to OPD Records Room Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1
Paging System 1
Water Sprinkler 1
Fire extinguisher 1

204
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
ADMITTING/
April 2016 OUTPATIENT REGISTRATION COUNTER 250B-OPD-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit OPD staff, patients & visitors

Fire risk LOW: medium: high

Other risks NA

205
6000

1
T
D
3 3 3

3000
SD

4 2

KEY SCALE 1:100 M

1 Counter, with transaction window


2 Cabinet, 450 x 2000mm
3 Stool, adjustable
4 Waste bin

206
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT RECORDS ROOM 250B-OPD-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. OPD staff reads, writes, files and retrieves records of Steel ladder, 4-step, heavy-duty 2
patients Electric fan 1
Fire extinguisher 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Records officer FIXTURE CHECKLIST
1 x Clerk Shelving, open, steel 18

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent and accessible to OPD registration counter Outlet, 10A,2P,240V, single 1 emergency light
b. Adjacent to OPD waiting area
c. Close to entrance to OPD
d. Close to the Office of the OPD chief
e. Close to consultation rooms

207
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT RECORDS ROOM 250B-OPD-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit OPD staff & authorized users

Fire risk low: medium: HIGH

Other risks NA

208
6000

1 1

6000
1 1 2

1 1

KEY SCALE 1:100 M

1 Shelving, open, steel


2 Ladder, steel

209
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
OFFICE OF THE FAMILY
April 2016 OUTPATIENT MEDICINE CHIEF 250B-OPD-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Reads, writes and uses telephone in his work station Computer/ Laptop 1
b. Receives visitors Printer 1
c. Consulted by patients Waste bin w/ black lining 2
d. Stores, files, and retrieves records
e. Supervises/ monitors clinical activities
f. Use of toilet facilities

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Family Medicine chief FIXTURE CHECKLIST
1 x Family Medicine staff Desk, 750 x 1500mm 1
Visitors Desk, extension, 400 x 900mm 1
Shelf, open 1
Cabinet, steel, filing 3
Chair, junior executive 1
Chair, visitor 2
Sofa, 2-seater 1
Counter, 900mm high, with 1
cabinets above and below
Sink, stainless steel 1
Table, side, 400 x 400mm 2
Water closet 1
Lavatory 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to OPD consultation rooms Window curtain rail 2
b. Close to OPD registration counter Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1
Aircon, window type 1

210
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT OFFICE OF THE FM CHIEF 250B-OPD-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit FM chief, staff & visitors

Fire risk LOW: medium: high

Other risks NA

211
4300 1700

9 CH 8
12 11
4
4 2
5
4
1 T

6000
SD D
6
3
6

11

1900
10 7 10

KEY SCALE 1:100 M

1 Desk, 750 x 1500mm 8 Counter, 900mm high, with


2 Desk, extension, 400 x 900mm cabinets above and below
3 Shelf, open 9 Sink, stainless steel
4 Cabinet, steel, filing 10 Table, side, 400 x 400mm
5 Chair, junior executive 11 Waste bin
6 Chair, visitor 12 Concealed floor drain
7 Sofa, 2-seater

212
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT CONFERENCE ROOM 250B-OPD-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. OPD staff, physicians and visitors hold meetings LCD projector, built-in 1
and special lectures Negatoscope 1
Aircon 1
Computer/ Printer 1
Whiteboard/ Projection screen 2
Waste bin w/ black lining 2 biodegradable
non-biodegradable

People Involved: FURNITURE AND QUANTITY REMARKS


OPD doctors FIXTURE CHECKLIST
OPD staff Table, 500 x 1500mm 6
Visitors Cabinet, 400 x 2000mm 1
Chair, swivel 12
Counter, 900mm high, with 1
cabinets above and below
Sink, stainless steel 1
Water closet 1
Lavatory 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Staff Area Window curtain rail 1
b. Close to the Office of the OPD chief Outlet, 10A,2P,240V, duplex 6 grounding type,
c. Close to OPD consultation rooms universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

213
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT CONFERENCE ROOM 250B-OPD-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit OPD staff & visitors

Fire risk LOW: medium: high

Other risks NA

214
1700 6000

4 7 6

CH 3 3
6
1
5
8 3 3
1 1
3 3

6000
SD

3 3
7 1 1
3 3

1
3 3
7 2

KEY SCALE 1:100 M

1 Table, 500 x 1500mm 5 Sink, stainless steel


2 Cabinet, 400 x 2000mm 6 Whiteboard/projection screen
3 Chair, swivel 7 Waste bin
4 Counter, 900mm high, with 8 Concealed floor drain
cabinets above and below

215
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (MEDICINE) 250B-OPD-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot Examination light 1
b. Patient may arrive in wheelchair Sphygmomanometer, non-mercurial 1
c. Transfer patient to/from a wheelchair to examining Examination bed 1
table and vice versa Adult weighing scale 1
d. Clinical handwashing Paper towel dispenser 1
e. Use of monitoring/diagnostic equipment Towel rack 1
f. Medical, surgical, nursing and first aid activities Opthalmoscope 1
Otoscope 1
Neuro hammer 1
2-film Negatoscope 1
Mayo Table 1
Gooseneck lamp 1
Stethoscope 1
IV stand 1
Sharps collector, puncture-proof 1
container
Footstool 1
People Involved: Waste bin w/ black lining 1
1 x Resident Physician Waste bin w/ yellow lining 1
2 x Nurse
1 x Nursing Attendant FURNITURE AND QUANTITY REMARKS
1 x Patient FIXTURE CHECKLIST
Desk 1
Chair, upright, stacking 2
Stool, adjustable height 1
Cabinet, steel, filing 1
Table, side; 400 x 500mm 1
Counter, 900mm high, 1
cabinets above and below
Sink, with drainboard, with 1
gooseneck spout & foot/
elbow control
Concealed floor drain 1
Planning Relationships:
a. Close to other Ancillary Services ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
b. Close to OPD Minor OR ENGINEERING TERMINALS
Window curtain rail 1
This activity space provides facilities needed for Outlet, 10A,2P,240V, duplex 6 grounding type,
the delivery of general patient care universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1
Cubicle curtain rail 1

216
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (MEDICINE) 250B-OPD-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

217
3000

D 1 2
T
2
16
5 4

15
6 7

6000
9 SD
8
13

10
14
16 3 17
11 CH 12

KEY SCALE 1:100 M


1 Desk 11 Counter, 900mm high,
2 Chair, upright, stacking cabinets above and below
3 Stool, adjustable height 12 Sink, with drainboard, with
4 Adult weighing scale gooseneck spout & foot/
5 Cabinet, steel, filing elbow control
6 Table, side; 400 x 500mm 13 Negatoscope
7 Examination light 14 Rack, towel
8 Examination bed 15 Cubicle curtain with rod
9 Footstool 16 Waste bin
10 Trolley 17 Concealed floor drain

218
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (OB-GYNE) 250B-OPD-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is ambulatory Examination light 2
b. Patient may arrive in wheelchair Examination bed 2
c. Transfer patient to/from a wheelchair to examining Adult weighing scale 2
table and vice versa Sphygmomanometer, non-mercurial 2
d. Clinical handwashing Paper towel dispenser 1
e. Use of monitoring/diagnostic equipment Speculum set (vaginal) 2
f. Medical, surgical, nursing and first aid activities Histerometer 1
g. Administration of Tetanus Toxoid (TT) immunization Ovum forceps 1
Towel rack 2
Stainless container 3
Trolley 2
Stethoscope 1
Kelly Pad 1
NSD set 1
Waste bin w/ yellow lining 3
Fetal Doppler 1
Line hamper 2
People Involved: Dressing cart w/ acessories 1
2 x Resident Physicians Puncture-proof container 2
2 x Nurses Foot stool 2
2 x Nursing Attendants FURNITURE AND QUANTITY REMARKS
2 x Patients FIXTURE CHECKLIST
Desk, 750mmX1200mm 3
Chair, upright, stacking 7
Side extension, 400 x 900mm 1
Side extension, 400 x 1200mm 2
Bench 1
Water Closet 2
Lavatory 2

Planning Relationships:
a. Close to OPD Consultation Room (Pedia/ Under six) ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
b. Close to other Ancillary Services ENGINEERING TERMINALS
c. Close to toilet facilities
Outlet, 10A,2P,240V, duplex 17 grounding type,
This activity space provides facilities needed for universal slots
the delviery of general patient care Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 2
Outlet, Telephone 2
Smoke detector 4

219
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (OB-GYNE) 250B-OPD-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

220
9000
3000 3000 3000

3 DT 4 5 4 TD 3

2500
4 1 SD SD 1 4

4500
10 SD 4 10
6

6000
4
1
8 4 8

3500
7 SD 10 2 SD 7

1500
10 10
9 11 11 9

KEY SCALE 1:150 M


1 Desk 7 Examination bed
2 Side extension, 400 x 900mm 8 Footstool
3 Side extension, 400 x 1200mm 9 Linen hamper
4 Chair, upright, stacking 10 Waste bin
5 Bench
6 Adult weighing scale 11 TOILET

221
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (PEDIA/ UNDER SIX) 250B-OPD-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is ambulatory Adult weighing scale 1
b. Patient may arrive in wheelchair Infant weighing scale 1
c. Transfer patient to/from a wheelchair to examining Examination bed 2
table and vice versa Footstool 2
d. Use of monitoring/diagnostic equipment Paper towel dispenser 2
e. Medical, surgical, nursing and first aid activities Examination light 2
Trolley 2
Lamp, gooseneck 2
Refrigerator, for meds 1
Negatoscope 2
Rack, for towel 1
Waste bin w/ yellow lining 3

People Involved: FURNITURE AND QUANTITY REMARKS


2 x Resident Physicians FIXTURE CHECKLIST
2 x Nurse Desk, 750mmX1200mm 1
2 x Nursing Attendants Chair, upright, stacking 3
2 x Patients Table, side, 400 x 500mm 2
Counter, 900mm high, 1
cabinets above and below
Sink, with drainboard, with 1
gooseneck spout & foot/
elbow control
Stool, adjustable 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to OPD Consultation Rooms ENGINEERING TERMINALS
b. Close to other Ancillary Services Window curtain rail 2
Outlet, 10A,2P,240V, duplex 17 grounding type,
This activity space provides facilities needed for universal slots
the delivery of general patient care Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 4
Electronic queuing machine, optional 1

222
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (PEDIA/ UNDER SIX) 250B-OPD-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

223
6000
3100 2900

18 8 9 6 13
12 CH
19
5 15 17
11

3000
SD 7 SD
18

10 16 14

6000
10 16
2
1 DT

3000
SD 7 SD
2
11 4
5
3
18 8 9 6 2 2

KEY SCALE 1:100 M


1 Desk 12 Counter, 900mm high,
2 Chair, upright, stacking cabinets above and below
3 Adult weighing scale 13 Sink, with drainboard, with
4 Infant weighing scale gooseneck spout & foot/
5 Examination bed elbow control
6 Table, side, 400 x 500mm 14 Refrigerator, for meds
7 Footstool 15 Stool, adjustable
8 Paper towel dispenser 16 Negatoscope
9 Examination light 17 Rack, for towel
10 Trolley 18 Waste bin
11 Lamp, gooseneck 19 Concealed floor drain

224
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (SURGERY) 250B-OPD-RDS-09A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot Thermometer, non-mercurial 1
b. Patient may arrive in wheelchair Sphygmomanometer, non-mercurial 1
c. Transfer patient to/from a wheelchair to examining Examination bed 1
table and vice versa Adult weighing scale 1
d. Clinical handwashing Paper towel dispenser 1
e. Use of monitoring/diagnostic equipment Towel rack 1
f. Medical, surgical, nursing and first aid activities Opthalmoscope 1
Otoscope 1
Neuro hammer 1
2-film Negatoscope 1
Mayo Table 1
Examination light 1
Stethoscope 1
IV stand 1
Sharps collector 1
Footstool 1
Cast remover 1
People Involved: Mirror set 1
1 x Resident Physician I and D set 1
1 x Nurse Suture removal set 1
1 x Nursing Attendant Trolley 1
1 x Patient Waste bin w/ black lining 1
Waste bin w/ yellow lining 1
FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Desk, 750mmX1200mm 1
Chair, upright, stacking 2
Stool, adjustable height 1
Cabinet, steel, filing 1
Side table, 400mmX500mm 1
Counter, 900mm high, 1
cabinets above and below
Sink, with drainboard, with 1
Planning Relationships: gooseneck spout & foot/
a. Close to other Ancillary Services elbow control
b. Close to OPD Minor OR Concealed floor drain 1
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
This activity space provides facilities needed for ENGINEERING TERMINALS
the delivery of general patient care Window curtain rail 1
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1
Cubicle curtain rail 1

225
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (SURGERY) 250B-OPD-RDS-09B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

226
3000

12 CH 11
17 3 16
14
10

13
8

6000
SD
9
7 6
15

4 5
16
2
T
2 1 D

KEY SCALE 1:100 M


1 Desk 11 Counter, 900mm high,
2 Chair, upright, stacking cabinets above and below
3 Stool, adjustable height 12 Sink, with drainboard, with
4 Adult weighing scale gooseneck spout & foot/
5 Cabinet, steel, filing elbow control
6 Table, side; 400 x 500mm 13 Negatoscope
7 Examination light 14 Rack, towel
8 Examination bed 15 Cubicle curtain with rod
9 Footstool 16 Waste bin
10 Trolley 17 Concealed floor drain

227
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (DENTAL) 250B-OPD-RDS-10A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is ambulatory Dental chair, hydraulic 2
b. Patient may arrive in wheelchair Amalgamator, electric 2
c. Transfer patient to/from a wheelchair to examining Instrument sterilizer 2
table and vice versa Dental unit with monitor 2
d. Use of monitoring/diagnostic equipment Dental unit with hydraulic 2
e. Medical, surgical, nursing and first aid activities Dental x-ray, wall model 1
f. Dentists perform normal and special dental Dental operating light 2
procedures to treat Developing tank 1
Compressor, dental air 1
Towel rack 2
Bane pole, stainless 3
Coton files sow 2
High-speed handpiece w/ burr 1
remover 1
Waste bin w/ yellow lining 2
Puncture-proof container 1
Surgical chisel 1
People Involved: Surgical mallette ronquer 2
2 x Dentists *18 upper molar dental chair unit 1
2 x Dental Aides
2 x Patients FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Desk 4
Chair, upright, stacking 7
Cabinet, file, steel 3
Counter, 900mm high, cabinets 5
below
Sink, with gooseneck spout 2
Sink, elbow-controlled 1
Cabinet, dental instrument 2
Stool, adjustable 2
Concealed floor drain 3

Planning Relationships:
a. Close to OPD Consultation Rooms ADDITIONAL EQUIPMENT & QUANTITY REMARKS
b. Close to other Ancillary Services ENGINEERING TERMINALS

This activity space provides facilities needed for Outlet, 10A,2P,240V, duplex 18 grounding type,
the delivery of general patient care universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 4
Outlet: Gas, Air, Electic 1
Electronic queuing machine, optional 1

228
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (DENTAL) 250B-OPD-RDS-10B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 5,000-1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: heat generating instrument

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: at sink and lavatory

tolerated Maximum temperature (°C) 70

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

229
9075
3900 2200 2975

9 10 11 22 5 7 21 17
4 CH 8
4 20 SD
13 14 CH

3000
17 6 22
SD 4 SD 18
15 12

16

6000
9 10 11 2 DT
4
2
13 14

3000
1
17 SD SD
15 12 CH
4
16 22 5 2 2 2 2 2 3 3 3

KEY SCALE 1:150 M


1 Desk 12 Chair, dental
2 Chair, upright, stacking 13 Dental unit with monitor
3 Cabinet, file, steel 14 Dental unit, hydraulic
4 Counter, 900mm high, cabinets 15 Dental operating light
below 16 Stool, adjustable
5 Sink, with gooseneck spout 17 Waste bin
6 Sink, elbow-controlled 18 Dental X-ray, wall model
7 Developing tank
8 Compressor, dental air 19 Dental Laboratory
9 Instrument sterilizer 20 Outlet : Gas, Air, Eletric
10 Amalgamator 21 Rack, towel
11 Cabinet, dental instrument 22 Concealed floor drain

230
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (ENT) 250B-OPD-RDS-11A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is ambulatory Compressed air & vacuum apparatus 1
b. Patient may arrive in wheelchair Table, treatment 1
c. Transfer patient to/from a wheelchair to examining Table, with instrument 1
table and vice versa ENT instruments 1
d. Use of monitoring/diagnostic equipment ENT chair-diagnostic 1
e. Medical, surgical, nursing and first aid activities Head mirror 1
Instrument Sterilizer 2
Sharps collector 1
Examination light 1
Indirect laryngoscopy 1
Otoscope 1
Sphygmomanometer 1
Adult weighing scale 1
Stethoscope, non-mercurial 1
Surgical set 1
Alligator forcep 1
ENT endoscopy set 1
People Involved: Thermometer, digital 1
1 x Medical Specialist Whiteboard 1
1 x Nurse Rack, towel 1
1 x Patient Clock 1
Waste bin 2
Footstool 1
FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Desk, 600 x 1200mm 2
Chair, upright, stacking 3
Chair, gang-type 2
Cabinet, steel; filing 3
Stool, adjustable height 1
Counter, 900mm high, cabinets 1
above and below
Sink, with gooseneck spout & 1
Planning Relationships: foot/elbow control
a. Close to OPD Consultation Rooms Sink, combination instrument/scrub 1
b. Adjacent to consultation room (Ophtha) w/ gooseneck spout & foot/elbow
control
This activity space provides facilities needed for Cabinet, supply 1
the delivery of general patient care Concealed floor drain 1
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
ENGINEERING TERMINALS
Window curtain rail 2
Outlet, 10A,2P,240V, duplex 10 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 2
Outlet, Telephone 2
Smoke detector 2

231
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (ENT) 250B-OPD-RDS-11B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 5,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: instrument sterilizer

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

232
6000
3000 3000

19 17

2
10
1
2
T 7

6000
3 3 D
SD SD

11 12
12 9
4 13
1 T
D 18 16
5
2 14
5 CH
6
15 21
5 20 8 20

KEY SCALE 1:100 M


1 Desk, 600 x 1200mm 14 Counter, 900mm high, cabinets
2 Chair, upright, stacking above and below
3 Chair, gang-type 15 Sink, with gooseneck spout &
4 Adult weighing scale foot/elbow control
5 Cabinet, steel; filing 16 Sink, combination instrument/scrub;
6 Whiteboard w/ gooseneck spout & foot/elbow
7 Table, treatment control
8 Table, with instrument 17 Cabinet, supply
9 Compressed air and vacuum apparatus 18 Rack, towel
10 Footstool 19 Clock
11 Stool, adjustable height 20 Waste bin
12 Examination light 21 Concealed floor drain
13 ENT Chair

233
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (OPHTHA) 250B-OPD-RDS-12A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is ambulatory Examinination light 1
b. Patient may arrive in wheelchair Trial lens case 1
c. Transfer patient to/from a wheelchair to examining Illuminated test card cabinet 1
table and vice versa Clock 1
d. Use of monitoring/diagnostic equipment IV stand 1
e. Medical, surgical, nursing and first aid activities Minor ophthalmic set 1
Trolley 1
Tonometer 1
Opthalmic set 1
Sneller chart 1
Sphygmomanometer, non-mercurial 1
Adult weighing scale 1
Stethoscope, non-mercurial 1
Swivel chair 1
Sharps collector 1
Rack, towel 1
Table, treatment 1
People Involved: Compressed air & vacuum apparatus 1
1 x Resident Physician Waste bin, w/ yellow lining 2 infectious
1 x Medical Specialist
1 x Patient FURNITURE AND QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
1 x Intern Desk 1
Nursing Affiliates Chair, upright, stacking 10
Clinical Secretary Chair, ENT 1
Stool, adjustable height 2
Cabinet, steel, filing 3
Counter, 900mm high, 1
cabinets above and below
Sink, with gooseneck spout & 1
foot/elbow control
Sink, combination instrument/ 1
scrub; w/ gooseneck spout
Planning Relationships: & foot/elbow control
a. Close to OPD Consultation Rooms Cabinet, supply 1
b. Adjacent to consultation room (ENT) Concealed floor drain 1

This activity space provides facilities needed for ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
the delivery of general patient care ENGINEERING TERMINALS
Window curtain rail 1
Outlet, 10A,2P,240V, duplex 9 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 2

234
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (OPHTHA) 250B-OPD-RDS-12B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

235
6000

16 5
12 CH 11
5 17 4 16
2
T 5 15
D 1
6 7
2
2 2 9

6000
SD SD
2 2 3
2 2 4 8
13
2 2

10

14

KEY SCALE 1:100 M


1 Desk 11 Counter, 900mm high,
2 Chair, upright, stacking cabinets above and below
3 Chair, ENT 12 Sink, with gooseneck spout &
4 Stool, adjustable height foot/elbow control
5 Cabinet, steel, filing 13 Sink, combination instrument/
6 Adult weighing scale scrub; w/ gooseneck spout
7 Table, treatment & foot/elbow control
8 Examination light 14 Cabinet, supply
9 Compressed air and vacuum 15 Rack, towel
apparatus 16 Waste bin
10 Trolley 17 Concealed floor drain

236
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (TB-DOTS) 250B-OPD-RDS-13A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is ambulatory Stethoscope 2
b. Clinical handwashing Thermometer, non-mercurial 2
c. Recording and reporting of TB data Examination bed 2
d. Sputum microscopy for diagnosis Sphygmomanometer, non-mercurial 2
e. Distribution of anti-TB drugs Footstool 2
Mayo table 2
Gooseneck Lamp 2
Computer 1
Towel rack 2
Printer 3
Waste bin, foot-controlled 4
Puncture-proof container 1
Negatoscope 2

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Resident Physician FIXTURE CHECKLIST
1 x Nursing Attendant Chair, upright, stacking 11
1 x Patient Counter, 900mm high, 2
1 x Patient's companion cabinets above and below
Sink, with drainboard 2
Desk 3
Cabinet, filing 3
Counter, cabinets below 2
Sink 2
Concealed floor drain 4
Water Closet 1
Urinal 1
Lavatory 1

Planning Relationships:
a. Close to other Ancillary Services ADDITIONAL EQUIPMENT & QUANTITY REMARKS
b. Within the OPD Department but with separate ENGINEERING TERMINALS
entrance for patients Window curtain rail 2
Outlet, 10A,2P,240V, duplex 20 grounding type,
This activity space provides facilities needed for universal slots
the delivery of general patient care Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 4
Exhaust fan 1

237
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CONSULTATION ROOM
April 2016 OUTPATIENT (TB-DOTS) 250B-OPD-RDS-13B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 3

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patients

Fire risk LOW: medium: high

Other risks NA

238
14900
4300 4400 3100 3100

17 15 17 15 18 178 8 8
14 14
11 18 11 18 5
4 4 18 17
10 16 10 16
SD SD
6
12 12 2
13 13

6000
9 9 7 DT 2
SD
2 2 CH 2 CH 2
SD
7 2 7 2 2 2
3 3 2
1
19

KEY SCALE 1:200 M


1 Receiving Area : 9 Consult/Exam Room :
2 Chair, upright, stacking 10 Examination bed
3 Counter, 900mm high, 11 Table, Mayo
cabinets above and below 12 Footstool
4 Sink, with drainboard 13 Lamp, gooseneck
5 Toilet 14 Counter, cabinets below
15 Sink
6 Interview Area : 16 Negatoscope
7 Desk 17 Waste bin
8 Cabinet, filing 18 Concealed floor drain

19 Storage/Supply Room

239
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT STAFF PANTRY & LOUNGE 250B-OPD-RDS-14A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. OPD staff make use of toilet facilities Electric fan 1
b. OPD staff eat during breaks Waste bin w/ black lining 1
c. Staff reads, writes and uses telephone
d. Staff rests while awaiting their shifts

People Involved: FURNITURE AND QUANTITY REMARKS


OPD staff and doctors FIXTURE CHECKLIST
Sofa, 2-seater 1
Chair, dining 6
Table, 6-seater 1
Table, side 1
Counter, 900mm high, 1
cabinets above and below
Sink, with drainboard 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT & QUANTITY REMARKS


Planning Relationships: ENGINEERING TERMINALS
a. Accesible from all OPD facilities Window curtain rail 1
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A, 2P 240V, single 1 for emergency light
Smoke detector 2

240
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT STAFF PANTRY & LOUNGE 250B-OPD-RDS-14B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit OPD staff

Fire risk LOW: medium: high

Other risks NA

241
3000

4 1

2 3 2

6000
SD

2 2

8
5 7
6

KEY SCALE 1:100 M


1 Sofa, 2-seater 5 Counter, 900mm high,
2 Chair, dining cabinets above and below
3 Table, 6-seater 6 Sink, with drainboard
4 Table, side 7 Waste bin
8 Concealed floor drain

242
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT PUBLIC TOILETS 250B-OPD-RDS-15A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient, patient's companions, hospital visitors makes Waste bins, foot-controlled 2
use of toilet facilities Exhaust fans 2

People Involved: FURNITURE AND


QUANTITY REMARKS
Patients FIXTURE CHECKLIST
Patients' companions Counter, open below; with 2
Hospital visitors vanity mirror
Lavatory, over-the-counter 4
Water closet 5
Partition, cubicle, with door 5
Slop sink 2
Partition, urinal 2
Urinal 2
Floor drain 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accessible from all OPD facilities
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A, 2P 240V, single 1 for emergency light

243
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT PUBLIC TOILETS 250B-OPD-RDS-15B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit general public

Fire risk LOW: medium: high

Other risks NA

244
3100 3100

10 6 3 2 3
11
4
8
5
SH 7 9
4 8
5 9

6000
4 5
5 4

SH 5
1 4
11
3 3
2 10 6

KEY SCALE 1:100 M


1 FEMALE PUBLIC TOILET: 7 MALE PUBLIC TOILET:
2 Counter, open below; with 8 Partition, urinal
vanity mirror 9 Urinal
3 Lavatory, over-the-counter 10 Waste bin, general
4 Water closet 11 Floor drain
5 Partition, cubicle, with door
6 Slop sink

245
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT CLINIC (TYPICAL) 250B-OPD-RDS-16A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot Examination light 1
b. Patient may arrive on wheelchair Sphygmomanometer 1
c. Transfer patient to/from wheelchair to examining Examination bed 1
table and vice versa Gooseneck lamp 1
d. Clinical handwashing Stethoscope 1
e. Use of monitoring/diagnostic equipment IV stand with IV fluid 1
f. Medical, surgical, nursing and first aid Sharps collector, puncture- 1
activities proof container
Footstool 1
Waste bin, black lining 1
Waste bin, yellow lining 1
Note: provide other equipment and accessories necessary to
specific clinic type
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Desk 1
People Involved: Chair, upright, stacking 3
1 x Physician Cabinet, steel, filing 2
1 x Nurse or secretary Counter, 900mm high, cabinets 1
1 x Patient above and below
Sink, w/ gooseneck faucet 1
Concealed floor drain 1
Note: provide other furniture and fixture necessary to
specific clinic type
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 6 grounding type,
Planning Relationships: universal slots
a. Close to other Ancillary Services Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, data 1
This activity space provides facilities needed for Outlet, telephone 1
the delivery of general patient care Smoke detector 1
Cubicle curtain rail 1
Note: provide terminals and related accessories necessary to
specific clinic type

246
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OUTPATIENT CLINIC (TYPICAL) 250B-OPD-RDS-16B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit patient and medical staff

Fire risk LOW: medium : high

Other risks NA

247
3000

12 9
8 7 CH
13 10

4
5
6

6000
11 SD 2

3
3
12

2
T
2 1 D

KEY SCALE 1:100 M

1 Desk 8 Sink, with gooseneck faucet;


2 Chair, upright, stacking stainless steel
3 Cabinet, steel, filing 9 Cart, supply
4 Examination bed 10 Sharps container
5 Footstool 11 Cubicle curtain with rod
6 Examination light 12 Waste bin
7 Counter, 900mm high, cabinets 13 Concealed floor drain
above and below

248
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
RECEPTION/ WAITING AREA 250B-ASC-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient enters room with relative/companion Computer with monitor and 1
(Patient may be ambulant, in a wheelchair, printer
or on a stretcher) Waste bin 1
b. Patient approaches reception counter and
registers / companion registers for patient
c. Patient waits for his/her turn: consultation,
examination, procedure, etc.
d. Patient gets called for his/her turn
e. Clinical handwashing
f. Use of monitoring/diagnostic equipment
g. Surgical activities

People Involved: FURNITURE AND


QUANTITY REMARKS
Patients FIXTURE CHECKLIST
Relatives/companions Chair, swivel 1
Nurse Chair, visitor 1
Nursing attendant Chair, gang-type 2
Desk 1
Cabinet, steel, filing 3

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accesible to ancillary services Outlet, 10A,2P,240V, duplex 4 grounding type,
b. Near Consult/Exam Room universal slots
c. Near Treatment Room Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Outlet, data 1
Smoke detector 1
Window curtain rail 1

249
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
RECEPTION/
April 2016
AMBULATORY
SURGERY CLINIC WAITING AREA 250B-ASC-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ASC patients and staff

Fire risk LOW: medium: high

Other risks NA

250
3000

6 5
5

2 5
T
D 1

6000
SD

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 4 Chair, gang-type


2 Chair, swivel 5 Cabinet, steel; filing
3 Chair, visitor 6 Waste bin

251
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
TREATMENT ROOM 250B-ASC-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient enters room with relative/companion Examination table/bed 2
(Patient may be ambulant, in a wheelchair, Examination lamp 2
or on a stretcher) Instrument cart 2
b. Clinical handwashing Suction apparatus 2
c. Use of diagnostic equipment Glucometer 2
d. Patient is treated for minor injuries and/or illness Negatoscope 2
e. Transfer of patient to ASC Recovery Room, or Thermometer, non-mercurial 2
Operating Room, or be discharged Sphygmomanometer, non-mercurial 2
Neuro hammer 2
Stethoscope 2
IV Stand 2
Suture removal set, surgical 1 each
set, ortho set, EENT
People Involved: diagnostic set, etc.
2 x Patients Pulse oximeter 2
2 x Nurses Waste bins, various types 6
2 x Nursing Attendants FURNITURE AND
QUANTITY REMARKS
2 x Physicians FIXTURE CHECKLIST
Footstool 2
Table, side 2
Cubicle curtain and rod 2
Lavatory, wall-hung 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near Waiting Area Outlet, 10A,2P,240V, duplex 9 grounding type,
b. Near Ambulatory Surgery Clinic Operating Room universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Smoke detector 2
Window curtain rail 2
Window curtain rail

252
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
TREATMENT ROOM 250B-ASC-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 5,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.5

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff, patients

Fire risk LOW: medium: high

Other risks NA

253
6000
3000 3000

8 8

7 7

6000
SD SD

4 4

9 1 9 1
3 3

5 5
6 2 6 2

KEY SCALE 1:100 M

1 Examination table 6 Lavatory, wall-hung


2 Table, side; 400 x 500mm 7 Negatoscope
3 Footstool 8 Cubicle curtain and rod
4 Instrument cart 9 Waste bin
5 Examination lamp

254
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
CONSULT/ EXAM 250B-ASC-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient enters room with relative/companion Examination table/bed 1
(Patient may be ambulant, in a wheelchair, Examination lamp 1
or on a stretcher) Instrument cart 1
b. Doctor examines patient records Opthalmoscope 1
c. Clinical handwashing Otoscope 1
d. Doctor examines patient using Negatoscope 1
monitoring/diagnostic equipment Thermometer, non-mercurial 1
e. Surgical activities Sphygmomanometer, non-mercurial 1
Neuro hammer 1
Stethoscope 1
IV Stand 1
Suture removal set, etc. 1 each
Waste bins, various types 3
People Involved:
1 x Patient FURNITURE AND
QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
1 x Nursing Attendant Desk 1
1 x Physician Chair, swivel 1
Chair, visitor 1
Stool, adjustable height 1
Footstool 1
Table, side 1
Counter, w/ cabinets 1
Sink, stainless steel 1
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near Waiting Area Outlet, 10A,2P,240V, duplex 5 grounding type,
b. Near Treatment Room universal slots
c. Near Ambulatory Surgery Clinic Operating Room Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Outlet, data 1
Smoke detector 1
Window curtain rail 1

255
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
CONSULT/ EXAM 250B-ASC-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff, patients

Fire risk LOW: medium: high

Other risks NA

256
3000

T 1 3
D
2

15 13

11

6000
SD
10
7
6
12
5

4 14
15 16 8 CH 9
17

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 10 Examination lamp


2 Chair, swivel 11 Instrument cart
3 Chair, visitor 12 Negatoscope
4 Stool, adjustable height 13 Cubicle curtain and rod
5 Table, side; 400 x 500mm 14 Concealed floor drain
6 Examination table 15 Waste bin, infectious
7 Footstool 16 Waste bin, pathological and
8 Counter, with cabinets below anatomical
9 Sink, stainless steel 17 Sharps container

257
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
PATIENT DRESS/ TOILET 250B-ASC-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient enters room to change into Gown 1
gown; clean linen from cabinet Waste bin 1
b. Toileting activities
c. After procedure / discharge from Recovery
Room, patient returns to dressing room cubicle
and changes back into own clothing; soiled
linen is placed in hamper

People Involved: FURNITURE AND


QUANTITY REMARKS
Patients FIXTURE CHECKLIST
Relatives/companions Chair, upright; stacking 2
Shelf, for clean linen 1
Hamper, for soiled linen 1
Cubicle curtain and rod 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near Waiting/Reception Area Outlet, 10A,2P,240V, duplex 2 grounding type,
b. Near Treatment Room universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

258
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
PATIENT DRESS/ TOILET 250B-ASC-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) NA Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ASC patients and staff

Fire risk LOW: medium: high

Other risks NA

259
4000

2
1
4

4500
SD
5
2 3
1

1500

KEY SCALE 1:100 M

1 Cubicle curtain and rod


2 Low partition, 1800mm high
3 Chair, upright; stacking
4 Hamper, soiled linen
5 Shelf, clean linen

260
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
SCRUB-UP AREA 250B-ASC-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Physician and nurses wash hands and arms Soap dispenser 3
with water and soap before and after Hand dryer 1
surgical operation / procedure in the Operating Room Waste bin 1
b. Use of hand dryer Clock 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Physician FIXTURE CHECKLIST
1 x Nurse Scrub sink, 3-station; with 1
goose-neck spout and
foot-control
Shelves, overhead 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Operating Room Outlet, 10A,2P,240V, duplex 2 grounding type,
b. Near Staff Dress & Toilet universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

261
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
SCRUB-UP AREA 250B-ASC-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) 250

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 30 Standby light essential:desirable:UNNECESSARY

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.6

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at scrub sink

tolerated Maximum temperature (°C) 70

Access limit ASC medical staff

Fire risk LOW: medium: high

Other risks NA

262
2500

6
57

2700
SD
4
1
2
3

KEY SCALE 1:100 M

1 3-Station scrub sink, with goose- 4 Shelves, overhead


neck spout & foot control, 5 Waste bin
sensor type 6 Clock
2 Soap dispenser 7 Concealed floor drain
3 Hand dryer

263
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
CLEAN-UP AREA 250B-ASC-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Physician and nurses wash hands and arms Soap dispenser 3
with water and soap before and after Hand dryer 1
surgical operation / procedure in the Operating Room Waste bin, infectious 1
b. Use of hand dryer
Waste bin, pharmaceutical 1

Sharps container 1

Hamper, soiled linen 1

Clock 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Physician FIXTURE CHECKLIST
1 x Nurse Double compartment laundry 1
sink w/ drainboard
Shelves, overhead 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Operating Room Outlet, 10A,2P,240V, duplex 2 grounding type,
b. Near Staff Dress & Toilet universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

264
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
CLEAN-UP AREA 250B-ASC-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) 250

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 30 Standby light essential:desirable:UNNECESSARY

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.6

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at scrub sink

tolerated Maximum temperature (°C) 70

Access limit ASC medical staff

Fire risk LOW: medium: high

Other risks NA

265
2500

6 4 5 7

3300
SD CH

KEY SCALE 1:100 M

1 Counter, with cabinets above 4 Waste bin, infectious


and below 5 Waste bin, pharmaceutical
2 Double compartment laundry 6 Sharps container
sink with drainboard 7 Concealed floor drain
3 Hamper, soiled linen

266
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
RECOVERY ROOM 250B-ASC-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives in a stretcher trolley Stretcher bed 3
b. Patient is transferred from stretcher trolley to bed Outlet, oxygen; wall-mounted 3 per bed; 1.6m high
c. Regular monitoring of patient's vital signs Outlet, suction; wall-mounted 3 per bed; 1.6m high
d. Use of monitoring and diagnostic equipment Suction apparatus 3 per bed; 1.6m high
e. Patient is transferred to wheelchair and Cart, instrument 1
discharged from Ambulatory Surgery Clinic Clock 1
Waste bin, general 1
Waste bin, infectious 1
Waste bin, pharmaceutical 1
Sharps container 1

People Involved: FURNITURE AND


QUANTITY REMARKS
3 x Patient FIXTURE CHECKLIST
1 x Nurse Desk 1
1 x Nursing Attendant Table, side 3
1 x Physician Chair, upright; stacking 1
Chair, visitor 2
Cabinet, steel; filing 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near Ambulatory Surgery Clinic Operating Room Outlet, 10A,2P,240V, duplex 10 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Outlet, data 1
Nurse Call System 1
Bed light 3 per bed;
at bed head
Smoke detector 1
Window curtain rail 2

267
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
RECOVERY ROOM 250B-ASC-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.5

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at toilet lavatory

tolerated Maximum temperature (°C) 70

Access limit ASC medical staff, patients

Fire risk LOW: medium: high

Other risks NA

268
7000
2000 5000

5 4 4

2
6
T
11 1 D
10
12 9 3

6000
SD
3
7
8

6 6
9

5 5

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 8 Clock


2 Chair, upright; stacking 9 Waste bin, general
3 Chair, visitor 10 Waste bin, infectious
4 Cabinet, steel; filing 11 Waste bin, pharmaceutical
5 Table, side; 400 x 500mm 12 Sharps container
6 Stretcher/hospital bed
7 Instrument cart

