D D
18'-421"
D
A A
8'-7"
A
50'-6"
C C A
421"
22'-721"
4'-10"
16'-9" 5'-9" 6'-9" 4' 6'-9"
A A
5'-521"
B B A A A A
C
A
10'-6"
B
10'-9"
B A A C
A
5'-1" 7'-10" A 12'-1021"
9'-9" C
721"
B
12'-1121"
4'-121"
A
6'-1121"
A 1'-7"
B A B
6'-9"
C 14'-3" 7' 3' 3' 5'
D
A
C
105'-1" B B B
5'-7"
B A A C A
10'-7"
A
9'-9"
B
B B
5'-121"
B B B
B 2'-8" C
D
B
B B B A
7'-121"
6'-9"
A A
15'-2"
B B
6'-9"
25'
5'-1"
A C
C B B
6'-821" B
9'-621"
9'-1121"
A B B B A
1'-5"
NOTE:-
1. FOUNDATION HAS BEEN DESIGNED FOR DOUBLE STORIES USING 0.75 TSF BEARING CAPACITY OF SOIL
B B
166°
AS PER GEOTECHNICAL INVESTIGATION. B
2. USE CONCRETE HAVING MINIMUM CYLINDER STRENGTH OF 3,000 PSI FOR STRUCTURAL
MEMBERS AS 28 DAYS STRENGTH. A
4'-9"
3. USE DEFORMED STEEL HAVING MINIMUM YIELD STRENGTH OF 60,000 PSI AS PER ASTM 615
10'-6"
4. CONCRETE COVER
I. FOUNDATION
BOTTOM = 1-1/2" 6'-7"
D B B B B
TOP = 3"
8'-421"
10'-1"
SIDES = 3"
A B
II. COLUMN = 1-1/2" B B
B
5'-421"
III. PLINTH BEAM = 3" 1'-5" C
5. BRICK MASNORY IN SUB STRUCTURE WILL BE 1:6 CEMENT SAND MORTAR AND SUPER C B A
D
10'-121"
STRUCTURE WILL BE 1:5.
6. HORIZONTAL D.P.C. WILL BE 1½" TH. P.C.C (1:2:4) WITH 1 COAT OF HOT BITUMEN 10/20@20 12'-1021" 22'-1021" 5'-6"
A
5'-7"
A
5'-1"
4'-9"
A A A C C C 10
SHEET, 500 GAUGE.
A
7. VERTICAL D.P.C. WILL BE 3/4" THICK VERTICAL D.P.C. 1:3 CEMENT SAND MORTAR WITH HOT
BITUMEN 1 COAT 10/20 @ 20 Lbs/100 Sft & ONE
3'-721"
4'-10"
LAYER OF POLYTHENE SHEET, GAUGE 500. 175°
A A
1'-3"
175°
8. IN 4-1/2" THICK WALLS, A REINFORCEMENT OF 1" WIDE 18 GAUGE HOOP IRON SHALL BE
PLACED IN COURSES NOT MORE THAN 12" APART
AND CONTINUED FOR 9" INTO THE MAIN WALL ON WHICH THE PARTITION WALL ABUTS. IF
THE PARTITION WALL EXCEEDS 20' IN 5' 6'-821" 4'-4" 10'-9" 48' 6'-6" 9'-7" 3'-1021" 3'-1021" 3'-1021" 3'-1021" 4' 3'-11"
LENGTH OR 15' HEIGHT, THE HOOP IRON SHALL BE INTRODUCED AT COURSES NOT MORE
THAN 6" APART.
EXCAVATION PLAN
SCALE:- 1/8" = 1'-0"
3"
PLINTH 2" THICK SAND PLINTH
BEAM 8" THICK SUB-BASE BEAM
1'-6"
1'-6"
1'-6"
1'-6"
COMPACTED EARTH
7"
SLOPE P.L
P.L+1'-6" P.L+1'-6" P.L+1'-6" P.L+1'-6"
6"
/c
1 2"c
1'-6"
1'-6"
1'-6"
1'-6"
# 3@
c
1'-121" 12" "c/
R.L ±0'-0" R.L ±0'-0" R.L ±0'-0" R.L ±0'-0" @ 10
2" THICK P.C.C. 1:2:4 #3
4" THICK CONC. 1:4:8
2'
4"THICK COMPACTED
SAND FILLING 1'-6"
VARIES
VARIES
VARIES
VARIES
COMPACTED EARTH
6"
6"
P.C.C. 1:4:8 F.F.L.
N.S.L N.S.L N.S.L
2' N.S.L
VARIES
#3@10"c/c
VERTICAL
#3@12"c/c
9" 9"
TYPE-A 421"
6"
9" 13½"
4'
4'
4'
4'
N.S.L.
