R2KA 34 /20
0476
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
SUMMARY
SUMMARY
INTRODUCTION 4
1. INSTALLER SECTION 7
1.1. INSTALLATION 8
1.1.1. GENERAL INSTALLATION WARNINGS 8
1.1.2. BOILER LOCATION ENVIRONMENTAL REQUIREMENTS 8
1.1.3. REFERENCE LEGISLATION 9
1.1.4. UNPACKING 10
1.1.5. OVERALL DIMENSIONS 11
1.1.6. JIG 11
1.1.7. POSITIONING AND MINIMAL TECHNICAL SPACES 12
1.1.8. CIRCULATOR PREVALENCE/FLOW DIAGRAM 13
1.1.9. HYDRAULIC CONNECTION 14
1.1.10. D.H.W. CIRCULATING LOOP 15
1.1.11. SYSTEM FILLING 16
1.1.12. FILLING THE CONDENSATE COLLECTION SIPHON 17
1.1.13. ANTI-FREEZE PROTECTION 18
1.1.14. GAS CONNECTION 19
1.1.15. ELECTRICAL CONNECTION 19
1.1.16. POWER SUPPLY 20
1.1.17. OPTIONAL ELECTRICAL CONNECTIONS 21
1.1.18. FUME EXHAUST FITTINGS 23
1.1.19. INSTALLATION MODES (IN ACCORDANCE WITH UNI 10642) 24
1.1.20. TYPES OF FUME EXHAUST SYSTEMS 26
2.2. MAINTENANCE 43
2.2.7. GENERAL MAINTENANCE WARNINGS 43
2.2.8. TECHNICAL DATA 45
2.2.9. TECHNICAL ASSEMBLY 47
2.2.10. HYDRAULIC BOARD 48
2.2.11. 3-WAY VALVE OPERATION 49
2
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
SUMMARY
3. USER SECTION 61
3.1. USE 62
3.1.1. GENERAL USE WARNINGS 62
3.1.2. CONTROL PANEL 63
3.1.3. DISPLAY ICONS 64
3.1.4. INFO MENU DISPLAY DATA 65
3.1.5. START-UP 66
3.1.6. OPERATING MODE 66
3.1.7. INFORMATIONAL NOTE ON ANTI-FREZZE FUNCTION 67
3.1.8. SYSTEM FILLING 68
3.1.9. FAULT SIGNALLING CODES 69
3.1.10. ACTIVE FUNCTIONS SIGNALLING CODES 71
3.1.11. MAINTENANCE 72
3.1.12. COVER CLEANING 72
3.1.13. DISPOSAL 72
R2KA 34.20_EN
3
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2.
INTRODUCTION
INTRODUCTION
WARNING DANGER
It identifies an information related to a
Before starting any operation it is mandatory to general danger that if not complied with, may cause
read this instruction manual, in relation to the serious personal damage or even death.
activities to be carried out as described in each
relevant section. Proper operation and optimal ATTENTION
performance of the boiler are ensured by strict It identifies an information that if not
compliance with all the instructions given in this complied with may cause small or medium level
manual. lesions to the person or serious deterioration to the
boiler.
The installation, use and maintenance manual is
an integral and essential part of the product and WARNING
must be delivered to the user. It identifies a precaution information that
must be observed in order to avoid damaging the
MANUAL USERS machine or parts of it.
The manual users are all those who install, use MANUAL STORAGE
and maintain the boiler.
The manual must be carefully stored and replaced
The boiler must be used and accessed only by in case of deterioration and/or low legibility.
qualified operators that fully read and understood
the use and maintenance manual, paying particular If you misplace the use and maintenance manual,
attention to the warnings. you can request it from the Technical Support
Centre giving the serial number and model of the
READING AND SYMBOLS OF THE MANUAL boiler indicated on the plate placed on the right
side of its casing.
To ease the understanding of this manual,
recurrent symbols where used, in particular: As an alternative, the use and maintenance manual
can be downloaded free from the on-line site www.
› On the outer margin of the page is placed a radiant.it, accessing the “download” section and _Prefazione_EN
thumb index indicating the type of user to which entering the boiler model.
the instructions in that section address.