269
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
OPERATING ROOM 250B-ASC-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on wheelchair or stretcher trolley Operating table 1
b. Patient is transferred to operating table Operating lamp 1
c. If necessary, anesthesia is administered, Anesthesia unit 1 w/ scavenging sys
d. Clinical handwashing Suction apparatus 1
e. Use of diagnostic equipment Negatoscope 1
f. Pre-operative care is given to the patient Mayo table 1
g. Patient is surgically operated on Anesthesist's table 1
h. After procedure/operation, patient is stabilized Instrument table 1
and wheeled out of the room Pack table 1
Single basin stand 1
Double basin stand 1
Kick bucket 1
Medical gas unit 1 Oxygen, Nitrogen
People Involved: Tracheostomy, surgical, ortho set 1 each
1 x Patient Laryngoscope 1
1 x Nurse, circulatory Cardiac monitor w/ pulse oximeter 1
1 x Nurse, scrub Defibrillator 1
2 x Physicians Sphygmomanometer, non-mercurial 1
1 x Anesthesiologist FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Footstool 2
Stool, adjustable 1
Stool, anesthetist's 1
Shelf 1
Clock 1
Planning Relationships: ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
a. Adjacent to Scrub-Up Area ENGINEERING TERMINALS
b. Near Recovery Room Outlet, 10A,2P,240V, duplex 10 grndg type, univ'l
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Outlet, data 1
Smoke detector 1
Isolation monitor 1 1600mm fr FFL
Grounding terminal 4 duplex
Heat detector 1 hospital grade
Window curtain rail 2

270
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
OPERATING ROOM 250B-ASC-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 700 - 1,000

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000 - 40,000

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.5

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff, patients

Fire risk low : medium: HIGH

Other risks NA

271
6000

5
13
7
14
3
15
4 4

6000
2 SD
12
9 1 16
9 6
10
8 11

18 DT 17

KEY SCALE 1:100 M

1 Operating table 10 Anesthetist's table


2 Operating lamp 11 Anesthesia unit
3 Mayo table 12 Kick bucket
4 Footstool 13 Shelf, adjustable
5 Instrument table 14 Pack table
6 Single basin stand 15 Clock
7 Double basin stand 16 Double film negatoscope
8 Anesthetist's stool 17 Floor clean-out
9 Adjustable stool 18 Door; with vision panel

272
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
STERILIZATION ROOM 250B-ASC-RDS-09A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Washing of instruments Sterilizer, dressing 1
b. Sterilizing of instruments Sterilizer, hot air 1
c. Preparation of sterilized instruments for Sterilizer, instrument 1 w/ scavenging sys
future use Autoclave 1
Rack, glove drying 1
Sharps container 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Sterilization Room Staff FIXTURE CHECKLIST
1 x Nurse Counter, with cabinets 1
1 x Nursing Attendant above and below
Sink, deep; with drainboard 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Near Ambulatory Surgery Clinic Operating Room ENGINEERING TERMINALS
b. Near Ambulatory Surgery Clinic Sterile Instrument Outlet, 10A,2P,240V, duplex 5 grounding type,
and Supply Storage Room universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1

* Note : provide circuit breaker/s


where necessary

273
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
AMBULATORY
SURGERY CLINIC
STERILIZATION ROOM 250B-ASC-RDS-09B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit ASC medical/service staff

Fire risk LOW: medium: high

Other risks exposure to hazardous chemicals

274
3500

3 6
CH
4 5
CH

3400
7 SD
1

2
9 10
8

KEY SCALE 1:100 M

1 Counter, with cabinets above 6 Autoclave


and below 7 Rack, glove drying
2 Deep sink with drainboard 8 Sharps container
3 Sterilizer, dressing 9 Door, with vision panel
4 Sterilizer, hot air 10 Concealed floor drain
5 Sterilizer, instrument

275
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ASC-RDS-10A
AMBULATORY STERILE INSTRUMENT SUPPLY &
April 2016 STORAGE ROOM
SURGERY CLINIC
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of sterilized/washed instruments
b. Dispensing of supplies in ASC
c. Inventory of instruments and supplies

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Sterilization Room Staff FIXTURE CHECKLIST
Shelves 1
Cabinet 3
Cart 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Near Ambulatory Surgery Clinic Operating Room ENGINEERING TERMINALS
b. Near Ambulatory Surgery Clinic Sterilization Room Outlet, 10A,2P,240V, duplex 2 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1

276
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ASC-RDS-10B
AMBULATORY STERILE INSTRUMENT
April 2016 SUPPLY & STORAGE ROOM
SURGERY CLINIC
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ASC medical/service staff

Fire risk low: medium: HIGH

Other risks NA

277
3500

2 3

2600
2
SD

4
2 1

KEY SCALE 1:100 M

1 Shelves, 450mm deep


2 Cabinet; instrument, etc.
3 Cart, instrument
4 Door, with vision panel

278
SCALE 1:300 M

12000

TREATMENT AREA T T CONSULT/


EXAM
12000

INFO/
SUPPLY
RECEPTION

GYM
AREA

WAITING
AREA

279
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHYSICAL REHAB RECEPTION & WAITING 250B-PR-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Reception/waiting area for patients, relatives, and White board 1
visitors.
Waste bin, w/ black or 2
colorless lining

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Receptionist FIXTURE CHECKLIST
Patients, relatives, and visitors Counter, two-level 1
Chair, upright, stacking 2
Chair, gang-type 2
Cabinet, filing, steel 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Preferably near the Main Hospital Lobby ENGINEERING TERMINALS
b. Preferably at the Ground Floor Window curtain rail 1
Outlet, 10A, 2P, 240V, duplex 6 grounding type,
universal slots
ACU, window/split type 1
Outlet, intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, Data 1
Smoke Detector 1 Ionization type

280
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHYSICAL REHAB RECEPTION & WAITING 250B-PR-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Phys Rehab staff, patients, visitors

Fire risk LOW: medium: high

Other risks NA

281
4
2 TD
CH
2
1

6600
SD

3 3

3000

KEY SCALE 1:100 M

1 Counter, 2-level 4 White board


2 Chair; upright, stacking 5 Waste bin
3 Chair; gang-type 6 Wheelchair park/area

282
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHYSICAL REHAB CONSULT/EXAM ROOM 250B-PR-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot. Sphygmomanometer, non-mercurial 1

b. Patient may arrive on wheelchair or stretcher trolley Examination table 1

c. Patient is transferred to/from wheelchair or Negatoscope 1


stretcher trolley to examination bed and vice versa Waste bin, general 1

d. Clinical handwashing
e. Use of monitoring/diagnostic equipment
f. Medical, nursing, and related activities FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Desk, 600 x 1200mm 1

Chair, upright, stacking 3


Table, side, 400 x 400mm 1
Foot stool 1

People Involved:
1 x Physician
1 x Nurse
1 x Patient, relatives, and visitor

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Waiting Area/Reception ENGINEERING TERMINALS
b. Adjacent to Treatment/Patient Area Window curtain rail 1
Outlet, 10A, 2P, 240V, duplex 5 grounding type,
universal slots
ACU, window/split type 1
Outlet, intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, Data 1
Smoke Detector 1 Ionization type

283
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHYSICAL REHAB CONSULT/EXAM ROOM 250B-PR-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Phys Rehab staff, patients, visitors

Fire risk LOW: medium: high

Other risks NA

284
2100

4
5
3
7

4000
SD
6
1 2
T
D
2
2

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm


2 Chair; upright, stacking
3 Table, side, with cabinet below
4 Examination table
5 Footstool
6 Negatoscope
7 Waste bin, general

285
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHYSICAL REHAB TREATMENT/GYM AREA 250B-PR-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
Ultrasound 3
a. Patient may arrive on foot. Exercise bike 2
b. Patient may arrive on wheelchair or stretcher Parallel bar, adjustable 1
trolley Stair exerciser 1
c. Patient is transferred to/from wheelchair or Pulley system, wall mounted 1
stretcher trolley to plinth, or therapy equipment Waste bin, general 2
and vice versa FURNITURE AND
QUANTITY REMARKS
d. Use of therapeutic equipment FIXTURE CHECKLIST
e. Therapeutic activities Chair, upright, stacking
Table, side, with cabinet below 3
Counter, with sink, and cabinets 1
above and below
Lavatory, wall-mounted 1
People Involved: Concealed floor drain 1
5-7 x Physical Therapists Plinth 3
5-7 x Patients
relatives, visitors

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Planning Relationships: Window curtain rail 1
a. Adjacent to Waiting Area/Reception Outlet, 10A, 2P, 240V, duplex 15 grounding type,
b. Adjacent to Toilets/Dress Cubicles universal slots
ACU, split type 2
Outlet, intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Smoke Detector 2
Ionization type

286
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHYSICAL REHAB TREATMENT/GYM AREA 250B-PR-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Phys Rehab staff, patients

Fire risk LOW: medium: high

Other risks NA

287
6100 2900

4 3 4 3 4 3
2 2 2

5400
1
5 5 5
CH SD
7
8 6
17 T

12000
D
16

1700
SD
3 10 18
3

10
14

4900
15
3 SD 3
3 12
11 14

3 16 9 13

KEY SCALE 1:200 M

1 TREATMENT AREA 10 Ergometer


2 Plinth 11 Parallel bars
3 Chair, upright, stacking 12 Exercise/training stairs
4 Table, side 13 Pulley exerciser, wall-mounted
5 Cubicle curtain with rod 14 Mirror, full-size
15 Clock
6 GYM AREA 16 Waste bin
7 Counter, with cabinets above 17 Concealed Floor Drain
and below
8 Sink, stainless steel 18 STORAGE ROOM
9 Lavatory, wall-hung

288
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-PR-RDS-04A
TOILETS, DRESS CUBICLES & SOILED
April 2016 PHYSICAL REHAB LINEN AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient makes use of toilet facilities Waste bin, general 2
b. Patient makes use of dressing cubicles Hamper, linen 1
c. Soiled/used linen is placed in hamper

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Water closet w/ spray hose 2
Lavatory 2
People Involved: Floor strainer 2
Physical Rehab patients and staff Grab bar, wall-mounted 2
Curtain rail with rod 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Waiting Area/Reception ENGINEERING TERMINALS
b. Adjacent to Treatment/Patient Area Window curtain rail 2
Outlet, 10A, 2P, 240V, duplex 2 grounding type,
universal slots
Smoke Detector 1 Ionization type

289
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-PR-RDS-04B
TOILETS, DRESS CUBICLES &
April 2016 PHYSICAL REHAB SOILED LINEN AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) NA Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Phys Rehab staff, patients, visitors

Fire risk LOW: medium: high

Other risks NA

290
250B-PR-RDS-04C

1900 1900

2 2

1900
1 3

2150
SD
5 5 5

1350
6
4 4
7

KEY SCALE 1:100 M

1 MALE TOILET
2 Waste bin

3 FEMALE TOILET

4 DRESS CUBICLE
5 Cubicle curtain and rod

6 SOILED LINEN HOLDING


7 Linen hamper, for soiled linen

291
SCALE 1:300 M

18000 6000

TOILET
WAITING STORAGE

UP
AREA

ISOLATION
PANTRY
12000

INFORMATION/
ADMITTING DIALYSIS TREATMENT AREA

6000
WATER
TREATMENT
RE-
ROOM
PROCESSING
CONSULT ROOM

292
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
INFORMATION, ADMITTING &
April 2016 DIALYSIS WAITING AREA 250B-DIA-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Information/Admitting area for patients, relatives, White board, wall mounted 1
and visitors Waste bin, w/ black or 1
b. Waiting area for patients, relatives, and visitors. colorless lining
c. Maintenance of OPD register

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Receptionist FIXTURE CHECKLIST
Patients, relatives, and visitors Desk, 600 x 1200mm 1
Chair, upright, stacking 3
Chair, gang-type 3
Cabinet, filing, steel 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near/accesible from the Main Hospital Lobby Outlet, 10A, 2P, 240V, duplex 7 grounding type,
universal slots
ACU, window/split type 1
Outlet, Intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, Data 1
Smoke Detector 2 Ionization type

293
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
INFORMATION, ADMITTING &
April 2016 DIALYSIS WAITING AREA 250B-DIA-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTAIL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Dialysis staff, patients, visitors

Fire risk LOW: medium: high

Other risks NA

294
3

3 3

SD
7 7

8900
SD

1
2
T D

2 2
6 4 4
5

3700

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 5 White board


2 Chair; upright, stacking 6 Waste bin
3 Chair; gang-type 7 Wheelchair park/area
4 Cabinet, filing, steel

295
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS CONSULT ROOM 250B-DIA-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot. Sphygmomanometer, non-mercurial 1
b. Patient may arrive on wheelchair or stretcher Examination table 1
trolley Waste bin, general 1
c. Patient is transferred to/from wheelchair or
stretcher trolley to examination bed and vice versa
d. Clinical handwashing
e. Use of monitoring/diagnostic equipment
f. Medical, nursing, and related activities

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Physician FIXTURE CHECKLIST
1 x Nurse Desk, 600 x 1200mm 1
1 x Patient, relatives, and visitor Chair, upright, stacking 3
Cart, supply 1
Foot stool 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Info/Admitting Area Window curtain rail 1
b. Near dialysis treatment area Outlet, 10A, 2P, 240V, duplex 5 grounding type,
universal slots
ACU, window/split type 1
Outlet, intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, Data 1
Smoke Detector 1 Ionization type

296
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS CONSULT ROOM 250B-DIA-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Dialysis staff, patients, visitors

Fire risk LOW: medium: high

Other risks NA

297
3700

2 2 T
1 D
2

3100
SD

5
4
6 3

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm


2 Chair; upright, stacking
3 Cart, supply
4 Examination table
5 Footstool
6 Waste bin, general

298
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS DIALYSIS TREATMENT AREA 250B-DIA-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot. Weighing scale, floor-type 1
b. Patient may arrive on wheelchair or stretcher Dialysis machine 8
trolley Bed, trolley/stretcher 5
c. Patient is weighed; weight and vital signs are Chair, dialysis; reclinable 3
recorded Emergency cart 1
d. Patient is transferred to/from wheelchair to Waste bin, general 2
dialysis chair, or stretcher trolley and vice versa
e. Use of dialysis equipment
f. Monitoring of dialysis treatment

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Physician-on-duty FIXTURE CHECKLIST
2 x Nurse Chair, upright, stacking 3
8 x Patients Counter, two-level 1
relatives, visitors Counter, with sink, and cabinets 1
below
Lavatory, wall-mounted 2
White board 1
Clock 1
Cubicle curtain and rod 8

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Information/Admitting Area Window curtain rail 1
Outlet, 10A, 2P, 240V, Duplex 22 grounding type,
universal slots
Outlet, 10A, 2P, 240V, Single 1 for emergency light
ACU, Split type 2
Outlet, Intercom 1 at Nurse Station
Outlet, Telephone 1 at Nurse Station
Smoke Detector 2 Ionization type

299
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIA-RDS-03B
DIALYSIS TREATMENT
April 2016 DIALYSIS AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR)

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: at sink & lavatory

tolerated Maximum temperature (°C) 70

Access limit Dialysis staff, patients

Fire risk LOW: medium: high

Other risks NA

300
8300 3800

4 2 4 2 4 2 9 11

5 5 5

6000
8 8 8
SD

12

CH 10

12000
13
T 11 9
7 2CH2 2 D
3 1 CH

6000
SD SD
8 8 8 8 8

5 5
6 6 6
4 2 4 2 4 2
4 2 4 2

12100
KEY SCALE 1:200 M

1 Counter, 2-level; with 7 Emergency cart


cabinets below 8 Cubicle curtain and rod
2 Chair; upright, stacking 9 Lavatory, wall-hung
3 Weighing scale, floor-type 10 Sink, stainless steel
4 Dialysis machine 11 Waste bin
5 Bed, trolley / stretcher 12 White board
6 Chair, dialysis; adjustable back, 13 Clock
fully reclinable

301
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS ISOLATION ROOM 250B-DIA-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on foot. Dialysis machine 1
b. Patient may arrive on wheelchair or stretcher Bed, trolley/stretcher 1
trolley Waste bin, general 1
c. Patient is weighed; weight and vital signs are
recorded
d. Patient is transferred to/from wheelchair to
dialysis chair, or stretcher trolley and vice versa
e. Use of dialysis equipment
f. Monitoring of dialysis treatment
g. Observance of infection control protocol for
isolated patient

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Physician FIXTURE CHECKLIST
1 x Nurse Chair, upright, stacking 1
1 x Patient, relatives, and visitor Lavatory, wall-mounted 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Information/Admitting Area Window curtain rail 1
b. Near Dialysis Treatment Area Outlet, 10A, 2P, 240V, duplex 4 grounding type,
universal slots
ACU, window/split type 1
Smoke Detector 1 Ionization type

302
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS ISOLATION ROOM 250B-DIA-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature 23 Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 10 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.75

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit Dialysis staff, patients

Fire risk LOW: medium: high

Other risks NA

303
3000

3 2

4000
SD

5 4

KEY SCALE 1:100 M

1 Bed, trolley / stretcher


2 Chair, upright; stacking
3 Dialysis machine
4 Lavatory, wall-hung
5 Waste bin, general

304
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIA-RDS-05A
JAN CLO., SOILED LINEN &
April 2016 DIALYSIS WASTE HOLDING AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
1. Janitor's Closet Counter, with deep sink 1
a. Storage of janitor's cleaning tools Mop rack 1
b. Use of slop sink for cleaning of tools/implements Mop bucket 1
Linen hamper 2 medical
2. Waste Holding Area Waste bin, color-coded 4 mobile
a. Storage of different types of waste :
general (biodegradable & non-biodegradable),
infectious, sharps

3. Soiled Linen Area


a. Holding area for soiled linen

People Involved: FURNITURE AND QUANTITY REMARKS


Dialysis staff FIXTURE CHECKLIST
Janitor/Utility staff Slop sink 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Dialysis Treatment Area Window curtain rail 1
Outlet, 10A, 2P, 240V, duplex 3 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke Detector 2 Ionization type

305
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
JAN CLO., SOILED LINEN &
April 2016 DIALYSIS WASTE HOLDING AREA 250B-DIA-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Dialysis staff, utility staff

Fire risk LOW: medium: high

Other risks NA

306
3000

800
8 9 10 11

1700
SD

4100
7

6
5

1600
SD
4
CH 1 2 3

KEY SCALE 1:100 M

JANITOR'S CLOSET : SOILED LINEN AREA :


1 Counter, with top and 7 Linen hamper, for soiled linen
bottom cabinets
2 Sink, stainless steel WASTE HOLDING AREA :
3 Slop sink, with faucet bibb 8 Waste bin, green lining
4 Concealed floor drain 9 Waste bin, black lining
5 Mop rack 10 Waste bin, yellow lining
6 Mop bucket, with casters 11 Waste bin, for sharps;
puncture-proof

307
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS PANTRY 250B-DIA-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Dialysis staff makes use of the pantry Refrigerator 1
b. Dialysis patients make use of the pantry Counter, with sink 1
c. Dialysis staff does clean up activities Waste bin, general 1
Waste bin, biodegradable 1 medical

People Involved: FURNITURE AND QUANTITY REMARKS


Dialysis staff FIXTURE CHECKLIST
Dialysis patients Concealed floor drain 1
Patient relatives, visitors

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near dialysis treatment area Outlet, 10A, 2P, 240V, duplex 3 grounding type,
universal slots
Smoke Detector 1 Ionization type

308
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS PANTRY 250B-DIA-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Dialysis staff, patients, visitors

Fire risk LOW: medium: high

Other risks NA

309
3100

3000
SD
2

1
CH
6 5

KEY SCALE 1:100 M

1 Counter, with top and


bottom cabinets
2 Sink, stainless steel
3 Concealed floor drain
4 Refrigerator
5 Waste bin, general
6 Waste bin, bio-degradable waste

310
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS REPROCESSING ROOM 250B-DIA-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Dialysis staff brings used dialyzer for reprocessing Reprocessing sterilizing machine 1
b. Staff does washing activities Dialyzer rack 2
c. Staff uses reprocessing sterilizing machine Waste bin, general 1
d. Reprocessed dialyzer is placed in dialyzer rack
for storage
e. Staff does clean up activities

People Involved: FURNITURE AND QUANTITY REMARKS


Dialysis staff FIXTURE CHECKLIST
Counter, with sink, and cabinets 1
above and below
Sink, deep 2
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Near dialysis treatment area Window curtain rail 1
Outlet, 10A, 2P, 240V, duplex 4 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke Detector 1 Ionization type

311
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DIALYSIS REPROCESSING ROOM 250B-DIA-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-1000

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Dialysis staff

Fire risk LOW: medium: high

Other risks NA

312
2300

CH
3

4100
4
SD 1

4 2
6

KEY SCALE 1:100 M

1 Counter, with top and


bottom cabinets
2 Sink, deep
3 Reprocessor sterilizing machine
4 Dialyzer rack
5 Waste bin, general
6 Concealed floor drain

313
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.4 ANCILLARY SERVICE FACILITIES


3.4.1 PHARMACY
3.4.2 LABORATORY
3.4.3 BLOOD STATION
3.4.4 RADIOLOGY

First Edition
DEPARTMENT OF HEALTH
Manila
2017

315
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 ANCILLARY 250B-AN-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
PHARMACY 243.00 250B-PHAR-DDS-01 319
Chief Pharmacist's Office 18.00 250B-PHAR-RDS-01 320
Counseling Room 9.00 250B-PHAR-RDS-02 323
Dispensing Area & Drug Information 36.00 250B-PHAR-RDS-03 326
Receiving/ Breakout/ Inspection Area 36.00 250B-PHAR-RDS-04 329
Bulk Storage 108.00 250B-PHAR-RDS-05 332
Staff Pantry/ Lounge 18.00 250B-PHAR-RDS-06 335
Parenteral Admixture Room 9.00 250B-PHAR-RDS-07 338
Extemporaneous Preparation Area 9.00 250B-PHAR-RDS-08 341

LABORATORY 454.00 250B-LAB-DDS-01 344


Waiting Area 82.00 250B-LAB-RDS-01 345
Reception/ Receiving/ Releasing 15.00 250B-LAB-RDS-02 348
Extraction Area 17.00 250B-LAB-RDS-03 351
Conference Room 23.00 250B-LAB-RDS-04 354
Pathology Office/ Library 26.00 250B-LAB-RDS-05 357
Chief Pathologist's Office 16.00 250B-LAB-RDS-06 360
Chemistry 44.00 250B-LAB-RDS-07 363
Hematology 23.00 250B-LAB-RDS-08 366
Serology/Immunology 23.00 250B-LAB-RDS-09 369
Microbiology/Bacteriology 43.00 250B-LAB-RDS-10 372
Microscopy 23.00 250B-LAB-RDS-11 375
Histopathology 26.00 250B-LAB-RDS-12 378
Blood Typing, Cross Matching, Post BTR 25.00 250B-LAB-RDS-13 381
Glass Washing 9.00 250B-LAB-RDS-14 384
Autoclave 9.00 250B-LAB-RDS-15 387
Staff Locker Room and T&B 37.00 250B-LAB-RDS-16 390
Staff Pantry 13.00 250B-LAB-RDS-17 393

317
Hospital: Department of Health
250-Bed (Level 3)
SERVICE FACILITY SHEET INDEX
Hospital HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 ANCILLARY 250B-AN-SFSI-02
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
BLOOD STATION 124.00 250B-BS-DDS-01 396
Waiting Area 27.00 250B-BS-RDS-01 397
Screening & Assessment 12.00 250B-BS-RDS-02 400
Component Preparation Room 14.00 250B-BS-RDS-03 403
Testing Room 13.00 250B-BS-RDS-04 406
Blood Component Storage 20.00 250B-BS-RDS-05 409
Blood Collection Room 24.00 250B-BS-RDS-06 412
Staff Lockers, Pantry and T&B 14.00 250B-BS-RDS-07 415

RADIOLOGY 479.00 250B-RAD-DDS-01 418


Sub-Lobby/ Waiting Area 86.00 250B-RAD-RDS-01 419
Clerical Room 19.00 250B-RAD-RDS-02 422
Chief Radiologist's Office 16.00 250B-RAD-RDS-03 425
Conference Room 21.00 250B-RAD-RDS-04 428
Reading Room 21.00 250B-RAD-RDS-05 431
Files Room 12.00 250B-RAD-RDS-06 434
Ultrasound Room 20.00 250B-RAD-RDS-07 437
Mammography Room 21.00 250B-RAD-RDS-08 440
Radiographic X-Ray Room 30.00 250B-RAD-RDS-09 443
Radiographic X-Ray Control Room 11.00 250B-RAD-RDS-10 446
Radiographic-Fluoroscopic X-Ray Room 37.00 250B-RAD-RDS-11 449
CT-Scan 45.00 250B-RAD-RDS-12 452
CT-Scan Control Room 11.00 250B-RAD-RDS-13 455
MRI Magnet Room 44.00 250B-RAD-RDS-14 458
MRI Control Room 32.00 250B-RAD-RDS-15 461
MRI System Component Room 14.00 250B-RAD-RDS-16 464
Dark Room 6.00 250B-RAD-RDS-17 467
Staff Lounge/ T&B 33.00 250B-RAD-RDS-18 470

318
SCALE 1:300 M

12000

BULK
9000

STORAGE
ROOM
21000

STAFF WORK STAFF


AREA PANTRY
6000

RECEIVING/
BREAKOUT/
INSPECTION
AREA CHIEF
OFFICE
3000

COUNSELING EXTEMPORANEOUS
PARENTERAL
ROOM PREPARATION
ADMIXTURE
AREA
3000

DISPENSING DISPENSING
AREA AREA

3000 3000 3000 3000

319
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY CHIEF PHARMACIST'S OFFICE 250B-PHAR-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pharmacist reads, writes, and uses intercom on his desk Computer w/ printer 1
b. Pharmacist stores, files and retrieves records Waste bin w/ black lining 1
c. Pharmacist receives visitors Waste bin w/ yellow lining 1
d. Pharmacist develops policies
e. Pharmacist plans and coordinates activities
f. Pharmacist requisitions drugs and medicines for
actual procurements
g. Pharmacist maintains and updates dangerous drug book
(RA 9165) or the Comprehensive Dangerous Drugs Act
of 2002 FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Desk, 750mm x 1500mm 1
Junior executive chair 1
Chair, upright, stacking 2
Steel filing cabinet, 1
People Involved: 500mm x 700mm
1 x Pharmacist Cabinet, 400mm x 1200mm 1 for narcotics
Desk return (extension) 1
Shelving, 300m x 1500mm 1
for narcotic drugs

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Distribution Area ENGINEERING TERMINALS
b. Close to Patient Dispensing Area Outlet, 10A,2P,240V, duplex 6 grounding type,
c. Close to Staff Area universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1
Window blinds 2

320
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-PHAR-RDS-01B
CHIEF PHARMACIST'S
April 2016 PHARMACY OFFICE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacist, hosp. staff & visitors

Fire risk LOW: medium: high

Other risks NA

321
6000

7 7 DT 2 8
9
4 1
6

3000
SD

3 5

KEY SCALE 1:100 M

1 Desk 5 File cabinet


2 Desk return (extension), 6 Chair, junior executive
400 x 900mm 7 Chair, upright, stacking
3 Cabinet (for narcotics), 8 Waste bin, pharmaceutical
400 x 1200mm 9 Waste bin, general
4 Shelving, 300 x 1500mm

322
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY COUNSELING ROOM 250B-PHAR-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pharmacist evaluates the appropriateness of the drug Computer w/ printer 1
therapy being used by the patient Waste bin w/ black lining 1
b. Pharmacist recommends compliance of the patient with or colorless lining
the treatment regimen
c. Pharmacist advises the patient to understand his/her illness
and its treatment
d. Pharmacist gives the patient instructions about the proper
use of the medicines and knowledge about its side effects

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Pharmacist FIXTURE CHECKLIST
Desk, 600mm x 1200mm 1
Chair, upright, stacking 2
Clerical Chair, standard 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Patient Dispensing Area ENGINEERING TERMINALS
b. Close to Chief Pharmacist's Office Outlet, 10A,2P,240V, duplex 2 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1

323
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY COUNSELING ROOM 250B-PHAR-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.65

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacist, patient & companion

Fire risk LOW: medium: high

Other risks NA

324
3000

3000
3 SD
D
T 1
2
4

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm


2 Chair, clerical
3 Chair, upright, stacking
4 Waste bin

325
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
DISPENSING AREA & DRUG
April 2016 PHARMACY INFORMATION 250B-PHAR-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Screens, fills, dispenses drugs, medicines, and galenicals Computer w/ printer 5
b. Supplies floor stocks to wards and other treatment areas Pharmaceutical refrigerator 1
c. Provides drug information services w/ freezer
d. Preparation of IV admixtures Waste bin w/ yellow lining 1
e. Displays stocks on respective shelves Waste bin w/ black lining 2
Glass partition with transaction 2
window

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Pharmacist FIXTURE CHECKLIST
1 x Pharmacy aide Counter, transaction, with 2
300mm deep cabinets below
Table, computer 1
Chair; upright, stacking 1
Shelving, open 1
Sink, stainless 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Inpatient Nursing Wards ENGINEERING TERMINALS
b. Close to Out Patient Department and Emergency Outlet, 10A,2P,240V, duplex 9 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1

326
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
DISPENSING AREA &
April 2016 PHARMACY DRUG INFORMATION 250B-PHAR-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL


Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNESCESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacy staff

Fire risk low: medium: HIGH

Other risks NA

327
12000

9 10
1
CH

3000
8 SD SD 8
2
4
2
CH CH CH 5 7 TD 3 10
8 8 1 8 6
2

KEY SCALE 1:150 M

1 Counter, transaction, with 5 Sink, stainless steel


300mm deep cabinets below 6 Shelving, open
2 Glass partition with transaction 7 Refrigerator, pharmaceutical
window 8 Computer, with printer
3 Table, computer 9 Waste bin, pharmaceutical
4 Chair; upright, stacking 10 Waste bin, regular

328
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
RECEIVING/ BREAKOUT/
April 2016 PHARMACY INSPECTION AREA 250B-PHAR-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pharmacist receives/ inspects pharmaceutical & Exhaust fan 1
biological deliveries Waste bin w/ yellow lining 1
b. Records data of deliveries in stock cards Waste bin w/ black lining 1
c. Records data of stocks transferred from bulk storage or colorless lining
to the active storage

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Pharmacist FIXTURE CHECKLIST
1 x Storekeeper Counter, 750mm high, 1
w/ cabinets above & below
Sink-in-counter, drainboard 1
Chair, upright, stacking 1
Concealed floor drain w/ 1
waterless trap

Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS


a. Adjacent to Bulk Storage ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1

329
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-PHAR-RDS-04B
RECEIVING/ BREAKOUT/
April 2016 PHARMACY INSPECTION AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL


Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNESCESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacy staff, delivery, COA

Fire risk LOW:medium:high

Other risks NA

330
6000

CH
2
1
6 3

CH

6000
SD
4
5

KEY SCALE 1:100 M

1 Counter, 750mm high, with cabinets above & below


2 Sink, with drainboard
3 Chair, upright, stacking
4 Waste bin, pharmaceutical
5 Waste bin, general
6 Concealed floor drain
7 Exhaust fan

331
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY BULK STORAGE 250B-PHAR-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of pharmaceuticals Plastic Palletes 3
Waste bin w/ yellow lining 1
Waste bin w/ black lining 1
or colorless lining

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Pharmacist FIXTURE CHECKLIST
1 x Utility Worker Shelving, adjustable, rail mounted 7

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Receiving/ Breakout/ Inspection Area ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 10 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 4

332
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY BULK STORAGE 250B-PHAR-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacy staff

Fire risk low: medium: HIGH

Other risks NA

333
12000

2 SD
1 SD

9000
1
1

1
SD SD

34 2 2
1 1

KEY SCALE 1:200 M

1 Shelving, open, adjustable, rail


mounted
2 Pallet, plastic
3 Waste bin, pharmaceutical
4 Waste bin, general

334
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY STAFF PANTRY/ LOUNGE 250B-PHAR-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pharmacy staff eat their meals Computer w/ printer 1
b. Pharmacy staff rests and stores clothings Refrigerator 1
and other belongings at the lockers Water Dispenser 1
c. Staff do clean-up activities Waste bin w/ black lining 1 non-biodegradable
Waste bin w/ green lining 1 biodegradable

People Involved: FURNITURE AND


QUANTITY REMARKS
Pharmacy Staff FIXTURE CHECKLIST
Dining table, 4-seater 1
Dining chair 4
Steel lockers 4
Sink w/ drainboard 1
Counter w/ cabinets below 1
Lavatory 1
Water Closet 1
Concealed floor drain w/ 1
waterless trap

Planning Relationships ADDITIONAL EQUIPMENT & REMARKS


QUANTITY
a. Within the Pharmacy department ENGINEERING TERMINALS
Window curtain rail 1
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1

335
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY STAFF PANTRY/ LOUNGE 250B-PHAR-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacy staff

Fire risk LOW: medium: high

Other risks NA

336
6000

6
4 4 7

3000
SD 3 CH
5 4 4 1
10 5
5 2
5 89

KEY SCALE 1:100 M

1 Counter, with cabinets below 6 Refrigerator


2 Sink, with drainboard 7 Water dispenser
3 Table, 4-seater dining 8 Waste bin, general
4 Chair, dining 9 Floor drain, concealed
5 Locker, metal 10 Toilet

337
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY PARENTERAL ADMIXTURE 250B-PHAR-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pharmacist and pharmacist's assistant Pharmaceutical refrigerator 1
perform admixture activities inside the room Cabinet, IV visual clarity 1
b. Finished items/products are stored and/or inspection
placed in cart for release to nursing wards and Scanner, laser 1
other hospital units Compounding machine, high 1
speed
Counting machine, for tablet 1
and capsule
Cart, stainless steel; with 1
casters
Waste bin 2
People Involved: FURNITURE AND
QUANTITY REMARKS
1 x Pharmacist FIXTURE CHECKLIST
1 x Pharmacist's assistant Counter, work; with overhead 1
cabinets
Sink, stainless steel 1
Chair, upright 2
Dispenser, soap and paper 1
towel
Clock 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Planning Relationships: Outlet, 10A,2P,240V, duplex 5 grounding type,
a. Near or accesible to the Bulk Storage Room universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, Telephone 1

338
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
PARENTERAL
April 2016 PHARMACY ADMIXTURE 250B-PHAR-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 22 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacy staff

Fire risk low : medium : HIGH

Other risks NA

339
3000

4 98 7 6
2 1
3
12

3000
SD
T
11 10

5
13

KEY SCALE 1:100 M

1 Counter, work; with overhead 7 Scanner, laser; handheld


cabinets for storage 8 Machine, compounder; high
2 Sink, stainless steel; with faucet speed
3 Chair, upright 9 Machine, counting; tablet and
4 Dispenser, soap and paper towel capsule
5 Refrigerator, pharmaceutical 10 Cart, stainless steel; w/ casters
6 Cabinet, IV visual clarity 11 Clock
inspection 12 Waste bin
13 Window

340
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY EXTEMPORANEOUS PREP 250B-PHAR-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pharmacist and pharmacist's assistant Counting machine, for tablet 1
perform extemporaneous preparation and and capsule 1
compounding of medication as required Unit dose packing machine 1
b. Activities include preparation. Assembly, labeling Computer with printer 1
patient medications Waste bin 2
c. Clerical work is performed (documentation,
inventory, etc.)