SCALE:- 1/2" = 1'-0" 18" 1'-121"
6"
13½" 9"
6"
6"
22½" 7"
1'-6"
6"
18"
6"
6"
6"
13½"
1'-1021" #4@6"c/c
4" 6"
4" 6"
4" 6"
4" 6"
P.C.C. 1:4:8 P.C.C. 1:4:8 P.C.C. 1:4:8 P.C.C. 1:4:8
2'-6"
6"
6"
6"
6"
1'
#3@6"c/c COMPACTED SAND FILL COMPACTED SAND FILL #4@6"c/c #3@8"c/c 2'-6"
UP TO 95% MODIFIED UP TO 95% MODIFIED
#3@8"c/c PROCTOR DENSITY PROCTOR DENSITY #3@8"c/c #3@10"c/c COMPACTED SAND FILL
4" 3' 4" 4" 4'-6" 4" 4" 2' 4" UP TO 95% MODIFIED
6"
PROCTOR DENSITY
TYPE-D P.C.C (1:4:8)
1' 1'
F.F.L+3'-0" F.F.L+3'-0"
#4@6"c
/c SCHEDULE OF LINTEL BEAMS
6"
BW F.F.L
3"
SPAN W D MK-1 MK-2 MK-3
1'-6"
6"
5"
P.L+1'-6" 2-#4
WIDTH OF MK1
UP TO 3'-0" 6" 2-#4 2-#4 3#8" c/c
1 :2:4 WALL
6"
. C.
P.L+1'-6" R.C
1'
#3@8"
3'
9" WIDTH OF
4:8
. 1: 3'-6" TO 5'-0" 9" 2-#4 2-#6 3#7" c/c MK3
4"
C.C WALL
D
P.
3'
2-#6
3"
9"
9" MK2
1'-6"
WIDTH OF 2-#6 +
7'-6" TO 9'-0" 12" 2-#4 3#6" c/c
SECTION A-A WALL 1-#4 W
4"
4"
P.C.C .1:4:8 P.C.C .1:4:8
SCALE:- 3/4" = 1'-0" #3@6"c/c WIDTH OF
9'-6" TO 12'-0" 15" 2-#4 3-#6 3#5" c/c
6"
1'-6"
4" 1'-6" 4" PLINTH BEAM
RAMP DETAIL SCALE:- 1" = 1'-0" NOTE:-
SCALE:- 3/4" = 1'-0" WHEN SPAN DIFFERENCE TO LOWER SIDE IS EXCESSIVE
INTERPOLATE DEPTH USING SAME STEEL
#3@8"
#3@8"
#3@8"
#3@6"
#3@6"
B3
CB1 #3@8" #3@8"
#3@8" #3@8"
#3@8"
#3@8"
#3@10"
#3@6"
#3@8"
#3@8"
#3@8"
#3@8"
SATIR
#3@8"
#3@8" VOID #3@10" #3@10"
#3@6"
#3@8"
#3@8"
#3@6"
#3@8" #3@8"
#3@6"
4-#4
B2 #3@8"
#3@8"
#3@8"
#3@10"
#3@10"
CB1
#3@6"
#3@8"
#3@8" #3@6"
B2
#3@6"
#3@8"
#3@10"
#3@6"
#3@8"
#3@8" #3@8"
#3@8"
#3@8"
#4@6"
#3@6"
#3@6"
#3@6"
#3@6"
#3@6"
#3@8"
#3@8" #3@6"
#3@6" #3@6" #3@8" #4@8"
CB1
#3@8"
#3@6"
#3@8"
#3@8"
#3@6"
#3@8"
#3@10"
CB1
CB1
#4@6"
#3@8"
#3@8"
CB1 #4@8" #3@10"
#3@10"
TYPICAL
#3@6"
CB1
5'
#3@6" #3@6"
B1 R.C.C PAD
#3@8"
#3@6"
#3@8"
TYPICAL
#4@6"
#3@10"
#3@8"
#3@6"
#3@6"
#3@6"
#3@8"
#3@8" #3@8"
#4@8"
TYPICAL
B5
VOID
5'
B1
B1
B1
B1
#4@6"
#3@6"
#4@6"
#3@6"
#4@6"
#3@6"
#4@6"
#3@6" #3@6"
#3@6"
#3@8"
#3@8"
#3@8" #3@8" #3@8" #3@8"
#4@6"
#3@8"
#3@10"
#3@8" #4@8"
CB1
CB1
"
#3@10"
#3@8
B1
#3@8"
#3@8"
#3@8"
#3@8"
#3@10" #4@6"
#3@6"
#3@8"
#3@6"
CB1
#3@6"
#3@6"
#3@6"
#3@6" #3@6"
#3@8"
#3@8" #3@8"
#3@8"
#3@6"
#3@8"
#3@10"
#4@8"
CB1
#3@6"
#3@8"
GROUND FLOOR
CB1
#3@8" #3@8"
#3@8" #3@8"
REINFORCEMENT PLAN #3@8"
4"
#3@6"
2"
3"
1
3-#4
9"
#3@5"
9"
9"
2" 4-#4
AS PER ARCH. 9"
1'-3"
DWG.
9"
9"
DO NOT REMOVE SHADE DETAIL
SHUTTERING UNTIL
X SLAB IS CASTED 4-#6 2-#6+ 3-#6
B4 B4 2-#4
1'-3" 9" 1'
#3@6"
#3@6"
#3@6"
2-#4
#4@8"
(+)19'-7½" 3-#4
B4
#4@6"
#3@8"c/c
1'-6"
#3@5"c/c
1'-6"
#3@6"
LINTEL LEV.
2-#6
5-#4 TOP 5' LENGTH TYPICAL 3-#6
FOR ALL CORNERS
1'-121"
9"
BEAM B4 BEAM B5
SCALE:- 1" = 1'-0" SCALE:- 1" = 1'-0"
AS PER
9" WALL
2-#4
2-#4
9"
#3@6" #3@8"
9"
2-#6
4-#4
4"
3-#3
421"
3-#3
2'-121"
#3@8"