2. with the conditions and purposes to which › Performance at 100% Pn and 30% (partial load
assets of the same type are intended. Pn) - D.P.R. 412/93 (regulation implementing
Law 10/91 art. 4, paragraph 4) and subsequent
For more information on the warranty validity, modifications
its duration, the obligations and the exemptions,
please consult the First start-up certificate The gas boilers also comply with the directives
attached to this manual. below:
› the right to modify the tools and relative › PERFORMANCE DIRECTIVE 92/42 CEE
technical documentation without any obligation
to third parties; › ELECTROMAGNETIC COMPATIBILITY
DIRECTIVE 2004/108/CE
› the material and intellectual ownership of
this manual and forbids its distribution and › LOW VOLTAGE DIRECTIVE 2006/95/CEE
_Prefazione_EN
5
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLER SECTION
The installation operations described in this section should
1.1. INSTALLATION
1.1.1. GENERAL INSTALLATION › The device is suitable for use with the type of
WARNINGS gas available by checking the boiler data plate
(placed on the inner side of the front casing.
WARNING
This machine may be used only for the › Make sure that the tubes and couplings are
purpose for which it has been designed: heat water perfectly sealed, without any gas leaks.
to a temperature below boiling point at atmospheric
pressure. Any other use is considered wrong and › Make sure that the grounding system works
dangerous. The manufacturer is excluded from properly.
any contractual or out of contract responsibility for
damage caused to people, animals or property due › Make sure that the electrical systems is
to errors during installation. suitable for the maximum power absorbed by
the equipment, value indicated on the data plate.
WARNING
This boiler should be installed only WARNING
by qualified personnel, having the appropriate Use only original RADIANT optional or kit
technical training in the field for the installation and accessories (including electrical).
maintenance of components of civil and industrial
domestic hot water production and heating plants as
provided by art. 3 of D.M. n°37 dated 22.01.2008. 1.1.2. BOILER LOCATION
ENVIRONMENTAL
WARNING REQUIREMENTS
After having removed the packing, make
sure the equipment is intact. In case of doubt, do not Two devices intended for the same use in the
use the equipment and contact the supplier. same location or in directly communicating
locations, generating a total heat capacity of
BEFORE INSTALLING THE BOILER, THE over 35 kW, represent a heating unit, subjected
INSTALLER MUST MAKE SURE THAT THE to the requirements provided by D.M. n°74 dated
FOLLOWING CONDITIONS ARE MET: 12.04.1996 “Approval of the fire prevention technical 1Avvertenzegeneraliperl'installazione_Localecaldaia_EN
rule for design, manufacture and operation of gas-
› The device is connected to a heating plant and a supplied thermal plants”.
water supply network appropriate for its power
and performance. As the device's heat capacity is lower than 35 kW,
the location housing the boiler must meet the
› The location must be properly vented through provisions laid down by technical standard UNI
an air vent. 7129-3: 2008.
The air vent must be placed at floor level to prevent The capacities of more devices intended for
it from being obstructed, protected by a grid that different uses (e.g. heating and cook top), installed
does not hamper the useful section of passage. in a single housing unit must not be added.
8
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
The device's installation location should be vented
due to the presence of threaded joints on the gas
adduction line (UNI 7129-3: 2008). The location
should be therefore provided with vents as to
ensure air exchange, with output grid in the natural
accumulation area of eventual gas losses.
WARNING
If the temperature in the boiler installation
location goes below -10° centigrades, please fill
the plant with anti-freeze liquid and insert and
electrical resistances kit (see chapter ‘ANTI-FREEZE
PROTECTION’).
9
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
1.1.4. UNPACKING
WARNING
Please unpack the boiler just before
installing it. The Company is not responsible for
the damages caused to the device due to incorrect
storage.
WARNING
The packing elements (cardboard box,
wooden crate, nails, fasteners, plastic bags, expanded
polystyrene, etc.) must be kept out of the reach of
children as they may be dangerous. Therefore they
should be dismantled suitably differentiating them in
accordance with the standards in force.
› Lift the box (fig. 1-C) and remove the guards (fig.
