TRANSMISSION POWER DIVISION

TRANSMISSION COMMISSIONING DEPARTMENT


TP/TCD/FPS/I/MKE/ * Ground Floor Fire Detection and Alarm system Cables Installation Verification Issue.1/ Rev.0

Substation Name SCADA Name


Contract No. Manufacturer
Contractor Visit number
Consultant Date

Start Arrival Supv P Supv S Supv F Supv D = (TF-TS)


Contractor:
Consultant:
DEWA:

Sl.No Description Reference (Yes / No/NA ) Remarks

1.0 Fire Resistant/fire rated cable & accessories material verification is cleared Signed MV Document

2.0 Validate the following for the fire rated (FR) cables from devices to device:- -

2.1 Zero damage -

2.2 Cables clips/saddles provided in regular intervals from device to device. OEM procedure
Indoor - Plastic & Outdoor -
2.3 Cables identification tag at devices end
Stainless Steel
2.4 Minimum bending radius OEM procedure

2.5 No power cables along with fire resistant/fire rated cable -

2.6 Cable gland provided at devices. OEM procedure

3.0 Location of the devices DDCMS ID 418 & 515

4.0 Validate the availability of conduit pipe for the following places:- -

4.1 Floor void area galvanized iron (G.I) pipe

4.2 Wall crossing galvanized iron (G.I) pipe

4.3 Ceiling crossing galvanized iron (G.I) pipe

4.4 Floor crossing galvanized iron (G.I) pipe

5.0 Validate the cover fixed for cable trunking By screw/Clips

6.0 Unused gland holes closed by dummy covers for device enclosures -

7.0 Validate the following sleeves closed by fire sealant:- -

7.1 Wall -

7.2 Floor -

7.3 Ceiling -

8.0 No earthing of fire rated cable at the devices/cabinets/loop IN/OUT connections OEM procedure

9.0 Fire rated cables are wounded and supported at celling/ floor void Extended cables

INSTALLATION RECOMMENDATION: To be filled by DEWA.

☐ Can proceed to Cable IR test. ☐ Rejected, Re-site visit required to clear the pending points.

Comments if Any:-

EXECUTED BY: VERIFIED BY: VERIFIED BY:

☐ Contractor ☐ Manufacturer Consultant DEWA - TCD

© DEWA/TP/TCD
TRANSMISSION POWER DIVISION
TRANSMISSION COMMISSIONING DEPARTMENT
TP/TCD/FPS/I/MKE/ * Basement Floor Fire Detection and Alarm system Cables Installation Verification Issue.1/ Rev.0

Substation Name SCADA Name


Contract No. Manufacturer
Contractor Visit number
Consultant Date

Start Arrival Supv P Supv S Supv F Supv D = (TF-TS)


Contractor:
Consultant:
DEWA:

Sl.No Description Reference (Yes / No/NA ) Remarks

1.0 Fire Resistant/fire rated cable & accessories material verification is cleared Signed MV Document

2.0 Validate the following for the fire rated (FR) cables from devices to device:- -

2.1 Zero damage -

2.2 Cables clips/saddles provided in regular intervals from device to device. OEM procedure
Indoor - Plastic/Stainless
2.3 Cables identification tag at devices end
Steel & Outdoor - Stainless
2.4 Minimum bending radius OEM procedure

2.5 No power cables along with fire resistant/fire rated cable -

2.6 Cable gland provided at devices. OEM procedure

3.0 Location of the devices DDCMS ID 418 & 515

4.0 Validate the availability of conduit pipe for the following places:- -

4.1 Floor void area galvanized iron (G.I) pipe

4.2 Wall crossing galvanized iron (G.I) pipe

4.3 Ceiling crossing galvanized iron (G.I) pipe

4.4 Floor crossing galvanized iron (G.I) pipe

5.0 Validate the cover fixed for cable trunking By screw/Clips

6.0 Unused gland holes closed by dummy covers for device enclosures -

7.0 Validate the following sleeves closed by fire sealant:- -

7.1 Wall -

7.2 Floor -

7.3 Ceiling -

8.0 No earthing of fire rated cable at the devices/cabinets/loop IN/OUT connections OEM procedure

9.0 Fire rated cables are wounded and supported at celling/ floor void Extended cables

INSTALLATION RECOMMENDATION: To be filled by DEWA.

