Professional Documents
Culture Documents
Overcurrent Relay Setting & Coordination For A Power Transformer
Overcurrent Relay Setting & Coordination For A Power Transformer
Design No. 1: In the Single-Line Diagram shown below, fault currents and
CT Ratios are already indicated to ease the demonstration on how to set and
coordinate overcurrent protective devices.
500 MVAsc
U1
Bus1 8.4kA
34.5 kV
CT1 R1
200/5 50/51
T1
7.5 MVA
DS 34.5/13.8 kV
7 %Z
CT2 R2
400/5 50/51
3.7kA
Bus2
13.8 kV
IFL-L = 3.2KA
1
Solution:
= 4.9 amp
SELECT TD = 3, CO-11
= (2 ~ 3) 126 (5/200)
2
Theory to Remember in setting Time Dial:
3
Referring from the relay manufacturer’s curve;
= 5.28
3.2.Instantaneous Setting
64.75 amp
SELECT : 65 amp
4
4. OTHER USEFUL INFORMATIONS ON THE OVERCURRENT PROTECTION
OF TRANSFORMER CIRCUIT
5
2. When to use a resistance grounded delta-wye system?
Delta-Wye systems are usually resistance grounded when the low-voltage side
is rated at medium voltage below 13.8kV. The aim is to limit the line-to-ground
fault current to a value below the secondary full load rating of the transformer
so that a line-up of fused contactors can be used instead of the more expensive
circuit breakers.
THINGS TO REMEMBER
6
7
C U R R EN T IN A M P S X 1 0 0 @ 1 3 8 0 0 V O L TS
1 3 5 10 30 50 100 300 500 1,000 3,000 5,000 10,000
1,000 1,000
FLA
R2
West. (ABB) 500 MVAsc
500 CO 11 U1 500
CT 400/ 5
Tap =5.00 ( 4 - 12)
300 Time Dial =3.000 300
3 x Tap =2.19 sec
Bus1
R1 34.5 kV
West. (ABB)
100 CO 11 100
CT 200/ 5
Tap =7.00 ( 4 - 12)
Time Dial =4.000 CT1 R1
50 3 x Tap =2.93 sec 50
200/5 50/51
Inst = 65.0 (20 - 80)
30 30
T1
10 7.5 MVA 10
DS 34.5/13.8 kV
T1
7 %Z
7500 KVA 7.00 %Z
5 Delta-Wye Solid Grd 5
SECONDS
SECONDS
1 1
B u s2
13.8 kV
.5 .5
IFL-L = 3.2KA
.3 .3
.1 .1
Inrush
.05 .05
IF 13.8KV
.03 .03
IF 34.5KV
IF L-L
.01 .01
1 3 5 10 30 50 100 300 500 1,000 3,000 5,000 10,000
C U R R EN T IN A M P S X 1 0 0 @ 1 3 8 0 0 V O L TS
A P S TC , I N C . TIM E C U R R EN T C U R V ES TC C 1
8
9