1-D). fig. 1
1 Disimballo_murale_EN
C D
10
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
1.1.5. OVERALL DIMENSIONS
4 25
28 15 3
9 0
22
900
49 0
0 50
1.1.6. JIG
1 Dimensioni_R2KA .20_EN
272
86 78 70 80 102 74
R C G F A
R- RETURN Ø 3/4
C - HOT Ø 1/2
G- GAS Ø 3/4
F- COLD Ø 1/2
A - INFEED Ø 3/4
11
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
1. Trace a line using a spirit level (min. length 25 cm) on the installation wall.
2. place the top of the jig along the traced line respecting the distances of the water connections; then
mark the two points to insert the two knobs or the fasteners, then trace the points for the fume
exhaust fittings;
4. hang the device using the knobs or the bracket and perform the connections.
1Spazitecniciminimieposizionamento_murale_v.2_EN
1 2 3 4
Ø80
Ø125
Ø100
26 358 26
54 302 54
821
785
699
681
49 78 70 80 102 31
fig.2
12
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
WARNING
Make sure, using a level, that the boiler
is properly inclined being levelled (see fig.1) so as to
allow the condense to drain.
fig.1
8 80
7 70
85%
6 60
75%
5 50
m
ax
65% .
4 40
55%
3 30
1Diagrammaportata-prevalenzacircolatore_R2K28_PM_EN
45%
2 20
35%
1 25% 10
15%
5%
0 0
0 0,4 0,8 1,2 1,6 2,0 2,4 Q/m³/ h
30
20
10
0
0 0,4 0,8 1,2 1,6 2,0 2,4 Q/m³/ h
Appliance Loss
13
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
INSTALLER
1.1.10. D.H.W. CIRCULATING LOOP
RC
VR
A
C
F
fig. 1
1 Ricircolo_boiler_20_litri_EN
KEY
RC- D.H.W. CIRCULATING LOOP
VR- NO-RETURN VALVE
C- CIRCULATOR
U- TAPS
F- COLD WATER MAINS
15
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
WARNING
For system filling use only clean tap water. 1
WARNING
If the system is filled by adding ethylene
glycol-type chemical agents you have to install on
the loading system a hydraulic trip unit in order to
separate the heating circuit from the domestic circuit.
16
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
7. open the air relief valves of the radiators and
check the air removal process. When the
water starts to leak close the radiators air
relief valves.
fig. 4
17
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
1 Protezione antigelo_EN
18
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
1.1.14. GAS CONNECTION 1.1.15. ELECTRICAL CONNECTION
DANGER DANGER
In order to connect the gas connector of The equipment is electrically safe only
the boiler to the supply pipe use a stop seal of an if it is properly connected to an efficient grounding
appropriate size and material. The use of hemp, system, performed in compliance with the safety
teflon tape or similar materials is strictly forbidden. standards in force (STANDARDS CEI 64-8 and 64-9
Electrical Section). You should check this essential
BEFORE PERFORMING THE GAS CONNECTION, safety requirement. If in doubt, request an accurate
MAKE SURE THAT: check of the electrical system performed by qualified
staff, as the manufacturer is not responsible for any
› the gas adduction line complies with the damages caused by lack of grounding system.
standards and regulations in force (UNI-CIG
7129/01 – D.M. 12.04.1996); › Make sure that the electrical systems is
suitable for the maximum power absorbed by
› the tubing's section suits the requested capacity the equipment, value indicated on the data plate.
and its length;
› make sure that the cables section is appropriate
› the tubing is equipped with all safety and control for the maximum power absorbed by the
devices required by the standards in force; equipment and that it is however not lower than
1 mm2.
› the internal and external seals of the gas infeed
plant are checked; › The equipment works with alternating current
of 230 V and 50 Hz. The electrical connection
› the device is suitable for use with the type of must be performed using an all-pole switch with
gas available by checking the boiler data plate an opening of at least 3 millimetres between
(placed on the inner side of the front casing. If contacts placed upstream from the device.
they do not match you must take the necessary
measures to adapt the boiler to another type of WARNING
gas (see chapter GAS TRANSFORMATION); Make sure that the phase and neutral
cables connection is performed in compliance with
› the gas supply pressure falls within the values the wiring diagram (see chapter POWER SUPPLY).
indicated on the data plate.
1 Allacciamento gas_elettrico_MIAH4_EN
WARNING
It is strictly forbidden the use of adaptors,
multiple plugs and/or extensions for the general
power supply of the equipment from the electrical
network.