☐ Can proceed to Cable IR test. ☐ Rejected, Re-site visit required to clear the pending points.

Comments if Any:-

EXECUTED BY: VERIFIED BY: VERIFIED BY:

☐ Contractor ☐ Manufacturer Consultant DEWA - TCD

© DEWA/TP/TCD
TRANSMISSION POWER DIVISION
TRANSMISSION COMMISSIONING DEPARTMENT
TP/TCD/FPS/I/MKE/ * First Floor Fire Detection and Alarm system Cables Installation Verification Issue.1/ Rev.0

Substation Name SCADA Name


Contract No. Manufacturer
Contractor Visit number
Consultant Date

Start Arrival Supv P Supv S Supv F Supv D = (TF-TS)


Contractor:
Consultant:
DEWA:

Sl.No Description Reference (Yes / No/NA ) Remarks

1.0 Fire Resistant/fire rated cable & accessories material verification is cleared Signed MV Document

2.0 Validate the following for the fire rated (FR) cables from devices to device:- -

2.1 Zero damage -

2.2 Cables clips/saddles provided in regular intervals from device to device. OEM procedure
Indoor - Plastic/Stainless
2.3 Cables identification tag at devices end
Steel & Outdoor - Stainless
2.4 Minimum bending radius OEM procedure

2.5 No power cables along with fire resistant/fire rated cable -

2.6 Cable gland provided at devices. OEM procedure

3.0 Location of the devices DDCMS ID 418 & 515

4.0 Validate the availability of conduit pipe for the following places:- -

4.1 Floor void area galvanized iron (G.I) pipe

4.2 Wall crossing galvanized iron (G.I) pipe

4.3 Ceiling crossing galvanized iron (G.I) pipe

4.4 Floor crossing galvanized iron (G.I) pipe

5.0 Validate the cover fixed for cable trunking By screw/Clips

6.0 Unused gland holes closed by dummy covers for device enclosures -

7.0 Validate the following sleeves closed by fire sealant:- -

7.1 Wall -

7.2 Floor -

7.3 Ceiling -

8.0 No earthing of fire rated cable at the devices/cabinets/loop IN/OUT connections OEM procedure

9.0 Fire rated cables are wounded and supported at celling/ floor void Extended cables

INSTALLATION RECOMMENDATION: To be filled by DEWA.

☐ Can proceed to Cable IR test. ☐ Rejected, Re-site visit required to clear the pending points.

Comments if Any:-

EXECUTED BY: VERIFIED BY: VERIFIED BY:

☐ Contractor ☐ Manufacturer Consultant DEWA - TCD

© DEWA/TP/TCD
TRANSMISSION POWER DIVISION
TRANSMISSION COMMISSIONING DEPARTMENT
TP/TCD/FPS/I/MKE/ * Fire Pump Room Fire Detection and Alarm system Cables Installation Verification Issue.1/ Rev.0

Substation Name SCADA Name


Contract No. Manufacturer
Contractor Visit number
Consultant Date

Start Arrival Supv P Supv S Supv F Supv D = (TF-TS)


Contractor:
Consultant:
DEWA:

Sl.No Description Reference (Yes / No/NA ) Remarks

1.0 Pump room pre-installation verification check list is cleared TP/TCD/FPS/I/MKE/ *

2.0 Fire Resistant/fire rated cable & accessories material verification is cleared Signed MV Document

3.0 Validate the following for the fire Rated (FR) cables from devices to device:- -

3.1 Zero damage -

3.2 Cables clips/saddles provided in regular intervals from device to device. OEM procedure
Indoor - Plastic/Stainless
3.3 Cables identification tag at devices end
Steel & Outdoor - Stainless
3.4 No power cables along with fire resistant/fire rated cable OEM procedure