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Pharmacist FIXTURE CHECKLIST
1 x Pharmacist's assistant Counter, work; with overhead 1
cabinets 1
Sink, stainless steel 1
Chair, upright 1
Clock 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Planning Relationships: Outlet, 10A,2P,240V, duplex 4 grounding type,
a. Near or accesible to Bulk Storage Room universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 3
Outlet, data 1
Outlet, telephone 1

341
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PHARMACY EXTEMPORANEOUS PREP 250B-PHAR-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature 22 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pharmacy staff

Fire risk low: MEDIUM : high

Other risks NA

342
3000

3 4 5
2 1

3000
SD
8
6
7
T
D 10

KEY SCALE 1:100 M

1 Counter, work; with overhead 6 Desk, work; with computer and


cabinets for storage printer
2 Sink, stainless steel; with faucet 7 Chair, upright
3 Pegboard, wall-mounted 8 Clock
4 Machine, counting; tablet and 9 Waste bin
capsule 10 Window
5 Machine, unit dose packer

343
12000 SCALE 1:300 M
3900 2100 6000

UP
JAN
2100 2100 2900

3300 2000 2900


CLO M STAFF
F STAFF LOCKERS T&B
T&B

AUTOCLAVE

GLASS
WASHING/
STORAGE
ROOM STORAGE PANTRY

3700
7300

MICROSCOPY

HISTOPATHOLOGY

5200
MICROBIOLOGY/
BACTERIOLOGY

1900
ANTE
STREAKING
ROOM
ROOM
11200

CHEMISTRY
3700

SEROLOGY/
IMMUNOLOGY
48000

4100

BLOOD TYPING,
CROSS MATCHING, POST
BTR INVESTIGATION
1500 3100

CHIEF PATHO
OFFICE
3700

HEMATOLOGY
2500

CMT
OFFICE
5900

PATHOLOGY
OFFICE
3700

AFFILIATES'
ROOM
2500

RECORDS
3700

ROOM
CONFERENCE
ROOM
4200

EXTRACTION
(2) RECEPTION/
RECEIVING/
RELEASING
7600
5200

WAITING
AREA
3000

2500 3900

344
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY WAITING AREA 250B-LAB-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patients await their turns to be examined attended to Waste bin w/ black or colorless 3
by Medical Laboratory Aide lining
b. Patients/ Donors await their turns for their blood to be
extracted

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Laboratory Aide FIXTURE CHECKLIST
Patients/ Relatives Counter; with queuing system 1
monitor
3-Seater Gang Chair 3
4-Seater Gang Chair 10
10-Seater Gang Chair 1
Water Closet 3
Urinal 1
Lavatory 2

Planning Relationships:
a. Close to Blood Donor's Room
b. Close to Pathologist's Office

ADDITIONAL EQUIPMENT & QUANTITY REMARKS


ENGINEERING TERMINALS

Outlet, 10A, 2P, 240V, duplex 5 grounding type,


universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Smoke Detector 2

345
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY WAITING AREA 250B-LAB-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff & general public

Fire risk LOW: medium: high

Other risks NA

346
12000

3 3 3 3 3 1

5200
SD 3 SD

3 3
3 3 3 3

4 3 3

3000

4
5

6
4

2500 3900

KEY SCALE 1:150 M

1 WAITING AREA 5 MALE TOILET


2 Counter; with queuing system
monitor 6 FEMALE TOILET
3 Chair, gang-type
4 Waste bin

347
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-02A
RECEPTION/ RECEIVING/
April 2016 LABORATORY RELEASING
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Medical Laboratory Aide attends to patients Computer w/ printer 1
b. Laboratory Staff receives specimen to be examined Waste bin w/ black lining 1
c. Laboratory Staff stores, files, and retrieves records
d. Laboratory Staff release examination results to patients

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Laboratory Aide FIXTURE CHECKLIST
2 x Clerks Counter, 2-level, with 1
Patients/ Relatives bottom shelves below
Counter, 900mm high, with 1
shelves below
Stool, adjustable height 2
Cabinet, steel, filing 5

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Pathologist's Office Outlet, 10A, 2P, 240V, duplex 4 grounding type
b. Accessible to Blood Donor's Room universal
c. Close to Main Laboratory Outlet, 10A, 2P, 40V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 1

348
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-02B
RECEPTION/ RECEIVING/
April 2016 LABORATORY RELEASING

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff and visitors

Fire risk LOW: medium: high

Other risks NA

349
6000

5 4 4 4 4 4 2
CH

2450
SD
T
3 3 D
CH CH
1

KEY SCALE 1:100 M

1 Counter, 2-level, with


bottom shelves below
2 Counter, 900mm high, with
shelves below
3 Stool, adjustable height
4 Cabinet, steel, filing
5 Waste bin, general

350
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY EXTRACTION AREA 250B-LAB-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Extraction of blood Cart, instrument 2
Cart, supply 2
Sharps container, wall-mounted 2
Waste bin, w/ black lining 2
Waste bin, w/ yellow lining 2 infectious

People Involved: FURNITURE AND QUANTITY REMARKS


2 x Medical Technologists FIXTURE CHECKLIST
2 x Laboratory Technicians Low partition, 1800mm high 1
2 x Patients Desk, 600 x 1000mm 2
Chair, swivel 2
Chair, upright, stacking 2
Chair, extraction 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Waiting Area Outlet, 10A, 2P, 240V, duplex 10 grounding type
b. Close to Pathologist's Room universal
c. Close to Receiving Area Outlet, 10A, 2P, 40V, single 1 emergency light
d. Adjacent to Screening Area Smoke Detector 1

351
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY EXTRACTION AREA 250B-LAB-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff and patients

Fire risk LOW: medium: high

Other risks NA

352
3900

8 9 7

2100
4
2
6
5 1 3

4200
SD 10
8 9 7

2100
4
2
6
5 1 3

KEY SCALE 1:100 M

1 Desk, 600 x 1000mm


2 Chair, swivel
3 Chair, upright, stacking
4 Chair, extraction
5 Cart, instrument
6 Cart, supply
7 Sharps container, wall-mounted
8 Waste bin, general
9 Waste bin, infectious
10 Low partition, 1800mm high

353
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY CONFERENCE ROOM 250B-LAB-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pathologist meets with Medical Technologist and White board/ projection screen 1
Medical Laboratory Technician/ Laboratory Aides, staff Projector, ceiling-mounted 1
and patient's relatives Waste bin w/ black lining 1
b. Pathologist interprets laboratory results
c. Forum for information sharing and discussion of
common laboratory procedures

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Pathologist FIXTURE CHECKLIST
Medical Technologist Table, conference, 10-seater 1
Medical Technician Chair, conference 10
Physicians
Hospital Staff
Companion/ Watcher

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Pathologist's Office and staff Outlet, 10A, 2P, 240V, duplex 7 grounding type
universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1
Outlet, Telephone 1
Outlet, DATA 1

354
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY CONFERENCE ROOM 250B-LAB-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff and visitors

Fire risk LOW: medium: high

Other risks NA

355
6000

2 2 2 2
T
D

3700
2 1 SD 2

2 2 2 2

5 3

KEY SCALE 1:100 M

1 Table, conference, 10-seater


2 Chair, conference
3 White board/ projection screen
4 Projector, ceiling-mounted
5 Waste bin, general

356
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY PATHOLOGY OFFICE/ LIBRARY 250B-LAB-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pathologist reads, writes, examines histopath Whiteboard 1
samples and uses telephone in his desk 5-headed training microscope 1
b. Pathologist receives visitors Waste bin w/ black lining 1
c. Pathologist stores, files and retrieves records

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Pathologist FIXTURE CHECKLIST
Visitors/ Consultants Shelf, open 2
1 x Registered Medical Technologist Desk, 600 x 1000mm; with 4
computer
Table, 600 x 1800mm 1
Table, meeting, 4- or 5-seater 1
Chair, swivel 4
Chair/Stool, adjustable height 6
Chair, with arm rest 4

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Waiting Area/ Receiving Area Outlet, 10A, 2P, 240V, duplex 8 grounding type
b. Close to Main Laboratory universal
c. Adjacent to Donor's Screening Area Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1
Outlet, DATA 4

357
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-05B
PATHOLOGY OFFICE/
April 2016 LABORATORY LIBRARY
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pathologist and visitors

Fire risk LOW: medium: high

Other risks NA

358
1950

10

1500
10 8

5 5

5 5 10
9
5 5 D
2 4
1

5900
SD

4 D
6 6 1
3
4 D
6 6 1

4 D
7 7 1

3900

KEY SCALE 1:100 M

1 Desk, 600 x 1000mm; with 7 Shelf, open


computer 8 Whiteboard
2 Table, 600 x 1800mm 9 5-headed training microscope
3 Table, meeting, 4- or 5-seater 10 Waste bin, general
4 Chair, swivel
5 Chair/Stool, adjustable height
6 Chair, with arm rest

359
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY CHIEF PATHOLOGIST'S OFFICE 250B-LAB-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pathologist reads, writes, examines histopath Waste bin w/ black lining 2
samples and uses telephone in his desk
b. Pathologist receives visitors
c. Pathologist stores, files and retrieves records

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Pathologist FIXTURE CHECKLIST
Visitors/ Consultants Shelf, open 1
1 x Registered Medical Technologist Desk, 600 x 1200mm; with 1
computer
Desk extension 1
Chair, swivel 1
Chair, visitor 1
Cabinet, steel, filing 2
Counter, with top and 1
bottom cabinets
Lavatory
Water closet

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Waiting Area/ Receiving Area Outlet, 10A, 2P, 240V, duplex 4 grounding type
b. Close to Main Laboratory universal
c. Adjacent to Donor's Screening Area Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1
Outlet, DATA 1
Outlet, Telephone 1

360
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-06B
CHIEF PATHOLOGIST'S
April 2016 LABORATORY OFFICE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit pathologist and visitors

Fire risk LOW: medium: high

Other risks NA

361
3900

6 6 2 TD 4
3
5 1

3100
CH SD

8 7

1500
8

1950

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 5 Counter, with top and


2 Desk, extension bottom cabinets
3 Chair, swivel 6 Cabinet, steel, filing
4 Chair, visitor 7 Shelf, open
8 Waste bin, general

362
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY CHEMISTRY 250B-LAB-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Microscopic & biochemistry examinations Urine Analyser 1
Clinical analysis, titrations & other procedures Cup Sink 1
b. Clinical handwashing Sink, utility, with drainboard 2
& wall-mounted pegboard
Refrigerator, 8 cu. Ft. 1
Exhaust air grills 2
Clinical centrifuge 1 Floor-type
Microscope 1
Chemistry Analyzer 1
Electrolyte Analyzer 1
Pipetor 1 set
Sharps Container 1
Waste bin w/ yellow lining 3 infectious
chemical
People Involved: pathological &
2 (Urinalysis) anatomical
2 (Biochemistry)
1 x Registered Medical Technologist
1 x Medical Laboratory Technician
1 x Laboratory Aide
FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Counter, laboratory, with 1
cabinets above & below 1
Desk, 600 x 1200mm 1
Chair, upright, stacking 1
Stool, adjustable height 3
Concealed floor drain 2

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Histopathology Section Window curtain rail 5
b. Close to Hematology Section Outlet, 10A, 2P, 240V, duplex 10 grounding type
universal
3 floor-type
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 2
Outlet, DATA 1

363
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY CHEMISTRY 250B-LAB-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks NA

364
3900

CH 9 D 5
7 6
CH

1
11
SD

FO
2
4

10
CH

11200
FO
CH

2 FO
4
SD
10

CH
7 7
3 CH11 8 121314

KEY SCALE 1:150 M

1 Counter, laboratory, with 8 Centrifuge, clinical; floor-type


cabinets above & below 9 Refrigerator
2 Sink, utility, with drainboard 10 Concealed floor drain
and wall-mounted pegboard 11 Sharps container, wall-mounted
3 Sink, cup 12 Waste bin, infectious
4 Exhaust air grille 13 Waste bin, pathological &
5 Desk, 600 x 1200mm anatomical
6 Chair, upright, stacking 14 Waste bin, chemical
7 Stool, adjustable height

365
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY HEMATOLOGY 250B-LAB-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Hemoglobin tests, sedimentation rates, Sink, cup 1
staining and washing of pipettes Exhaust air grille 1
b. Clinical handwashing Centrifuge, micro-hematocrit 1
Refrigerator 1
Sharps container 1 wall-mounted
Waste bin w/ yellow lining 2 chemical
pathological &
anatomical
Hematology Analyzer 1

People Involved: FURNITURE AND QUANTITY REMARKS


2 x Medical Technologists FIXTURE CHECKLIST
1 x Medical Laboratory Technician Counter, laboratory, with 1
cabinets above & below
Sink, staining, with drainboard 2
& wall-mounted pegboard
Desk, 600 x 1200mm 1
Chair, upright, stacking 1
Stool, adjustable height 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Urinalysis/ Biochemistry Section Outlet, 10A, 2P, 240V, duplex 7 grounding type
b. Adjacent to Pathologist's Office universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1
Outlet, DATA 1

366
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY HEMATOLOGY 250B-LAB-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks NA

367
6000

12 13 11 CH 3 CH

7 CH

3700
SD 4

6 10 CH

5 9 1 CH
D 8

KEY SCALE 1:100 M

1 Counter, laboratory, with 7 Stool, adjustable height


cabinets above & below 8 Centrifuge, micro-hematocrit
2 Sink, staining, with drainboard 9 Refrigerator
and wall-mounted pegboard 10 Concealed floor drain
3 Sink, cup 11 Sharps container, wall-mounted
4 Exhaust air grille 12 Waste bin, pathological &
5 Desk, 600 x 1200mm anatomical
6 Chair, upright, stacking 13 Waste bin, chemical

368
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY SEROLOGY/ IMMUNOLOGY 250B-LAB-RDS-09A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Testing of blood for serological test Sink, cup 1
Exhaust air grille 1
Refrigerator/ freezer 2
Sharps container 1 wall-mounted
Centrifuge 1 table-top
Incubator 1
VDRL Rotator 1
Vortex Mixer 1
Microscope 1
Computer w/ printer 1
Airconditioning Unit 1
Waste bin w/ yellow lining 3 infectious
chemical
pathological &
People Involved: anatomical
2 x Medical Technologists
1 x Medical Laboratory Technician
1 x Laboratory Aide

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Counter, laboratory, with 1
cabinets above & below
Sink, staining, with drainboard 1
& wall-mounted pegboard
Desk, 600 x 1200mm 1
Chair, upright, stacking 1
Stool, adjustable height 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Hispathology Section Outlet, 10A, 2P, 240V, duplex 7 grounding type
b. Close to Hematology Section universal
c. Adjacent to Clerical Room Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1
Outlet, DATA 1

369
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY SEROLOGY/ IMMUNOLOGY 250B-LAB-RDS-09B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks NA

370
6000

12 3 8
13 14 15 CH 11 CH
1
7 CH

3700
SD 4

CH
6 7 10
5 D 9 9 CH

KEY SCALE 1:100 M

1 Counter, laboratory, with 8 Centrifuge, table-top


cabinets above & below 9 Refrigerator / freezer
2 Sink, utility, with drainboard 10 Concealed floor drain
and wall-mounted pegboard 11 Incubator
3 Sink, cup 12 Sharps container, wall-mounted
4 Exhaust air grille 13 Waste bin, infectious
5 Desk, 600 x 1200mm 14 Waste bin, pathological &
6 Chair, upright, stacking anatomical
7 Stool, adjustable height 15 Waste bin, chemical

371
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-10A
MICROBIOLOGY/
April 2016 LABORATORY BACTERIOLOGY
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Preparation of culture media Hamper, soiled linen 1
b. Staining of slides Exhaust air grille 2
c. Preparation of specimens from suspect cases of Autoclave 1
tuberculosis, fungi and viral diseases Refrigerator 3
d. Washing/ Decontamination Freezer 2
e. Sample Receipt Room Sharps container 1 wall-mounted
f. Determination/ quantification and description Oven, hot air 1
of microbes Stove, electric 1
g. Reference culturing of microorganisms Incubator 1
Water Bath 1
Negative Pressure Hepa Filter Hood 1
Analytical Balance 1
Microscope 1
Infrared Microsterilizer 1
People Involved: Heating Plate 1
2 x Medical Technologists Balance, rough 1
1 x Medical Laboratory Technician Biosafety cabinet 1
1 x Bacteriologist Waste bin w/ yellow lining 3 chemical, infectious,
1 x Pathologist pathological &
1 x Laboratory Aide anatomical
FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Cabinet, PPE; with hook strip 1
Counter, laboratory, with 3
cabinets above and below
Sink, utility, with drainboard 1
& wall-mounted pegboard w/ electric grinder
Stool, adjustable height 3
Concealed floor drain 2
Sink, staining, w/ drainboard & 1
wall-mounted pegboard
Biosafety cabinet 1
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Histo pathology Section Window curtain rail 5
b. Close to Sterilizing and Glass Washing Rooms Outlet, 10A, 2P, 240V, duplex 16 grounding type
universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 3
Outlet, DATA 1
Outlet, Telephone 1
Utility Control Breaker Boxes
Gas Shut-Off Valves
Automatic Voltage Regulator 1
Outlet, for heavy-duty machine 1

372
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-10B
MICROBIOLOGY/
April 2016 LABORATORY BACTERIOLOGY
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: Autoclave

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100

Quality which cannot be Tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks exposure to hazardous elements

373
6000

7 7 7 8 8

5200
CH SD CH
D 9 9
T 3

7100
5
4
10
CH CH
3 12 13 14 CH
11 6

2
1900

SD
5 10 SD 9
1 3 16
CH 17 CH 19
15 18

KEY SCALE 1:00 M


ANTE ROOM: 10 Concealed floor drain
1 Cabinet, PPE; with hook strip 11 Sharps container, wall-mounted
2 Hamper, soiled linen 12 Waste bin, infectious
13 Waste bin, pathological & anatomical
MICROBIOLOGY/BACTERIOLOGY LAB: 14 Waste bin, chemical
3 Counter, laboratory, with cabinets above
and below STREAKING ROOM:
4 Sink, utility, with drainboard & wall-mounted 15 Sink, staining, with drainboard and
pegboard; with electric grinder wall-mounted pegboard
5 Exhaust air grille 16 Biosafety cabinet
6 Autoclave 17 Oven, hot air
7 Refrigerator 18 Stove, electric
8 Freezer 19 Incubator
9 Stool, adjustable height

374
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY MICROSCOPY 250B-LAB-RDS-11A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Viewing of samples and objects that cannot be seen Exhaust air grille 1
by the naked eye Centrifuge, clinical 1
b. Processing and staining of tissue/ samples Refrigerator 1
c. Clinical handwashing Sharps container 1 wall-mounted
d. Examination of surgical and autopsy specimens Analytical balance 1
Fume hood 1
Cylinder, carbon dioxide 1
Cylinder, gas 1
Clinical microscope 1
Waste bin w/ yellow lining 3 chemical
infectious
pathological &
anatomical

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Technologist FIXTURE CHECKLIST
1 x Microscopist Counter, laboratory, with 1
cabinets above & below
Sink, utility, with drainboard 1
and wall-mounted pegboard
Sink, staining 1
Desk, 600 x 1200mm 1
Chair, upright, stacking 1
Stool, adjustable height 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Histopathology Section Outlet, 10A, 2P, 240V, duplex 8 grounding type
b. Close to Microbiology/ Bacteriology Section universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1
Outlet, DATA 1

375
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY MICROSCOPY 250B-LAB-RDS-11B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks NA

376
6000

5 D 12 13 9 8 CH
6 7 CH

3700
SD 4

10 CH

15 16 17 3 1 CH
14 11

KEY SCALE 1:100 M

1 Counter, laboratory, with 9 Analytical balance


cabinets above & below 10 Concealed floor drain
2 Sink, utility, with drainboard 11 Fume hood
and wall-mounted pegboard 12 Cylinder, carbon dioxide
3 Sink, cup 13 Cylinder, gas
4 Exhaust air grille 14 Sharps container, wall-mounted
5 Desk, 600 x 1200mm 15 Waste bin, infectious
6 Chair, upright, stacking 16 Waste bin, pathological &
7 Stool, adjustable height anatomical
8 Centrifuge, clinical 17 Waste bin, chemical

377
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY HISTOPATHOLOGY 250B-LAB-RDS-12A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Examination of surgical and autopsy specimens Sink, cup 1
Processing and staining of tissue/ samples Exhaust air grille 1
b. Clinical handwashing Centrifuge 1 table-top
Refrigerator 1
Sharps container 1 wall-mounted
Analytical balance 1
Fume hood 1
Cryostat 1
Microtome 1
Hot plate 1
Microscope 1
Hot air oven 1
Gross Cutting Cabinet 1
Immunohistochemistry analyzer 1
People Involved: Waste bin w/ yellow lining 3 chemical
1 x Pathologist infectious
2 x Medical Technologist pathological &
2 x Laboratory Aide anatomical
Medical Laboratory Technician Interns
Affiliates FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Counter, laboratory, with 1
cabinets above & below
Sink, utility, with drainboard 1
and wall-mounted pegboard
Stool, adjustable height 2
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Clinical Microscopy Outlet, 10A, 2P, 240V, duplex 9 grounding type
b. Close to Microbiology/ Bacteriology Section universal
c. Adjacent to Pathologist's Office Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1

378
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY HISTOPATHOLOGY 250B-LAB-RDS-12B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks NA

379
3900

3 6 CH 9 11
CH CH
12
13
14 5 5 10
CH CH
10

5500
2
4
8
16
1 SD

15

17
18
1800 19
7 20

2700
KEY SCALE 1:100 M
1 Counter, laboratory, with cabinets 10 Microtome
above & below 11 Hot plate
2 Sink, utility, with drainboard and 12 Hot air oven
wall-mounted pegboard 13 Analytical balance
3 Sink, cup 14 Microscope
4 Exhaust air grille 15 Immunohistochemistry analyzer
5 Stool, adjustable height 16 Concealed floor drain
6 Gross cutting cabinet 17 Sharps container, wall-mounted
7 Refrigerator 18 Waste bin, infectious
8 Cryostat 19 Waste bin, pathological & anatomical
9 Centrifuge, table-top 20 Waste bin, chemical

380
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY
BLOOD TYPING, CROSS MATCHING,
POST-BRT INVESTIGATION 250B-LAB-RDS-13A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Blood typing procedures Centrifuge 1
b. Cross matching procedures Serofuge 1
c. Post BRT investigation Water bath 1
d. other related/necessary procedures Refrigerator 2
Waste bin, infectious 1
Waste bin, pathological and 1
anatomical
Waste bin, chemical 1
Sharp container 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Laboratory Technician FIXTURE CHECKLIST
1 x Laboratory Aide Chair, upright; stacking 1
Stool, adjustable height 1
Counter, laboratory 1
Sink, staining; with drainboard 1
and wall-mounted pegboard 1
Sink, cup 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accessible to Blood Station Outlet, 10A,2P,240V, duplex 8 grounding type
b. Preferable with direct access to outside universal
corridor/hallway Outlet, 10A,2P,240V, single 1 emergency light
Outlet, data 1
Smoke detector 1
Window curtain rail 3

381
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-13B
BLOOD TYP, CROSS MATCH.,
April 2016 LABORATORY POST-BRT INVEST.

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory/Blood Station staff

Fire risk low: MEDIUM : high

Other risks NA

382
6000

13
14 15 16
11 11

4100
SD
4
2
6 7 CH
12
5 D 3 CH
10 9 CH
8

KEY SCALE 1:100 M

1 Counter, laboratory, with 8 Centrifuge


cabinets above & below 9 Serofuge
2 Sink, staining, with drainboard 10 Water bath
and wall-mounted pegboard 11 Refrigerator
3 Sink, cup 12 Concealed floor drain
4 Exhaust air grille 13 Sharps container, wall-mounted
5 Desk, 600 x 1200mm 14 Waste bin, infectious
6 Chair, upright, stacking 15 Waste bin, pathological &
7 Stool, adjustable height anatomical
16 Waste bin, chemical

383
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY GLASS WASHING 250B-LAB-RDS-14A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Washing of instruments/ glasswares Fume hood 1
b. Preparation of glasswares/ instruments for Oven, hot air 1
future use Sharps container 1
Waste bin w/ yellow lining 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Laboratory Aide FIXTURE CHECKLIST
Counter, with cabinets above 1
and below
Sink, two compartment; 1
200mm deep
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Locker Room & Toilet Outlet, 10A, 2P, 240V, duplex 4 grounding type
b. Close to Storage Room universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1

384
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY GLASS WASHING 250B-LAB-RDS-14B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: pressure sterilizer

Speech privacy essential:desirable: UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks NA

385
3900

3 2 CH
4 1
5

2100
SD

KEY SCALE 1:100 M

1 Counter, with cabinets above


and below
2 Sink, two compartment;
200mm deep
3 Fume hood
4 Oven, hot air
5 Concealed floor drain

386
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY AUTOCLAVE 250B-LAB-RDS-15A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Sterilization of instruments/ glasswares Autoclave 1

People Involved: FURNITURE AND QUANTITY REMARKS


Laboratory Staff FIXTURE CHECKLIST
Counter, with cabinets below 1
Sink, with drainboard 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accessible to Bacteriology Section Outlet, 10A, 2P, 240V, duplex 3 grounding type
b. Close to Staff Lounge & Pantry universal
c. Adjacent to Main Clinical Laboratory Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1

387
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY AUTOCLAVE 250B-LAB-RDS-15B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: autoclave

Speech privacy essential:desirable: UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit Laboratory staff

Fire risk low: MEDIUM: high

Other risks NA

388
3900

CH 4

2100
1 SD

2
3

KEY SCALE 1:100 M

1 Counter, with cabinets below


2 Sink, with drainboard
3 Concealed floor drain
4 Autoclave

389
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY STAFF LOCKER ROOM AND T&B 250B-LAB-RDS-16A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Laboratory staff change clothes in toilet Hamper, linen 1
and locker room Waste bin, w/ black lining 2
b. Laboratory staff bathe in shower cubicle
c. Storing of clothing and personal effects

People Involved: FURNITURE AND QUANTITY REMARKS


Laboratory Staff FIXTURE CHECKLIST
Water Closet w/ spray hose 4
Lavatory 4
Urinal 3
Slop sink, with faucet 1
Shelf, open 1
Locker, steel 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Accessible to Staff Work Area and Main Entrance Outlet, 10A, 2P, 240V, duplex 1 grounding type
to the Laboratory universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1
Outler, Water heater,
30A, 2P, 240V 2 T&B

390
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LAB-RDS-16B
STAFF LOCKER ROOM AND
April 2016 LABORATORY T&B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff

Fire risk LOW: medium: high

Other risks NA

391
12000
3900 1300 1900 4900

6 9
5
4

3300
SD 7

1 8 3
2 2

KEY SCALE 1:150 M

1 FEMALE T&B 7 LOCKER ROOM


2 Waste bin, general 8 Locker, steel
9 Hamper, linen
3 MALE T&B

4 JANITOR'S CLOSET
5 Slop sink, with faucet
6 Shelf, open

392
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY STAFF PANTRY 250B-LAB-RDS-17A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Laboratory staff makes use of the pantry Whiteboard 1
b. Janitorial services do clean-up activities Water dispenser 1
Refrigerator 1
Waste bin w/ black lining 1
Microwave oven 1

People Involved: FURNITURE AND QUANTITY REMARKS


Laboratory Staff FIXTURE CHECKLIST
Visitors Table, dining, 4- or 5-seater 1
Table, side, 400 x 400mm 1
Chair, dining 4
Sofa, 2-seater 1
Counter, with top and 1
bottom cabinets
Sink, stainless steel 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Within the Laboratory Department Outlet, 10A, 2P, 240V, duplex 6 grounding type
universal
Outlet, 10A, 2P, 40V, single 1 emergency light
Smoke Detector 1

393
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LABORATORY STAFF PANTRY 250B-LAB-RDS-17B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff

Fire risk LOW: medium: high

Other risks NA

394
3900

3 3 8
2

3300
SD 1 CH
4 3 3 5
6
7 1011

KEY SCALE 1:100 M

1 Table, dining, 4- or 5-seater 6 Sink, stainless steel


2 Table, side, 400 x 400mm 7 Whiteboard
3 Chair, dining 8 Water dispenser
4 Sofa, 2-seater 9 Refrigerator
5 Counter, with top and 10 Concealed floor drain
bottom cabinets 11 Waste bin, general

395
SCALE 1:300 M

15000
2600 3600 3100 3200 2500

TESTING
ROOM

5900
6400

BLOOD BLOOD
COLLECTION COMPONENT
ROOM STORAGE
BLOOD
ISSUANCE
12400

AREA

2600
2100

RECORDS
ROOM
3900

3900
COMPONENT STAFF
WAITING SCREENING/ PREPARATION LOCKERS
AREA ASSESSMENT ROOM & PANTRY

3000 1500 3000 3500 1500 2500

396
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION WAITING AREA 250B-BS-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patients await their turns to be examined/ attended Weighing scale 1
to by Medical Laboratory Aide Waste bin, general 2
b. Patients/Donors await their turns for their blood
to be extracted
c. Patients await the release of their examination
results

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Laboratory Aide FIXTURE CHECKLIST
Patients/ Relatives Desk, 600 x 1200mm 1
Cabinet, steel, filing 1
Chair, upright, stacking 2
Chair, gang-type 3 4-seater
1 5-seater
1 6-seater
Water closet 1
Urinal 1
Lavatory 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Blood Donor's Room ENGINEERING TERMINALS
b. Close to Pathologist's Office
Outlet, 10A, 2P, 240V, duplex 6 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1
Smoke Detector 1

397
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION WAITING AREA 250B-BS-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff & general public

Fire risk LOW: medium: high

Other risks NA

398
4500

5 4

3300
3
4 4
1
3

6000
SD TD
6 2
6

2700
4

3000 1500
KEY SCALE 1:100 M

1 Desk, 600 x 1200mm


2 Cabinet, steel, filing
3 Chair, upright, stacking
4 Chair, 4- or 5-seater, gang-type
5 Weighing scale
6 Waste bin, general

399
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION SCREENING & ASSESSMENT 250B-BS-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Collecting blood samples for the presence of infectious Waste bin, w/ black lining 2
or transmittable diseases Waste bin, w/ yellow lining 1
b. Screening potential donors Low partition, with sliding door 2
c. Collecting appropriate donor information and Weighing scale, heavy duty 1
administering donor health questionnaire Sphygmomanometer 1
d. Documentation of patients' record Stethoscope 1
Thermometer, non-mercurial 1
Refrigerator 1
Rotator 1
Phlebotomist's Tray 1
Microscope 1
Hemoglobin Ometer w/ reader, 1
washer & incubator
Needle Disposal 1
Sharps Container 1
Detecto w/ rod 1
People Involved: FURNITURE AND QUANTITY REMARKS
2 x Medical Technologist/ Phlebotomist FIXTURE CHECKLIST
Patient Desk, 600 x 1200mm 2
Clerk/ Staff Cabinet, steel, filing 1
Blood Station Nurse Chair, swivel 2
Blood Donor Chair, visitor 3

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Waiting Area ENGINEERING TERMINALS
b. Close to Staff Room
c. Accessible to Pathologist's Office Outlet, 10A, 2P, 240V, duplex 4 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Outlet, DATA 2 wall-mounted
Outlet, Telephone 1
Smoke Detector 1

400
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION SCREENING & ASSESSMENT 250B-BS-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff & blood donors

Fire risk LOW: medium: high

Other risks NA

401
3000

6
4
1 D
3

3900
6 5
SD
2
5
1
3
4 4 TD

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm


2 Cabinet, steel, filing
3 Chair, swivel
4 Chair, visitor
5 Waste bin, general
6 Low partition, with sliding door

402
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION COMPONENT PREPARATION ROOM 250B-BS-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Labeling of blood component Centrifuge 1
b. Storing of whole blood and blood components as a Platelet incubator 1
part of blood donation Weighing scale 1
Waste bin, general 1
Waste bin, w/ yellow lining 1 pathological
anatomical waste
Computer w/ Printer 1
Biosafety cabinet 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Technologist FIXTURE CHECKLIST
1 x Medical Laboratory Technician Counter, laboratory; with 1
cabinets above and below
Sink, with drainboard 1
Stool, adjustable height 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Donor's Blood Donation Area/ Screening Area ENGINEERING TERMINALS
b. Close to Extraction Area
c. Adjacent to Hematology Outlet, 10A, 2P, 240V, duplex 7 grounding type,
d. Adjacent to Immunology/ Serology universal
e. Adjacent to Pathologist's Office Outlet, 10A, 2P, 240V, single 1 emergency light
Smoke Detector 1

403
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-BS-RDS-03B
COMPONENT PREPARATION
April 2016 BLOOD STATION ROOM

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff

Fire risk LOW: medium: high

Other risks blood contamination

404
3500

9 10
4

3900
SD CH
3
7
8 CH
5 CH 1 CH
2

KEY SCALE 1:100 M

1 Counter, laboratory; with 6 Platelet incubator


cabinets above and below 7 Weighing scale
2 Sink, with drainboard 8 Concealed floor drain
3 Stool, adjustable height 9 Waste bin, general
4 Biosafety cabinet 10 Waste bin, pathological and
5 Centrifuge anatomical waste

405
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION TESTING ROOM 250B-BS-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Labeling of blood component Microscope 1
b. Storing of whole blood and blood components as a Refrigerator 2
part of blood donation Waste bin, general 1
Waste bin, w/ yellow lining 1 pathological
anatomical waste

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Technologist FIXTURE CHECKLIST
1 x Medical Laboratory Technician Counter, laboratory; with 1
cabinets above and below
Sink, with drainboard 1
Stool, adjustable height 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Donor's Blood Donation Area/ Screening Area ENGINEERING TERMINALS
b. Close to Extraction Area
c. Adjacent to Hematology Outlet, 10A, 2P, 240V, duplex 7 grounding type,
d. Adjacent to Immunology/ Serology universal
e. Adjacent to Pathologist's Office Outlet, 10A, 2P, 240V, single 1 emergency light
Smoke Detector 1

406
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION TESTING ROOM 250B-BS-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff

Fire risk LOW: medium: high

Other risks blood contamination

407
3200

5 1
CH

3900
SD 3 CH

6
7 2

KEY SCALE 1:100 M

1 Counter, laboratory; with 5 Refrigerator


cabinets above and below 6 Waste bin, general
2 Sink, with drainboard 7 Waste bin, pathological and
3 Stool, adjustable height anatomical waste
4 Concealed floor drain

408
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION BLOOD COMPONENT STORAGE 250B-BS-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Labeling of blood component Refrigerator/ Freezer 6
b. Storing of whole blood and blood components as a Waste bin, general 1
part of blood donation Computer w/ Printer

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Technologist FIXTURE CHECKLIST
1 x Medical Laboratory Technician Desk, 600 x 1200mm 1
Chair, upright, stacking 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Donor's Blood Donation Area/ Screening Area ENGINEERING TERMINALS
b. Close to Extraction Area
c. Adjacent to Hematology Outlet, 10A, 2P, 240V, duplex 7 grounding type,
d. Adjacent to Immunology/ Serology universal
e. Adjacent to Pathologist's Office Outlet, 10A, 2P, 240V, single 1 emergency light
Smoke Detector 1
Outlet, DATA 1

409
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-BS-RDS-05B
BLOOD COMPONENT
April 2016 BLOOD STATION STORAGE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff

Fire risk LOW: medium: high

Other risks blood contamination

410
3100

6400
SD 1
2 D
3

4
3

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm


2 Chair, upright, stacking
3 Refrigerator / Freezer
4 Waste bin, general

411
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION BLOOD COLLECTION ROOM 250B-BS-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Blood extraction/ donation or collecting blood from Table, instrument 3
eligible donors Refrigerator 1
b. Supervising donor's recovery Clock 1
c. Checking and storing donated blood prior to examination Television 1
Sharps container 3
Waste bin, w/ black lining 1
Waste bin w/ yellow lining 2 infectious
pathological
& anatomical

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Medical Technologist FIXTURE CHECKLIST
1 x Medical Laboratory Technician Desk, 600 x 1200mm 1
1 x Blood Station Nurse Chair, upright, stacking 1
1 x Patient Blood donor bed, adjustable 3
1 x Utility Worker

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Waiting Area ENGINEERING TERMINALS
b. Close to Pathologist's Office Outlet, 10A, 2P, 240V, duplex 9 grounding type,
c. Adjacent to Screening Area universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Smoke Detector 1
Outlet, DATA 1

412
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION BLOOD COLLECTION ROOM 250B-BS-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff & blood donors

Fire risk LOW: medium: high

Other risks NA

413
3600

4 1
2
3 D

10 5
11
9
8
4 6

6400
3 SD

10 7
11
9

3
10
11
9

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 7 Television


2 Chair, upright, stacking 8 Waste bin, general
3 Blood donor bed, adjustable 9 Waste bin, infectious
4 Table, instrument 10 Waste bin, pathological &
5 Refrigerator anatomical
6 Clock 11 Sharps container

414
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BLOOD STATION STAFF LOCKERS, PANTRY & TOILET 250B-BS-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Blood Station staff makes use of the pantry Refrigerator 1
b. Janitorial Services do clean-up activities Microwave oven 1
Water dispenser 1
Waste bin w/ black lining 2

People Involved: FURNITURE AND QUANTITY REMARKS


Blood Station Staff FIXTURE CHECKLIST
Visitors Counter, with top and 1
bottom cabinets
Sink, stainless steel 1
Table, 4- or 5-seater 1
Chair, dining 4
Locker, steel 4
Concealed floor drain 1
Water Closet 1
Lavatory 1
Urinal 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Blood Station Department ENGINEERING TERMINALS
Outlet, 10A, 2P, 240V, duplex 5 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 emergency light
Smoke Detector 1

415
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-BS-RDS-07B
STAFF LOCKERS, PANTRY &
April 2016 BLOOD STATION TOILET

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Laboratory staff

Fire risk LOW: medium: high

Other risks NA

416
4000

1100
7 7 7 7

9 4 4

3900
SD 3

2800
4 4
9
8
2 CH 1 6 5

1500 2500

KEY SCALE 1:100 M

1 Counter, with top and 5 Refrigerator


bottom cabinets 6 Water dispenser
2 Sink, stainless steel 7 Locker, steel
3 Table, 4- or 5-seater 8 Concealed floor drain
4 Chair, dining 9 Waste bin, general

417
11900
6500 2400 3000

UP

3000
CONFERENCE/
2200 3100

TRAINING
ROOM

T CONTROL

3900
PANTRY &
LOCKERS

3000
7100

CT-SCAN
STAFF
FT
1900 3000
STAFF
MT

JAN
T
CLO
5300

R/F
X-RAY
4100

RAD
HEAD
OFFICE
1550

DARK
T
ROOM CONTROL
4200

6700

X-RAY 2
READING
ROOM
3000

T DARK
51000

CONTROL
ROOM
T
FILM
3900

FILE
STORAGE
4200

X-RAY 1

SUB-
4500
3150

WAITING
MAMMOGRAPHY AREA
3400 1600
2100 3100

ULTRA T
SOUND 3
DRESS

SUPPLY DRESS

2500 7300 2200


4600

ULTRA ULTRA
SOUND 1 SOUND 2
WAITING
AREA
12000

6100

CONTROL TECHNICAL
CLERICAL
4400

ROOM ROOM
ROOM MRI
RECEPTION/ MAGNET
INFO ROOM
3000

2900

FT
MT

418
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY SUB-LOBBY/ WAITING AREA 250B-RAD-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patients wait to be x-rayed Wheelchair 2
b. Patients wait for the release of their x-rayed results Stretcher 1
c. Patients in stretchers and wheelchairs and their Waste bin w/ black lining 3
comapnionship/ watchers wait

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Chair, gang-type, 4- & 5-seater 10
Television w/ queuing system 1

People Involved:
1 x X-Ray Clerk
Patients
Companion/ Watchers

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Frontline area of the Radiology Department ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1
Outlet, TV 1

419
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
SUB-LOBBY/ WAITING
April 2016 RADIOLOGY AREA 250B-RAD-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit radiology staff & patient

Fire risk LOW: medium: high

Other risks NA

420
5500

2
1 1 1

4600
SD

1 1 1
1

12000
7400
SD
4

1 1 1
3

8950

KEY SCALE 1:200 M

1 Chair, gang-type, 4- & 5-seater


2 Waste bin
3 Wheelchair & stretcher park
4 Television w/ queuing system

421
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CLERICAL ROOM 250B-RAD-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Clerk receives request of patients to be x-rayed Computer 1
b. X-ray Technician/ Technologist schedules patient Waste bin w/ black lining 3
and special radiographic procedures Airconditioning Unit 1
c. Clerk types results, files and retrieves records. Uninterrupted Power Supply 1
d. Clerk issues results of radiographic procedures done Automatic Voltage Regulator 1

People Involved: FURNITURE AND


QUANTITY REMARKS
Radiologic Technician/ Technologist FIXTURE CHECKLIST
3 x Clerks Desk, 600 x 1200mm 1
X-ray interns, if there are any Desk, extension, 400 x 800mm 1
Desk, 600 x 1200mm 2
Counter, 1200mm high 1
Chair; upright, stacking 3
Visitor's Chair 1
Stool, adjustable height 1
Cabinet, filing, steel 4

Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS


a. Adjacent to Film Storage ENGINEERING TERMINALS
b. Close to Radiologist's Office Window Curtain Rail 2
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
Smoke detector 1
Outlet, DATA 3
Outlet, Telephone 2
Outlet, ACU 1

422
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CLERICAL ROOM 250B-RAD-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit radiology staff

Fire risk LOW: medium: high

Other risks NA

423
4200

9 2 TD 6 9
5
5
1 3 T
D

4400
SD

D 3 4
5
7
8 8 8 8 9

KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 6 Chair; visitor


2 Desk, extension, 400 x 800mm 7 Stool, adjustable height
3 Desk, 600 x 1200mm 8 Cabinet, filing, steel
4 Counter, 1200mm high 9 Waste bin
5 Chair; upright, stacking

424
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CHIEF RADIOLOGIST'S OFFICE 250B-RAD-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Radiologist interprets x-ray film and/ or ultrasound image Wall-mounted negatoscope 4 1
b. Clerk type results banks 14 x 17 sg. In per bank 1
c. Radiologist meets with x-ray technologist, physicians Magnifying lens 1
and other hospital staff Computer 1
d. Radiologist receives visitors or patients Printer 1
Uninterrupted Power Supply 1
Automatic Voltage Regulator 1
Waste bin w/ black lining 3
Whiteboard 1

People Involved: FURNITURE AND


QUANTITY REMARKS
Radiologist FIXTURE CHECKLIST
1 x X-Ray Clerk Desk, 600 x 1200mm 1
Companions/ Watchers Desk, extension 1
Desk, 600 x 100mm 1
Shelf, open 1
Cabinet, steel, filing 1
Chair, upright; stacking 2
Chair, visitor 2
Pass-through window 1
Lavatory 1
Water Closet 1

Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS


a. Easily accessible to all other rooms ENGINEERING TERMINALS
within the Radiology Department Window Curtain Rail
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 2 wall-mounted
Outlet, Telephone 1 desktop
Outlet, ACU 1

425
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
CHIEF RADIOLOGIST'S
April 2016 RADIOLOGY OFFICE 250B-RAD-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Chief Radiologist, staff and visitors

Fire risk LOW: medium: high

Other risks NA

426
1500

1900
12

11

8
4
2 6
T 1
D

4100
7 SD
5
7 11

3
6
D
10 9

3000
KEY SCALE 1:100 M

1 Desk, 600 x 1200mm 8 Negatoscope


2 Desk, extension 9 Whiteboard
3 Desk, 600 x 100mm 10 Pass-through window
4 Shelf, open 11 Waste bin
5 Cabinet, steel, filing 12 TOILET
6 Chair, upright; stacking
7 Chair, visitor

427
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CONFERENCE ROOM 250B-RAD-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Radiology staff members meet for conferences, Negatoscope (X-Ray film viewer) 1
discussions or trainings Whiteboard 1
Wall Clock 1
Airconditioning Unit 1
Liquid-Crystal Projector (LCD) 1
Waste bin w/ black lining 1
Projection Screen 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Radiologist FIXTURE CHECKLIST
Radiologic Technologist Table, conference 1
Physicians Cabinet, low 1
Hospital staff Chair, conference 10

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Radiologist Office and Staff ENGINEERING TERMINALS
Window Curtain Rail 1
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, ACU 1

428
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CONFERENCE ROOM 250B-RAD-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Radiology Staff

Fire risk LOW: medium: high

Other risks NA

429
6500

7 5 6
SH

3 3 3 3

3100
2 3 1 SD 3

CH 3 3 3 3

4 TD

KEY SCALE 1:100 M

1 Table, conference
2 Cabinet, low
3 Chair, conference
4 Projection screen
5 Negatoscope
6 Whiteboard
7 Waste bin

430
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY READING ROOM 250B-RAD-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Radiology staff members meet for conferences, Negatoscope (X-Ray film viewer) 6
discussions or trainings Whiteboard 1
Wall Clock 1
Airconditioning Unit 1
Digitizer, floor-mounted unit 1
Automatic Voltage Regulator 1
Uninterrupted Power Supply 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Radiologist FIXTURE CHECKLIST
Radiologic Technologist Desk, 600 x 1000mm; with 3
Physicians computer and monitor (linked to
Hospital staff imaging units)
Desk, 600 x 1200mm; with 3
computer and monitor (linked to
imaging units)
Chair; swivel-type 6
Shelf, open 1
Pass-through window 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Radiologist Office and Staff ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 10 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, DATA 2 wall-mounted
Outlet, Telephone 1 desktop
Outlet, ACU 1

431
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY READING ROOM 250B-RAD-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Radiology Staff

Fire risk LOW: medium: high

Other risks NA

432
3000

9
71 3 3 2 7

71 3
3 2 7

71 3
3 2 7

6700
T
D SD

10

5 4
D

6 8

KEY SCALE 1:100 M

1 Desk, 600 x 1000mm; with 5 Digitizer, floor-mounted unit


computer and monitor (linked to 6 AVR and UPS
imaging units) 7 Negatoscope
2 Desk, 600 x 1200mm; with 8 Whiteboard
computer and monitor (linked to 9 Pass-through window
imaging units) 10 Waste bin, general
3 Chair; swivel-type
4 Shelf, open

433
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY FILES ROOM 250B-RAD-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Radiologic Technician/ Technologist/ Clerk stores Exhaust fan 1
radiographs
b. Radiologic Technician/ Technologist/ Clerk retrieves
radiographs on file for follow-up of patient conditions

Note: Radiographs beyond five years of age will be stored


in the central records

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Radiologist FIXTURE CHECKLIST
Radiologic Technologist Shelf, open 1
Physicians Aluminum ladder 1
Hospital staff

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Radiologist Office and Staff ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, Exhaust fan 2 wall-mounted

434
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY FILES ROOM 250B-RAD-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Radiology Staff

Fire risk LOW: medium: high

Other risks NA

435
3000

3900
SD

KEY SCALE 1:100 M

1 Shelf, open
2 Ladder, aluminum

NOTE : Provide 1000mm clear distance from ceiling


to topmost shelf

436
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY ULTRASOUND ROOM 250B-RAD-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is assisted on to examination table Ultrasound unit 1
b. Ultrasonologist performs specified examination Ultrasound Printer 1
c. Patient and staff use toilet Automatic Voltage Regulator 1
Uninterrupted Power Supply 1
Examination bed 1
Exhaust fan 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Ultrasonologist FIXTURE CHECKLIST
1 x Patient Table, with computer 1
Desk, 600 x 1200mm 1
Stool, adjustable 1
Chair, upright; stacking 2
Footstool 1
Counter, with cabinets below 1
Sink, stainless steel 1
Concealed floor drain 1
Cubicle curtain and rod 1
Water Closet 1
Lavatory 1
Hook, wall-mounted 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to X-ray Room ENGINEERING TERMINALS
b. Close to Waiting Area Window Curtain Rail 2
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, 30A,2P,240V 1 for ultrasound machine
Smoke detector 1
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1

437
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY ULTRASOUND ROOM 250B-RAD-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit Radiology Staff & patient

Fire risk LOW: medium: high

Other risks NA

438
1900 4600

16 3 4 2 15 TD
12 7 5
6 1
14

3100
SD 7
8
CH
9 13
10 11 SH

KEY SCALE 1:100 M

1 Examination bed 9 Counter, with cabinets below


2 Ultrasound machine 10 Sink, stainless steel
3 Table, with computer 11 Concealed floor drain
4 Automatic Voltage Regulator (AVR) 12 Uninterrupted Power Supply
5 Desk, 600 x 1200mm (UPS)
6 Stool, adjustable 13 Cubicle curtain and rod
7 Chair, upright; stacking 14 Toilet
8 Footstool 15 Hook, wall-mounted
16 Waste bin

439
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY MAMMOGRAPHY ROOM 250B-RAD-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient enters room; enters dress cubicle to change
into hospital gown Mammography machine 1
b. Patient stands in front of mammography machine and control unit
c. 1 breast will be placed on the X-Ray plate. To ensure a Negatoscope 1
clear and correct image, the technologist may Waste bin 1
palpate the breast before placing it on the plate.
d. The technologist operates the machine, bringing
down the top plate to compress the breast against
the X-Ray plate. Patient is asked to hold breath while
image is being taken.
e. Technologist will operate the controls, taking 2
pictures at different angles of each breast FURNITURE AND
QUANTITY REMARKS
f. When the 1st breast is finished, the patient FIXTURE CHECKLIST
undergoes the same procedures with the 2nd breast Chair, upright 1
g. After the X-Rays have been taken, patient waits for Stool, adjustable height 1
the films to be examined by a radiologist to ensure Hamper, soiled linen 1
that the images are clear. Additional images will be Hook, wall-mounted 1
taken if images are not satisfactory. Cubicle curtain with rod 1
h. If images are already satisfactory, patient is asked to
dress back into street clothes; hospital gown is placed
into soiled linen hamper

People Involved
1 x Patient
1 x Technologist

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Accessible to Waiting Area ENGINEERING TERMINALS
b. Accessible to Dress Cubicle/s Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, telephone outlet 1
Smoke detector 1
Window curtain rail 1

440
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY MAMMOGRAPHY ROOM 250B-RAD-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit radiology staff & patient

Fire risk LOW: medium: high

Other risks NA

441
6500

TD 10 8

1 6
2 4
7

3150
SD
9
9
11
SH
3 5

KEY SCALE 1:100 M

1 Mammography unit 6 Dress cubicle


2 Mammo control unit 7 Hamper, soiled linen
3 Chair, upright 8 Hook, wall-mounted
4 Stool, adjustable height 9 Cubicle curtain with rod
5 Negatoscope 10 Waste bin
11 Indicator light (above door,
exterior side)

442
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY RADIOGRAPHIC X-RAY ROOM 250B-RAD-RDS-09A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient puts on hospital gown Radiographic X-ray Unit 1
b. X-ray technologist prepares and positions patient Vertical Casette Stand 1
for x-ray examination IV stand 1
c. Patient undergoes radiographic examination X-ray machine transformer 1
d. Patient puts on personal clothing after instructions Waste bin w/ black lining 1
to leave Lead rubber gown/ apron 1
Lead rubber gloves 1 pair
Patient caliper 1
Compression band 1
Film ID marker set 1
Lead apron hanger 1
People Involved: Pelvimeter 1
X-ray Technologists Oxygen Tank 1
Patient Contact 90 nadal shields 1
Nurse Upright 90 nadal shields 1
Institution Worker/ Companion
X-ray Technologist Interns
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST

Footstool 1
Cabinet, storage 1
Indicator light (above door, 1
exterior side)
Water Closet 1
Lavatory 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Outpatient Department ENGINEERING TERMINALS
b. Close to Emergency Department Outlet, 10A,2P,240V, duplex 8 grounding type,
c. Close to other Ancillary Services universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, Airconditioning unit 1 Window type
Smoke detector 1
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1

443
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-RAD-RDS-09B
RADIOGRAPHIC X-RAY
April 2016 RADIOLOGY ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C)

Access limit Radiology Staff & patient

Fire risk LOW: medium: high

Other risks exposure to radiation

444
6350

2
3

3600
4200
5 SD 9
6
7
TD

8 4

13
10

(SHARED)
11 12

4200
3000

2000 1800 2550

KEY SCALE 1:100 M


1 Radiographic X-Ray Machine 8 Cabinet, storage
2 Transformer 9 Indicator light (above door,
3 X-Ray cassette stand, vertical exterior side)
4 Lead apron rack 10 TOILET
5 Footstool 11 DARK ROOM
6 IV stand 12 CONTROL ROOM
7 Oxygen tank 13 Waste bin

445
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-RAD-RDS-10A
RADIOGRAPHIC X-RAY
April 2016 RADIOLOGY CONTROL ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. X-ray Radiologic Technician/Technologist formulates/ sets Control console 1
radiographic techniques Automatic Voltge Regulator 1
b. X-ray Radiologic Technician/Technologist gives instruction to Lead Glass View Window 2
patient undergoing radiographic examinations Automatic Film Processor 2
c. X-ray Radiologic Technician/Technologist conducts Waste bin w/ black lining 1
radiographic exposures
d. X-ray Radiologic Technician/ Technologist views patient
during radiographic examination

People Involved: FURNITURE AND


QUANTITY REMARKS
X-ray Technicians/ Technologist FIXTURE CHECKLIST
RT Interns Chair, swivel 2
Radiologist Cassette rack 2
Resident Physician

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to X-ray Rooms ENGINEERING TERMINALS

Outlet, 10A,2P,240V, duplex 5 grounding type,


universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Power supply for x-ray machine 1 1 dia. Or 3 dia.
Smoke detector 1

446
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-RAD-RDS-10B
RADIOGRAPHIC X-RAY
April 2016 RADIOLOGY CONTROL ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Radiology Staff & patient

Fire risk LOW: medium: high

Other risks NA

447
2550

6
1
5
3

4200
SD
2

2
3
5
1
6

KEY SCALE 1:100 M


1 Control console
2 Cassette rack
3 Automatic film processorr
4 Automatic voltage regulator
5 Chair, swivel
6 Window, with lead glass panel

448
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
RAD-FLUOROSCOPIC X-RAY
April 2016 RADIOLOGY ROOM 250B-RAD-RDS-11A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient puts on hospital gown Radiographic-Fluoroscopic X-ray Unit 1
b. X-ray technologist prepares contrast medium Bucky Vertical Casette Stand 1
c. X-ray technologist prepares and position patient IV stand 1
d. X-ray radiologist introduces contrast medium X-ray machine transformer 1
e. Patient undergoes radiographic and/ or fluoroscopic Waste bin w/ black lining 1
examination Lead rubber gown/ apron 1
f. Patient uses toilet Lead rubber gloves 1 pair
Patient caliper 1
Compression band 1
Film ID marker set 1
Lead apron hanger 1
People Involved: Immobilizing device 1
X-ray Technologists Oxygen Tank 1
Patient Contact 90 nadal shields 1
Nurse Upright 90 nadal shields 1
Institution Worker/ Companion Barium preparation gadgets 1
X-ray Technologist Interns Lead goggles 1
Radiologist Thyroid shield 1
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Counter, w/ cabinets above & below 1
Cabinet, mobile 1
Sink, stainless steel 1
Footstool 1
Monitor, vital signs 1
Hamper, soiled linen 1
Sharps disposal unit 1
Clock 1
Planning Relationships Concealed floor drain 1
a. Close to Outpatient Department Indicator light 1
b. Close to Emergency Department ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
c. Close to other Ancillary Services ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 8 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, Airconditioning unit 1
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1

449
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-RAD-RDS-11B
RAD-FLUOROSCOPIC X-RAY
April 2016 RADIOLOGY ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary

Cooling load (TR) 2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C)

Access limit Radiology Staff & patient

Fire risk LOW: medium: high

Other risks exposure to radiation

450
6350

1 15

4650
9 6

5250
12 SD
16

6800
7

10
TD
14
4 CH
5 3
13 11

2150
1550

17 19 18

1960 1800 2550

KEY SCALE 1:100 M


1 Rad/Fluoro X-Ray Machine 11 Sharps disposal unit
2 Transformer 12 Clock
3 Counter, with cabinets above and below 13 Waste bin, infectious
4 Cabinet, mobile 14 Concealed floor drain
5 Sink, stainless steel 15 Medical gas console : Air,
6 IV stand Oxygen, Vacuum)
7 Lead apron rack 16 Indicator light (above door,
8 Footstool exterior side)
9 Monitor, vital signs 17 TOILET
10 Hamper, soiled linen 18 CONTROL ROOM
19 DARK ROOM

451
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CT-SCAN 250B-RAD-RDS-12A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient puts on hospital gown Radiographic unit, Computerized 1
b. Radiologic Technologist prepares and position patient Tomography
c. for CT-Scanning procedure Emergency kit 1
d. Patient undergoes CT-Scanning procedure IV stand 1
e. Patient uses toilet Transformer & Power Distrubution 2
Unit
Negatoscope 1
CT Injector Unit 1
Lead rubber gown 1
Lead rubber gloves 1 pair
Dehumidifier 1
People Involved: Medical gas console : (Air, 1
1 x Radiologic Technologist Oxygen, Vacuum)
1 x Radiologist Waste bin w/ yellow lining 1
Patient
Patient's Companion FURNITURE AND
QUANTITY REMARKS
RT Intern FIXTURE CHECKLIST
Counter, with cabinets above and below 1
Cabinet, mobile 1
Sink, stainless steel 1
Footstool 1
Concealed floor drain 1
Indicator light (above door, 1
exterior side) 1
Lead apron rack 1
Clock 1
Lavatory 1
water closet 1
Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS
a. Close to Outpatient Department ENGINEERING TERMINALS
b. Close to Emergency Department Outlet, 10A,2P,240V, duplex 6 grounding type,
c. Close to other Ancillary Services universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, Airconditioning unit 2 Split-type
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1
Hospital Pole Transformer 1 75 KVA min., 3 dia.
Standby Generator Set 1 75 KVA min., 3 dia.

452
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CT-SCAN 250B-RAD-RDS-12B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary

Cooling load (TR) 2.8

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Radiology Staff & patient

Fire risk LOW: medium: high

Other risks exposure to radiation

453
1650 4800

2200
17 18

15

2 8
9

7080
1
SD
D
T
4
10
12 6 16
13
14 CH
3 11 5 7

6350
KEY SCALE 1:150 M
1 Radiographic unit, Computerized 11 Sharps disposal unit
Tomography 12 Clock
2 Transformer & power distribution unit 13 Waste bin
3 Counter, with cabinets above and below 14 Concealed floor drain
4 Cabinet, mobile 15 Medical gas console : Air,
5 Sink, stainless steel Oxygen, Vacuum)
6 IV stand 16 Indicator light (above door,
7 Lead apron rack exterior side)
8 Footstool 17 TOILET
9 Negatoscope 18 CONTROL ROOM
10 CT injector unit

454
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CT-SCAN CONTROL ROOM 250B-RAD-RDS-13A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Radiologic Technician/Technologist formulates/ sets Control console 1
CT techniques Automatic Voltage Regulator 1
b. Radiologic Technician/Technologist gives instruction to Lead Glass View Window 1
patient undergoing CT-Scans Automatic Film Processor 1
c. Radiologic Technician/Technologist conducts Waste bin w/ black lining 1
CT-Scan examination Uninterrupted Power Supply 1
d. Radiologic Technician/ Technologist views patient Surge Supressor 1
during CT-Scan examinations

People Involved: FURNITURE AND


QUANTITY REMARKS
Radiologic Technologist FIXTURE CHECKLIST
RT Interns Desk, with computer & printer 1
Radiologist Chair, swivel 2
Resident Physician Clock 1
Whiteboard 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to CT-Scan ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Power supply for CT-Scan 1 1 dia. Or 3 dia.
Smoke detector 1
Outlet, Telephone 1
Outlet, Data 1

455
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY CT-SCAN CONTROL ROOM 250B-RAD-RDS-13B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Radiology Staff

Fire risk LOW: medium: high

Other risks NA

456
4800

2280
SD
3
3
1 2
6 TD 4

KEY SCALE 1:100 M

1 Control console
2 Desk, with computer & printer
3 Chair, swivel
4 Clock
5 Whiteboard
6 Waste bin

457
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY MRI MAGNET ROOM 250B-RAD-RDS-14A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient enters room wearing hospital gown MRI Machine 1
b. Patient is positioned by technologist on the Penetration panel 1
moveable examination table. Oxygen monitor/depletion 1
c. Patient will be fitted with devices depending alarm
on requirement of procedure Medgas Console 1
d. If necessary, physician, technologist, or nurse
will insert IV line into patient's hand/arm
and inject contrast media.
e. Patient will be placed into the magnet of the
MRI unit and radiologist and technologist will
perform the examination from the control room
f. After images have been taken, patient waits FURNITURE AND
QUANTITY REMARKS
until radiologist and technologist checks the FIXTURE CHECKLIST
images to ensure that no additional images are Footstool 1
necessary IV Stand 1
g. IV line is removed, and patient is asked to dress Sharps disposal unit 1
back into street clothes; hospital gown is placed Cabinet, storage 1
into soiled linen hamper

People Involved:
1 x Patient
1 x Technologist

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to MRI Control Room ENGINEERING TERMINALS
b. Adjacent to MRI System Component Room Outlet, 10A,2P,240V, duplex 8 grounding type,
c. Near Imaging Department universal slots
d. Accessible from ER Department Outlet, 10A,2P,240V, single 1 emergency light
e. Accessible from OPD Medical gas console (Air, 1
f. Accessible from Nursing Wards Oxygen, Vacuum flowmeter)

458
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY MRI MAGNET ROOM 250B-RAD-RDS-14B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out ESSENTIAL:desirable:unnecessary

Cooling load (TR) 2.5 - 3

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit MRI, radiology staff & patient

Fire risk LOW: medium: high

Other risks exposure to radiation

459
7300

8
2

5900
3

4
5 6 7

KEY SCALE 1:100 M


1 MRI Machine 5 Sharps disposal unit
2 Penetration panel (locate between 6 Medical gas console : Air,
MRI Magnet Room and System Oxygen, Vacuum)
Component Room) 7 Oxygen monitor / depletion alarm
3 Footstool 8 Cabinet, storage
4 IV stand

460
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY MRI CONTROL ROOM 250B-RAD-RDS-15A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. MRI technologist prepares MRI technique/ MRI control console 1
program per patient's requirement Clock 1
b. After briefing and preparing the patient in the
MRI Magnet Room, technologist returns to
Control Room
c. Technologist performs MRI examination
on patient from Control Room
d. Technologist checks the images before
informing the patient that examination is
finished
f. If necessary, technologist performs additional
examination on patient FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Desk 1
Computer with printer 1
Chair, swivel 1
Whiteboard 1
People Involved: Waste bin 1
1 x Technologist
1 x Radiologist

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to MRI Magnet Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light

461
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY MRI CONTROL ROOM 250B-RAD-RDS-15B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out ESSENTIAL:desirable:unnecessary

Cooling load (TR) 2.5 - 3

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit MRI, radiology staff

Fire risk LOW: medium: high

Other risks exposure to radiation

462
5500

1
3

T
D

9000
SD
5 2 4
6

KEY SCALE 1:100 M


1 Control console 4 Clock
2 Desk, with computer & printer 5 Whiteboard
3 Chair, swivel 6 Waste bin

463
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-RAD-RDS-16A
MRI SYSTEM COMPONENT
April 2016 RADIOLOGY ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Location of MRI system components MRI system components refer to vendor for qty
MRI magnet chiller refer to vendor for qty
Note : MRI magnet chiller located remotely Penetration panel located between
MRI Magnet Room
& Sys Component
Room

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Technologist FIXTURE CHECKLIST
1 x Radiologist

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to MRI Magnet Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

464
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-RAD-RDS-16B
MRI SYSTEM COMPONENT
April 2016 RADIOLOGY ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) refer to supplier Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) refer to supplier Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) refer to supplier Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration refer to supplier Privacy essential:desirable:UNNECESSARY

Humidity (%RH) refer to supplier Black out essential:desirable:UNNECESSARY

Cooling load (TR) refer to supplier

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit MRI, radiology staff

Fire risk LOW: medium: high

Other risks NA

465
2200

2
3 2

6100
SD

KEY SCALE 1:100 M


1 MRI system components (per MRI
vendor)
2 MRI magnet chiller (remotely
located)
3 Penetration panel (locate between
MRI Magnet Room and System
Component Room)

466
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY DARK ROOM 250B-RAD-RDS-17A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. X-ray Technician/Technologist mixes/ prepares processing Manual Film Processing tank 1
b. X-ray Technician/Technologist loads unexposed X-ray films Leaded pass box 1
to the casette Safelight 1
c. X-ray Technician/Technologist unloads exposed X-ray films Automatic Film Processor 1
from the casette for processing X-ray casetter w/ intensifying screens 1
d. X-ray Technician/ Technologist processes X-ray film Exhaust fan 1
X-ray Technician/ Technologist cleans manual processing Luminous timer 1
tanks and automatic processor Film hanger rock 1
X-ray Technician/ Technologist maintains processing Waste bin w/ yellow lining 1
equipment and performs dark room quality control tests Metallic Stem dial type thermometer 1
Towel bar 1
Film Dryer 1
Plastic Paddles 2
Patient ID film marker 1

People Involved:
X-ray Radiologic Technologist
Radiology Department Staff
X-ray Interns FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Film loading counter 1
Counter, with cabinets above and 1
below
Sink, stainless steel 1
Concealed floor drain 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to X-ray Room ENGINEERING TERMINALS
b. Adjacent to Control Room Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1
Outlet, Telephone 1
Outlet, Data 1

467
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY DARK ROOM 250B-RAD-RDS-17B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Radiology Staff

Fire risk low: MEDIUM : high

Other risks NA

468
1800

3
1 2
7

3000
SD
T
D 10
8 9
5CH
6 4

KEY SCALE 1:100 M


1 Film processor 6 Sink, stainless steel
2 Film loading counter 7 Pass-through box
3 Film bin 8 Concealed floor drain
4 Processing tank 9 Exhaust fan, ceiling mounted
5 Counter, with cabinets above and 10 Waste bin
below

469
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY STAFF LOUNGE/ T&B 250B-RAD-RDS-18A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Lounging area for Radiology staff Waste bin w/ black lining 3
b. Radiology staff stores personal belongings Exhaust fan 1
c. Radiology staff uses toilet facilities Ceiling fan 1
Refrigerator 1
Water dispenser 1

People Involved: FURNITURE AND


QUANTITY REMARKS
10 x Radiologic Technologist FIXTURE CHECKLIST
1 x Ultranologist Table, dining 1
3 x Clerk Chair; dining 4
Resident Physicians Counter, with cabinets above 1
and below
Sink, stainless steel 1
Locker, steel, 300 x 500mm 5
Concealed floor drain 1
Slop sink with faucet 1
Shelf, open 1
Water closet 4
Lavatory 4
Urinal 2

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Radiologist's office ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1

470
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 RADIOLOGY STAFF LOUNGE/ T&B 250B-RAD-RDS-18B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.75

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit Radiology Staff

Fire risk LOW: medium : high

Other risks NA

471
3000

9 CH
3
2 2
1 8 4

3900
2 2
SD 5
6

77 77 7

3000
11800
10

11

3000
14 13
1900

12

KEY SCALE 1:150 M


1 Table, dining 8 Concealed floor drain
2 Chair; dining 9 Waste bin
3 Counter, with cabinets above
and below 10 FEMALE STAFF TOILET
4 Sink, stainless steel
5 Refrigerator 11 MALE STAFF TOILET
6 Water dispenser
7 Locker, steel, 300 x 500mm 12 JANITOR'S CLOSET
13 Slop sink with faucet
14 Shelf, open

472
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.5 NURSING SERVICE FACILITIES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

473
Hospital: Department of Health
250-Bed (Level 3)
SERVICE FACILITY SHEET INDEX
Hospital HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 NURSING WARDS 250B-NU-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
NURSING WARDS 178.00 250B-NU-DDS-01 476
Nurse Station 42.00 250B-NU-RDS-01 477
Treatment Area 12.00 250B-NU-RDS-02 480
Department Head's Office 21.00 250B-NU-RDS-03 483
Conference Room 31.00 250B-NU-RDS-04 486
Patient Room (Typical) 18.00 250B-NU-RDS-05 489
4-Bed Ward (Typical) 36.00 250B-NU-RDS-06 492
Isolation Room (Typical) 18.00 250B-NU-RDS-07 495

475
476
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS NURSE STATION 250B-NU-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse makes plan of her activities and determines Nurse call console 1
priorities Rack, chart 1
b. Nurse makes proper inventory of available resources: E-cart 1
supplies, medicine, etc.; to determine requisitions Whiteboard 1
c. Nurse prepares for admission of patient Clock 1
d. Nurse enters name of patient in admission book, Sharps container 1
ward directory, and diet work book Hamper, dirty linen 1
e. Nurse makes phones calls to coordinate with other Computer 1
hospital units regarding admitted patient Waste bin w/ yellow lining 1 infectious
f. Nurse entertains queries from visitors of patient Waste bin w/ black lining 1 general
g. Nurse records and reports patient care activities and
observations made
h. Nurse receives endorsements
i. Nurse carries out doctor's orders FURNITURE AND QUANTITY REMARKS
j. Nurse prepares and gives out medication FIXTURE CHECKLIST
k. Nurse conducts health education Counter, 2-level 1
l. Nurse transfers patient to examining table Table, 6-seater 1
m. Physician/Nurse administers necessary medical and Chair, upright; stacking 6
surgical treatment to patient Stool, adjustable height 2
Counter, with cabinets above 1
and below
Sink 2
People Involved: Concealed floor drain 1
1 x Chief Nurse Desk, 600 x 1200mm; with 1
2 x Staff Nurse computer and printer
1 x Nursing Attendant Chair, swivel 1
Physicians Shelf 1
Cabinet 1
Sink, deep 1
Stretcher / wheelchair nook 1
Lavatory 1
Water closet 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Nursing Wards ENGINEERING TERMINALS
b. Adjacent to Utility Rooms and Linen Rooms Window curtain rail 1
c. Close to Treatment Room Outlet, 10A,2P,240V, duplex 12 grounding type,
universal
Outlet, 10A, 2P, 240V, single 3 for emergency light
Outlet, telephone 2
Outlet, DATA 2
Paging System 1
Smoke detector 1

477
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS NURSE STATION 250B-NU-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General Illumination (LUX) 750

Room temperature (°C) 23 Night illumination (LUX) 750

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.8

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be Tonal Impact Domestic hot water: at medical preparation sink

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

478
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS NURSE STATION 250B-NU-RDS-01C
TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS:
DIRECT SERVICES DESIGN DATA 4000 2000

Disposal hospital solid waste type: A, B, G


Hot Water required at medical sink

3000
Cold Water required at sink & toilet fixtures 22

Drainage req'd at sink, toilet fixt. & floor


Gas NA
12 9 DT
11 CH
4 6

Compressed Air NA
11

4300
CH

Steam NA
10 SD 2 3 CH
4
CH
1

Others NA
1513
14

DIRECT DEMANDS ON FLOOR AND WALL


8 5

DT 20

Loading NA 1700
17 16

19 21 7

Spillage SLIGHT:occasional:frequent
18

KEY SCALE 1:150 M

Foot Traffic light:MEDIUM:heavy NURSE STATION: 13 Waste bin, general

Wheel Traffic NA
1 Counter, 2-level 14 Waste bin, infectious
2 Table, 6-seater 15 Sharps container
3 Chair, upright; stacking
Impacts NA
OFFICE:
4 Stool, adjustable height
16 Desk, 600 x 1200mm; with
5 Rack, chart

Abrasion NA
6 Nurse call console computer and printer
7 E-cart 17 Chair, swivel

Easy Maintenance ESSENTIAL:desirable:unnecessary


18 Shelf
8 Whiteboard
9 Clock CLEAN LINEN:

Vibration Free essential:DESIRABLE:unnecessary


19 Cabinet
MEDICATION PREPARATION & CLEAN

Door Set NA, open to circulation


UTILITY: DIRTY UTILITY/DIRTY LINEN:
10 Counter, with cabinets above 20 Sink, deep
and below
Windows NA
21 Hamper, dirty linen
11 Sink

SPACE DEMANDS (Total Minimum Space Required in sq.m.) :


12 Concealed floor drain 22 Stretcher / wheelchair nook

Internal Glazing NA
Space Components Minimum Space Required/Component (sq.m.)
Work Area
Medicine Preparation
Toilet

REGULATIONS AND NOTES:

479
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS TREATMENT AREA 250B-NU-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on foot, in wheelchair or on a Footstool 1
stretcher trolley from ward Table, instrument 1
b. Transfer of patient from wheelchair or stretcher Table, Mayo 1
trolley to examining table Cart, dressing 1
c. Physician or nurse administers necessary medical, Examination lamp 1
surgical and/or first-aid treatment to patient IV / Irrigator stand 1
Negatoscope 1
Nurse call 1
Whiteboard 1
Kick bucket 1
Sharps container 1
Waste bin w/ yellow lining 1 infectious
Waste bin w/ black lining 1 general

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Physician FIXTURE CHECKLIST
1 x Nurse/ Nursing Attendant Examination table 1
1 x Patient Stool, adjustable height 1
Counter, with cabinets above 1
and below
Sink, combination scrub and 1
instrument; with goose-neck
foot-operated/elbow control
Cubicle curtain and rod or 1
PVC folding partition
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Nurse Station ENGINEERING TERMINALS
b. Close to Inpatient Nursing Wards Window curtain rail 1
Nurse call station, emergency 1
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke Detector 1

480
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS TREATMENT AREA 250B-NU-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.8

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at sink & toilet lavatory

tolerated Maximum temperature (°C) 70

Access limit medical staff & patient

Fire risk LOW: medium: high

Other risks NA

481
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS TREATMENT AREA 250B-NU-RDS-02C
TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS:
DIRECT SERVICES DESIGN DATA
Disposal hospital solid waste type: A,B,G
Hot Water required at sink
4000

Cold Water required at sink 5


11 6 7 15

Drainage required at floor below sink 8


9

Medical Oxygen 20 lpm @ 4.0 Bar

3000
16 SD
17 1

Medica Vacuum 40 lpm @ 450mm Hg


19 18 12
3
CH 10 2 13
Compressed Air NA 4 14

Steam NA
Others 1 Nurse Call (to Nurse Station)

DIRECT DEMANDS ON FLOOR AND WALL


Loading NA
Spillage SLIGHT:occasional:frequent KEY SCALE 1:100 M

Foot Traffic light:MEDIUM:heavy 1 Examination table 10 IV / Irrigator stand

Wheel Traffic light:MEDIUM:heavy


2 Stool, adjustable height 11 Negatoscope
3 Footstool 12 Nurse call

Impacts NA
4 Counter, with cabinets above 13 Whiteboard
and below 14 Cubicle curtain and rod or
Abrasion NA
5 Table, instrument PVC folding partition
6 Table, Mayo 15 Kick bucket
Easy Maintenance ESSENTIAL:desirable:unnecessary 7 Cart, dressing 16 Concealed floor drain

Vibration Free ESSENTIAL:desirable:unnecessary


8 Sink, combination scrub and 17 Waste bin, infectious
instrument; with goose-neck 18 Waste bin, general

Door Set examining table, wheel-


foot-operated/elbow control 19 Sharps container
9 Examination lamp

chair & stretcher access SPACE DEMANDS (Total Minimum Space Required in sq.m.) :
Windows clear, solar control, Space Components Minimum Space Required/Component (sq.m.)
privacy control Treatment Area
Internal Glazing NA

REGULATIONS AND NOTES:


Provide window shade

482
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS DEPARTMENT HEAD'S OFFICE 250B-NU-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Department Head reads, writes and uses telephone Waste bin w/ black lining 2 general
on his desk
b. Department Head receives visitors
c. Department Head is consulted by patients/relatives
d. Secretary stores, files and retrieves records
e. Department Head supervises the nursing
department's activities

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Department Head FIXTURE CHECKLIST
Physicians Clerical desk 1
Nurses Executive desk, 1200mm x 600mm 1
Visitors Shelves 1
Table, side; 400 x 400mm 1
Chair, upright; stacking 4
Visitor's Chair 1
Executive chair w/ armrest 1
Sofa, 2-seater 1
Steel filing cabinet 3
Lavatory 1
Water closet 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Department's main entrance ENGINEERING TERMINALS
b. Close to Inpatient Nursing Wards Station Window curtain rail 1
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, Telephone 2
Outlet, DATA 2
Smoke Detector 1

483
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS DEPARTMENT HEAD'S OFFICE 250B-NU-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) 70

Access limit Department Head, Staff, Visitors

Fire risk LOW: medium: high

Other risks NA

484
NA

485
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS CONFERENCE ROOM 250B-NU-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Department Head receives visitors Whiteboard / projection screen 1
b. Department Head is consulted by patients/relatives Waste bin w/ black lining 1
c. Department Head conducts staff meetings and LCD Projector 1
special lectures Sound System 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Department Head FIXTURE CHECKLIST
Physicians Table, 500 x 1500mm 6
Nurses Counter, with cabinets above 1
Visitors and below 1
Chair, upright; stacking 12

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Department's main entrance ENGINEERING TERMINALS
b. Close to Inpatient Nursing Wards Station Window curtain rail 2
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, Telephone 1
Outlet, DATA 1
Smoke Detector 1

486
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS CONFERENCE ROOM 250B-NU-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) 70

Access limit Department Head, Staff, Visitors

Fire risk LOW: medium: high

Other risks NA

487
NA

488
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS PATIENT ROOM (TYPICAL) 250B-NU-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on foot, in wheelchair or on a stretcher Television 1
trolley Console, bedhead 1
b. Transfer of patient to a hospital bed from a Waste bin w/ yellow lining 1 infectious
wheelchair or a stretcher trolley and vice versa Waste bin w/ black lining 2 non-biodegradable
c. Patient undresses/dresses in the vicinity of Water Heater 1
hospital bed, with or without assistance
d. Patient takes meal in bed or in sitting area FURNITURE AND
QUANTITY REMARKS
e. Patient receives visitors FIXTURE CHECKLIST
f. Patient stores clothing and other personal Hospital bed, adjustable; with 1
belongings adjustable side rails
g. Patient requires privacy Chair, upright; stacking 1
h. Patient uses toilet and bath Footstool 1
i. Use of monitoring/ diagnostic equipment on the patient Bench, cushioned 1
j. Physicians and nurses check on patients Table, side; with cabinet 1
k. Handwashing and other clean up activities Table, overbed 1
l. Nurse gives medication to patient Closet, wardrobe 1
m. Nurse may feed or wash patient, in the absence of Lavatory, wall-hung 1 at strategic locations
a relative or watcher along corridor
Concealed floor drain 1
Water Closet w/ spray hose 1
Lavatory 1
People Involved: Shower Set 1
1 x Patient
2 x Visitors ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
1 x Resident Physician/ Medical Specialist ENGINEERING TERMINALS
1 x Nurse or Nursing Aide Window curtain rail 1
Bedhead light w/ night lamp 1 fluorescent, 20W
w/ pendant switch
Outlet, 10A,2P,240V, duplex 6 grounding type,
Planning Relationships: universal
a. Close to Nurse Station Outlet, 10A,2P,240V, single 1 for emergency light
b. Close to Medical/Surgical Services Nurse call station, normal 1 w/ pendant switch
c. Distant from Out-patient Department Nurse call station, emergency 1 w/ pendant switch
Outlet, antenna/Cable 1
Smoke Detector 1

489
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS PATIENT ROOM (TYPICAL) 250B-NU-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70


medical staff, relatives/watcher &
Access limit
patient
Fire risk LOW: medium: high

Other risks NA

490
491
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS 4-BED WARD (TYPICAL) 250B-NU-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on foot, in wheelchair or on a stretcher Television 1
trolley Console, bedhead 4
b. Transfer of patient to a hospital bed from a Waste bin w/ yellow lining 1 infectious
wheelchair or a stretcher trolley and vice versa Waste bin w/ black lining 2 non-biodegradable
c. Patient undresses/dresses in the vicinity of Water Heater 1
hospital bed, with or without assistance
d. Patient takes meal in bed or in sitting area FURNITURE AND
QUANTITY REMARKS
e. Patient receives visitors FIXTURE CHECKLIST
f. Patient stores clothing and other personal Hospital bed, adjustable; with 4
belongings adjustable side rails
g. Patient requires privacy Chair, upright; stacking 4
h. Patient uses toilet and bath Footstool 4
i. Use of monitoring/ diagnostic equipment on the patient Cubicle curtain and rod 4
j. Physicians and nurses check on patients Table, side; with cabinet 4
k. Handwashing and other clean up activities Table, overbed 4
l. Nurse gives medication to patient Closet, wardrobe 4
m. Nurse may feed or wash patient, in the absence of Lavatory, wall-hung 1 at strategic locations
a relative or watcher along corridor
Concealed floor drain 2
Water Closet w/ spray hose 1
Lavatory 1
People Involved: Shower Set 1
4 x Patient
4 x Visitors ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
1 x Resident Physician/ Medical Specialist ENGINEERING TERMINALS
1 x Nurse or Nursing Aide Window curtain rail 1
Bedhead light w/ night lamp 4 fluorescent, 20W
w/ pendant switch
Outlet, 10A,2P,240V, duplex 16 grounding type,
Planning Relationships: universal
a. Close to Nurse Station Outlet, 10A,2P,240V, single 1 for emergency light
b. Close to Medical/Surgical Services Nurse call station, normal 1 w/ pendant switch
c. Distant from Out-patient Department Nurse call station, emergency 1 w/ pendant switch
Outlet, antenna/Cable 1
Smoke Detector 1