19
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
DANGER
Ta Ta Se Se
Cut off the voltage from the main switch.
BLUE
N
› loosen the two screws and remove the plate “A”
(see fig. 1). YELLOW/GREEN
L
› after removing the plate, connect the electrical BROWN
cables to terminal “B” (see fig. 1): B
1 Alimentazione elettrica_EN
20
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
1.1.17. OPTIONAL ELECTRICAL
CONNECTIONS SE
A
Ta Ta Se Se
• (SE) EXTERNAL TEMPERATURE PROBE COD.
73518LA
N
• (CR) REMOTE CONTROL OPEN THERM COD. 40-
00017 TA
L
use the terminal placed inside the control panel
CR
as follows: B
DANGER
Cut off the voltage from the main switch.
fig. 1
› remove the front casing of the boiler (see
chapter ACCESSING THE BOILER); unscrew the
screws and remove plate “A” (see fig. 1). NB: In case of simultaneous presence of external probe and
remote control, the modulation board only sends the external
› After removing the plate, connect the electrical temperature value to the remote device without using it for
cables to terminal “B” (see fig. 1): modulation.
· For the external temperature Probe connect The communication between board and remote control takes
the two non-polarized conductors to the Se- place independently from the boiler's operating mode and after
Se contacts. establishing the connection, the used interface on the board is
disabled and the display shows the symbol ‘ ’.
· For the environment Thermostat or Remote
control, first remove the bridge on the Ta-
1Collegamentielettriciopzionali_SE_TA_CR_MIAH4_EN
21
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
use the electronic board placed inside the control After performing these operations, remount the
panel as follows: crankcase and the front casing.
MIAH4 SVZ
M1
4 5 6 7 8 9 10 11 M4
M8 1
gr
3 2
2 3 ar
1
M10
4 SRB
5 N
M3
6 L
987 M4
M2
M15
68
67
66 12
65
64
63 13
62
14
TP 61
60
15
16
59
ne
58
ro
17
57
M16
M2
TAZ 2 TAZ 1
CT ar
M14
56
ar 55
ne
ne 54
ma 53
ce 52
51
L
M13
29
28
31
30
37
36
35
34
33
32
44
43
42
41
40
39
38
27
26
220 V - 50 Hz
BUS+ M12 M9 M7 M5
N
COD.40-00133
GND 1Collegamentielettriciopzionali_MIAH4_noPM_EN
BUS 0-10V VZR VZ2 VZ1
fig. 1
FC FC
INSTALLER
1.1.18. FUME EXHAUST FITTINGS › Make sure that the discharge tube doe not
protrude inside the fumes exhaust duct, stop
WARNING before it reaches the inner surface of the latter.
In order to ensure proper operation and
efficiency of the device you have to connect the boiler › The discharge duct must be perpendicular with
fume exhaust fitting to the fume exhaust duct using the opposite internal wall of the chimney or of
appropriate polypropylene flue fittings for condensing the fumes exhaust duct (fig. 2).
boilers. It is recommended to install discharge
systems approved by Radiant.
WARNING
You cannot use traditional flue fittings for
the discharge ducts of the condensing boilers, nor
vice versa.
WARNING
For fumes exhaust and condensate
collection, please follow standard UNI 11071.
23
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
C33 C33
› B23P- Indoor suction and outdoor C53 C93 B33
discharge.
24
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
DISCHARGE OF COMBUSTION PRODUCTS FOR location ventilation. The natural air intake must
B-TYPE DEVICES (IN ACCORDANCE WITH UNI take place directly through:
7129)
· permanent openings on the external walls of
The gas devices, provided with connection for the location (windows);
fumes exhaust tube, must be directly connected
to efficient chimneys or fume exhaust ducts: · single or collective, ramified ventilation ducts.
only if these are missing you can discharge the
combustion products directly through the gas The openings on the external walls of the location
devices. must respect the following requirements:
The connection to the chimney or to the fume · have a net overall free passage section of
exhaust ducts must respect the following at least 6 cm2 for every kW of heat capacity
requirements: installed with a minimum of 100 cm2;
· Be sealed and realised in materials suitable · they must be realized so as to make sure that
to resist normal mechanical stress, heat, the opening inlets are not obstructed (neither
the action of combustion products and any indoors nor outdoors);
condensate forming;
· they must be protected with grids, metal
· have no more than three changes in direction, meshes, etc. so as to keep the useful section
including the chimney and/or fume exhaust mentioned above.