3.5 No power cables along with fire Resistant/fire rated cable -

3.6 Cable gland provided at devices. OEM procedure

4.0 Location of the devices DDCMS ID 418 & 515

5.0 Validate the availability of conduit pipe for the following places:- -

5.1 Floor void area galvanized iron (G.I) pipe

5.2 Wall crossing galvanized iron (G.I) pipe

5.3 Ceiling crossing galvanized iron (G.I) pipe

5.4 Floor crossing galvanized iron (G.I) pipe

6.0 Validate the cover fixed for cable trunking By screw/Clips

7.0 Unused gland holes closed by dummy covers for device enclosures -

8.0 Validate the following sleeves closed by fire sealant:- -

8.1 Wall -

8.2 Floor -

8.3 Ceiling -

9.0 No earthing of fire rated cable at the devices/cabinets/loop IN/OUT connections OEM procedure

10.0 Fire rated cables are wounded and supported at celling/ floor void Extended cables

INSTALLATION RECOMMENDATION: To be filled by DEWA.

☐ Can proceed to Cable IR test. ☐ Rejected, Re-site visit required to clear the pending points.

Comments if Any:-

EXECUTED BY: VERIFIED BY: VERIFIED BY:

☐ Contractor ☐ Manufacturer Consultant DEWA - TCD

© DEWA/TP/TCD
TRANSMISSION POWER DIVISION
TRANSMISSION COMMISSIONING DEPARTMENT
TP/TCD/FPS/I/MKE/ * Security Room Fire Detection and Alarm Cables Installation Verification Issue.1/ Rev.0

Substation Name SCADA Name


Contract No. Manufacturer
Contractor Visit number
Consultant Date

Start Arrival Supv P Supv S Supv F Supv D = (TF-TS)


Contractor:
Consultant:
DEWA:

Sl.No Description Reference (Yes / No/NA ) Remarks

1.0 Security room pre-installation verification check list is cleared TP/TCD/FPS/I/MKE/ *

2.0 Fire Resistant/fire rated cable & accessories material verification is cleared Signed MV Document

3.0 Validate the following for the fire Rated (FR) cables from devices to device:- -

3.1 Zero damage -

3.2 Cables clips/saddles provided in regular intervals from device to device. OEM procedure
Indoor - Plastic/Stainless
3.3 Cables identification tag at devices end
Steel & Outdoor - Stainless
3.4 No power cables along with fire resistant/fire rated cable OEM procedure

3.5 No power cables along with Fire Resistant/fire rated cable -

3.6 Cable gland provided at devices. OEM procedure

4.0 Location of the devices DDCMS ID 418 & 515

5.0 Validate the availability of conduit pipe for the following places:- -

5.1 Floor void area galvanized iron (G.I) pipe

5.2 Wall crossing galvanized iron (G.I) pipe

5.3 Ceiling crossing galvanized iron (G.I) pipe

5.4 Floor crossing galvanized iron (G.I) pipe

6.0 Validate the cover fixed for cable trunking By screw/Clips

7.0 Unused gland holes closed by dummy covers for device enclosures -

8.0 Validate the following sleeves closed by fire sealant:- -

8.1 Wall -

8.2 Floor -

8.3 Ceiling -

9.0 No earthing of fire rated cable at the devices/cabinets/loop IN/OUT connections OEM procedure

10.0 Fire rated cables are wounded and supported at celling/ floor void Extended cables

INSTALLATION RECOMMENDATION: To be filled by DEWA.

☐ Can proceed to Cable IR test. ☐ Rejected, Re-site visit required to clear the pending points.

Comments if Any:-

EXECUTED BY: VERIFIED BY: VERIFIED BY:

☐ Contractor ☐ Manufacturer Consultant DEWA - TCD