492
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS 4-BED WARD (TYPICAL) 250B-NU-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70


medical staff, relatives/watcher &
Access limit
patient
Fire risk LOW: medium: high

Other risks NA

493
494
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS ISOLATION ROOM (TYPICAL) 250B-NU-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on foot, in wheelchair or on a stretcher Television 1
trolley Waste bin w/ yellow lining 1 infectious
b. Transfer of patient to a hospital bed from a Waste bin w/ black lining 1 general
wheelchair or a stretcher trolley and vice versa Water Heater 1
c. Patient undresses/dresses in the vicinity of Console, bedhead 1
hospital bed, with or without assistance
d. Patient takes meal in bed or in sitting area FURNITURE AND QUANTITY REMARKS
e. Patient receives visitors FIXTURE CHECKLIST
f. Patient stores clothing and other personal Hospital bed, adjustable; with 1
belongings adjustable side rails
g. Patient requires privacy Chair, upright; stacking 1
h. Patient uses toilet and bath Footstool 1
i. Patient uses monitoring/diagnostic equipment Bench, cushioned 1
j. Physicians and nurses check on patients Table, side; with cabinet 1
k. Handwashing and other clean up activities Table, overbed 1
l. Nurse gives medication to patient Closet, wardrobe 1
m. Nurse may feed or wash patient, in the absence of Lavatory, wall-hung 1
a relative or watcher Concealed floor drain 1
Cabinet, PPE 1
Water closet 1
Lavatory 1
People Involved: Shower set 1
1 x Patient
2 x Visitors ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
1 x Resident Physician/ Medical Specialist ENGINEERING TERMINALS
1 x Nurse or Nursing Aide Window curtain rail 1
Bedhead light w/ night lamp 1 fluorescent, 20W
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal
Planning Relationships: Outlet, 10A,2P,240V, single 1 for emergency light
a. Acessible to Nurse Station Nurse call station, emergency 1 w/ pendant switch
b. Located at end portion of Nursing Ward Outlet, antenna/Cable 1
c. Close to medical/surgical services Smoke Detector 1

495
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NURSING WARDS ISOLATION ROOM (TYPICAL) 250B-NU-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 50

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.75

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70


medical staff, relatives/watcher &
Access limit
patient
Fire risk LOW: medium: high

Other risks NA

496
497
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.6 BURN UNIT SERVICE FACILITIES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

499
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 BURN UNIT 250B-BU-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
BURN UNIT 39.00 250B-BU-DDS-01 502
Nurse Station 15.00 250B-BU-RDS-01 503
Patient Cubicle 13.00 250B-BU-RDS-02 506
Whirlpool Bath 11.00 250B-BU-RDS-03 509

501
SCALE 1:300 M

10600

DN
COUNSELLING COUNSELLING
ROOM ROOM
FAMILY
WAITING
ROOM
2400

WHIRLPOOL
BATH 4

DIRTY
2700

UTILITY/
LINEN
3
12000

1500 2100

CLEAN
UTILITY

2
T BURN UNIT
3300

VIEWING CORRIDOR

CHANGING 1
AREA

SURGICAL ICU

502
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
APRIL 2016 BURN UNIT NURSE STATION 250B-BU-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a wheelchair or stretcher trolley Emergency light 1
b. Patient is transferred to bed and vice versa Central monitor (cardiac) 1
c. Nurses and nursing attendants monitor vital E-cart 1
signs of patient at regular intervals EENT diagnostic set 1
d. Nurses and nursing attendants attend to patient's Computer, with monitor and 1
needs at regular intervals: cleaning and dressing printer
of wounds, application of medicine, etc. Clock 1
e. High level nursing and medical dependence Rack, chart 1
Waste bin w/ yellow lining 2 hazardous
Waste bin w/ black lining 2
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Counter, nurse station 1
People Involved: Counter, work, with cabinets 1
Patients above and below
1 x Resident Physician / Medical Specialist Shelf, open 1
1 x Nurse Sink, stainless steel 1
1 x Nursing Attendant Sink, utility 1
Stool, adjustable height 2
Lavatory 1
Water closet 1
ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 8 grounding type,
universal slots
Outlet, 10A,2P,240V, single 2 for emergency light
Outlet, data 1
Planning Relationships: Outlet, telephone 1
a. Close to patient cubicles Paging system 1
b. Visual control of main entrance and visitors' Nurse call console 1
changing room Split-type, ACU 3-ton 1
Smoke detector 2

503
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
APRIL 2016 BURN UNIT NURSE STATION 250B-BU-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 12.75 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m.hr.) 900 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Exhaust (psi) NA Daylight essential:DESIRABLE:unnecessary

Inlet (psi) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 6

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit patient and medical staff

Fire risk LOW: medium : high

Other risks infection from bacteria

504
2250

9
T
D

4 1
5
3 2

6600
SD
8

KEY SCALE 1:100 M

1 Counter 7 Glass board / white board


2 Computer, with printer 8 Clock
3 Chair; adjustable 9 Waste bin
4 Counter, with cabinets
above and below
5 Sink
6 E-cart

505
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BURN UNIT PATIENT CUBICLE 250B-BU-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a wheelchair or stretcher trolley Emergency light 1
b. Patient is transferred to bed and vice versa Volume respirator 1
c. Nurses and nursing attendants monitor vital Sphygmomanometer, wall-mtd 1
signs of patient at regular intervals Ambu bag, adult/pedia 1
d. Nurses and nursing attendants attend to patient's Suction apparatus 1
needs at regular intervals: cleaning and dressing Oxygen gauge 1
of wounds, application of medicine, etc. Tracheostomy set 1
e. High level nursing and medical dependence Infusion pump 1
f. Nurses and nursing attendants screen potentially Respirator/defribrillator 2

infectious visitors Patient headwall 2


g. Nurses and nursing attendants observe barrier IV track 1
technique: use of gloves and gown during contact Bedhead light/lamp 1
with patient, washing or disinfecting of hands patient monitor 1
before donning gloves and after removal of gloves

FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
People Involved: Hospital bed, adjustable 1
1 x Patient Bedhead console, w/ med gas 1
1 x Resident Physician Table, overbed 1
1 x Nurse Counter, with storage 1
1 x Nursing Attendant Door, glass; w/ windows 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 8 grounding type,
Planning Relationships: universal slots
a. Visible from Burn Unit Nurse Station Outlet, 10A,2P,240V, single 2 for emergency light
Outlet, data 1
Outlet, telephone 1
Paging system 1
Nurse call console 1
Smoke detector 2

506
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BURN UNIT PATIENT CUBICLE 250B-BU-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature 20-22 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Exhaust (psi) NA Daylight essential:DESIRABLE:unnecessary

Inlet (psi) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) 70

Access limit patient and medical staff

Fire risk LOW: medium : high

Other risks infection from bacteria

507
4100

4 2
5
8
1
10

3000
7 SD 6
3

KEY SCALE 1:100 M

1 Hospital bed, adjustable 6 Light, emergency


2 Bedhead console, with medical 7 Alcohol/alcogel station;
gas outlets, power outlet, and wall-mounted
bedhead light 8 Waste bin
3 Table, overbed 9 Door, glass; with full windows
4 Monitor, patient 10 Window
5 Counter; for medicine, supplies

508
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BURN UNIT WHIRPOOL BATH 250B-BU-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Immersion tub is filled with sterile water Emergency light 1
b. Patient is gently placed in tub (using a transfer patient monitor 1
trolley) Clock 1
c. Nurse/nursing attendant perform initial evaluation
d. Nurse/nursing attendant perform debridement,
blisters and wounds area cleaned and cared for
e. After the hydrotherapy procedure, patient is
gently lifted out of the immersion tub
f. Patient is returned to his/her cubicle for

dressing of wounds, and application of topical


antimicrobial agent, and dressed again FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Immersion tub, stainless steel 1
Counter, with storage 1
People Involved: Cart, supply 1
1 x Patient Towel rack 1
1 x Resident Physician
1 x Nurse
1 x Nursing Attendant

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Planning Relationships: Outlet, 10A,2P,240V, duplex 4 grounding type,
a. Visible from Burn Unit Nurse Station universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Paging system 1
Nurse call console 1
Smoke detector 1

509
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 BURN UNIT WHIRPOOL BATH 250B-BU-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature 22-25 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1,000

Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Exhaust (psi) NA Daylight essential:desirable:UNNECCESARY

Inlet (psi) NA View out essential:desirable:UNNECCESARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SAFETY

SOUND Accessible hot surface: NA

Acceptable sound level (db) 40 Maximum temperature (°C) NA

Speech privacy essential:desirable:UNNECESSARY Domestic hot water: at tub

Quality which cannot be tonal impact Maximum temperature (°C) 70 (water temperature

tolerated depends on patient comfort)

Access limit patient and medical staff

Fire risk LOW: medium : high

Other risks infection from bacteria

510
4350

4
2
5

2400
SD 1
3
6

KEY SCALE 1:100 M

1 Immersion tub; stainless steel


2 Counter, with overhead cabinets
3 Cart, supply
4 Towel rack
5 Floor drain, concealed
6 Clock

511
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.7 OPERATING ROOM & ICU SERVICE FACILITIES

3.7.1 OR
3.7.2 ICU
3.7.3 CSSR

First Edition
DEPARTMENT OF HEALTH
Manila
2017

513
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX 250B-OR-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
OPERATING ROOM COMPLEX 390.00 250B-OR-DDS-01 516
Transfer Area 12.00 250B-OR-RDS-01 517
Pre-Operation Area 23.00 250B-OR-RDS-02 520
Nurse Station 36.00 250B-OR-RDS-03 523
Operating Room 36.00 250B-OR-RDS-04 526
Post-Anesthetic Care Unit (PACU) 78.00 250B-OR-RDS-05 529
Dress, Lockers, T&B 31.00 250B-OR-RDS-06 532
Lounge 24.00 250B-OR-RDS-07 535
Anesthesiologist's Office 30.00 250B-OR-RDS-08 538
Anesthesia Storage 7.00 250B-OR-RDS-09 541
Sterile Instrument and Supply Storage 9.00 250B-OR-RDS-10 544
Scrub-Up Area 18.00 250B-OR-RDS-11 547
Sub-Sterile Room 18.00 250B-OR-RDS-12 550
Clean-Up Room 18.00 250B-OR-RDS-13 553
Janitor's Closet 5.00 250B-OR-RDS-14 556
Family Waiting Room 18.00 250B-OR-RDS-15 559
Scope Room 27.00 250B-OR-RDS-16 562
Dirty / Trauma 27..00 250B-OR-RDS-17 565

INTENSIVE CARE UNIT 158.00 250B-ICU-DDS-01 568


Nurse Station 46.00 250B-ICU-RDS-01 569
Patient Bay 57.00 250B-ICU-RDS-02 572
Isolation Room 13.00 250B-ICU-RDS-03 575
Office 13.00 250B-ICU-RDS-04 578
Family Counseling Room 13.00 250B-ICU-RDS-05 581
Visitor's Dressing Room 5.00 250B-ICU-RDS-06 584
Staff Lockers and Toilet 11.00 250B-ICU-RDS-07 587

CENTRAL STERILIZING & SUPPLY ROOM 129.00 250B-CSSR-DDS-01 590


Receiving Room 13.00 250B-CSSR-RDS-01 591
Work Area 71.00 250B-CSSR-RDS-02 594
Autoclave Room 16.00 250B-CSSR-RDS-03 597
Storage Room 29.00 250B-CSSR-RDS-04 600

515
516
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-01A
OPERATING ROOM
April 2016 COMPLEX TRANSFER AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient scheduled for delivery is transferred from Stretcher, ward 1 ward use
ward stretcher to surgical suite stretcher Stretcher, OR Complex 1 surgical suite use

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Nursing Attendant FIXTURE CHECKLIST
1 x Patient

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Located at the entrance of Operating Room Complex ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 2 grounding type,
parallel slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1

517
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX TRANSFER AREA 250B-OR-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit patient and medical staff

Fire risk LOW: medium: high

Other risks NA

518
519
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-02A
OPERATING ROOM
April 2016 COMPLEX PRE-OPERATION AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient may arrive on a stretcher trolley Thermometer, non-mercurial 1
b. Patient may arrive in a wheelchair Sphygmomanometer 1 non-mercurial
c. Patient is transferred from stretcher/ wheelchair Paper towel dispenser 1
to examining bed and vice-versa Towel rack 1
d. Preparation of a patient for surgery Gooseneck lamp 1
e. Evaluation of laboratory tests and medical history Sharps collector 1
f. Sterilizing the bowel with drugs Waste bin w/ black lining 1
g. Anesthesia is administered

People Involved:
3 x Anesthesiologist
3 x Nurse
3 x Nursing Attendant
3 x Patient
FURNITURE AND QUANTITY REMARKS
FIXTURE CHECKLIST
Hospital bed, adjustable 3
Footstool 3

Planning Relationships:
a. Close to Anesthesiologist's Office ADDITIONAL EQUIPMENT & QUANTITY REMARKS
b. With direct access to Transfer Area ENGINEERING TERMINALS
Window curtain rail 2
Cubicle curtain rail 1
Outlet, 10A,2P,240V, duplex 9 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, telephone 1
Outlet, DATA 1
Airconditioning unit 1 window/ split type
Smoke Detector 1

520
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX PRE-OPERATION AREA 250B-OR-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.4

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) 70

Access limit medical staff and patient

Fire risk low: MEDIUM: high

Other risks NA

521
NA

522
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-03A
OPERATING ROOM
April 2016 COMPLEX NURSE STATION
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Hamper, soiled linen 2
b. Patient is transferred from a stretcher trolley to bed Glass board / white board 1
and vice versa Clock 1
c. Nurses and nursing attendants monitor vital signs of Waste bin w/ black lining 3
patient at regular intervals
d. Use of monitoring and diagnostic equipment
e. High level nursing and medical dependence

People Involved: FURNITURE AND QUANTITY REMARKS


Patients FIXTURE CHECKLIST
1 x Resident Physician/ Medical Specialist Counter, 2-level 1
1 x Nurse Counter, with cabinets above 2
1 x Nursing Attendant and below
Sink, stainless steel; with 2
drainboard
Desk, 600 x 1200mm; with 1
computer
Chair; upright, stacking 1
Stool, adjustable height 2
Shelf, 450mm deep 1
Concealed floor drain 2
Lavatory 1
Water Closet 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Post-Anesthetic Care Unit Window curtain rail 2
b. Close to Nurse Supervisor's Office Outlet, 10A,2P,240V, duplex 10 grounding type,
universal
Outlet, 10A, 2P, 240V, single 2 for emergency light
Outlet, DATA 1
Outlet, telephone 1
Smoke detector 4

523
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX NURSE STATION 250B-OR-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 12.75 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 900 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 5000% Black out essential:desirable:UNNECESSARY

Cooling load (TR) 6

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit patient and medical staff

Fire risk LOW: medium: high

Other risks infection from transmissible diseases

524
525
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-04A
OPERATING ROOM
April 2016 COMPLEX OPERATING ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Double X-ray Film Illuminator 1
b. Patient is transferred from stretcher trolley to Anesthesia Unit 1 w/ scavenging sys.
operating table Clock 1
c. Anesthesia is administered Operating lamp 1
d. Clinical handwashing UV Light 1
e. Use of diagnostic equipment Oxygen Unit 1 w/ tank holder
f. Patient is surgically operated Nitrogen 1
g. Pre-operative care O2 tank holder 1
Double-film negatoscope 1
Footstool 2
Glass/ white board 1
Suction apparatus 1
Tracheostomy set 1
Laryngoscope 1
E-cart 1
Suction machine 1
Orthopedic instrument set 1
ACU 1
Cardial monitor w/ pulse oximeter 1
Sphygmomanometer, non-mercurial 1
Defibrillator 1
People Involved: FURNITURE AND
QUANTITY REMARKS
2 x Physicians FIXTURE CHECKLIST
1 x Circulatory Nurse Operating table 1
1 x Scrub Nurse Mayo table 1
1 x Patient Instrument table 2
1 x Anesthesiologist Double basin stand 1
Single basin stand 1
Anesthetist's stool 1
Adjustable stool 2
Anesthetist's table 1
Anesthesia unit 1
Kick bucket 1
Irrigator stand 1
Sponge rack 1
Shelving; adjustable, 500mm deep 1
Pack table 1
Floor clean-out 1
Planning Relationships: ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS
b. Adjacent to Scrub-Up Shades, light-proof 1 light-proof for special
eye/ dark rm. surgery
Outlet, 10A,2P,240V, duplex 11 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 2 for emergency light
Isolation Monitor 1 1.6m above floor
Grounding terminal 4 duplex
Outlet, telephone 1
Outlet, DATA 1 wall-mounted
Heat Detector 1 hospital grade,
locking type
Door with vision panel 1

526
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX OPERATING ROOM 250B-OR-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1000

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000-40,000

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patient

Fire risk low: medium: HIGH

Other risks NA

527
NA

528
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-05A
OPERATING ROOM
April 2016 COMPLEX POST-ANESTHETIC CARE UNIT

FUNCTIONAL DESIGN REQUIREMENTS:


This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Oxygen outlet, mounted 1600mm 8
b. Patient is transferred from stretcher trolley to bed Suction outlet, mounted 1600mm 8
and vice versa Suction apparatus 8
c. Nurses monitor vital signs of patient at regular Laundry hamper 1
intervals Waste bin w/ yellow lining 1 infectious
d. Use of monitoring and diagnostic equipment Standby BP apparatus 2
Wall Clock 1
Emergency light 1
Oxygen unit 1
Footstool 8
Sharps container 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Physcian FIXTURE CHECKLIST
Nurses Hospital bed, adjustable 8
Nursing Attendants Cabinet, bedside 8
Chair, upright, stacking 8
Nurse counter, w/ cabinets 1
above
Desk 1
Chair, swivel 3
Bed pan flusher 1
Sink, work 1
Water closet 1
Lavatory 1
Urinal 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room Complex ENGINEERING TERMINALS
Cubicle curtain and rod 8
Outlet, 10A,2P,240V 21 grounding type,
parallel slots
Outlet, 15A, 2P, 240V 1 grounding type,
tandem slots
Outlet, intercom 1
Split type, ACU, 3 ton 1 preferably ceiling
mounted FCU
Smoke Detector 2
Bedlight 8
Nurse Call System 1 set

529
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-05B
POST-ANESTHETIC CARE
April 2016 OPERATING ROOM COMPLEX UNIT
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.75

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patient

Fire risk LOW: medium: high

Other risks NA

530
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-05C
POST-ANESTHETIC CARE
April 2016 OPERATING ROOM COMPLEX UNIT
TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS:
DIRECT SERVICES DESIGN DATA 6000

Disposal hospital solid waste type: A, B 3 4 4 3

Hot Water required at sink


1 1

Cold Water required at plumbing fixtures


2 8 8 2
3 4 4 3

Drainage required at toilet 1 1

Medical Oxygen 20 lpm/bed @ 4.0 Bar 2 8 SD 8 2

Medical Vacuum 40 lpm/bed @ 450mm Hg


3 4 4 3

1 1

Medical Air 40 lpm/bed @ 4.0 Bar

12200
2 8 8 2

Steam NA 4 3

Others NA
1

DIRECT DEMANDS ON FLOOR AND WALL


SD 2
8
5
4 3
7

Loading NA
7
1
7

Spillage SLIGHT: occasional: frequent


T 2
D6 8
5

Foot Traffic LIGHT: medium: heavy


Wheel Traffic LIGHT: medium: heavy
9 10

Impacts NA

2100
13

Abrasion NA
11 12

Easy Maintenance ESSENTIAL:desirable:unneccesary


KEY
SCALE 1:150 M
1 Hospital bed, adjustable 6 Desk

Vibration Free ESSENTIAL:desirable:unneccesary


2 Cabinet, bedside 7 Chair, swivel CLEAN UTILITY ROOM:
3 Chair, upright, stacking 8 Cubicle curtain and rod 11 Bed pan flusher
12 Sink, work

Door Set bed, stretcher trolley


4 Footstool 9 Waste bin, infectious
5 Nurse counter, w/ cabinets 10 Sharps container 13 Concealed floor drain

SPACE DEMANDS (Total Minimum Space Required in sq.m.) :


above

chair, wheelchair access


Windows clear, solar control Space Components Minimum Space Required/Component (sq.m.)
privacy control
Internal Glazing NA

REGULATIONS AND NOTES:

531
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-06A
OPERATING ROOM
April 2016 COMPLEX DRESS, LOCKERS, T&B
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. OR staff change clothes in toilet and bathroom Waste bin w/ black lining 1
b. OR staff bathe in the bathroom Linen hamper 2
c. Storing of clothing and personal effects Dressing cubicle 1
Water heater, potable 2

People Involved: FURNITURE AND


QUANTITY REMARKS
Resident Physicians FIXTURE CHECKLIST
Bench 2
Locker; steel 11
Lavatory 2
Water closet 2
Shower 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room Complex ENGINEERING TERMINALS
b. Close to access door of Operating Room Complex Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 2

532
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX DRESS, LOCKERS, T&B 250B-OR-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at toilet and bath

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

533
NA

534
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-07A
OPERATING ROOM
April 2016 COMPLEX LOUNGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Resident Physician to take rest in between surgeries Airconditioning unit 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
Resident Physicians and Operating Room Staff FIXTURE CHECKLIST
Sofa, 2-seater 2
Table, low corner 1
Table, 6-seater dining 1
Chair, dining 6
Counter, with cabinets 1
above and below
Sink, kitchen 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room Complex ENGINEERING TERMINALS
Outlet, 10A, 2P 240V, double 6 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1

535
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX LOUNGE 250B-OR-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

536
NA

537
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-08A
OPERATING ROOM ANESTHESIOLOGIST'S OFFICE &
April 2016 COMPLEX STAFF OFFICE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Anesthesiologist reads and writes in the work station Hamper, soiled linen 1
b. Anesthesiologist records, stores and retrieves data Waste bin w/ black lining 2
from data file

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Anesthesiologist FIXTURE CHECKLIST
1 x Nurse or Nursing Attendant Desk, 600 X 1500mm 1
Desk, 600 x 1200mm 1
Desk, extension, 400 x 1200mm 1
Cabinet, steel; filing 2
Shelf, open 1
Table, meeting 1
Chair, junior executive 1
Chair, swivel 1
Chair, upright, stacking 2
Chair, with armrest 4
Cabinet, storage 1
Lavatory 1
Water Closet 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Dress, Lockers, T&B ENGINEERING TERMINALS
b. Adjacent to Operatiing Room Outlet, 10A,2P,240V, duplex 5 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1 wall-mounted
Outlet, Telephone 2 desktop
Smoke detector 1 ionization type
Outlet, TV 1 ceiling-mounted

538
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-08B
ANESTHESIOLOGIST'S
April 2016 OPERATING ROOM COMPLEX OFFICE & STAFF OFFICE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

539
540
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-09A
OPERATING ROOM
April 2016 COMPLEX ANESTHESIA STORAGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of materials related to anesthetics Waste bin w/ black lining 1
b. Retrieval of stored materials Fluorescent lamp, explosion-proof 1
c. Physical inventory of stored materials

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician/ Anesthesiologist FIXTURE CHECKLIST
Shelving, 450mm deep 2
Sink, with gooseneck spout & 1
knee or elbow control
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Located within the Surgical Area ENGINEERING TERMINALS
b. Close to Surgical Supervisor's Area Explosion-proof light fixture 1 240-W
Smoke detector 1 ionization type
Explosion-proof outlet 1

541
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX ANESTHESIA STORAGE 250B-OR-RDS-09B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

542
NA

543
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-10A
OPERATING ROOM STERILE INSTRUMENT & SUPPLY
April 2016 COMPLEX STORAGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse checks the availability of supplies for issuance
b. Nursing Attendants prepare needed supplies and articles
listed in requisition form
c. Nursing Attendants pack items individually, in bulk or
wrap w/ clean paper before issuance
d. Nurse performs physical inventory and updates stock cards
e. Nurse receives sterile supplies and instruments, puts
entry into stock cards and stores supplies into shelves

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
1 x Nursing Attendant Shelf, open 1
Cabinet, instrument 2
Door with vision panel 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Located at the Surgical Area ENGINEERING TERMINALS
b. Adjacent to Nurse Supervisor's Room Outlet, 10A,2P,240V, duplex 1 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1

544
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-10B
STERILE INSTRUMENT &
April 2016 OPERATING ROOM COMPLEX SUPPLY STORAGE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

545
NA

546
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-11A
OPERATING ROOM
April 2016 COMPLEX SCRUB-UP AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Physician and nurse rinse arms and hands with water Soap dispenser 6
and soap prior to and after surgical operation Hand Dryer 2
Clock 1
Waste Bin w/ yellow lining 1 infectious

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Physician FIXTURE CHECKLIST
1 x Nurse 3-Station Scrub sink, 2
with gooseneck spout & foot
control, sensor type
Shelves, overhead 2
Concealed floor drain 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Operating Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 3 grounding type,
or drier (touch free)
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1 ionization type

547
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX SCRUB-UP AREA 250B-OR-RDS-11B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) 250

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 30 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.6

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at scrub sink

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

548
NA

7 Concealed Floor Drain

549
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-12A
OPERATING ROOM
April 2016 COMPLEX SUB-STERILE ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Preparation of packed surgical instruments Sterilizer, small instrument 1
b. Storing and retrieving of instruments from cabinets
c. Minor sterilizing works
d. Handwashing and other clean-up activities

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Physician FIXTURE CHECKLIST
1 x Nurse or Nursing Attendant Counter, 900mm high; 2
open below
Sink with drainboard 1
Concealed floor drain 1
Door with vision panel 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Operating Room ENGINEERING TERMINALS
b. Adjacent to Scrub-Up Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1 ionization type
ACU window/ split type 1

550
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX SUB-STERILE ROOM 250B-OR-RDS-12B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.4

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: at sterilizer

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk low: MEDIUM: high

Other risks NA

551
NA

552
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-13A
OPERATING ROOM
April 2016 COMPLEX CLEAN-UP ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse and Nursing Attendant perform post-operation Hamper, linen 2
clean-up activities Waste bin w/ yellow lining 1 infectious
1 pharmaceutical

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
1 x Nursing Attendant Counter, with cabinets below 1
Counter, open below 1
Double compartment laundry tray 1
with drainboards
Clinical sink 1
Concealed floor drain 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1 ionization type

553
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX CLEAN-UP ROOM 250B-OR-RDS-13B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.75

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

554
NA

555
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-14A
OPERATING ROOM
April 2016 COMPLEX JANITOR'S CLOSET
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of janitor's cleaning tools

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Janitor FIXTURE CHECKLIST
Slop sink 1
Open shelving 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal slots

556
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX JANITOR'S CLOSET 250B-OR-RDS-14B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit janitorial/ utility staff

Fire risk LOW: medium: high

Other risks NA

557
NA

558
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-OR-RDS-15A
OPERATING ROOM
November 2015 COMPLEX FAMILY WAITING ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Resident Physician explains to patient's relatives complex Airconditioning Unit 1
medical terminologies and technologies Waste bin w/ black lining 1
b. Resident Physician updates and advises patient's relatives
on his/her isolation status/prognosis and care preferences
while acknowledging uncertainty
c. Clinician listens with patience and sensitivity to relatives'
emotions, including anger, grief and guilt
d. Ciinician prepares families for a patient's death

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician/ Clinician FIXTURE CHECKLIST
Patient's Relatives Sofa, single-seater 2
Sofa, 2-seater 2
Table, 400 x 400mm 2
Lavatory 1
Water Closet 1
Urinal 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Nurse Station ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1

559
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
November 2015 OPERATING ROOM COMPLEX FAMILY WAITING ROOM 250B-OR-RDS-15B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA


Resident Physician, Patient's
Access limit
Relatives
Fire risk LOW: medium: high

Other risks NA

560
561
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX SCOPE ROOM 250B-OR-RDS-16A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is assessed/scheduled to be brought to Endoscopic viewing monitor 1
Scope Room Light source and processor 1
b. Patient arrives on a stretcher trolley Diathermy recorder and printer 1
c. Patient is transferred from stretcher trolley to Monitoring equipment 1
procedure table Anesthesia unit 1
d. Anesthesia is administered Endoscope washer 1
e. Clinical handwashing Computer and printer 1
f. Use of scope/s equipment; necessary
procedure is done on patient
g. Patient is wheeled out to PACU for recover/ FURNITURE AND
QUANTITY REMARKS
observation FIXTURE CHECKLIST
Trolley/cart 1
Endoscope/scope storage 1
cabinet
Desk 1
Side table 1
People Involved: Chair, upright 1
1-2 x gastroenterologists/specialists Counter, w/ cabinets above and 1
1 x Nurse below
1 x Nursing Attendant Sink, stainless steel 1
1 x Patient
1 x Anesthesiologist ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
ENGINEERING TERMINALS
Planning Relationships: Outlet, 10A,2P,240V, duplex 9 grounding type,
a. Adjacent to Nurse Station universal slots
b. Near PACU Outlet, 10A,2P,240V, single 1 for emergency light
c. Accessible from sub-sterile corridor Outlet, data 1
d. Outside OR Complex sterile area Outlet, telephone 1
Smoke detector 1

562
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX SCOPE ROOM 250B-OR-RDS-16B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1,000

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000-40,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (psi) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (psi) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patient

Fire risk low : medium : HIGH

Other risks NA

563
6000

DT CH

9 11 3 6
4 5 12

10 13

4500
SD 1 14
7

2
15 8

KEY SCALE 1:100 M

1 Stretcher 9 Desk
2 Endoscope viewing monitor 10 Side table, with computer and
3 Light source and processor printer
4 Diathermy / recorder and printer 11 Chair, upright
5 Trolley/cart 12 Counter, 900mm high; with
6 Monitoring equipment cabinets above and below
7 Endoscope washer 13 Sink, stainless steel with
8 Endoscope/scope storage gooseneck faucet
cabinet 14 Concealed floor drain
15 Door with vision panel

564
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX DIRTY/TRAUMA ROOM 250B-OR-RDS-17A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient is assessed to be brought to Trauma Room Double X-ray film illuminator 1
b. Patient arrives on a stretcher trolley Anesthesia unit 1 w/ scavenging sys.
c. Patient is transferred from stretcher trolley to Clock 1
operating table Operating lamp 1
d. Anesthesia is administered UV light 1
e. Clinical handwashing Oxygen unit 1 w/ tank holder
f. Use of diagnostic equipment, if necessary Nitrogen 1
g. Patient is surgically operated O2 tank holder 1
h. Pre-operative care Footstool 1
Glass/white board 1
Suction apparatus 1
Tracheostomy set 1
Laryngoscope 1
E-cart 1
Orthopedic instrument set 1
Cardiac monitor w/ pulse oximeter 1
Sphygmomanometer, non-merc. 1
Defibrillator 1
People Involved: FURNITURE AND QUANTITY REMARKS
2 x Surgeons FIXTURE CHECKLIST
1 x Circulation Nurse Operating table 1
1 x Scrub Nurse Mayo table 1
1 x Patient Instrument table 1
1 x Anesthesiologist Double basin stand 1
Single basin stand 1
Adjustable stool 1
Anesthesist's stool 1
Anesthesist's table 1
Kick bucket 1
Irrigator stand 1
Sponge rack 1
Shelving; adjustable, 500mm deep 1
Pack table 1
Floor clean-out 1
ADDITIONAL EQUIPMENT & QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Nurse Station Shades, light-proof 1 light-proof for
b. Accessible from sub-sterile corridor special dark rm
c. Outside OR Complex sterile area Outlet, 10A,2P,240V, duplex 8 grounding type,
universal slots
Outlet, 10A,2P,240V, single 2 for emergency light
Isolation Monitor 1 1.6m above floor
Grounding terminal 4 duplex
Outlet, Telephone 1
Outlet, Data 1 wall-mounted
Door with vision panel 1

565
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 OPERATING ROOM COMPLEX DIRTY/TRAUMA ROOM 250B-OR-RDS-17B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1,000

Room temperature 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000 - 40,000

Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (psi) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (psi) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patient

Fire risk low: medium : HIGH

Other risks NA

566
6000

DT
14
12 5

20 10
4 3
6

4500
8
18 SD 2 1
11 4
7
13 5

17 9 9 16 15 19

KEY SCALE 1:100 M

1 Operating table 12 Kick bucket


2 Operating lamp 13 Irrigator stand
3 Mayo table 14 Sponge rack
4 Footstool 15 Clock
5 Instrument table 16 Double-film negatoscope
6 Double basin stand 17 Floor clean-out
7 Single basin stand 18 Shelving; adjustable, 500mm
8 Anesthetist's stool deep
9 Adjustable stool 19 Pack table
10 Anesthetist's table 20 Door with vision panel
11 Anesthesia unit

567
568
Hospital: Department of Health

ROOM DATA SHEET


(250-Bed, Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT NURSE STATION 250B-ICU-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Emergency light 1
b. Patient is transferred from a stretcher trolley to bed Central monitor/ Cardiac 1
and vice versa Laryngoscope w/ blades 1
c. Nurses and nursing attendants monitor vital signs of of assorted sizes
patient at regular intervals E-cart 4
d. Use of monitoring and diagnostic equipment EENT diagnostic set 1
e. High level nursing and medical dependence Mirror Set 2
Computer, w/ monitor and printer 1
Clock 1
Rack, chart 1
Hamper, medical 2
Waste bin w/ yellow lining 2 infectious
Waste bin w/ black lining 2
Sharps container 1

FURNITURE AND QUANTITY REMARKS


FIXTURE CHECKLIST
Counter, nurse station 1
People Involved: Counter, work; with cabinets 2
Patients above and below
1 x Resident Physician/ Medical Specialist Shelf, open 1
1 x Nurse Sink, stainless steel 1
1 x Nursing Attendant Sink, utility 1
Slop sink 1
Stool, adjustable height 2
Concealed floor drain 2
Lavatory 1
Water Closet 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Medical/Surgical Services Outlet, 10A,2P,240V, duplex 8 grounding type,
universal
Outlet, 10A, 2P, 240V, single 2 for emergency light
Outlet, DATA 1
Outlet, telephone 1
Paging System 1
Nurse Call Console 1
Split type, ACU 3-ton 1
Smoke detector 2

569
Hospital: Department of Health
ROOM DATA SHEET
(250-Bed, Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT NURSE STATION 250B-ICU-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 12.75 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 900 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY

Cooling load (TR) 6

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit patient and medical staff

Fire risk LOW: medium: high


infection from transmissible
Other risks
diseases

570
571
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT PATIENT BAY 250B-ICU-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Volume respirator 1
b. Patient is transferred from a stretcher trolley to bed Sphygmomanometer, wall-mtd 5
and vice versa Cuffs, pediatric 1
c. Nurses and nursing attendants monitor vital signs of Ambu bag, pediatric 1
patient at regular intervals Ambu bag, adult/pediatric 1
d. Use of monitoring and diagnostic equipment Suction apparatus 5
e. High level nursing and medical dependence Oxygen gauge 5
O2 set 5
O2 tank holder 5
Tracheostomy set 1
Infusion pump 1
Respirator/defribrillator 1
Emergency light 5
Patient Monitor 5

People Involved:
5 x Patients
1 x Resident Physician/ Medical Specialist FURNITURE AND
QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
1 x Nursing Attendant Hospital bed, adjustable 5
Bedhead console, with medical 5
gas outlets, power outlets, and
bedhead light
Table, overbed 5
Footstool 5

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Window curtain rail 4
Planning Relationships: Cubicle curtain and rod 5
a. Close to Medical/Surgical Services Outlet, 10A,2P,240V, duplex 21 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 5

572
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT PATIENT BAY 250B-ICU-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 12.75 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 900 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 5000% Black out essential:desirable:UNNECESSARY

Cooling load (TR) 6

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) 70

Access limit patien and medical staff

Fire risk LOW: medium: high


infection from transmissible
Other risks
diseases

573
574
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT ISOLATION ROOM 250B-ICU-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Emergency light 1
b. Patient is assessed by physician and nurse to determine Volume respirator 1
isolation requirements Sphygmomanometer, wall-mtd 1
c. Patient is transferred from a stretcher trolley to bed Cuffs, pediatric 1
and vice versa Ambu bag, pediatric 1
d. Nurses and nursing attendants monitor vital signs of Ambu bag, adult/pediatric 1
patient at regular intervals Suction apparatus 1
e. Use of monitoring and diagnostic equipment Oxygen gauges 1
f. High level nursing and medical dependence O2 set 1
g. Nurses and nursing attendants screen potentially infectious O2 tank holder 1
visitors Tracheostomy set 1
Infusion pump 1
Respirator/defribrillator 1
ICU patient headwall 1
ICU IV track 1
Bedhead light/lamp 1
Patient Monitor 1
People Involved:
1 x Patient FURNITURE AND
QUANTITY REMARKS
1 x Resident Physician FIXTURE CHECKLIST
1 x Nurse Hospital bed, adjustable 1
1 x Nursing Attendant Bedhead console, with medical 1
gas outlets, power outlets, and
bedhead light
Table, overbed 1
Footstool 1
Planning Relationships Door, glass; with full windows 1
a. Close to Operating Room Complex ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
b. Visible from ICU Nurse Station ENGINEERING TERMINALS
c. At the end of ICU patient bays Window curtain rail 1
Outlet, DATA 1
Outlet, Telephone 1
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
ACU, split-type; 1-ton 1
Fire alarm 1
Smoke detector 1

575
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT ISOLATION ROOM 250B-ICU-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) 10 Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit patient and medical staff

Fire risk LOW: medium: high

Other risks infection from transmissible diseases

576
577
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT OFFICE 250B-ICU-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Resident Physician reads and writes in his work station Computer 1 w/ printer & scanner
b. Resident Physician records, stores and retrieves data Airconditioning unit 1
from data file Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician FIXTURE CHECKLIST
Desk, 600 X 1200mm 1
Desk, extension, 400 x 1200mm 1
Cabinet, steel; filing 2
Shelf, open 1
Chair, junior executive 1
Chair, upright, stacking 2

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the ICU unit ENGINEERING TERMINALS
b. Adjacent to Operating Room Outlet, 10A,2P,240V, duplex 3 grounding type,
universal
Outlet, 15A,2P,240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Outlet, Aircon 1
Smoke detector 1

578
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT OFFICE 250B-ICU-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) NA

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.32

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Resident Physician

Fire risk LOW: medium: high

Other risks NA

579
580
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT FAMILY COUNSELING ROOM 250B-ICU-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Resident Physician explains to patient's relatives complex Airconditioning Unit 1
medical terminologies and technologies Waste bin w/ black lining 1
b. Resident Physician updates and advises patient's relatives
on his/her isolation status/prognosis and care preferences
while acknowledging uncertainty
c. Clinician listens with patience and sensitivity to relatives'
emotions, including anger, grief and guilt
d. Ciinician prepares families for a patient's death

