Professional Documents
Culture Documents
Higth-Voltage DC Conversion
Higth-Voltage DC Conversion
dc Conversion
Boosting Transmission
Capacity in the Grid
By Tayeb Meridji,
Frida Ceja-Gomez,
Jose Restrepo,
and Ramy Azar
T
The electric grid is undergoing a techno
logical transformation due to advances in a number of
fields, including power electronics, photovoltaic cells, wind
turbines, telecommunications, and many others. An increase
in environmental awareness and the need to meet emission
targets implemented throughout the world further drive
grid evolution. These social and technological changes are
leading to a transition in the composition of the power sup
ply, with a reduction in the number of large conventional
thermal and nuclear plants and a proliferation of solar and
wind generation.
It is commonly recognized that, in the future, electrical
energy will come from a combination of distributed and
remote resources. Solar and wind resources needed for util
ity-scale plants typically need to be located far away from
load centers, so it is necessary to transmit bulk renewable
power over large distances. However, rights-of-way for new
power transmission infrastructure are extremely challenging
to secure and permit, bringing the time required between
existing conductors if
they are in good con
dition. In most cases,
however, it will be nec
essary to change the
insulators because
their performance for air pollution under dc voltages is network capabilities. Several experimental dc breakers
inferior compared to their performance under ac volt are under development, but LCC-HVdc is still widely
ages. To minimize outage times, insulator replacement considered for ac-to-dc conversion applications.
can be done before the conversion to dc, while the ac
line remains in operation. Engineering Considerations
✔✔ Locating the converter stations as close as possible to Although the conversion of an existing ac line to dc is an
the existing ac yards: With the widespread use of volt attractive uprating solution, several technical aspects must
age source converter (VSC) high-voltage dc (HVdc) be evaluated to verify the feasibility of the conversion as
technology, it is easier to find a location closer to the well as to select the most suitable implementation.
existing ac yard given that VSC stations have a re
duced footprint compared to their line commutated Pole Configuration
converter (LCC) counterparts. However, this is not One of the challenges of ac-to-dc conversion of transmission
always straightforward because standard half bridge lines is that ac lines have three fully rated phases, which can
VSC configurations generally require that a dc fault be be composed of a bundle of conductors, whereas dc lines are
tripped on the ac side, thereby yielding long recovery designed with two or three conductor configurations and, in
times, which are not necessarily compatible with the ac some cases, use a ground electrode for a neutral return path.
It follows that the mapping of the ac conductors to a dc sys
tem must be studied on a case-by-case basis to determine the
optimal dc configuration, while avoiding modifications to
ac Phase ac Phase ac Phase
a b c the existing structures as much as possible.
ac Phase a ac Phase a
ac Phase b ac Phase b
ac Phase c ac Phase c
Emergency Emergency
ac Phase b ac Phase b
Return Return
systems are lower than those in ac systems. As such, the air Voltage Selection
clearances for dc are determined by examining the lightning As previously discussed, the requirements for dc line insula
performance requirements. Additionally, the air clearances tion are more stringent than for ac lines, so the length of the
for dc systems require a higher margin for high altitudes. existing ac insulators is a defining parameter to select the
At 2,000 m above sea level, the air clearances for an HVdc voltage at which the dc line will operate. To illustrate this
system need to be increased by 25%, as compared to 15% point, this section presents typical calculations for the selec
for a high-voltage ac system. tion of the dc voltage when considering existing ac transmis
DC systems are also more susceptible to pollution because sion lines operating at various voltage levels.
the dc electric field surrounding the insulation attracts Table 1 shows the requirements for dc insulators from
more pollution particles. This issue can be overcome by CIGRE and the International Electrotechnical Commission
the use of composite insulators, which have better pollution (IEC). The last two columns show the selected design value
performance than glass or ceramic insulators for a given in millimeters per kilovolt and in inches per kilovolt.
string length. Table 2 shows the selected dc voltage for each conver
sion, which was calculated based on the existing ac insula
Corona Effect tors’ leakage distance and the light pollution requirements
The losses attributed to the corona effect are similar for both for dc insulators. It should be noted that, if the calculations
ac and dc systems in fair weather conditions. However, rain were done for a system under heavy or extreme pollution, the
and frost cause a large increase in corona losses for ac sys conversion to dc would not be as advantageous because the
tems, whereas the corona losses for dc systems are not as maximum allowed dc voltage would be too low compared to
impacted by these factors. Additionally, dc systems in monop the ac voltage.
olar operation can lead to a surface gradient on the earth wires
that exceeds their corona inception gradient. This can result
in high levels of corona between the pole conductor and earth table 1. The minimum creepage distances
wire, which will have a detrimental impact on the corona per for different pollution levels.