duct inlet connection, made with internal
angles greater than 90°. The changes in · they must be placed at a height next to the
direction must be made only by using curved floor level such as to allow proper operation of
curved elements; the combustion products discharge systems;
if such position can not be obtained, please
· have the axis of the inlet end perpendicular to increase by at least 50% the section of the
the internal wall opposite to the chimney or vents.
fume exhaust duct;
25
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
Ø80
Ø125
reference length) can be calculated summing the
length of the linear tube and that equivalent to
each additional curve with respect to the first.
26
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
KIT H - HORIZONTAL SPLIT SYSTEM Ø80/80 MADE
OF POLYPROPYLENE, ADJUSTABLE AT 360°.
121
a linear length of tube according to the indications
Ø80
below:
Ø80
27
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1. INSTALLATION
INSTALLER
1 Tipologia di scarico_CK_50_EN
Ø 100
28
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1.
2. SUPPORT CENTRE SECTION
All operations described below relative to first start-up,
S.p.A.
2. FIRST START-UP
2.1.1. PRELIMINARY OPERATIONS › make sure that there are no flammable liquids
FOR FIRST START-UP or materials near the device;
The first start-up operations consist in checking › open the boiler gas tap and make sure that there
the correct installation, adjustment and operation are no gas leaks upstream from the device (the
SUPPORT CENTRE
of the device. Proceed as follows: burner gas connection must be checked while
the machine is running);
› check the inner system sealing in accordance
with the indications provided by standard UNI › in case of new installation of the gas supply
11137-1; network, the air inside the tubes may block the
device at its first start-up. You might have to
› check if the gas used is suitable for the boiler; repeat the start-up procedure to purge all the
air inside the tube.
› check if the gas capacity and relative pressures
comply with those on the plate;
30
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
WARNING
Make sure that the system is correctly
filled.
SUPPORT CENTRE
THE START-UP SYSTEM WILL AUTOMATICALLY
ACTIVATE THE SYSTEM AIR RELIEF CYCLE
FUNCTION DISPLAYED ON SCREEN WITH CODE
“F33” (ONLY AT FIRST START-UP WILL LAST FOR
5 MINUTES). When function “F33” is active, the
pump is enabled and the burner start-up request
is disabled. The boiler can work normally only
after completing the operation.
31
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
2.1.3. CO2 VALUE CHECK AND › Once completed the adjustment, tighten the
CALIBRATION protection screw ‘A’ (fig. 2) on the Off-Set
adjuster.
WARNING
The CO2 value should be checked with › Exit parameter ‘P10’ following the procedure
the casing assembled, while the gas valve should be described in chapter “ACCESSING AND
adjusted with the casing open. PROGRAMMING THE PARAMETERS”.
To check and calibrate the CO2 value to minimum › Activate the chimney sweep function holding the
SUPPORT CENTRE
FOR MAXIMUM HEATING POWER › Make sure that the CO2 value did not change
to maximum, if changed repeat the calibration
› Activate the chimney sweep function holding the described in the previous paragraph.
key ‘ ’ for 7 seconds.
32
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
To access the parameters menu and adjust their values, follow the procedure below:
SUPPORT CENTRE
1. Press the button ‘ ’ to select the OFF
mode displayed using the symbol ‘ ’.
33
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
34
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
1 = 18 KW (HEAT.) / 24 KW
(DOMESTIC)
SUPPORT CENTRE
2 = 25 KW
3 = 28 KW
4 = 34 KW
5 = 55 KW
6 = 100 KW
10 = R1K 50
1 = ISTANTANEOUS RKR
2 = ACCUMULATION
3 = ACCUMULATION
COMFORT
4 = ISTANTANEOUS COMFORT
- FAST H2O
5 = HEATING ONLY
35
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
2 = 100 SECONDS
3 = 200 SECONDS
4 = 400 SECONDS
2 Tabella parametri_MIAH4_EN
P06 DOMESTIC CIRCUIT PRESERVATION FUNCTION 0-1 0 = DISABLED
(ONLY FOR ISTANTANEOUS BOILERS) (SET BY DEFAULT)
THROUGH THIS PARAMETER YOU CAN PRESERVE THE
CIRCULATOR THE DIVERTER VALVE IN DOMESTIC POSITION 1 = ENABLED
FOR A PERIOD OF TIME EQUAL TO THE POST-CIRCULATION
(SEE PARAMETER P08), SO AS TO MAINTAIN THE SECONDARY
EXCHANGER HOT.