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Resident Physician/ Clinician FIXTURE CHECKLIST
Patient's Relatives Desk, 600 x 1200mm 1
Desk, extension; 400 x 1200mm 1
Cabinet, steel; filing 2
Chair, swivel 1
Chair, visitor 2
Sofa, 2-seater 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Nurse Station ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 2 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1

581
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ICU-RDS-05B
FAMILY COUNSELING
April 2016 INTENSIVE CARE UNIT ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA


Resident Physician, Patient's
Access limit
Relatives
Fire risk LOW: medium: high

Other risks NA

582
583
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT VISITOR'S DRESSING ROOM 250B-ICU-RDS-06A
CTIONAL DESIGN REQUIREMENTS:
activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Visitors/Patient's Family and relatives wear a gown Gown
and mask Gloves
b. Visitors/Patient's Family and relatives use alcohol N-95 mask
hand sanitizer
c. Storing of clothings and personal effects

People Involved: FURNITURE AND


QUANTITY REMARKS
Visitors FIXTURE CHECKLIST
Patient's family/relatives Closet, 600mm deep 1 with clothes rod
and hooks
Hamper, medical 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Should have direct access from the corridor ENGINEERING TERMINALS
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1

584
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT VISITOR'S DRESSING ROOM 250B-ICU-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit ICU staff, patient's visitors/relatives

Fire risk LOW: medium: high

Other risks NA

585
586
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT STAFF LOCKERS & TOILET 250B-ICU-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Resident Physician and nurses change clothes in staff Waste Bin w/ black lining 1
lockers room Hamper 1
b. Storing of clothings and personal effects Water Heater 1
c. Wearing of gowns, masks and gloves
d. Resident Physician and nurses wash hands
or use alcohol hand santizer
e. Resident Physician and nurses use toilet and bath

People Involved: FURNITURE AND


QUANTITY REMARKS
Resident Physicians FIXTURE CHECKLIST
Nurses Locker; steel 4
Nursing Attendants Shower set 1
Lavatory 1
Water Closet 1
Urinal 1
Concealed Floor Drain 1

Planning Relationships ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Should have direct access from the corridor ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal slots
Outlet, 15A,2P,240V, single 1 for emergency light
Smoke detector 1

587
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 INTENSIVE CARE UNIT STAFF LOCKERS & TOILET 250B-ICU-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

588
589
590
Hospital: Department of Health

ROOM DATA SHEET


(250-Bed, Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-01A
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM RECEIVING ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Receiving of instruments for washing and sterilizing
from the different departments of the hospital

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Central Supply Service Worker FIXTURE CHECKLIST
Counter, work; with cabinets 2
above and below
Sink, 350-400mm deep; with 1
drainboard
Stool, adjustable height 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Operating Room Complex ENGINEERING TERMINALS
b. Adjacent to Delivery Room Suite Outlet, 10A, 2P, 240V, duplex 3 grounding type,
c. Accessible from the different departments of universal
the hospital Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke Detector 1

591
Hospital: Department of Health
ROOM DATA SHEET
(250-Bed, Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-01B
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM RECEIVING ROOM

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-1000

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit CSSR staff

Fire risk low: medium:HIGH

Other risks exposure to hazardous chemicals

592
NA

593
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-02A
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM WORK AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Disassembling and arranging of instruments Multi rubber tube washer
b. Washing of instruments in a washer - sterilizer Dressing Sterilizer
c. Sterilizing of instruments Instrument Sterilizer
d. Preparation of instruments for future use Supply cart
Step lader
Heavy duty autoclave
Sterilizer, hot air 1
Water still 1
Rack, gloves drying 1
Whiteboard 1
Waste bin w/ black lining 2
Waste bin w/ yellow lining 1 chemical
Sharps container 1

People Involved: FURNITURE AND QUANTITY REMARKS


4 x Central Supply Service Workers FIXTURE CHECKLIST
Counter, work; with cabinets below 1
Counter, work; with cabinets 3
above and below
Sink, double compartment; 2
with drainboard
Table, work; with overhead shelf 1
Desk, 600 x 1200mm 1
Chair, upright; stacking 6
Concealed floor drain 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Operating Room Complex ENGINEERING TERMINALS
b. Adjacent to Delivery Room Suite Outlet, 10A,2P,240V, duplex 9 grounding type,
c. Accessible from the different departments of universal
the hospital Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 3

594
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-02B
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM WORK AREA

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-1000

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit CSSR staff

Fire risk low: medium:HIGH

Other risks exposure to hazardous chemicals

595
NA

596
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-03A
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM AUTOCLAVE ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Sterilization of instruments/ glasswares Sterilizer, instrument 1
Autoclave, heavy-duty 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Central Supply Service Worker FIXTURE CHECKLIST
Floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to CSSR ENGINEERING TERMINALS
b. Adjacent to the work area of the CSSR Outlet, 10A, 2P, 240V, duplex 4 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke Detector 1
Overhead room exhaust 1
Automatic Sprinkler System

597
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-03B
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM AUTOCLAVE ROOM

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight ESSENTIAL:desirable:unnecessary

Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary

% Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: Sterilizer

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit CSSR staff

Fire risk low: MEDIUM: high

Other risks NA

598
NA

599
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-04A
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM STORAGE ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of sterilized/ washed instruments Ladder 1
b. Issuance of instruments as requested by other
hospital services
c. Dispensing of supplies in clinical areas
d. Inventory of instruments and supplies

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Central Supply Service Worker FIXTURE CHECKLIST
Counter, with transaction window 1
Table, work 1
Cabinet, sterile supply 12

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Operating Room Complex ENGINEERING TERMINALS
b. Adjacent to Delivery Room Complex Outlet, 10A,2P,240V, duplex 4 grounding type,
c. Accessible from the different departments of universal
the hospital Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke Detector 2

600
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CSSR-RDS-04B
CENTRAL STERILIZING &
April 2016 SUPPLY ROOM STORAGE ROOM

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit CSSR staff

Fire risk low: medium: HIGH

Other risks NA

601
NA

602
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.8 DELIVERY ROOM & NICU SERVICE FACILITIES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

603
Hospital: Department of Health

SERVICE FACILITY SHEET INDEX HEALTH FACILITY


250-Bed (Level 3)
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 DELIVERY ROOM AND NICU 250B-DR-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
DELIVERY ROOM COMPLEX 350.00 250B-DR-DDS-01 606
Nurse Station 27.00 250B-DR-RDS-01 607
Labor Room 46.00 250B-DR-RDS-02 610
Delivery Room 36.00 250B-DR-RDS-03 613
Caesarian Delivery Room 36.00 250B-DR-RDS-04 616
Recovery Room 59.00 250B-DR-RDS-05 619
High-Risk Pregnancy Unit 42.00 250B-DR-RDS-06 622
Scrub-Up Area 9.00 250B-DR-RDS-07 625
Sub-Sterilizing Room 9.00 250B-DR-RDS-08 628
Sterile Instrument and Supply Storage 12.00 250B-DR-RDS-09 631
Dressing, Lockers, and T&B 36.00 250B-DR-RDS-10 634
Lounge 18.00 250B-DR-RDS-11 637
Clean-Up Room 9.00 250B-DR-RDS-12 640
Janitor's Closet 2.00 250B-DR-RDS-13 643
Wheeled Stretcher's Area 9.00 250B-DR-RDS-14 646

NEONATAL INTENSIVE CARE UNIT (NICU) 201.00 250B-NICU-DDS-01 649


Nurse Station 19.00 250B-NICU-RDS-01 650
Level III Sick Room 44.00 250B-NICU-RDS-02 653
Breastfeeding Room 14.00 250B-NICU-RDS-03 656
Lounge 14.00 250B-NICU-RDS-04 659
Dressing, Lockers, and T&B 28.00 250B-NICU-RDS-05 662
Isolation Room 20.00 250B-NICU-RDS-06 665
Level II Step-Down 31.00 250B-NICU-RDS-07 668
Level I Growers 31.00 250B-NICU-RDS-08 671

605
15000 SCALE 1:300 M
6000 3000 6000

DN
6000

6000
CS CS
DELIVERY DELIVERY
ROOM ROOM

SUB-
2000 3000

3000
TO NICU STERILIZATION
SCRUB ROOM
UP
NICU DR
RECEIVING RELEASING
AREA AREA

6000
DELIVERY
ROOM
9700

RECOVERY
ROOM 6000
DELIVERY
ROOM
3300

STERILE JANITOR'S
3000

CLEAN INSTRUMENTS/ CLOSET

UP STERILE SUPPLY
ISOLATION
ROOM
ROOM
51000

51000
2600

ESSENTIAL
INTRA-PARTUM
7300

NEWBORN
3500

NURSE
CARE
SUPPLY STATION
1700
2100

LABOR
ROOM
4000

HIGH RISK
6100

PREGNANCY
UNIT
3000

NURSES'
LOUNGE
2800

AFFILIATES' SEPTIC
ROOM DELIVERY
3000

DOCTORS'
9800

LOUNGE

SEPTIC
3000

F DR LABOR
DRESS
3000

M DR
2100

WHEELED
DRESS STRETCHER
AREA

606
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX NURSE STATION 250B-DR-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse administers nursing care clinical procedures to Hot plate, single element 1
baby Instrument sterilizer 1
b. Nurse examines baby and records data gathered Refrigerator, 10 cu. ft. 1
c. Nurse performs necessary monitoring activities to babies Glass board / white board 1
d. Nurse takes inventories of nursery supplies Clock 1
Waste bin w/ black lining 2 general waste
Waste bin w/ yellow lining 1 pharmaceutical
Sharps container 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
2 x Nursing Attendants Counter, nurse 1
Counter, work; with cabinets 2
above and below
Table, computer 1
Sink, stainless steel 1
Chair; upright, stacking 1
Stool, adjustable 1
Concealed floor drain 2
Shelf, 450mm deep 1
Lavatory 1
Water Closet 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Breastfeeding Room ENGINEERING TERMINALS
b. Adjacent to Sub-Sterilizing Room Outlet, 10A,2P,240V, duplex 6 grounding type,
c. Close to NICU universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 2

607
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX NURSE STATION 250B-DR-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.35

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory and sink

tolerated Maximum temperature (°C) 70

Access limit nursing staff

Fire risk LOW: medium: high

Other risks NA

608
NA

609
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX LABOR ROOM 250B-DR-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on foot Clock 1
b. Patient may arrive in a wheelchair or on a stretcher trolley Waste bin w/ yellow lining 1 infectious
c. Transfer patient from wheelchair or stretcher trolley 1 chemical
to obstetrical bed 1 pharmaceutical
d. Clinical handwashing Waste bin w/ black lining 1
e. Patient undergoes labor prior to delivery Sharps container 1
f. Use of toilet facilities

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Resident Physicians FIXTURE CHECKLIST
1 x Nurse Hospital bed, adjustable 6
1 x Nursing Attendant Footstool 6
6 x Maternity Patients Chair, upright, stacking 7
Side cabinet 6
Desk, 600 x 1000mm 1
Counter, with cabinets above 1
and below
Water closet 1
Lavatory 1
Floor Drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Delivery Room ENGINEERING TERMINALS
b. Close to Caesarian Delivery Room Outlet, 10A,2P,240V, duplex 9 grounding type,
c. Close to Scrub-up and Sub-Sterilizing Room universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1
Cubicle Curtain and Rod 6
Calling Station 6

610
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX LABOR ROOM 250B-DR-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.7

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patient

Fire risk LOW: medium: high

Other risks NA

611
NA

612
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX DELIVERY ROOM 250B-DR-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Anesthesia machine 1
b. Patient is transferred from stretcher trolley to Bag valve mask unit 1
delivery table Clinical infant weighing scale 1
c. Anesthesia is administered Thermometer, non-mercurial 1
d. Clinical handwashing D.R. instrument set 1
e. Normal delivery of a child by the patient Laryngoscope 1
O2 unit w/ tank holder 1
Suction apparatus 1
Stretcher 1
Obstetrical lamp 1
Emergency light, portable 1
Heated bassinet/warmer 1
People Involved: Aspirator 1
2 x Resident Physicians Clock 1
1 x Nurse BP apparatus 1
1 x Nursing Attendant Stethoscope 1
1 x Maternity Patient
FURNITURE AND
QUANTITY REMARKS
FIXTURE CHECKLIST
Delivery table 1
Mayo table 1
Instrument table 1
Single basin stand 2
Anesthetist's stool 1
Adjustable stool 1
Anesthetist's table 1
Planning Relationships: Anesthesia unit 1
a. Adjacent to Sub-Sterilizing Room Kick bucket 1
b. Adjacent to Scrub-Up Floor clean-out 1
Shelving; adjustable, 500mm deep 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Window curtain rail 2
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 15A, 2P, 240V, single 1 grounding type, tandem
Isolation Monitor 1 1.6m above floor
Ground terminal 2 duplex
Calling Station 1
Fixed emergency light 2
Heat Detector 1
Door w/ vision panel 1

613
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX DELIVERY ROOM 250B-DR-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000-20,000

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 3

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patient

Fire risk low: medium: HIGH

Other risks NA

614
615
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX CAESARIAN DELIVERY ROOM 250B-DR-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Aspirator 1
b. Patient is transferred from stretcher trolley to UV Light 1
operating table Oxygen Unit 1
c. Anesthesia is administered Sponge rack 1
d. Clinical handwashing Clock 1
e. Use of diagnostic equipment Double-film negatoscope 1
f. Patient is surgically operated

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Resident Physicians FIXTURE CHECKLIST
1 x Nurse Operating table 1
1 x Nursing Attendant Operating lamp 1
1 x Patient Mayo table 1
1 x Utility Worker Footstool 2
Instrument table 2
Double basin stand 1
Single basin stand 1
Anesthetist's stool 1
Adjustable stool 2
Anesthetist's table 1
Anesthesia unit 1
Kick bucket 1
Irrigator stand 1
Floor clean-out 1
Shelving; adjustable, 500mm deep 1
Pack table 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS
b. Adjacent to Scrub-Up Outlet, 10A,2P,240V, duplex 9 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, telephone 1
Outlet, DATA 1
Heat Detector 1

616
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX
CAESARIAN
DELIVERY ROOM 250B-DR-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1000

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 20,000-40,000

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patient

Fire risk low: medium: HIGH

Other risks NA

617
NA

618
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX RECOVERY ROOM 250B-DR-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient arrives on a stretcher trolley Oxygen outlet, mounted 1600mm 8
b. Patient is transferred from stretcher trolley to bed Suction outlet, mounted 1600mm 8
and vice versa Suction apparatus 8
c. Nurses monitor vital signs of patient at regular Standby BP apparatus 1
intervals Wall Clock 1
d. Use of monitoring and diagnostic equipment Emergency light 1
Oxygen unit 1
Waste bin w/ yellow lining 1 infectious
1 chemical
1 pharmaceutical
Sharps container 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Physcian FIXTURE CHECKLIST
Nurses Stretcher bed, adjustable 8
8 x Patients Cabinet, bedside 8
Chair, upright, stacking 8
Footstool 8
Work counter, 900mm high, 1
with cabinets below
Sink, with gooseneck spout 1
and knee control

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Delivery Room ENGINEERING TERMINALS
b. Adjacent to Sub-Sterilizing room Window curtain rail 1
c. Close to Caesarian Delivery room Cubicle curtain and rod 7
Outlet, 10A,2P,240V, duplex 20 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, telephone 1
Outlet, DATA 1
Split type, ACU, 3 ton 1 preferably ceiling
mounted FCU
Smoke Detector 2
Bedlight 8
Nurse Call System 8

619
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX RECOVERY ROOM 250B-DR-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) 100

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:DESIRABLE:unnecessary

Cooling load (TR) 2

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit medical staff and patient

Fire risk LOW: medium: high

Other risks NA

620
NA

621
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX HIGH-RISK PREGNANCY UNIT 250B-DR-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse performs nursing care Cardiac monitor w/pulse oxymeter 5
b. Monitoring of vital signs Cardiotomography machine 5
c. Use of monitoring and daignostic equipment O2 unit w/ gauge & humidifier 5
O2 tank holder 5
Suction apparatus 5
Waste bin w/ yellow lining 1 infectious
1 chemical
1 pharmaceutical
Sharps container

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Physician FIXTURE CHECKLIST
Nurses Hospital bed, adjustable 5
Midwives Cabinet, bedside 5
5 x Patients Chair, upright, stacking 6
Footstool 5
Desk 1
Counter, with cabinets above 1
and below
Water closet w/ spray hose 1
Lavatory 1
Floor Drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Delivery Room Window curtain rail 2
b. Adjacent to Sub-Sterilizing Room Cubicle curtain rail and rod 4
c. Close to Caesarian Delivery Room Outlet, 10A,2P,240V, duplex 14 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Nurse Call System 1
Smoke detector 1
Outlet, DATA 1
Outlet, Telephone 1

622
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DR-RDS-06B
HIGH-RISK
April 2016 DELIVERY ROOM COMPLEX
PREGNANCY UNIT
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 35 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.5

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: at scrub sink

tolerated Maximum temperature (°C) 70

Access limit patient and medical staff

Fire risk low: MEDIUM: high

Other risks NA

623
NA

624
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX SCRUB-UP AREA 250B-DR-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Physician and nurse rinse arms and hands with water Soap dispenser 3
and soap prior to and after surgical operation Hand dryer 1
Waste bin w/ yellow lining 1 infectious
Clock 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Physician FIXTURE CHECKLIST
1 x Nurse or Nursing Attendant 3-Station Scrub sink, w/ gooseneck 1
spout & foot control, sensor type
Shelves, overhead 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Caesarian Delivery Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
1 for hand dryer
Smoke detector 1

625
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX SCRUB-UP AREA 250B-DR-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.35

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at scrub sink

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

626
NA

627
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX SUB-STERILIZING ROOM 250B-DR-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Preparation of packed surgical instruments Sterilizer, instrument 1
b. Storing and retrieving of instruments from cabinets
c. Minor sterilizing works
d. Handwashing and other clean-up activities

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Physician FIXTURE CHECKLIST
1 x Nurse or Nursing Attendant Counter, work 1
Sink, with drainboard 1
Counter, 900mm high, open below 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Operating Room Window curtain rail 1
b. Adjacent to Scrub-up Area Outlet, 10A,2P,240V, duplex 3 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1

628
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX SUB-STERILIZING ROOM 250B-DR-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.35

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk low: MEDIUM: high

Other risks NA

629
NA

630
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DR-RDS-09A
STERILE INSTRUMENT & SUPPLY
April 2016 DELIVERY ROOM COMPLEX
STORAGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse checks the availability of supplies for issuance Waste bin w/ black or colorless 1
b. Nursing Attendants prepare needed supplies and articles lining
listed in requisition form
c. Nursing Attendants pack items individually, in bulk or
wrap w/ clean paper before issuance
d. Nurse performs physical inventory and update stock cards
e. Nurse receives sterile supplies and instruments, puts
entry into stock cards and stores supplies into shelves

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
1 x Nursing Attendant Counter, with 450mm deep shelving 1
above
Sink with drainboard 1
Cabinet, instrument 2
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Located at the Delivery Area ENGINEERING TERMINALS
b. Adjacent to Nurse Supervisor's Area
Outlet, 10A,2P,240V, duplex 4 grounding type,
parallel slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1

631
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
STERILE INSTRUMENT &
April 2016 DELIVERY ROOM COMPLEX
SUPPLY STORAGE 250B-DR-RDS-09B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

632
NA

633
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX DRESS, LOCKERS, T&B 250B-DR-RDS-10A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. DR staff change clothes in toilet and bathroom Waste bin w/ black lining 2
b. DR staff bathe in the bathroom Hamper, linen 2
c. Storing of clothing and personal effects

People Involved: FURNITURE AND


QUANTITY REMARKS
Resident Physicians FIXTURE CHECKLIST
Locker, steel 12
Bench 2
Lavatory 2
Water closet 2
Shower 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Delivery Room Complex ENGINEERING TERMINALS
b. Close to access door of Delivery Room Complex Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 2

634
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX DRESS, LOCKERS, T&B 250B-DR-RDS-10B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at toilet and bath

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

635
NA

636
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX LOUNGE 250B-DR-RDS-11A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Resident Physician to take rest in between surgeries Airconditioning unit 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
Resident Physicians and Delivery Room Staff FIXTURE CHECKLIST
Sofa, 1-seater with arms 1
Sofa, 2-seater with arms 1
Table, low corner 1
Table, 6-seater dining 1
Chair, dining 6
Counter, with cabinets below 1
Sink, kitchen 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room Suite ENGINEERING TERMINALS
b. Close to access door of Operating Room Suite
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1

637
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX LOUNGE 250B-DR-RDS-11B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

638
NA

639
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX CLEAN-UP ROOM 250B-DR-RDS-12A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse and Nursing Attendant perform post-delivery/ Hamper, linen 1
operation clean-up activities Waste bin, general 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
1 x Nursing Attendant Counter, work; w/ cabinets above 1
and below
Sink, double compartment; laundry; 1
350-400mm deep
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Delivery Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1

640
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX CLEAN-UP ROOM 250B-DR-RDS-12B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

641
NA

642
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX JANITOR'S CLOSET 250B-DR-RDS-13A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of janitor's cleaning tools

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Janitor FIXTURE CHECKLIST
Slop sink w/ faucet 1
Shelf 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal slots

643
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX JANITOR'S CLOSET 250B-DR-RDS-13B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff and patient

Fire risk LOW: medium: high

Other risks NA

644
NA

645
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 DELIVERY ROOM COMPLEX WHEELED STRETCHER'S AREA 250B-DR-RDS-14A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Patient scheduled for delivery is transferred from Delivery Room Complex stretcher 1 delivery suite use
ward stretcher to delivery suite stretcher Ward stretcher 1 ward use

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Nursing Attendants FIXTURE CHECKLIST
1 x Patient

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Located at the entrance of Delivery Room Suite ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1

646
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DR-RDS-14B
WHEELED STRETCHER'S
April 2016 DELIVERY ROOM COMPLEX AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal Impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit patient and medical staff

Fire risk LOW: medium: high

Other risks NA

647
NA

648
SCALE 1:300 M

25200
2300 2300 7300 3100 5100 5100
DN

SUPPLY

6000
LEVEL II
LEVEL III LEVEL 1
INTERMEDIATE/
SICK GROWERS
5700

ON- STEP-DOWN
STAFF NURSE
CALL
LOUNGE STATION

12000
ROOM

3000
13200

1500

SCRUB NICU

3000
F DRESS RECEIVING
DRESS/ AREA
6000

M
T&B ISOLATION
DRESS/ BREAST
T&B ROOM
FEEDING
ROOM

649
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-NICU-RDS-01A
NEONATAL INTENSIVE CARE
April 2016 UNIT NURSE STATION
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse administers nursing care clinical procedures to Hot plate, single element 1
baby Instrument sterilizer 1
b. Nurse examines baby and records data gathered Glass board / white board 1
c. Nurse performs necessary monitoring activities to babies Clock 1
d. Nurse takes inventories of nursery supplies Waste bin w/ yellow lining 1 infectious
1 pharmaceutical
Waste bin w/ black lining 1 general waste
Sharps container 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
2 x Nursing Attendants Counter 1
Chair; upright, stacking 1
Counter, with cabinets 1
above and below
Sink 1
Concealed floor drain 1
Shelf 1
Lavatory 1
Water Closet 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Breastfeeding Room ENGINEERING TERMINALS
b. Adjacent to Sub-Sterilizing Room Outlet, 10A,2P,240V, duplex 4 grounding type,
c. Close to NICU universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 2

650
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
NEONATAL INTENSIVE
CARE UNIT
NURSE STATION 250B-NICU-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.35

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at lavatory and sink

tolerated Maximum temperature (°C) 70

Access limit nursing staff

Fire risk LOW: medium: high

Other risks NA

651
NA

652
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-NICU-RDS-02A
NEONATAL INTENSIVE CARE
April 2016 UNIT LEVEL III SICK ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. A newborn premature baby is brought in from the Hot plate, single element 1
Delivery Room Instrument sterilizer 1
b. Nurse administers nursing care and clinical procedures Incubator 5
to baby Linen hamper 1
c. Nurse measures baby's height and head circumference Waste bin w/ yellow lining 1 infectious
d. Nurse weighs baby Sharps container 1
e. Nurse records data gathered
f. Nurse prepares baby, i.e. cleans and dresses baby
g. Nurse places baby in the bassinet

People Involved: FURNITURE AND


QUANTITY REMARKS
5 x Newborn infants FIXTURE CHECKLIST
1 x Nurse Counter, 900mm high with 1
1 x Nursing Attendant cabinets above and below
Desk, 600 x 1000mm 1
Chair, stacking, upright 1
Stool, adjustable 1
Sink, with gooseneck spout and 1
foot or elbow control
Cabinet, bedside 5
Partition, 1700mm high, clear 4
glass upper panel

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Nurse Station and Work Room ENGINEERING TERMINALS
b. Close to Delivery Room and Caesarian Delivery Room Outlet, 10A,2P,240V, duplex 9 grounding type,
c. Close to Labor Room universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1

653
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
NEONATAL INTENSIVE
CARE UNIT LEVEL III SICK ROOM 250B-NICU-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.5

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: instrument sterilizer

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: at sink and lavatory

tolerated Maximum temperature (°C) 70

Access limit newborn baby & nursing staff

Fire risk LOW: medium: high

Other risks NA

654
NA

655
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-NICU-RDS-03A
NEONATAL INTENSIVE CARE
April 2016 UNIT BREASTFEEDING ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Nurse brings in newborn infant to the waiting mother for Hand dryer 1
breastfeeding Waste bin w/ black lining 1
b. Nurse assists mothers in breastfeeding their babies

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nurse FIXTURE CHECKLIST
Newborn Infant Sofa, 2-seater with arms 2
Mother Table, low corner 2
Counter, with cabinets below 1
Sink, kitchen 1
Lavatory with gooseneck spout 1
and knee control
Floor drain, concealed 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Nurse Station and NICU ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Smoke detector 1

656
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
NEONATAL INTENSIVE
CARE UNIT
BREASTFEEDING ROOM 250B-NICU-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.5

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit mother, newborn infant & nurse

Fire risk low:MEDIUM: high

Other risks NA

657
NA

658
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-NICU-RDS-04A
NEONATAL INTENSIVE CARE
April 2016 UNIT LOUNGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Resident Physician to take rest in between surgeries Airconditioning unit 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
Resident Physicians and Delivery Room Staff FIXTURE CHECKLIST
Sofa, 1-seater with arms 1
Table, low corner 1
Table, 4-seater dining 1
Chair, dining 4
Counter, with cabinets above 1
and below
Sink, kitchen 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Operating Room Suite ENGINEERING TERMINALS
b. Close to access door of Operating Room Suite Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A, 2P, 240V, single 1 for emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke detector 1

659
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
NEONATAL INTENSIVE
CARE UNIT
LOUNGE 250B-NICU-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

660
2300

6 5 CH
8
7

4 4
3

5700
4 SD 4

D T2

KEY SCALE 1:100 M

1 Sofa, 2-seater with arms


2 Table, low corner
3 Table, 4-seater dining
4 Chair, dining
5 Counter, with cabinets above
and below
6 Sink, kitchen
7 Waste bin
8 Floor drain, concealed

661
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-NICU-RDS-05A
NEONATAL INTENSIVE CARE
April 2016 UNIT DRESS, LOCKERS, T&B
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. NICU staff change clothes in toilet and bathroom Waste bin w/ black lining 2
b. NICU staff bathe in the bathroom Hamper, linen 2
c. Storing of clothing and personal effects

People Involved: FURNITURE AND


QUANTITY REMARKS
Resident Physicians FIXTURE CHECKLIST
Locker, steel 18
Shelf 1
Lavatory 2
Water closet 2
Shower 2
Slop sink, w/ faucet 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to NICU ENGINEERING TERMINALS
b. Close to access door of NICU Outlet, 10A,2P,240V, duplex 2 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 2

662
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016
NEONATAL INTENSIVE
CARE UNIT
DRESS, LOCKERS, T&B 250B-NICU-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at toilet and bath

tolerated Maximum temperature (°C) 70

Access limit medical staff

Fire risk LOW: medium: high

Other risks NA

663
NA

664
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NEONATAL INTENSIVE CARE UNIT ISOLATION ROOM 250B-NICU-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. An infant is brought to Isolation Room to separate Hot plate, single element 1
him/her from other infants (suspected and Instrument sterilizer 1
confirmed infectious diseases) Incubator 1
b. Doctor/Nurse observes proper isolation Patient monitor 1
precautions and protocols: hand washing, gowning, Linen hamper 1
PPE, storage of clean supplies, among others Waste bin 1 w/ yellow lining
c. Nurse administers nursing care and clinical Sharps container 1
procedures to infant
c. Nurse administers nursing care and clinical
procedures to infant FURNITURE AND
QUANTITY REMARKS
d. Nurse measures infant's height and head FIXTURE CHECKLIST
circumference Cabinet, for storage of gowns, 1
e. Nurse weighs infant PPEs, clean supplies, etc.
f. Nurse records data gathered Counter, 900mm high with 1
g. Nurse prepared baby, i.e. cleans and dresses cabinets above and below
baby, feeds baby, etc. Lavatory 1
h. Nurse places baby in incubator Sink, with gooseneck faucet 1
i. Nurse monitors infant's vital signs Cabinet, bedside 1

People Involved:
1 x Infant ADDITIONAL EQUIPMENT &
QUANTITY REMARKS
1 x Nurse ENGINEERING TERMINALS
1 x Nursing Attendant Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, data 1
Planning Relationships: Outlet, telephone 1
a. Near Nurse Station Smoke detector 1

665
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NEONATAL INTENSIVE CARE UNIT ISOLATION ROOM 250B-NICU-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-700

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (psi) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (psi) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.5

SOUND SAFETY

Acceptable sound level (db) 30 Accessible hot surface: instrument sterilizer

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit infant and nursing staff

Fire risk LOW: medium : high

Other risks NA

666
3200

7
4 1

1300
SD
3 2 5
6
12 7
9
11
10 8
16

4700
17 SD

T
D

13
15 14

KEY SCALE 1:100 M

1 Ante Room 8 Isolation Room


2 Lavatory, with soap and paper 9 Counter, 900mm high with
towel dispenser cabinets above and below
3 Cabinet, for clean linen/PPE 10 Sink, with gooseneck faucet
4 Hamper, soiled linen 11 Hot plate, single element
5 Waste bin 12 Instrument sterilizer
6 Concealed floor drain 13 Isolette
7 Window, view 14 Cabinet, bedside
15 Monitor, patient
16 Sharps container
17 Waste bin, infectious

667
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
APRIL 2016 NEONATAL INTENSIVE CARE UNIT LEVEL II STEP DOWN 250B-NICU-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. An infant is transferred from Level III Sick to Hot plate, single element 1
Level II Step Down/Intermediate Care upon Instrument sterilizer 1
observance of infant's progress/development Incubator 4
and/or growing stability Radiant warmer 1
b. Nurse administers nursing care and clinical Weighing scale 1
procedures to infant Linen hamper 1
c. Nurse measures infant's height and head Waste bin 2 w/ yellow lining
circumference w/ black lining
d. Nurse weighs infant Sharps container 1
e. Nurse records data gathered
f. Nurse prepared baby, i.e. cleans and dresses FURNITURE AND
QUANTITY REMARKS
baby, feeds baby, etc. FIXTURE CHECKLIST
g. Nurse places baby in incubator Counter, 900mm high with 1
h. Nurse monitors infant's vital signs cabinets above and below
Desk, 600 x 1000mm 1
Chair, stacking, upright 1
People Involved: Stool, adjustable height 1
4 x Infants Sink, with gooseneck faucet 1
1 x Nurse Cabinet, bedside 4
1 x Nursing Attendant Partition, 1700mm high, clear 3
glass upper panel

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Nurse Station Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, data 1
Outlet, telephone 1
Smoke detector 1

668
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
APRIL 2016 NEONATAL INTENSIVE CARE UNIT LEVEL II STEP DOWN 250B-NICU-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature(°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (psi) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (psi) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.5

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: instrument sterilizer

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit infant and nursing staff

Fire risk LOW: medium : high

Other risks NA

669
5100

13 T D 2
8 3 8

11
12 12
CH

6000
8 10
SD

11 15
12 14
16
9
5
8
16
11 4 CH
17 17 7

KEY SCALE 1:100 M

1 Counter, 900mm high with 10 Weighing machine


cabinets above and below 11 Cabinet, bedside
2 Desk, 600 x 1000mm 12 Partition, 1700mm high, clear
3 Chair, stacking, upright glass upper panel
4 Stool, adjustable height 13 Hamper, soiled linen
5 Sink, with gooseneck faucet 14 Waste bin, infectious
6 Hot plate, single element 15 Waste bin, general
7 Instrument sterilizer 16 Sharps container
8 Incubator 17 Window, view
9 Radiant warmer

670
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NEONATAL INTENSIVE CARE UNIT LEVEL I GROWERS 250B-NICU-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. An infant is transferred from Level II Step Down/ Hot plate, single element 1
Intermediate Care to Level I Growers upon Instrument sterilizer 1
observance of infant's progress/development Incubator 5
and/or growing stability Linen hamper 1
b. Nurse administers nursing care and clinical Waste bin 2 w/ yellow lining
procedures to infant w/ black lining
c. Nurse measures infant's height and head Sharps container 1
circumference
d. Nurse weighs infant
e. Nurse records data gathered FURNITURE AND
QUANTITY REMARKS
f. Nurse prepared baby, i.e. cleans and dresses FIXTURE CHECKLIST
baby, feeds baby, etc. Counter, 900mm high with 1
g. Nurse places baby in incubator cabinets above and below
h. Nurse monitors infant's vital signs Desk, 600 x 1000mm 1
Chair, stacking, upright 1
Stool, adjustable height 1
People Involved: Sink, with gooseneck faucet 1
5 x Infants Cabinet, bedside 5
1 x Nurse Partition, 1700mm high, clear 4
1 x Nursing Attendant glass upper panel

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Planning Relationships: Outlet, 10A,2P,240V, duplex 7 grounding type,
a. Adjacent to Nurse Station universal slots
Outlet, 10A,2P,240V, single 1 for emergency light
Outlet, data 1
Outlet, telephone 1
Smoke detector 1

671
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NEONATAL INTENSIVE CARE UNIT LEVEL I GROWERS 250B-NICU-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature(°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m.hr.) 25 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (psi) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (psi) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.5

SOUND SAFETY

Acceptable sound level (db) 40 Accessible hot surface: instrument sterilizer

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit infant and nursing staff

Fire risk LOW: medium : high

Other risks NA

672
5100

TD 11
2
8 3 8

9 9
10 10

6000
8 8
SD

9 9
10 10
12
13
14
1 8
5
6 4 9
CH
7 15 15

KEY SCALE 1:100 M

1 Counter, 900mm high with 9 Cabinet, bedside


cabinets above and below 10 Partition, 1700mm high, clear
2 Desk, 600 x 1000mm glass upper panel
3 Chair, stacking, upright 11 Hamper, soiled linen
4 Stool, adjustable height 12 Waste bin, infectious
5 Sink, with gooseneck faucet 13 Waste bin, general
6 Hot plate, single element 14 Sharps container
7 Instrument sterilizer 15 Window, view
8 Incubator

673
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.9 NUTRITION & DIETETICS SERVICE FACILITIES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

675
Hospital: Department of Health
250-Bed (Level 3)
SERVICE FACILITY SHEET INDEX
Hospital HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 NUTRITION AND DIETETICS 250B-DIET-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
NUTRITION AND DIETETICS 609.00 250B-DIET-DDS-01 678
Hospital Staff Dining Room 216.00 250B-DIET-RDS-01 679
Cooking and Baking Area 78.00 250B-DIET-RDS-02 682
Food Preparation Area 37.00 250B-DIET-RDS-03 685
Blenderized and Tube Feeding Area 14.00 250B-DIET-RDS-04 688
Therapeutic Diet Preparation Area 3.00 250B-DIET-RDS-05 691
Serving and Food Assembly Area 20.00 250B-DIET-RDS-06 694
Food Conveyor Parking 22.00 250B-DIET-RDS-07 697
Cold Storage 14.00 250B-DIET-RDS-08 700
Dry Storage 14.00 250B-DIET-RDS-09 703
Storage for Utensils/ Silverware 7.00 250B-DIET-RDS-10 706
Delivery Receiving Area 18.00 250B-DIET-RDS-11 709
Dishwashing and Pots Washing Area 45.00 250B-DIET-RDS-12 712
Waste Holding Area 12.00 250B-DIET-RDS-13 715
Dietitian's Office/ Staff Office 41.00 250B-DIET-RDS-14 718
Nutrition Clinic 14.00 250B-DIET-RDS-15 721
Staff Dining Area 18.00 250B-DIET-RDS-16 724
Staff T&B/ Locker Room 36.00 250B-DIET-RDS-17 727

677
12000 SCALE 1:300 M

HOSPITAL
STAFF
DINING
HALL
18000

FOOD
ASSEMBLY
AREA
9000

RELEASING FOOD OUT


AREA TO WARDS
COOKING
AREA
FOOD CONVEYOR
PARKING
57000

3000

BAKING
AREA NUTRITION
CLINIC
6000

FOOD
PREPARATION STAFF
AREA OFFICE
3000
3000

TUBE
THERAPEUTIC
DIET PREP

FEEDING DIETITIAN'S
ROOM
AREA

OFFICE
3000

2050 3000

COLD
CONFERENCE
STORAGE

TRAYS IN
3000

RECEIVING FROM
DRY AREA
STORAGE WARDS
3000

DELIVERY
RECEIVING
AREA
POTS
WASHING
9900

STORAGE
3000

WASTE
ANTE FOR
HOLDING
ROOM UTENSILS/
AREA
SILVERWARE

DISH
FEMALE STAFF WASHING
3000

T&B/LOCKERS
3000

3000

STAFF
DINING
MALE STAFF
T&B/LOCKERS

678
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HOSPITAL STAFF
April 2016 NUTRITION & DIETETICS DINING ROOM 250B-DIET-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Authorized hospital staff diners take their Counter, food; with tray shelf 1
meals and bain marie
Water station 1
Cash register / POS 1
Waste bin w/ black lining 3

People Involved: FURNITURE AND QUANTITY REMARKS


72 x Hospital Staff/ Personnel per sitting FIXTURE CHECKLIST
Counter, work top; w/ cabinets 1
above and below
Sink, stainless steel 1
Counter; with lavatory 1
Table, dining; 4-seater 12
Table, dining; 6-seater 4
Chair, dining 72
Stool, adjustable height 1
Shelf, stainless steel 1 for dirty dishes
Trays/utensils station 1
Concealed floor drain 1
Lavatory 2
Water closet 2
Urinal 1
Planning Relationships:
a. Close to Serving & Food Assembly Area ADDITIONAL EQUIPMENT & QUANTITY REMARKS
b. Close to Dishwashing Area ENGINEERING TERMINALS
Window curtain rail 10
Outlet, 10A,2P,240V, duplex 9 grounding type,
universal
Split type ACU, 3 ton 2 optional
Outlet, telephone 1 countertop
grounding type,
Outlet, ceiling fan 3 grounding type,
universal
Outlet, 15A, 2P, duplex 1 for food warmer
grounding type
Outlet, 15A, 2P, duplex 1 for countertop
grounding type
Outlet, 15A, 2P, duplex 1 for countertop
grounding type
Outlet, 10A, 240V, single 2 exhaust fan, t&b
1 emergency light
Smoke Detector 6