formance of the dc line. However, this effect does not occur in Selected Selected
bipolar operation. CIGRE Design Design
Zone IEC B4-105 Value Value
(Pollution) (mm/kV) (mm/kV) (mm/kV) (in/kV)
Audible Noise
DC lines produce less audible noise compared to ac lines, I Light 27 26–34 30 1.2
mainly because the negative pole’s contribution is practi II Medium 34 32–44 38 1.5
cally negligible, whereas for the ac lines, the contribution III Heavy 43 56 56 2.2
from all three phases must be considered. This means that a IV Extreme 53 70 70 2.8
lower conductor bundle size can be used for a dc line to meet
the same noise requirements when compared to an ac line.
Audible noise will be at its highest under dry conditions for table 2. The dc voltage selection.
dc lines, and it will be at its highest under rain conditions AC Selected
for ac lines due to the effect of space charges. DC corona Voltage Insulator Number of Leakage dc Voltage
discharge generates space charges that reduce the electric (kV) Length Insulators Distance (kV)
field intensity between raindrops and the conductor surface, 138 3 ft, 4.2 in Seven 10 ft, 2.6 in 100
so rain causes a slight reduction in audible noise produced (1.02 m) (3.1 m)
by dc lines. AC corona discharge does not cause constant 230 6 ft, 8.5 in 14 20 ft, 5.3 in 200
space charges around the conductor, and the presence of (2.05 m) (6.2 m)
raindrops in the ac electric field leads to more stream dis 345 10 ft, 6.5 in 22 32 ft, 1.4 in 320
charges, resulting in an increase of audible noise. This dif (3.2 m) (9.8 m)
ference must be taken into account when selecting the dc 500 13 ft, 4.9 in 28 40 ft, 10.5 in 400
(4.1 m) (12.5 m)
conductor bundle size.
(188 MW)
38% selection. For the purpose of this
↓
Planning
102
Considerations
Load 1 101 This section examines system
Send planning considerations, with the
← 100% objective of identifying candidate
(500 MW) ac transmission lines that could
645 MW ← 100% benefit from an ac-to-dc conver
(500 MW)
1,500 MW sion. The thermal limit of an in
230 kV dividual circuit is not the only
Outaged Line consideration when identifying
355 MW ← 100%
103 (500 MW) the power transfer capability of a
230 kV
Load 2 given corridor, flow gate, or path.
The transmission capacity must
be assessed under outage condi
tions as well.
855 MW When considering the N-1 cri
Note: teria, the power transfer increase
230 kV
Line flows are shown as follows: % loading (MW loading).
for a given path also depends on
the parallel paths. This is illus
figure 10. Sample system 1 following ac-to-dc line conversion. trated in Figure 9, which shows
Proposed Ranking of
Conversion Options
figure 13. Sample system 3 with multiterminal solution. in a Large System
It is clear that an ac-to-dc line con
version can provide a significant
increase in the system operating
limit, which makes it an attractive
Bus 17 solution for large systems experienc
30 Bus 18 Bus 21 Bus 22 ing congestion. However, the system
32 33 38 planner will be faced with several
31
Bus 23 potential solutions and options.
28 29 34 36 The authors propose a meth
35 37
odology to rank the candidate
Bus 16 transmission lines for conver
Bus 19 Bus 20
22 sion based on their impact on
230 kV 24
25 23 Bus 14 21 Bus 13 the system power flow in steady
26
Bus 15 state. The proposed line-ranking
18 factor is calculated by consider
ing the sensitivity of the power
27 20
19 flow through the overloaded ele
Bus 24 Bus 11 Bus 12 ment to changes in the power flow
in any other given line, under
the most critical contingencies.
16 A high sensitivity indicates that
7 14 15 17
the changes in the power f low
Bus 10 Bus 6
Bus 3 6 Bus 9 Cable of a specific line would have the
10 highest impact on controlling the
8 Bus 5 power flow through an overloaded
9 13 Bus 8
138 kV Bus 4 line or path.
12
2 3 5
4
11
This ranking methodology is
Cable
explained in Figure 14 using the
1 Bus 7
Bus 1 Bus 2 IEEE 24-bus reliability test system.
For the outage of the 230-kV line
27, the limiting element is identi
Candidate Lines for ac–dc Line Conversion fied to be line 19. Therefore, the
distribution factors for each of
figure 14. The candidate lines for ac-to-dc conversion in the IEEE 24-bus reliability the system lines with respect to
test system. line 19 must be calculated under