36
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
SUPPORT CENTRE
P09 POST-CIRCULATION DOMESTIC / BOILER TIMING 0 - 90 VALUE EXPRESSED IN
THROUGH THIS PARAMETER YOU CAN SET THE PUMP MULTIPLES OF 5 SECONDS
OPERATION DURATION ON THE DOMESTIC CIRCUIT, AFTER (PRE-SET AT 18 X 5 = 90
THE TAP IS CLOSED. SECONDS)
P10 FAN MINIMUM SPEED ADJUSTMENT 33 - VALUE SET FOR THE VALUE IS EXPRESSED IN
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM PARAMETER P11 HERTZ
SPEED THAT CORRESPONDS TO THE MINIMUM POWER OF (1HZ = 30 RPM)
THE BURNER.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
P11 FAN MAXIMUM SPEED ADJUSTMENT VALUE SET FOR THE VALUE IS EXPRESSED IN
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM PARAMETER P10 HERTZ
SPEED THAT CORRESPONDS TO THE MAXIMUM POWER OF - 203 (1HZ = 30 RPM)
THE BURNER. THE VALUE IS PRE-SET BASED ON THE SET
POWER (SEE PARAMETER P00) AND ON THE GAS TYPE (SEE
PARAMETER P02)
P12 HEATING FAN MINIMUM SPEED ADJUSTMENT 33 - VALUE SET FOR THE VALUE IS EXPRESSED IN
2 Tabella parametri_MIAH4_EN
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM PARAMETER P13 HERTZ
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE (1HZ = 30 RPM)
MINIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN HEATING MODE. [SEE CHAPTER ‘HEAT CAPACITY DIAGRAM
(KW) – ELECTRIC FAN FREQUENCY (HZ)’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
37
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
P13 HEATING FAN MAXIMUM SPEED ADJUSTMENT VALUE SET FOR THE VALUE IS EXPRESSED IN
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM PARAMETER P12 HERTZ
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE - 203 (1HZ = 30 RPM)
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN HEATING MODE [SEE CHAPTER ‘HEAT CAPACITY DIAGRAM
(KW) –ELECTRIC FAN FREQUENCY (HZ)’].
SUPPORT CENTRE
P14 STARTING STEP ADJUSTMENT VALUE SET FOR THE VALUE IS EXPRESSED IN
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED PARAMETER P10 HERTZ
DURING START-UP - 203 (1HZ = 30 RPM)
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
2 Tabella parametri_MIAH4_EN
38
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
SUPPORT CENTRE
NATURE OF THE CORRECTION DEPENDS ON THE THERMO-
ADJUSTMENT VALUE KD SET (SEE CHART).
THE SELECTION OF THE CURVE IS DETERMINED BY THE
MAXIMUM DELIVERY TEMPERATURE TM AND THE MINIMUM
EXTERNAL TEMPERATURE TE TAKING INTO ACCOUNT THE
HOUSE INSULATION DEGREE.
THE VALUES OF THE DELIVERY TEMPERATURES TM, REFER
TO STANDARD SYSTEMS 30-80 °C OR FLOOR SYSTEMS 25-45
°C. THE SYSTEM TYPE CAN BE SET FROM PARAMETER P03.