679
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
HOSPITAL STAFF
April 2016 NUTRITION & DIETETICS
DINING ROOM
250B-DIET-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 4.8

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: Baine Marie (food warmer)

Speech privacy essential: DESIRABLE: unnecessary Maximum temperature (°C) 100

Quality which cannot be NA Domestic hot water: at lavatory

tolerated Maximum temperature (°C) 70

Access limit hospital staff

Fire risk low: MEDIUM: high

Other risks NA

680
NA

681
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS COOKING AND BAKING AREA 250B-DIET-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Cooking and baking of food Hood, exhaust 2
Range, with oven 4
Range, with broiler 8
Kettle, tilting 3
Heavy-duty frying pan 1
Cauldron (Kawa) 1
Griddle pan 1
Rice cooker 1
Pressure cooker 1
Drainage 1
Waste bin w/ black lining 3

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Dietitian FIXTURE CHECKLIST
2 x Cook Counter, 900mm high 1
4 x Food Service Workers Sink, single compartment with 2
drainboard; 350-400mm deep
Sink, double compartment with 1
drainboard; 350-400mm deep 2
Shelves, overhead 3
Drain, trench grating 9
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Staff Dining Room Window curtain rail 4
b. Close to Dietitian's Office Outlet, 10A,2P,240V, duplex 13 grounding type,
universal slots
Outlet, 10A,2P,240V, single 2 exhaust fan
1 emergency light
Smoke Detector 3 ionization type
High Pressure Gas Piping System 1

682
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-02B
COOKING AND
April 2016 NUTRITION & DIETETICS
BAKING AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight ESSENTIAL:desirable:unnecessary

Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: heat-generating appliances

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit dietetics staff

Fire risk low: medium: HIGH

Other risks NA

683
Others NA

684
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS FOOD PREPARATION AREA 250B-DIET-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Food Service Workers prepare food (i.e. wash and peel) Vertical Cutter 1
vegetables, slice and cut meat and fish, segregate food Vegetable slicer 1
b. Food Service Workers set-up and assemble cooked food Mixing bowl 3
c. Dietitian puts tags on prepared trays for pay patients Basket strainer 1
d. Food Service Workers place food trays and containers on Heavy-duty knives 3
food converyors to be taken to the wards Waste bin w/ green lining 1 biodegradable
e. Pre-preparation of food like embutido, relyeno, etc. Waste bin w/ black lining 1 non-biodegradable

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Dietitian FIXTURE CHECKLIST
2 x Cook Counter, work; stainless steel 1
4 x Food Service Workers Sink, single compartment, with 1
drainboard; 350-400mm deep
Sink, double compartment, with 1
drainboard; 350-400mm deep
Counter, food preparation; 1
stainless steel
Counter, tray set-up; stainless steel 1
Shelves, overhead 1
Drain, trench grating; stainless 4
steel

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Adjacent to Staff Dining Window curtain rail 2
b. Close to Dietitian's Office Outlet, 10A,2P,240V, duplex 7 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Outlet, DATA 1 local
Outlet, Telephone 1
Smoke Detector 1 ionization type

685
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS FOOD PREPARATION AREA 250B-DIET-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight ESSENTIAL:desirable:unnecessary

Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: heat-generating appliances

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit dietetics staff

Fire risk low: medium: HIGH

Other risks NA

686
NA

687
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS
BLENDERIZED &
TUBE FEEDING AREA 250B-DIET-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Preparation of food needed for blenderized and tube Food Blender 1
feeding Bottles
b. Preparation of equipment needed for blenderized Measuring cups 1 set
tube feeding Measuring spoons 1 set
Waste bin w/ black lining 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Nutritionist/ Dietitian FIXTURE CHECKLIST
2 x Food Service Workers Counter, work; stainless steel, 1
with cabinets above and
shelves below
Sink, single compartment, with 1
drainboard; 350-400mm deep
Stool, adjustable height 1
Concealed floor drain 1

ADDITIONAL EQUIPMENT & QUANTITY REMARKS


Planning Relationships: ENGINEERING TERMINALS
a. Close to Therapeutic Diet Area Window curtain rail 1
b. Adjacent to Dietitian/ Nutritionist's Office Outlet, 10A,2P,240V, duplex 3 grounding type,
universal
Outlet, 15A, 240V, single 3 countertop
Outlet, 10A,2P,240V, single 1 emergency light
1 exhaust
Smoke Detector 1
ACU, window type 1

688
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-04B
BLENDERIZED & TUBE
April 2016 NUTRITION & DIETETICS FEEDING AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit dietetics staff

Fire risk low: MEDIUM: high

Other risks NA

689
690
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-05A
THERAPEUTIC DIET
April 2016 NUTRITION & DIETETICS PREPARATION AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. The Nutritionist/ Dietitian prepare for the therapeutic Dietetic Scale 1
diet modified from regular diet Knives and chopping board 1 set
b. The Nutritionist/ Dietitian measures and determines the Vegetable peeler 1
portion or size to be given to the patient Measuring cups 1 set
Measuring spoons 1 set
Food trays
Food tags

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nutritionist/ Dietitian FIXTURE CHECKLIST
1 x Food Service Worker Counter, stainless steel, food 1
assembly
Stool, adjustable height 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Blenderized and Tube Feeding Area ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1
Outlet, 10A,2P,240V, single 3 emergency light
Outlet, Electric Fan 1 wall-mounted

691
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-05B
THERAPEUTIC DIET
April 2016 NUTRITION & DIETETICS PREPARATION AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit dietetics staff

Fire risk low: MEDIUM: high

Other risks NA

692
NA

693
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-06A
SERVING AND FOOD ASSEMBLY
April 2016 NUTRITION & DIETETICS AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Food Service Workers set up and assemble cooked food Dietetic Scale 1
b. Food Service Workers place food trays and containers Diet tags
on food conveyors to be taken to the wards

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nutritionist/ Dietitian FIXTURE CHECKLIST
2 x Food Service Workers Counter, work; stainless steel 1
Sink, single compartment, with 1
drainboard; 350-400mm deep
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Staff Dining Room ENGINEERING TERMINALS
b. Close to Dietitian's Office Outlet, 10A,2P,240V, duplex 3 grounding type
universal slot
Outlet, 10A,2P,240V, single 1 for emergency light
Smoke Detector 1

694
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-06B
SERVING AND FOOD
April 2016 NUTRITION & DIETETICS ASSEMBLY AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit dietetics staff

Fire risk low: MEDIUM: high

Other risks NA

695
NA

696
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS FOOD CONVEYOR PARKING 250B-DIET-RDS-07A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Washing of food tray truck/ conveyor Tray truck, stainless steel, 4
b. Transit station for food tray truck/ conveyor 700 x 1800

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Food Service Workers FIXTURE CHECKLIST
Faucet, with hose bibb 1
Floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Dishwashing Area ENGINEERING TERMINALS
b. Adjacent to Food Assembly/ Tray Set-up Area Window curtain rail 1
Outlet, 10A,2P,240V, duplex 1 grounding type
universal slot
Outlet, 10A,2P,240V, duplex 1 GFCI
Outlet, 10A,2P,240V, single 1 emergency light
Smoke Detector 1

697
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS FOOD CONVEYOR PARKING 250B-DIET-RDS-07B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: at faucet

tolerated Maximum temperature (°C) 70

Access limit dietetics staff

Fire risk LOW: medium: high

Other risks NA

698
NA

699
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS COLD STORAGE 250B-DIET-RDS-08A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of poultry, meat and dairy products procured Refrigerator, 20 c.u. ft. 2
b. Storage of food that easily spoils (egg, vegetables, fruits) Freezer, 20 cu. Ft. 2
c. Storage of leftover cooked food that are still edible Chiller, 20 cu. Ft., reach-in 3
Exhaust fan 1
Weighing scale 1
Food cart 1
Plastic pallet 2

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Food Service Worker FIXTURE CHECKLIST
Table, stainless steel; 1
750 x 1200mm
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Dry Storage Room ENGINEERING TERMINALS
b. Close to Receiving Area Outlet, 10A,2P,240V, duplex 10 grounding type
c. Adjacent to Dietitian's Office universal slots
Outlet, 10A,2P,240V, single 1 emergency light
1 exhaust fan
Smoke Detector 1

700
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS COLD STORAGE 250B-DIET-RDS-08B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit dietetics staff

Fire risk low: MEDIUM: high

Other risks NA

701
NA

702
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS DRY STORAGE 250B-DIET-RDS-09A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of food procured Ladder, step 1
b. Storage of food intended for the next two meals Cart, push 1
c. Storage of excess supplies for future use Digital Weighing Scale 1
d. Storage of food that does not spoil easily Calculator 1
Ceiling Fan 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Food Service Worker FIXTURE CHECKLIST
Counter, work 1
Shelves, 400mm deep 1
Cabinet, lockable 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Cold Storage Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, single 3 grounding type,
Smoke Detector parallel slots
1 emergency light
1

703
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS DRY STORAGE 250B-DIET-RDS-09B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential: desirable: UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit dietetics staff

Fire risk LOW: medium: high

Other risks NA

704
NA

705
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-10A
STORAGE FOR UTENSILS/
April 2016 NUTRITION & DIETETICS SILVERWARE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of kitchen utensils and silverware

People Involved: FURNITURE AND QUANTITY REMARKS


2 x Food Service Workers FIXTURE CHECKLIST
Shelves, open, 600mm deep

Planning Relationships: ADDITIONAL EQUIPMENT & QUANTITY REMARKS


a. Close to Dietitian's Office ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 2 groundng type,
universal
Outlet, 10A,2P,240V, single 1

706
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-10B
STORAGE FOR UTENSILS/
April 2016 NUTRITION & DIETETICS SILVERWARE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential: desirable: UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit dietetics staff

Fire risk LOW: medium: high

Other risks NA

707
NA

708
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS DELIVERY RECEIVING AREA 250B-DIET-RDS-11A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Dietitian on duty and Auditor witness weighing of food Scale, platform, heavy duty 1
delivered by the supplier Hanging scale with pan 2
b. Auditor inspects and checks quality of food items purchasedPush cart 1
from the market and those delivered by the supplier Electric fan, ceiling type 1
Plastic Pallets

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Nutritionist/ Dietitian FIXTURE CHECKLIST
1 x Food Service Worker Counter, stainless steel 1
1 x Auditor Sink, single compartment with 1
2 x Agency Inspectors drainboard; 350-400mm deep
Counter, tiled 1
Shelves, open 1
Concealed floor drain 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Dietitian's Office ENGINEERING TERMINALS
b. Close to Cold and Dry Storage Rooms Window curtain rail 1
Outlet, 10A,2P,240V, duplex 6 grounding type
universal slot
Outlet, 10A,2P,240V, single 1 for emergency light
Exhaust fan 1 ionization type
Smoke Detector 1

709
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS DELIVERY RECEIVING AREA 250B-DIET-RDS-11B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be Tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit chief dietitian & staff

Fire risk LOW: medium: high

Other risks NA

710
NA

711
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-12A
DISHWASHING & POTS
April 2016 NUTRITION & DIETETICS WASHING AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Washing of pots, pans, trays, dishes and other kitchen Dishwashing machine, floor unit 1
utensils. Waste container, 380mm dia. 1
b. Food Service Workers perform other clean-up activities Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Food Service Workers FIXTURE CHECKLIST
Counter, stainless steel 1
Sink, double compartment with 2
drainboard
Grease trap 1
Counter, with upturned edge 1
Shelves, open 2
Table, feeder, stainless steel 1
Table, work, stainless steel 2 700 x 1200mm
1 700 x 2400mm
Concealed floor drain 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Food Preparation Area ENGINEERING TERMINALS
b. Close to Dietitian's Office Window curtain rail 3
Outlet, 10A,2P,240V, duplex 6 grounding type
parallel
Outlet, 10A,2P,240V, single 1 emergency light
Smoke Detector 1

712
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-12B
DISHWASHING & POTS
April 2016 NUTRITION & DIETETICS WASHING AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit dietetics staff

Fire risk LOW: medium: high

Other risks NA

713
NA

714
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS WASTE HOLDING AREA 250B-DIET-RDS-13A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Food Service Workers sort garbage accordingly Garbage bin/ container 4
b. Food Service Workers pack garbage and/or place sorted Faucet w/ hose bib 1
garbage into proper bins/ container
c. Garbage generated for a day or two is temporarily
stationed in this area prior to being collected for transfer
to the waste management service

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Food Service Worker FIXTURE CHECKLIST
Floor Drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Located in the perimeter of the Dietetics Area ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 GFCI
Outlet, 10A,2P,240V, single 1 emergency light
1 exhaust fan
Smoke Detector 1

715
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS WASTE HOLDING AREA 250B-DIET-RDS-13B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential: desirable: UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit food service workers

Fire risk LOW: medium: high

Other risks NA

716
NA

717
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS
DIETITIAN'S OFFICE
& STAFF OFFICE 250B-DIET-RDS-14A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Chief Dietitian calls meetings with staff for the preparation Computer 1
of monthly menu Calculating machine 2
b. Chief Dietitian and staff reads, writes and uses telephone FAX machine 1
in his work station Printer 1
c. Dietitian and staff receive visitors Telephone 1
d. Dietitian and staff store, file and retrieves records Waste bin w/ black lining 4

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Chief Dietitian FIXTURE CHECKLIST
3 x Staff Desk, 600 x 1200mm 1
Desk, 600 x 1500mm 3
Desk, extension; 400mm deep 1
Cabinet, steel; filing 2
Chair, junior executive 1
Chair, visitor 5
Chair, swivel 3

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Located in the kitchen where it shall give the Dietitian Window curtain rail 6
extensive view of work areas and control over possible Outlet, 10A, 2P, 240V, duplex 12 grounding type,
pilferage of dietary supplies and equipment universal slots
Outlet, 15A, 2P, 240V, single 1 emergency light
Outlet, DATA 4
Outlet, Telephone 2
Smoke Detector 2
ACU, window/ split-type 1

718
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-14B
DIETITIAN'S OFFICE &
April 2016 NUTRITION & DIETETICS
STAFF OFFICE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 Micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.44

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit chief dietitian & staff

Fire risk LOW: medium: high

Other risks NA

719
NA

720
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS NUTRITION CLINIC 250B-DIET-RDS-15A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Dietitian/ Nutritionist does individual food-related Scale, weighing 1
counselling Whiteboard 1
b. Dietitian/ Nutritionist does body fat testing Food Model
c. Pamphlets on vegetarianism, exercise, cholesterol Food Pyramid Guide
and weight reduction are given to patients Measuring cups 1 set
d. Dietitian provides nutrition counselling to help treat and Measuring spoon 1 set
prevent disease through dietary changes Waste bin w/ black lining 1

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Dietitian/ Nutritionist FIXTURE CHECKLIST
1 x Patient Desk, 600 x 1200mm 1
Desk, extension, 400 x 1200mm 1
Chair; upright, stacking 6
Counter, 900mm high, shelves 1
above and below
Sink, stainless steel, with 1
drainboard
Concealed floor drain 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Located within the Dietary Department Window curtain rail 1
b. Adjacent to the Dietitian's Office Outlet, 10A,2P,240V, duplex 6 grounding type,
c. Must have an access outside the Dietary Department universal slots
ACU, window/ split-type 1
Outlet, Intercom 1 wall-mounted
Outlet, Telephone 1 desktop
Outlet, DATA 1
Smoke Detector 1 ionization type

721
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS NUTRITION CLINIC 250B-DIET-RDS-15B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 Micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE: unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit dietitian/nutritionist and patient

Fire risk LOW: medium: high

Other risks NA

722
NA

723
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS STAFF DINING AREA 250B-DIET-RDS-16A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Dietetics staff take their meals Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
Dietetics Staff/ Personeel FIXTURE CHECKLIST
Table, 1100 x 1800mm 1
Chair; upright, stacking 6
Counter, 900mm high, shelves 1
above and below
Sink, stainless steel 1
Concealed Floor Drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Dietetics Service ENGINEERING TERMINALS
Window curtain rail 2
Outlet, 10A,2P,240V, duplex 6 grounding type
universal slot
Outlet, 10A,2P,240V, single 1 emergency light
Smoke Detector 1

724
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 NUTRITION & DIETETICS STAFF DINING AREA 250B-DIET-RDS-16B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.53

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit dietetics staff

Fire risk low: medium: HIGH

Other risks NA

725
NA

726
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
STAFF T&B/
April 2016 NUTRITION & DIETETICS LOCKER ROOM 250B-DIET-RDS-17A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Food Service Supervisor/ Workers/ Cooks change Exhaust fan 2
clothes in toilet and bathroom Waste bin w/ black lining 2
b. Food Service Supervisor/ Workers/ Cooks bathe and
perform other personal hygiene activities
c. Food Service Supervisor/ Workers/ Cooks store clothing
and personal effects in the Locker Area

People Involved: FURNITURE AND


QUANTITY REMARKS
8 x Food Service Workers FIXTURE CHECKLIST
2 x Cooks Lockers, steel 20
1 x Food Supervisor Water Closet 4
Lavatory 6
Urinal 2
Floor Drain 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Dishwashing Area ENGINEERING TERMINALS
b. Adjacent to Food Assembly/ Tray Set-up area Window curtain rail 2
Outlet, 10A,2P,240V, duplex 2 grounding type,
universal slots
Water Heater, 6kw 2 Male & Female
T&B

727
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-DIET-RDS-17B
STAFF T&B/
April 2016 NUTRITION & DIETETICS LOCKER ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit dietetics staff

Fire risk LOW: medium: high

Other risks NA

728
NA

729
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3. 10 ENGINEERING, MAINTENANCE and


HOUSEKEEPING SERVICE FACILITIES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

731
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 ENGINEERING, MAINTENANCE & HOUSEKEEPING 250B-ENG-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
ENGINEERING, MAINTENANCE 429.00 250B-ENG-DDS-01 734
& HOUSEKEEPING
Garage, Work, and Parking Areas 135.00 250B-ENG-RDS-01 735
Drivers' Lounge 18.00 250B-ENG-RDS-02 738
Security Office 18.00 250B-ENG-RDS-03 741
Housekeeping Office 18.00 250B-ENG-RDS-04 744
Biomedical Engineering Workshop 36.00 250B-ENG-RDS-05 747
Carpentry Workshop 18.00 250B-ENG-RDS-06 750
Electrical and Mechanical Workshop 36.00 250B-ENG-RDS-07 753
Head's Office 18.00 250B-ENG-RDS-08 756
Staff Office 36.00 250B-ENG-RDS-09 759
Conference Room 18.00 250B-ENG-RDS-10 762
Staff Pantry 18.00 250B-ENG-RDS-11 765
Male Quarters & Lockers 23.00 250B-ENG-RDS-12 768
Male & Female Toilets, and Janitor's Closet 8.00 250B-ENG-RDS-13 771
Storage 18.00 250B-ENG-RDS-14 774
Plumbing Workshop 18.00 250B-ENG-RDS-15 777

733
SCALE 1:300 M

6000

6000
POWER
HOUSE

S E R V I C E Y A R D

7400
PUMP
ROOM

1600
CONFERENCE HEAD'S
6000

6000
CARPENTRY ROOM OFFICE STAFF
WORK MALE PANTRY
WORKSHOP OFFICE
AREA QUARTERS MT

MALE FT
LOCKERS
15000

15000
3000

3000
GARAGE
6000

6000
AMBULANCE DRIVERS' STORAGE HOUSE-
PARKING LOUNGE ROOM SECURITY
MECHANICAL & KEEPING
BIOMEDICAL OFFICE
ELECTRICAL OFFICE
ENGINEERING PLUMBING
WORKSHOP WORKSHOP WORKSHOP

3000 3000 3000 3000 3000 3000

9000 6000 6000 3000 6000 3000 3000

36000
12000

734
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-01A
ENGINEERING AND GARAGE, WORK & PARKING
April 2016 MAINTENANCE AREAS
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Mechanic checks/ repairs vehicles Hydraulic lifter 1
b. Driver parks vehicles Oil interceptor pit 1
c. Driver cleans vehicles Whiteboard 1
Pressure washer 1
Vacuum pump 1
Air compressor 1
Waste bin 1
Fire Extinguisher 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Mechanic FIXTURE CHECKLIST
1 x Driver Shelf, 500mm deep 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Workship (Electrical and Mechanical) and ENGINEERING TERMINALS
Drivers' Lounge Outlet, 10A,2P,240V, duplex 7 grounding type,
universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 4

735
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
ENGINEERING AND GARAGE, WORK &
April 2016 MAINTENANCE PARKING AREAS 250B-ENG-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering and maintenance staff

Fire risk low: MEDIUM: high

Other risks NA

736
NA

737
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-02A
ENGINEERING AND
April 2016 MAINTENANCE DRIVERS' LOUNGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Driver rests, sleeps, stores clothings and other Refrigerator 1
belongings while waiting for transport service Whiteboard / bulletin board 1
b. Driver types trip tickets and requests for gasoline Water dispenser 1
c. Driver prepares and fills-up the endorsement Waste bin w/ black lining 1
checklist form Typewriter 1
d. Driver receives request for transport
e. Driver stores, files and retrieves trip tickets and
other documents
f. Mechanic prepares and records in a log book the
preventive maintenance of vehicles and records of
registration renewal
g. Mechanic receives spare parts for repair of vehicle

People Involved: FURNITURE AND


QUANTITY REMARKS
Driver FIXTURE CHECKLIST
Mechanic Sofa, 2-seater 2
Table, side, 400 x 400mm 1
Counter, with cabinets 1
above & below
Sink, kitchen 1
Closet, built-in 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engineering and Maintenance ENGINEERING TERMINALS
Building Window curtain rail 3
Outlet, 15A,2P,240V, duplex 7 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

738
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-02B
ENGINEERING AND
April 2016 MAINTENANCE DRIVERS' LOUNGE

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering and maintenance staff

Fire risk low: MEDIUM: high

Other risks NA

739
NA

740
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-03A
ENGINEERING AND
April 2016 MAINTENANCE SECURITY OFFICE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Security staff reads, writes and uses telephone in Computer 1
work station Calculator 1
b. Security staff receives visitors CCTV monitor 1
c. Security staff stores, files and retrieves records Telephone 1
d. Security staff uses computer Hand Held Radio 1
e. Secuirty staff writes detailed reports on crime Fire Extinguisher 1
incidents within the hospital vicinity/ compound Metal Detector 1
f. Storage of firearms, handcuffs, and restraints ACU 1
g. If with CCTV's, the security staff watches/ monitors Whiteboard 1
video camera, alarm systems for signs of crime Waste bin w/ black lining 1
fire or disorder within the hospital compound
h. Secuirty staff stores clothing and personal
protective equipment in the storage room
i. Secuirty staff stores confiscated materials

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Chief Security FIXTURE CHECKLIST
2 x Security Guards Desk, 600 x 1200mm 1
Chair, swivel 1
Chair, upright, stacking 2
Shelves, 400 x 1500mm 1
Cabinet, side, 400 x 1200 1
Cabinet, steel filing 2
Shelves, open 1

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Within the Engineering and Maintenance Window curtain rail 1
Building Outlet, 15A,2P,240V, duplex 6 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Outlet, ACU 1
Smoke Detector 1

741
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-03B
ENGINEERING AND
April 2016 MAINTENANCE SECURITY OFFICE

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit security staff

Fire risk LOW: medium: high

Other risks NA

742
NA

743
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-04A
ENGINEERING AND
April 2016 MAINTENANCE HOUSEKEEPING OFFICE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Janitorial staff reads, writes and uses telephone in Computer 1
work station Calculator 1
b. Janitorial staff receives visitors CCTV monitor 1
c. Janitorial staff stores, files and retrieves records Whiteboard 1
d. Supervisor uses computer Waste bin w/ black lining 1
e. Supervisor makes iventory of cleaning supplies/
paraphernalia and places orders for them
or reports to the Supply Officer
f. Storage of clothing and personal protective
equipment
g. Storage of cleaning tools and supplies

People Involved: FURNITURE AND


QUANTITY REMARKS
Janitorial staff FIXTURE CHECKLIST
Supervisor Desk, 600 x 1200mm 1
Chair, swivel 1
Chair, upright, stacking 2
Shelves, 400 x 1500mm 1
Cabinet, side, 400 x 1200 1
Cabinet, steel filing 2
Counter, with cabinets above 1
and below
Sink, stainless steel 1
Concealed floor drain 1
Shelves, open 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engineering and Maintenance ENGINEERING TERMINALS
Building Window curtain rail 1
Outlet, 15A,2P,240V, duplex 6 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 1

744
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-04B
ENGINEERING AND
April 2016 MAINTENANCE HOUSEKEEPING OFFICE

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit janitorial staff

Fire risk LOW: medium: high

Other risks NA

745
NA

746
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
BIOMEDICAL ENGINEERING
250B-ENG-RDS-05A
ENGINEERING AND
April 2016 MAINTENANCE WORKSHOP
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Repair of medical equipment such as suction Circular pan 1
apparatus, negatoscope, BP apparatus, etc. Biomedical tools 1 set
b. Prepares the needed supplies and equipment for Whiteboard 1
the repair of medical apparatuses and units Waste bin w/ black lining 1 general

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Biomed Technician FIXTURE CHECKLIST
Table, work, 1 w/ 2" thk tabletop
Counter, work, 900mm high 1 w/ 2" thk tabletop
Cabinet, wall hung 1
Stool, adjustable 2
Bench 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engineering and Maintenance ENGINEERING TERMINALS
Building Window curtain rail 3
Outlet, 15A,2P,240V, duplex 8 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 1

747
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-05B
ENGINEERING AND BIOMEDICAL ENGINEERING
April 2016 MAINTENANCE WORKSHOP

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering and maintenance staff

Fire risk LOW: medium: high

Other risks NA

748
NA

749
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-06A
ENGINEERING AND
April 2016 MAINTENANCE CARPENTRY WORKSHOP
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Repair of hospital furniture, cabinets, chairs and Circular pan 1
other woordworks Carpentry tools 1 set
b. Assemble/ fabricate furniture and other woodworks Whiteboard 1
c. Painting, varnishing and refinishing of hospital Waste bin w/ black lining 1
furniture and other woodworks
d. Prepares the needed supplies and tools for the
repair of facilities

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Carpenter FIXTURE CHECKLIST
1 x Painter Table, work 1 w/ 2" thk tabletop
Counter, work, 900mm high 1 w/ 2" thk tabletop
Counter, work, open below 1
Cabinet, wall hung 1
Cabinet, with shelves 1
Stool, adjustable 1
Bench 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engineering and Maintenance ENGINEERING TERMINALS
Building Outlet, 15A,2P,240V, duplex 6 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 1

750
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-06B
ENGINEERING AND
April 2016 MAINTENANCE CARPENTRY WORKSHOP

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering and maintenance staff

Fire risk LOW: medium: high

Other risks NA

751
NA

752
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-07A
ENGINEERING AND ELECTRICAL & MECHANICAL
April 2016 MAINTENANCE WORKSHOP
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Repair of aircons and refrigerators Circular pan 1
b. Welding of trolleys, steel cabinets, cribs and other Electrical and mechanical tools 1 set
steel works Whiteboard 1
c. Prepares the needed supplies and tools for the Waste bin w/ black lining 1
repair of facilities and building equipment
d. Repair of telephone and other building apparatuses

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Electrician FIXTURE CHECKLIST
1 x Aircon Technician Table, work 1 w/ 2" thk tabletop
1 x Electronic Technician Counter, work, 900mm high 2 w/ 2" thk tabletop
Counter, work, open below 1
Cabinet, wall hung 1
Stool, adjustable 3
Bench 1
Shelving, open 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engineering and Maintenance ENGINEERING TERMINALS
Building Window curtain rail 1
Outlet, 15A,2P,240V, duplex 8 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 1

753
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-07B
ENGINEERING AND ELECTRICAL & MECHANICAL
April 2016 MAINTENANCE WORKSHOP

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering and maintenance staff

Fire risk LOW: medium: high

Other risks NA

754
NA

755
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-08A
ENGINEERING AND
April 2016 MAINTENANCE HEAD'S OFFICE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Reads, writes and uses telephone in Computer 1 w/ printer
work station Calculator 1
b. Receives visitors Drafting tools 1 set
c. Uses toilet facilities ACU 1
d. Reviews and approves engineering and Whiteboard 1
architectural plans Waste bin w/ black lining 1
e. Approves documents and receives reports

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Engineering Head FIXTURE CHECKLIST
Visitors Desk, 600 x 1500mm 1
Engineering Staff Desk extension, 300 x 1500mm 1
Chair, swivel 1
Chair, upright, stacking 2
Sofa, 2-seater 1
Cabinet, steel filing 2
Water closet w/ spray hose 1
Lavatory 1
Floor Strainer 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Staff Office, Conference Room and ENGINEERING TERMINALS
Storage Area Window curtain rail 1
Outlet, 10A,2P,240V, duplex 6 grounding type
universal
Outlet, 10A,2P,240V, duplex 1 GFCI
Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 1

756
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-08B
ENGINEERING AND
April 2016 MAINTENANCE HEAD'S OFFICE

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA


engineering head & maintenance
Access limit
staff
Fire risk LOW: medium: high

Other risks NA

757
NA

758
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-09A
ENGINEERING AND
April 2016 MAINTENANCE STAFF OFFICE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Reads, writes and uses telephone in Computer 1 w/ printer
work station Calculator 1
b. Receives visitors Drafting tools 1 set
c. Stores, files and retrieves records ACU 1
d. Uses drafting tools Photocopy machine 1
e. Uses computer Low partition, 1800mm high 1
f. Requests, receives, and stores spare parts and Whiteboard / bulletin board 1
supplies Waste bin w/ black lining 3
g. Prepares documents for repair of vehicles
h. Receives and records job order requests
i. Prepares and records in a logbook the preventive
maintenance of equipment and other facilities
j. Reproduces copies of plans and documents

People Involved: FURNITURE AND QUANTITY REMARKS


1 x Maintenance Supervisor FIXTURE CHECKLIST
2 x Mechanics/ Carpenters Desk, 600 x 1200mm 7
Plumber Chair, upright; stacking 12
Carpenter/ Painter Cabinet, steel filing 3
Electrician Counter, with cabinets 1
Electronic Technician above & below
Driver Sink, kitchen 1
Aircon Technician Table, 4-seater 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engineering and Maintenance ENGINEERING TERMINALS
Building Window curtain rail 2
Outlet, 10A,2P,240V, duplex 13 grounding type
universal
Outlet, 10A, 240V, single 2 emergency light
Outlet, DATA 5
Outlet, Telephone 2
Smoke Detector 1

759
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-09B
ENGINEERING AND
April 2016 MAINTENANCE STAFF OFFICE

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 2.4

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering & maintenance staff

Fire risk LOW: medium: high

Other risks NA

760
NA

761
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-10A
ENGINEERING AND
April 2016 MAINTENANCE CONFERENCE ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Engineering staff/ visitors hold meetings and/ or Computer 1
special lectures Projector 1
Sound System 1
ACU 1
Whiteboard/projection screen 1
Waste bin, general 1

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Maintenance Supervisor FIXTURE CHECKLIST
Engineering Staff Table, conference, 8-seater 1
Visitors Chair, conference 8
Table, 900mm high, with 1
shelves/cabinets below

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engingeering and Maintenance ENGINEERING TERMINALS
Building Outlet, 10A,2P,240V, duplex 9 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1
Outlet, Telephone 1
Smoke Detector 1

762
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-10B
ENGINEERING AND
April 2016 MAINTENANCE CONFERENCE ROOM

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-700

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering & maintenance staff

Fire risk LOW: medium: high

Other risks NA

763
NA

764
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-11A
ENGINEERING AND
April 2016 MAINTENANCE STAFF PANTRY
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Engineering Staff cook food for their meals Two-burner electric stove 1
b. Staff store their uncooked and cooked/ leftover food Exhaust fan 1
at the refrigerator Fire Extinguisher 1
c. Engineering Staff eat their meals at the party Refrigerator 1
d. Staff do clean-up activities Water dispenser 1
Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
6 x Engineering Staff FIXTURE CHECKLIST
Table, dining,6-seater 1
Chair, dining 6
Counter, with cabinets 1
above and below
Sink, stainless steel 1
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Withing the Engineering and Maintenance ENGINEERING TERMINALS
Building Window curtain rail 1
Outlet, 10A,2P,240V, duplex 8 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

765
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-11B
ENGINEERING AND
April 2016 MAINTENANCE STAFF PANTRY

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 1.2

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering & maintenance staff

Fire risk LOW: medium: high

Other risks NA

766
NA

767
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-12A
ENGINEERING AND
April 2016 MAINTENANCE MALE QUARTERS
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Maintenance staff rests, sleeps, and/ or store clothings ACU 1
and other personal belongings Waste bin w/ black lining 1

People Involved: FURNITURE AND


QUANTITY REMARKS
3 x Engineering Staff FIXTURE CHECKLIST
Bed, single, with mattress 3
Table, side 4
Closet 1
Locker, 300 x 400mm 8

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Engineering and Maintenance ENGINEERING TERMINALS
Building Window curtain rail 1
Outlet, 10A,2P,240V, duplex 7 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

768
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-12B
ENGINEERING AND
April 2016 MAINTENANCE MALE QUARTERS

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering & maintenance staff

Fire risk LOW: medium: high

Other risks NA

769
NA

770
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-13A
ENGINEERING AND
April 2016 MAINTENANCE T&B AND JAN. CLO.
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Engineering staff change clothes in T&B Exhaust fan 1
b. Engineering staff take a bath in T&B Waste bin w/ black lining 2
c. Engineering staff urinate and defecate

People Involved: FURNITURE AND


QUANTITY REMARKS
4 x Engineering Staff FIXTURE CHECKLIST
1 x Janitor Water closet w/ spray hose 3
Urinal 2
Lavatory 3
Janitor's slop sink; with faucet 1
Shelf, open 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Conference Room and Male Quarters ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 2 GFCI
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

771
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-13B
ENGINEERING AND
April 2016 MAINTENANCE T&B AND JAN. CLO.