Tm (°C)
45 MAX 80 Kd = 20 Kd = 25 Kd = 30
Kd = 15
75
70
35 65
Kd = 10
60
55
50 Kd = 5
30
45
40
35
Kd = 0
25 MIN 30
39
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
40
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
SUPPORT CENTRE
2 Tabella parametri_MIAH4_EN
41
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. FIRST START-UP
34
30
26
HEAT CAPACITY (kW)
22
SUPPORT CENTRE
18
G25
14
G20
10 G31
2
35 55 75 95 115 135 155 175
FREQUENCY (Hz)
G20 Hz 45 186
G30 Hz 45 176
G31 Hz 45 184
2Diagrammaportatatermica-frequenzaelettr_R2K34_EN
42
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
2.2. MAINTENANCE
2.2.7. GENERAL MAINTENANCE › remove and clean the burner from oxidation;
WARNINGS
› check the integrity and the position of the sealed
ATTENTION chamber sealing gasket;
All maintenance operations must be
SUPPORT CENTRE
performed in compliance with standards UNI 7129- › check the primary exchanger, if necessary,
3: 2008 and subsequent amendments by qualified clean it;
staff in accordance with art. 3 of D.M. n°37 dated
22.01.2008. and authorized by RADIANT BRUCIATORI › check the operation of the gas light up and
spa. safety systems. If necessary, remove and clean
the flame detection and light up electrodes from
WARNING incrustations paying attention to respect the
In accordance with art. 11 of D.P.R. 412/93 distances with respect to the burner;
and subsequent amendments, the maintenance
operations must be performed once every twelve › check the heating circuit safety systems: limit
months starting from the boiler installation date. temperature safety thermostat; limit pressure
safety;
WARNING
To ensure greater life span and proper › check the pre-load pressure of the expansion
operation of the device, during the maintenance vessel;
operations use only original spare parts.
› make sure that the permanent ventilation outlets
DANGER are present, correctly sized and functioning,
Before each components cleaning or based on the installed devices. Respect the
replacement operation, ALWAYS cut off the POWER, requirements provided by Local and National
WATER and GAS supply of the boiler. legislation;
Please perform the following operations once a › periodically check the integrity of the fume
year: exhaustion system for safety and proper
2Avvertenzegeneraliperlamanutenzione_conbinata_cond_EN
operation;
› check the sealing of the gas components, and
replace if necessary the gaskets; › check that the wiring is performed in compliance
with the requirements in the boiler instruction
› check the sealing of the water components, and manual;
replace if necessary the gaskets;
› check the wiring inside the control panel;
› visually check the flame and the condition of the
combustion chamber; › check the flow and temperature of domestic hot
water;
› if necessary make sure that the combustion
is suitably adjusted and if required proceed as › check the proper operation of the condensate
indicated in section “CO2 VALUE CHECK AND draining system, including the devices outside
CALIBRATION”; the boiler such as condensate collection devices
43
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
2Avvertenzegeneraliperlamanutenzione_conbinata_cond_EN
44
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
SUPPORT CENTRE
Energy efficiency 92/42 CEE no. stars 4
Energy efficiency EN13203-1 no. stars -
Maximum nominal heat capacity in heating circuit kW 34
Maximum nominal heat capacity in domestic circuit kW 34
Minimum nominal heat capacity in heating circuit kW 4.1
Minimum nominal heat capacity in domestic circuit kW 4.1
Useful thermal power - 60/80°C kW 33.35
Minimum useful thermal power - 60/80°C kW 3.94
Useful thermal power - 30/50°C kW 36.19
Performance at 100% Pn - 60/80°C % 98.08
Performance at 30% Pn - return 47°C % 102.14
Performance at 30% Pn - return 30°C % 108.57
Performance at 100% Pn - 30/50°C % 106.43
Maximum combustion Performance % 97.60
Fumes temperature at nominal heat capacity °C 71.93
CO2 at nominal heat capacity % 9.6
CO2 at minimum heat capacity % 8.84
CO2 at nominal heat capacity - G30 % 11.55
CO2 at minimum heat capacity - G30 % 10.8
CO2 at nominal heat capacity - G31 % 10.32
CO2 at minimum heat capacity - G31 % 9.89
CO at nominal heat capacity ppm 165
Fumes mass at nominal heat capacity g/s 14.96
Fumes mass at minimum heat capacity g/s 1.88
2 Dati tecnici_R2KA 34.20_EN
45
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
Continuous hot water supply - ΔT 30° - mixed water - for the litres 185
first 10 minutes
Dimensional characteristics
Width mm 490
Depth mm 500
Height mm 900
Gross weight Kg 67
Water connections
Flow Ø 3/4”