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering & maintenance staff

Fire risk LOW: medium: high

Other risks NA

772
NA

773
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-14A
ENGINEERING AND
April 2016 MAINTENANCE STORAGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of carpentry tools Exhaust fan 1
b. Storage of equipment used in the maintenance of Waste bin w/ black lining 1
vehicles and facilities
c. Storage of spare parts for motor vehicles
d. Storage of supplies and equipment for plumbing
electrical, carpentry, welding, and painting works

People Involved: FURNITURE AND


QUANTITY REMARKS
Maintenance/ Engineering Staff FIXTURE CHECKLIST
Shelving, open 2
Cabinet 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Biomedical Engineering Workship, ENGINEERING TERMINALS
Carpentry Workshop and Head Office Window curtain rail 1
Outlet, 10A,2P,240V, duplex 2 grounding type
universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

774
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-ENG-RDS-14B
ENGINEERING AND
April 2016 MAINTENANCE STORAGE

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit engineering & maintenance staff

Fire risk low:MEDIUM: high

Other risks NA

775
NA

776
777
778
3000

9
T
D
7

6000
SD

8 4
6
CH 2
3

KEY SCALE 1:100 M

1 Table, work; with 2" thick tabletop 6 Floor drain


2 Counter, work; 900mm high, with 7 Whiteboard/ bulletin board
2" thick tabletop 8 Waste bin
3 Counter, 750mm high, with deep 9 Window
work sink
4 Stool, adjustable
5 Bench

779
VOLUME 3
DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.11 SUPPORT SERVICE FACILITIES


3.11.1 LINEN and LAUNDRY
3.11.2 PROPERTY and SUPPLY
3.11.3 MORGUE
3.11.4. CENTRAL WASTE STORAGE

First Edition
DEPARTMENT OF HEALTH
Manila
2017

781
Hospital: Department of Health
SERVICE FACILITY SHEET INDEX
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Service Facility Title: Reference Sheet Number:
April 2016 SUPPORT SERVICE FACILITY 250B-SUP-SFSI-01
SPACE DEMAND TOTAL AREA REFERENCE SHEET
ROOM TITLE PAGE
(SQ. MTS.) (SQ. MTS.) NUMBER
LINEN AND LAUNDRY 172.00 250B-LL-DDS-01 784
Issuing, Office, Work Room, and Storage 68.00 250B-LL-RDS-01 785
Pressing and Ironing Room 41.00 250B-LL-RDS-02 788
Washing/ Drying Room 8.00 250B-LL-RDS-03 791
Receiving/ Sorting/ Disinfection Area 8.00 250B-LL-RDS-04 794
Staff Lockers and T&B 16.00 250B-LL-RDS-05 797
Sewing & Sorting Room 31.00 250B-LL-RDS-06 800

PROPERTY AND SUPPLY 246.00 250B-PS-DDS-01 803


Storage/ Warehouse 144.00 250B-PS-RDS-01 804
Work Area 42.00 250B-PS-RDS-02 807
Head's Office 24.00 250B-PS-RDS-03 810
Staff Pantry 9.00 250B-PS-RDS-04 813
Staff Lockers, T&B, & Janitor's Closet 27.00 250B-PS-RDS-05 816

MORGUE 157.00 250B-MOR-DDS-01 819


Autopsy and Tissue Processing Room 54.00 250B-MOR-RDS-01 820
Morgue 90.00 250B-MOR-RDS-02 823
Staff Lockers, T&B, & Janitor's Closet 13.00 250B-MOR-RDS-03 826

CENTRAL WASTE STORAGE 60.00 250B-CWS-DDS-01 829


Work Area 12.00 250B-CWS-RDS-01 830
Hazardous Waste Room 12.00 250B-CWS-RDS-02 833
Mercury-Containing Devices/ Lamps 12.00 250B-CWS-RDS-03 836
Biodegradables 12.00 250B-CWS-RDS-04 839
Non-Biodegradables 12.00 250B-CWS-RDS-05 842

783
784
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LL-RDS-01A
ISSUING, OFFICE, WORK ROOM
April 2016 LINEN AND LAUNDRY & STORAGE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Laundry workers classify, count and record clean linen in Trolley/pushcart, linen 1
the log book Sewing machine 2
b. Seamstress repairs or mends torn linen and Marking machine 1
records it in the log book Step ladder, adjustable 2
c. Head of unit receives linen issue slip and prepares linen Waste bin w/ black lining 2
items for issuance
d. Laundry workers pack linen and deliver to wards
e. Head of linen/ laundry unit prepares forms for purchase
of materials
f. Linen unit receive materials and do the sewing of linen
and other necessary preparations
g. Head of linen/ laundry unit prepares memo receipt to the
head of unit and notifies the requsitioning unit when
materials are ready
h. Head of linen unit retrieves and stores original copies
of forms in file and keeps an updated inventory of linens
i. Marking and remarking of linen for tap sheet, marking FURNITURE AND QUANTITY REMARKS
of name of hospital and inventory number at the center FIXTURE CHECKLIST
Counter, 900mm high, w/ 1
cabinets below
Counter, pass-through 1
People Involved: Counter, w/ cabinets above & below 1
1 x Laundry Unit Head Desk, 750 x 1200mm 2
2 x Laundry Workers Cabinet, steel; filing 2
2 x Seamstresses Chair, upright, stacking 4
Table, work 2
Stool, adjustable 3
Shelving, for linen, w/ glass doors 3

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
Planning Relationships: ENGINEERING TERMINALS
a. Close to Receiving Area Window curtain rail 1
b. Adjacent to Central Linen Storage Outlet, 10A,2P,240V, duplex 11 universal
c. Close to Pressing and Ironing Area Outlet, 10A, 240V, single 1 emergency light
Outlet, DATA 1 wall-mounted
Outlet, Telephone 1 desktop
Computer 1 for coverting,
reports/ changing
of extra linen
Smoke Detector 3

785
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LL-RDS-01B
ISSUING, OFFICE, WORK
April 2016 LINEN AND LAUNDRY ROOM & STORAGE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 1000

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit linen and laundry staff

Fire risk LOW: medium: high

Other risks NA

786
5200

13
14

3000
SD D

3000
A SD
7 1
2 12
13 11 8 10 8 10
9 9 9

3000
SD C SD B
5 5 7 4 3
7 7
13 14 DT 6 6
12

4000 2000

6000 6000

KEY SCALE 1:150 M


A ISSUING AREA 8 Table, work
1 Counter, 900mm high, w/ cabinets below 9 Stool, adjustable
2 Trolley/pushcart, linen 10 Sewing machine
11 Marking machine
B WORK AREA
12 Waste bin
3 Counter, pass-through
4 Counter, w/ cabinets above & below C STORAGE AREA
5 Desk, 750 x 1200mm 13 Shelving, for linen, w/ glass doors
6 Cabinet, steel; filing 14 Step ladder, adjustable
7 Chair, upright, stacking D SUPPLY ROOM

787
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LINEN AND LAUNDRY
PRESSING AND
IRONING ROOM 250B-LL-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Laundry Worker inspects linen brought in from the drying Flatwork ironer, 2-roll 1
area and segregates torn linen to be mended Mushroom laundry press 2
b. Laundry Worker shakes out, presses and irons clean linen Ironing board 1
brought in from the drying area Compressor 1
Ironing board 1

People Involved: FURNITURE AND


QUANTITY REMARKS
3 x Laundry Workers FIXTURE CHECKLIST

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Washing Area ENGINEERING TERMINALS
b. Adjacent to Issuing, Office, Work Room and Storage Window curtain rail 2
Outlet, 15A,2P,240V, duplex 8 universal
Outlet, 10A, 240V, single 2 emergency light
exhaust fan
Smoke Detector 1
Equipment specific outlet as required preferably GFU

788
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LL-RDS-02B
PRESSING AND
April 2016 LINEN AND LAUNDRY IRONING ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface:

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit linen and laundry staff

Fire risk low: medium: HIGH

Other risks NA

789
NA

790
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LINEN AND LAUNDRY WASHING/ DRYING ROOM 250B-LL-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Linens are washed by Laundry Workers Laundry tub, double compartment 1
Washing machine, industrial 5
Dryer, industrial 5

People Involved: FURNITURE AND


QUANTITY REMARKS
3 x Laundry Workers FIXTURE CHECKLIST
Table, shakeout 1
Stool, adjustable 1
Cabinet, supply storage 1
Concealed floor drain 5

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Sorting Area ENGINEERING TERMINALS
b. Adjacent to Pressing and Ironing Area Window curtain rail 2
c. Adjacent to Linen Office and Work room Outlet, 15A,2P,240V, duplex 13 universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

791
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LINEN AND LAUNDRY WASHING/ DRYING ROOM 250B-LL-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit linen and laundry staff

Fire risk LOW: medium: high

Other risks NA

792
NA

793
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LL-RDS-04A
RECEIVING/ SORTING/
April 2016 LINEN AND LAUNDRY DISINFECTION AREA
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Laundry worker counts soiled linen with Nursing Bins, sorting 1 for condemned
attendant and tallies the number with the linen list. 1 for infectious
b. Laundry worker inspects soiled linen and segregate those 1 for slightly
that need repair or those to be condemned, and used-white
linens to be washed 1 for heavily
c. Temporary transit area for soiled linen soiled-white
d. Soiled linen are sorted according to grouping system 1 for slightly
being adapted prior to washing used-colored
Trolley, dirty linen 3
Basin, big 2 for soaking of
heavily soiled
colored linen

People Involved: FURNITURE AND QUANTITY REMARKS


3 x Laundry Workers FIXTURE CHECKLIST
Table, pre-sorting 1
Stool, adjustable 2
Washing trough, tiled 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Washing/Drying Room ENGINEERING TERMINALS
b. Close to Issuing, Office, Work Room and Storage Window curtain rail 3
Outlet, 10A,2P,240V, duplex 7 grounding type,
universal
Outlet, 10A, 240V, single 2 exhaust fan,
emergency light
Smoke Detector 2

794
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-LL-RDS-04B
RECEIVING/ SORTING/
April 2016 LINEN AND LAUNDRY DISINFECTION AREA
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Exhaust (Pa) NA Daylight essential:DESIRABLE:unnecessary

Inlet (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit linen and laundry staff

Fire risk LOW: medium: high

Other risks NA

795
NA

796
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LINEN AND LAUNDRY STAFF LOCKERS AND T&B 250B-LL-RDS-05A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Laundry Unit Employees change from street clothes to Waste bin w/ black lining 2
work clothes and personal protective equipment (PPE)
b. Laundry Unit Employees perform personal hygiene
activities
c. Use of toilet facilities
d. Laundry Unit Employees store clothing and personal
effects in the Locker Area

People Involved: FURNITURE AND


QUANTITY REMARKS
Laundry Unit Workers FIXTURE CHECKLIST
Lockers, steel 9
Water Closet w/ spray hose 2
Lavatory 2
Urinal 1
Floor Strainer 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Located within or adjacent to the Laundy Department ENGINEERING TERMINALS
near the Linen Office to keep the area always clean Window curtain rail 2
and dry Outlet, 10A,2P,240V, duplex 1 universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

797
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LINEN AND LAUNDRY STAFF LOCKERS AND T&B 250B-LL-RDS-05B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit linen and laundry staff

Fire risk LOW: medium: high

Other risks NA

798
5300

2000 3300

2 2 2 3

1500
4

3000
SD
4

1500
1
3
2 2 2 2 2 2

2600 2700

KEY SCALE 1:100 M

1 LOCKER AREA
2 Lockers, steel

3 TOILET & BATH


4 Waste bin

799
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LINEN AND LAUNDRY SEWING & SORTING RM 250B-LL-RDS-06A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Laundry worker examines linen for repair and Trolley, linen 1
tallies number on linen list/inventory Sewing Machine 1
b. Laundry worker repairs torn/damaged linen
by hand and/or using sewing machine
c. Laundry worker folds repaired linen on work
table
d. Repaired linen is transferred to trolley
for transport to Pressing/Ironing Room

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Laundry Workers FIXTURE CHECKLIST
Table, sorting 1
Table, work 1
Stool, adjustable 3

ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
ENGINEERING TERMINALS
Planning Relationships: Outlet, 10A,2P,240V, duplex 4 grounding type,
a. Adjacent to Washing/Drying Room universal slots
b. Adjacent to Pressing/Ironing Room Outlet, 10A,2P,240V, single 1 for emergency light
Smoke detector 1

800
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 LINEN AND LAUNDRY SEWING & SORTING RM 250B-LL-RDS-06B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity (%RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit linen and laundry staff

Fire risk LOW: medium : high

Other risks NA

801
5100

6000
SD

3
2
4

KEY SCALE 1:100 M

1 Table, sorting
2 Table, work
3 Stool, adjustable
4 Machine, sewing
5 Trolley, linen

802
SCALE 1:300 M

12000
6000 6000

12000
LOADING/ STORAGE/ WAREHOUSE
UNLOADING BAY

27000
3000

HAZARDOUS ITEMS
STORAGE
ROOM 6000
3000

TEMPERATURE-
CONTROLLED ISSUING
STORAGE
ROOM
3000

HEAD'S
OFFICE
6000

WORK AREA
3000

MEETING
ROOM

STAFF
3000
3000

LOCKERS & T&B


STAFF
PANTRY
JAN
CLO

803
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY STORAGE/ WAREHOUSE 250B-PS-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of tools, equipment, instruments, materials, and Fire Extinguisher 4
other supplies needed by the different departments of Exhaust fan 4
the hospital

People Involved: FURNITURE AND


QUANTITY REMARKS
Property and Supply Staff FIXTURE CHECKLIST
Plastic Pallets, 1000mmX1200mm 6
Shelving, railing, adjustable 25
Door, Roll-up, Aluminum 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. With a good view from the Staff and Head's Office ENGINEERING TERMINALS
b. With direct access from the service road for easier Outlet, 10A,2P,240V, duplex 11 grounding type,
delivery/ loading and distribution of supplies universal
and equipment Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 4

804
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY STORAGE/ WAREHOUSE 250B-PS-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) atmospheric Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Property and Supply Staff

Fire risk low: MEDIUM: high

Other risks NA

805
NA

806
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY WORK AREA 250B-PS-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Staff reads, writes and uses computer in work station Computer 10 w/ internet access
b. Staff receives visitors/ vendors Calculator 10
c. Stores, files and retrieves records ACU 1
d. Staff assists the Property Supply Officer in locating vendors Whiteboard 3
of materials, equipment and supplies Waste bin w/ black lining 10
e. Staff checks on delayed orders and expedite delivery

People Involved: FURNITURE AND


QUANTITY REMARKS
10 x Clerks FIXTURE CHECKLIST
Visitors/ Vendors Desk, 600 x 1200mm 10
Desk extension, 400 x 800mm 10
Chair, clerical 10
Chair, visitor 5
Cabinet, steel filing 3

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to PSO's Office and Storage / Warehouse Area ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 3 grounding type,
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, telephone 2
Outlet, DATA 6
Smoke Detector 2

807
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY WORK AREA 250B-PS-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 500

Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.9

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA


Property & Supply Officer and
Access limit
Vendors/ Visitors
Fire risk LOW: medium: high

Other risks NA

808
NA

809
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY HEAD'S OFFICE 250B-PS-RDS-03A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Property Supply Officer makes requisition, inventory, Computer 1 w/ printer
distribution, and control of tools, equipment, materials, ACU 1
and supplies for a department or division Whiteboard 1
b. PSO controls purchasing department budgets Waste bin w/ black lining 1
d. PSO develops and implements purchasing and contract
supplies and interviews them to determine product
availability and terms of sales
e. Property Supply Officer analyzes market and delivery
systems to assess present and future material availability

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Property Supply Officer FIXTURE CHECKLIST
Visitors/ Vendors Desk, 750 x 1500mm 1
Desk, extension, 400 x 1200mm 1
Chair, junior executive 1
Chair, visitor 2
Cabinet, steel filing 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Work Area and Storage / Warehouse ENGINEERING TERMINALS
Window curtain rail 1
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal
Outlet, 10A, 240V, single 1 emergency light
Outlet, telephone 1
Outlet, DATA 1
Smoke Detector 1

810
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY HEAD'S OFFICE 250B-PS-RDS-03B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500

Room temperature (°C) 23 Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) Whiteboard

Volume (cu.m./hr.-person) 25 Color rendering Waste bin w/ black lining

Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary

Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY

Cooling load (TR) 0.6

Desk, 750 x 1500mm

Desk, extension, 400 x 1200mm

SOUND SAFETY Chair, junior executive

Acceptable sound level (db) 60 Accessible hot surface: Chair, visitor

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) Cabinet, steel filing

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA


Property & Supply Officer and
Access limit
Vendors/ Visitors
Fire risk LOW: medium: high

Other risks NA

811
NA

812
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY STAFF PANTRY 250B-PS-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Property and Supply Staff eat their meals Exhaust fan 1
b. Staff do clean-up activities Fire extinguisher 1
Refrigerator 1
Water dispenser 1
Waste bin 1

People Involved: FURNITURE AND


QUANTITY REMARKS
4 x Property and Supply Staff FIXTURE CHECKLIST
Table, dining, 4-seater 1
Chair, dining 4
Counter, w/ cabinets above & below 1
Sink, single basin, w/ drainboard 1
and below
Concealed floor drain 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within the Property and Supply Building ENGINEERING TERMINALS
Window curtain rail 1
Outlet, 10A,2P,240V, duplex 6 grounding type,
universal
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

813
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 PROPERTY AND SUPPLY STAFF PANTRY 250B-PS-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light essential:DESIRABLE:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Property and Supply Staff

Fire risk LOW: medium: high

Other risks NA

814
NA

815
Hospital: Department of Health

ROOM DATA SHEET


250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-PS-RDS-05A
STAFF LOCKERS, T&B, AND JAN.
April 2016 PROPERTY AND SUPPLY CLO.
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Property and Supply Staff change clothes in the T&B Waste bin w/ black lining 2
b. Property and Supply Staff store clothing and other Exhaust fan 1
personal belongings
c. Property and Supply Staff take a bath in the T&B
d. Property and Supply Staff urinate and defecate
e. Janitor stores cleaning supplies and tools

People Involved: FURNITURE AND


QUANTITY REMARKS
4 x Property and Supply Staff FIXTURE CHECKLIST
1 x Janitor Locker, steel, 300 x 500mm 5
Lavatory 4
Water closet 3
Urinal 1
Shower room 2
Slop sink, with floor strainer 1
Shelves, open 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Staff Pantry ENGINEERING TERMINALS
b. Close to Head Office and Work Area Window curtain rail 1
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal
Outlet, 10A,2P,240V, duplex 2 GFCI
Outlet, 10A, 240V, single 1 emergency light
Smoke Detector 1

816
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-PS-RDS-05B
STAFF LOCKERS, T&B, AND
April 2016 PROPERTY AND SUPPLY JAN. CLO.
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature (°C) ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity (% RH) NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be NA Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit Property and Supply Staff

Fire risk LOW: medium: high

Other risks NA

817
3000 3000 3000

4 4

1400
GFCI 3 1 3 GFCI

3000
SD

1600
5
6
2 7

1150
1725 1850
2775 1600
2400 1400
2100 1950
2925 1050
1575

KEY SCALE 1:150 M

1 LOCKER AREA 5 JANITOR'S CLOSET


2 Locker, steel, 300 x 500mm 6 Slop sink, with floor strainer
7 Shelves, open
3 TOILET & BATH
4 Waste bin

818
SCALE 1:300 M

15000
9000 6000

LOCKER &
T&B
TISSUE
J.C. PROCESSING
MORGUE AREA
10000

AUTOPSY
AREA
FAMILY
GRIEVING
ROOM

819
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-MOR-RDS-01A
AUTOPSY & TISSUE
April 2016 MORGUE PROCESSING ROOM
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Pathologist performs autopsy procedure on Table, mayo 1
deceased patients Footstool 1
b. Pathologist performs toileting activites after Suction apparatus 1
procedure Scale 1
Kick bucket 1
Instrument sterilizer, with stand 1
Autotechnicon tissue processor 1
Waste bin w/ yellow lining 1 infectious
Waste bin w/ yellow lining 2 pathological

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Pathologist FIXTURE CHECKLIST
1 x Medical Technologist Counter, tiled, with cabinets 2
above & below
Sink, instrument & scrub, with 2
gooseneck spout & spray, foot
control - sensor type
Stool, adjustable 2
Table, autopsy, with sink 1
Concealed floor drain 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Close to Ante Room/Lobby ENGINEERING TERMINALS
b. Adjacent to Locker Room and T&B Window curtain rail 4
c. Adjacent to Morgue Outlet, 10A,2P,240V, duplex 9 grounding type,
universal slots
Outlet, 15A,2P,240V, duplex 1 suction apparatus
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 2

820
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-MOR-RDS-01B
AUTOPSY & TISSUE
April 2016 MORGUE PROCESSING ROOM

TECHNICAL DESIGN DATA:


ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) 10,000

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: at sink

tolerated Maximum temperature (°C) 70

Access limit morgue staff

Fire risk LOW: medium: high

Other risks exposure to hazardous chemicals

821
6000
1500 1500 3000

CH 1 2
3 14

2800
11
SD

1500
13
13

10000
5 6

4
8
9

5700
SD 7

12

3
14
CH 1 2 CH
10

KEY SCALE 1:150 M

1 Counter, tiled, with cabinets 7 Suction apparatus


above & below 8 Scale
2 Sink, instrument & scrub, with 9 Kick bucket
gooseneck spout & spray, foot 10 Instrument sterilizer, with stand
control - sensor type 11 Autotechnicon tissue processor
3 Stool, adjustable 12 Waste bin, infectious
4 Table, autopsy, with sink 13 Waste bin, pathological
5 Table, mayo 14 Concealed floor drain
6 Footstool

822
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 MORGUE MORGUE 250B-MOR-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of deceased bodies awaiting claim by Refrigerator, mortuary 7
relatives Partition, foldable 2
Waste bin w/ black lining 1 general

People Involved: FURNITURE AND


QUANTITY REMARKS
1 x Pathologist FIXTURE CHECKLIST
1 x Medical Technologist Sofa, 2-seater 2
Relatives Table, 400 x 400mm 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Autopsy Room ENGINEERING TERMINALS
Window curtain rail 4
Outlet, 10A,2P,240V, duplex 11 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 2

823
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 MORGUE MORGUE 250B-MOR-RDS-02B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 50 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit morgue staff

Fire risk LOW: medium: high

Other risks NA

824
9000

2 2 2 2 2

SD SD

7400
10000
3
1

3
SD
2600

2 2
5 4

6 5
7

3450 2950 2600

KEY SCALE 1:150 M

1 MORGUE
2 Refrigerator, mortuary
3 Partition, foldable

4 FAMILY GRIEVING ROOM


5 Sofa, 2-seater
6 Table, 400 x 400mm
7 Waste bin, general

825
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-MOR-RDS-03A
STAFF LOCKERS, T&B
April 2016 MORGUE AND JAN. CLO.
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Morgue staff change clothes in Locker Room Waste bin w/ black lining 1
b. Storing of clothes and personal effects
c. Morgue staff perform toiletting activities in T&B

FURNITURE AND
QUANTITY REMARKS
People Involved: FIXTURE CHECKLIST
1 x Morgue Technician Locker, steel 1
1 x Pathologist Slop sink, with hose bibb faucet 1
1 x Medical Technologist Shelving, open 1
Lavatory 1
Water Closet 1
Shower 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Adjacent to Autopsy Room ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 1 grounding type,
universal slots
Outlet, 10A,2P,240V, duplex 1 GFCI
Outlet, 10A,2P,240V, single 1 emergency light
Window curtain rail 2
Smoke detector 1

826
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-MOR-RDS-03B
STAFF LOCKERS, T&B AND
Jan-00 MORGUE JAN. CLO.
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary

Pressure: Emergency light ESSENTIAL:desirable:unnecessary

Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 60 Accessible hot surface: NA

Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit morgue staff

Fire risk LOW: medium: high

Other risks NA

827
NA

828
829
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 CENTRAL WASTE STORAGE WORK AREA 250B-CWS-RDS-01A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Janitor places waste bins carts/trolleys Weighing scale 1
b. Janitor stores cleaning tools, supplies and PPEs Washer, high pressure 1
c. Janitor cleans/washes the waste bins and Waste bins / carts / trolleys 3
trolleys Fire extinguisher 1
d. Janitor weighs volume of waste
e. Janitor records volume of waste
f. Janitors performs hand washing

People Involved: FURNITURE AND


QUANTITY REMARKS
8 x Janitors FIXTURE CHECKLIST
Shelving, 400mm deep 1
Floor strainer 1

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within Central Waste Storage Facility ENGINEERING TERMINALS
Window curtain rail 1
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

830
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 CENTRAL WASTE STORAGE WORK AREA 250B-CWS-RDS-01B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY

Pressure: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit waste management staff

Fire risk LOW: medium: high

Other risks NA

831
NA

832
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 CENTRAL WASTE STORAGE HAZARDOUS WASTE ROOM 250B-CWS-RDS-02A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
Storage of the following hazardous waste before Waste bins / carts / trolleys 5 yellow
treatment : Exhaust fan 1 above door
a. Infectious Refrigerator 1
b. Sharps
c. Chemical
d. Pharmaceutical
e. Pathological / Anatomical

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Janitors FIXTURE CHECKLIST

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within Central Waste Storage Facility ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 5 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

833
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CWS-RDS-02B
HAZARDOUS WASTE
April 2016 CENTRAL WASTE STORAGE ROOM
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY

Pressure: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit waste management staff

Fire risk LOW: medium: high

Other risks NA

834
NA

835
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CWS-RDS-03A
MERCURY-CONTAINING
April 2016 CENTRAL WASTE STORAGE DEVICES/LAMPS
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of mercury-containing devices/lamps Exhaust fan 1 above door
before being collected by DENR-accredited TSD
(Treatment/Storage/Disposal) Facility

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Janitors FIXTURE CHECKLIST
Cabinet with shelves 2

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within Central Waste Storage Facility ENGINEERING TERMINALS
Window curtain rail 1
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1
Window curtain rail 1

836
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CWS-RDS-03B
MERCURY-CONTAINING
April 2016 CENTRAL WASTE STORAGE DEVICES/LAMPS
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY

Pressure: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit waste management staff

Fire risk LOW: medium: high

Other risks NA

837
NA

838
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 CENTRAL WASTE STORAGE BIODEGRADABLE WASTE 250B-CWS-RDS-04A
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of biodegradable waste before being Waste bins / carts / trolleys 3 black
picked up by the local waste transporter Exhaust fan 1 above door

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Janitors FIXTURE CHECKLIST

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within Central Waste Storage Facility ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

839
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
April 2016 CENTRAL WASTE STORAGE BIODEGRADABLE WASTE 250B-CWS-RDS-04B
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY

Pressure: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit waste management staff

Fire risk LOW: medium: high

Other risks NA

840
NA

841
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CWS-RDS-05A
NON-BIODEGRADABLE/
April 2016 CENTRAL WASTE STORAGE RECYLABLE WASTE
FUNCTIONAL DESIGN REQUIREMENTS:
This activity space provides facilities needed EQUIPMENT AND
QUANTITY REMARKS
for the following activities: ACCESSORY CHECKLIST
a. Storage of non-biodegradable/recyclable waste Waste bins / carts / trolleys 3 yellow
before being transfered to Material Recovery Facility Exhaust fan 1 above door
or before being subjected for recycling

People Involved: FURNITURE AND


QUANTITY REMARKS
2 x Janitors FIXTURE CHECKLIST

Planning Relationships: ADDITIONAL EQUIPMENT &


QUANTITY REMARKS
a. Within Central Waste Storage Facility ENGINEERING TERMINALS
Outlet, 10A,2P,240V, duplex 4 grounding type,
universal slots
Outlet, 10A,2P,240V, single 1 emergency light
Smoke detector 1

842
Hospital: Department of Health
ROOM DATA SHEET
250-Bed (Level 3) HEALTH FACILITY
DEVELOPMENT BUREAU
Updated Reference: Department: Room Title: Reference Sheet Number:
250B-CWS-RDS-05B
NON-BIODEGRADABLE/
April 2016 CENTRAL WASTE STORAGE RECYLABLE WASTE
TECHNICAL DESIGN DATA:
ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA

AIR LIGHTING AND VISUAL

Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150

Room temperature ambient Night illumination (LUX) NA

Mechanical ventilation Task illumination (LUX) NA

Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY

Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY

Pressure: Emergency light essential:desirable:UNNECESSARY

Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary

Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY

% Dust filtration NA Privacy essential:desirable:UNNECESSARY

Humidity NA Black out essential:desirable:UNNECESSARY

Cooling load (TR) NA

SOUND SAFETY

Acceptable sound level (db) 70 Accessible hot surface: NA

Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA

Quality which cannot be tonal impact Domestic hot water: NA

tolerated Maximum temperature (°C) NA

Access limit waste management staff

Fire risk LOW: medium: high

Other risks NA

843
NA

844
MANUAL on TECHNICAL GUIDELINES for
HOSPITAL PLANNING and DESIGN
250-BED HOSPITAL
(LEVEL 3)

VOLUME 4
APPENDICES

First Edition
DEPARTMENT OF HEALTH
Manila
2017

845
VOLUME 4
APPENDICES

TABLE OF CONTENTS

PAGE
APPENDIX A - EXISTING HOSPITALS 849

APPENDIX B - NEW CLASSIFICATION of 850


HOSPITALS

APPENDIX C - PATIENT CARE AREAS 854

APPENDIX D - CATEGORIES and SOURCES of 855


HOSPITAL HEALTHCARE
WASTE

847
APPENDIX A

EXISTING HOSPITALS

The devolution of health services to local government units (LGUs), brought


about by the Local Government Code of 1991, transferred among others, the
provision, management and maintenance of government health facilities
(provincial hospitals, district and municipal hospitals, RHUs, BHS) at different
levels of LGUs. Currently, the total number of hospitals is 729 of various types
such as special, specialty, medical centers, regional, provincial, district,
municipal and medicare community hospitals, totalling 49,538 hospital beds.
Majority of these existing hospitals are in Region 4-A (CALABARZON) but
the total number of beds are concentrated in the National Capital Region /
Metro Manila area. However, private hospitals make up for this inequity of
health resource distribution with 1,202 hospitals, functional and provided with
the latest medical equipment, totalling about 43,645 beds scattered all over the
country.

(sources : DOH – Health Facility Development Bureau, formerly NCHFD; and


DOH – Health Services and Facilities Regulatory Bureau, formerly BHFS)

849
APPENDIX B

NEW CLASSIFICATION OF HOSPITALS

Department of Health
Administrative Order No. 2012-0012
“Rules and Regulations Governing the New Classification of Hospitals and
Other Health Facilities in the Philippines”

and

R.A. 4226
“Hospital Licensure Act”

Based on the above, hospitals shall be classified as follows :

a. ACCORDING TO OWNERSHIP
1. Government Hospital – created by law. A government health
facility may be under the national government, DOH, Local
Government Unit (LGU), Department of National Defense (DND),
Philippine National Police (PNP), Department of Justice (DOJ),
State Universities and Colleges (SUCs), Government Owned and
Controlled Corporations (GOCC) and others.
2. Private Hospital – owned, established and operated with funds
through donation, principal, investment or other means by any
individual, corporation, association or organization. A private
health facility may be a single proprietorship, partnership,
corporation, cooperative, foundation, religious, non-government
organization and others.
b. ACCORDING TO SCOPE OF SERVICES
1. General – a hospital that provides services for all kinds of
illnesses, diseases, injuries or deformities. A general hospital shall
provide medical and surgical care to the sick and injured,
maternity, newborn and childcare. It shall be equipped with the
service capabilities needed to support board certified / eligible
medical specialties and other licensed physicians rendering
services in, but not limited to, the following :
a) Clinical Services
1) Family Medicine
2) Pediatrics
3) Internal Medicine

850
4) Obstetrics and Gynecology
5) Surgery
b) Emergency Services
c) Outpatient Services
d) Ancillary and Support Services such as, Clinical
Laboratory, Imaging Facility and Pharmacy
2. Specialty – a hospital that specializes in a particular disease or
condition or in one type of patient. A specialized hospital may be
devoted to treatment of any of the following :
a) Treatment of a particular type of illness or for a particular
condition requiring a range of treatment
Examples : Philippine Orthopedic Center, National
Center for Mental Health, San Lazaro
Hospital, a hospital dedicated to the treatment
of cancer
b) Treatment of patients suffering from diseases of a
particular organ or group of organs
Examples : Lung Center of the Philippines, Philippine
Heart Center, National Kidney and
Transplant Institute, a hospital dedicated to
the treatment of eye disorders
c) Treatment of patients belonging to a particular group such
as children, women, elderly, and others.
Examples : Philippine Children’s Hospital, Dr. Jose
Fabella Memorial Hospital
c. ACCORDING TO FUNCTIONAL CAPACITY
1. General Hospital
a) Level 1
A Level 1 hospital shall have as a minimum the services
stipulated under Rule V.B.1.b.1. of this Order, including,
but not limited to, the following:
1) A staff of qualified medical, allied medical and
administrative personnel headed by a physician
duly licensed by the Professional Regulatory
Commission (PRC);

851
2) Bed space for its authorized bed capacity in
accordance with DOH Guidelines in the Planning
and Design of Hospitals;
3) An Operating Room with standard equipment and
provision for sterilization of equipment and
supplies in accordance with:
a. DOH Reference Plan in the Planning and
Design of an Operating Room/Theater (Annex
A)
b. DOH Guidelines on Cleaning, Disinfection
and Sterilization of Reusable Medical Devices
in Hospital Facilities in the Philippines
(Annex B)
4) A Post-Operative Recovery Room;
5) Maternity facilities, consisting of ward(s), room(s),
a Delivery Room, exclusively for maternity
patients and newborns;
6) Isolation facilities with proper procedures for the
care and control of infectious and communicable
diseases as well as for the prevention of cross
infections;
7) A separate dental section/clinic;
8) Provision for blood station;
9) A DOH licensed Secondary Clinical Laboratory
with the services of a consulting Pathologist;
10) A DOH licensed Level 1 Imaging Facility with the
services of a consulting Radiologist; and
11) A DOH licensed Pharmacy.
b) Level 2
A Level 2 hospital shall have as a minimum, all of Level 1
capacity, including, but not limited to, the following:
1) An organized staff of qualified and competent
personnel with Chief of Hospital/Medical Director
and appropriate board certified Clinical
Department Heads;
2) Departmentalized and equipped with the service
capabilities needed to support board
certified/eligible medical specialists and other
licensed physicians rendering services in the
specialties of Medicine, Pediatrics, Obstetrics and
Gynecology, Surgery, their subspecialties and
ancillary services;

852
3) Provision for general ICU (Intensive Care Unit) for
critically ill patients;
4) Provision for NICU (Neonatal Intensive Care
Unit);
5) Provision for HRPU (High-Risk Pregnancy Unit);
6) Provision for respiratory therapy services;
7) A DOH licensed Tertiary Clinical Laboratory;
8) A DOH licensed Level 2 Imaging Facility with
Mobile X-Ray inside the institution and with
capability for contrast examinations.
c) Level 3
A Level 3 hospital shall have as a minimum, all of Level 2
capacity, including, but not limited to, the following:
1) Teaching and/or training hospital with accredited
residency training program for physicians in the
four (4) major specialties namely: Medicine,
Pediatrics, Obstetrics and Gynecology, and
Surgery;
2) Provision for Physical Medicine and Rehabilitation
Unit;
3) Provision for Ambulatory Surgical Unit;
4) Provision for Dialysis facility;
5) Provision for Blood Bank;
6) A DOH licensed Tertiary Clinical Laboratory with
standard equipment/reagents/supplies necessary for
the performance of histopathology examinations;
7) A DOH licensed Level 3 Imaging facility with
interventional Radiology.
2. Specialty Hospital (refer to Rule V.B.1.b.2. of this Order)
3. Trauma Capability of Hospitals
The trauma capability of hospitals shall be assessed in accordance
with the guidelines formulated by the Philippine College of
Surgeons (PCS).
a) Trauma-Capable Facility – a DOH licensed hospital
designated as a Trauma Center.
b) Trauma-Receiving Facility – a DOH licensed hospital
within the trauma service area which received trauma
patients for transport to the point of care or a trauma center.

853
APPENDIX C

PATIENT CARE AREAS

Patient care areas, classified as follows, shall be those areas designated by the
governing body of the health care facility in accordance with the type of patient
care anticipated:

1. General Care Areas are patient bedrooms, examining rooms, treatment


rooms, clinics and similar areas in which it is intended that the patient
shall come in contact with ordinary appliances such as a nurse call
system, electrical beds, examining lamps, telephone and entertainment
devices. In such areas, it may also be intended that patients be connected
to electromedical devices (such as heating pads, electrocardiographs,
drainage pumps, monitors, otoscope, opthalmoscopes, peripheral
intravenous lines).
2. Critical Care Areas are those special care units, intensive care units,
coronary care units, angiography, laboratories, cardiac catheterization
laboratories, delivery rooms, operating rooms and similar areas in which
patients are intended to be subjected to invasive procedures and
connected to line-operated, electromedical devices.
3. Wet Locations are patient care areas that are normally subject to wet
conditions while patients are present. These include standing fluids on the
floor or drenching of the work area, either of which condition is intimate
to the patient or staff. Routing housekeeping procedures and incidental
spillage on liquids do not define a wet location.

(source : Philippine Electrical Code, Article 5.17.1.2.)

854
APPENDIX D

CATEGORIES and SOURCES of HOSPITAL HEALTHCARE WASTE

“Health care Waste” (HCW) includes all the solid and liquid waste generated
as a result of any of the following :

 Diagnosis, treatment or immunization of human beings;


 Research pertaining to the above activities;
 Research using laboratory animals for the improvement of human health;
 Production or testing of biologicals; and
 Other activities performed by the health care facility

“Healthcare Facilities” (HCF), for this purpose, are public, private and non-
governmental institutions/facilities that contribute to the improvement of the
health status of an individual.

Categories of Healthcare Waste

A. Infectious
- All waste suspected to contain pathogens (or their toxins) in sufficient
concentration to cause diseases to a potential host.
- Discarded materials or equipment used for diagnosis, treatment and
prevention of disease of patients with infectious disease.
- Highly infectious waste include microbial cultures and stocks of
highly infectious agents from Medical Analysis Laboratories and
biofluids from patients with highly infectious diseases (these require
disinfection at source)
Examples : Solid wastes from patients with infectious disease (e.g.,
dressings, swabs, blood bag, urine bag, sputum cup); Liquid
wastes from patients with infectious disease (e.g., feces,
urine, blood or other body secretions); Food wastes (liquid
or solid) of patients with highly infectious disease.
B. Sharps
- Items that can cause cuts or puncture wounds.
Examples : Used or expired sharps (e.g., hypodermic, intravenous or
other needles, auto-disable syringes, syringes with attached
needles, infusion sets, scalpels, pipettes, knives, blades,
broken glass, wet ampoules); Except syringes and needles
used for antineoplastic purposes

855
C. Pathological and Anatomical
- Refers to tissue sections and body material derived from biopsies or
surgical procedures that are then examined in the laboratory.
- Anatomical waste is a subgroup of pathological waste. This type of
waste refers to recognizable human body parts such as amputated
limbs, etc.
Examples : Placenta, internal organs, tissues used for diagnostic
procedures such as biopsy, blood, fetus; Amputated body
parts like legs.
D. Pharmaceutical
- Refers to expired, spilt and contaminated pharmaceutical products,
drugs and vaccines. Also refers to discarded items used in handling
pharmaceuticals.
- Pharmaceuticals wastes include antineoplastic, cytotoxic, and
genotoxic waste. Drugs usually used in oncology (antineoplastic
drugs) or radiotherapy units have a high hazardous mutagenic or
cytotoxic effect.
Examples : Empty vials, bottles, connective tubing; Medical supplies
and containers of cytotoxic drugs or chemicals
E. Chemical
- Discarded chemicals (solid, liquid, or gaseous) generated during
disinfecting and sterilizing procedures
- Chemical wastes can be further classified into corrosive, reactive,
toxic and flammable
- Chemical wastes also include wastes with high content of heavy
metals and their derivatives
Examples : Laboratory reagents, film developer, disinfectants and
soaking solutions, solvents; Concentrated ammonia
solutions, concentrated hydrogen peroxide chlorine, silver
nitrate; Cadmium, mercury from broken thermometers,
sphygmomanometers
F. Radioactive
- Wastes exposed to radionuclide. Residues from shipment of
radioactive materials and unwanted solution of radionuclide intended
for diagnostic or therapeutic use.

856
- Liquids, gas and solids contaminated with radionuclide whose
ionizing radiations have genotoxic effects.
Examples : Cobalt (60 Co), Technetium (99 Tc), Iodine (131 I)), and
Iridium (192 Ir); Contaminated waste, patient’s excretion
and all materials used by patients exposed with radionuclide
within 48 hours
G. Non-Hazardous or General
- Waste that has not been in contact with communicable or infectious
agents, hazardous chemicals or radioactive substances, and does not
pose a hazard.
Examples : Paper, cardboard, empty bottle, tetra pack, scrap material,
pressurized containers, office waste, food waste and other
materials of patients with non-communicable disease, X-Ray
plates.

(source : DOH Manual on Healthcare Waste Management – Third Edition)

857
REFERENCES

 Manual on Technical Guidelines for Hospitals and Health Facilities


Planning and Design 100-Bed Hospital. Department of Health, Manila.
1994.
 Signage Systems Manual for Hospitals and Offices. Department of
Health, Manila. 1994.
 Healthcare Waste Management Manual 3rd Edition. Department of
Health, Manila. 2011.
 The Fire Code of the Philippines and its Implementing Rules and
Regulations RA 9514. Bureau of Fire Protection, Manila. 2009.
 National Building Code of the Philippines and its Implementing Rules
and Regulations PD 1096. Department of Public Works and Highways.
2005.
 The Law to Enhance Mobility of Disabled Persons BP 344. 1983.
 DOH Administrative Order 2010-0036 : Universal Health Care for All
Filipinos “Kalusugang Pangkalahatan”
 DOH Administrative Order No. 2012-0012 : Rules and Regulations
Governing the New Classification of Hospitals and Other Health
Facilities in the Philippines
 PhilHealth Benchbook for Quality Assurance in Healthcare. 2006.
 Safe Hospitals in Emergencies and Disasters, Philippine Indicators.
Department of Health, Manila. 2011.

CROSS-REFERENCES

 Manual for Medical Social Workers 5th Edition. Department of Health,


Manila. 2010.
 Manual of Standards and Guidelines on the Management of Hospital
Emergency. Department of Health, Manila. 2010.
 Hospital Nursing Service Administration Manual. Department of Health,
Manila. 2010.
 Hospital Nutrition and Dietetics Service Management Manual.
Department of Health, Manila. 2010.
 Hospital Information Management Systems Manual. Department of
Health, Manila. 2010.
 Hospital Property and Supply Management Manual. Department of
Health, Manila. 2010.
 National Standards Infection Control for Healthcare Facilities Revised
Edition. Department of Health, Manila. 2010.
 Manual on Standards on Quality Management of the Administrative and
Finance Service for Hospitals. Department of Health, Manila. 2008.

859