SUPPORT CENTRE
46
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
1 8
8
2
11
3 12
13
4 14
SUPPORT CENTRE
15
16
5
17
18
6
19
20
7
21
8
22
9 23
24
9. CIRCULATOR
10. ANODE
11. SAFETY VALVE 8 bar
12. SAFETY THERMOSTAT
13. HEATING PROBE
14. LIGHT UP ELECTRODE
15. AIR SUCTION TUBE
16. CYLINDER
17. PROPORTIONAL VENTURI
18. GAS VALVE
19. EXPANSION TANK D.H.W.
20. BY-PASS
21. WATER PRESSURE SWITCH
22. DIVERTER VALVE
47
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
22
1 6 23
10 6
2
11 24
3 12
13
SUPPORT CENTRE
4
14
5
15
25
26
16
6 17
7 18
8 19
9 20
21
R C G SC F A
SUPPORT CENTRE
› The BLUE color (with C-B) indicates the
operation in Heating mode.
2 Funzionamento valvola dev._EN
49
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
MP
VD
Ta Ta Se Se
PM
N
220 V
SUPPORT CENTRE
50 Hz
L
ma
ma
ne
ce
ce
ER
ma
4 5 6 7 8 9 10 11 M4
M8
ce
3
ma 2
ce 1
EA
M10
Tra
SRi M15
ma 68
67
VG
ce 66 ma
65 12
64 ce
63 13
62
14
ma 15
61
gi 60 ce
bi 59 16
gr 58 17 ma
57
M16
M2
M14
56
55
54
53
52
51
M13
29
28
31
30
37
36
35
34
33
32
44
43
42
41
40
39
38
27
26
M12 M9 M7 M5
ma
ma
ma
ne
ne
ne
ne
ce
ce
ce
ar
ar
MF
EV
TF
+24V
PWM
HS
GND
2 Schema elettrico_R2KA_.20_PM_EN
TS
SR
SS
Pacq
ER: DETECTION ELECTRODE TS: SAFETY THERMOSTAT MP: PANEL TERMINAL CE: BLUE
EA: START-UP ELECTRODE PACQ:WATER PRESSURE SWITCH SE: EXTERNAL PROBE MA: BROWN
PM: MODULATING PUMP MF: MICRO-FLOW SWITCH TA: ENVIRONMENT THERMOSTAT AR: ORANGE
VG: GAS VALVE SR: HEATING PROBE L: LINE GI: YELLOW
TRA:START-UP TRANSFORMER SS: DOMESTIC CIRCUIT PROBE N: NEUTRAL BI: WHITE
TF: FUMES THERMOFUSE (102°C) EV: ELECTRIC FAN NE: BLACK GR. GREY
VD: DIVERTER VALVE SRI: RETURN SENSOR
50
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
SUPPORT CENTRE
To intervene on the front of the boiler proceed as
follows:
51
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
DANGER
Cut off the voltage from the main switch.
SUPPORT CENTRE
52
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
SUPPORT CENTRE
› turn off the main power supply switch;
53
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
54
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
To view the last 5 fault signalling codes chronologically, starting with the most recent one, activate the
‘OFF’ mode by pressing the FUNCTION ‘ ’ key and hold the key INFO ‘ ’ for 5 seconds. Use keys ‘
’ and ‘ ’ of the heating circuit to scroll through the list of saved faults. To reset the fault history
press the RESET ‘ ’ key. To exit display mode press the INFO ‘ ’ key.
SUPPORT CENTRE
E01 FLAME BLOCK NO FLAME LIGHT UP MANUAL RESET
(PRESS THE RESET
GAS MISSING; CHECK THE ADDUCTION NETWORK; ‘ ’ KEY).
55
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
E02 SAFETY THERMOSTAT THERMOSTAT CABLE CHECK THE WIRING: MANUAL RESET
(95°C) DISCONNECTED; (PRESS THE RESET
‘ ’ KEY).
BROKEN THERMOSTAT. REPLACE IT.
E04 WATER MISSING IN THE INSUFFICIENT WATER LOAD THE SYSTEM; AUTOMATIC.
SYSTEM PRESSURE INSIDE THE SYSTEM
(LOWER THAN 0.3 BAR);
56
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
SUPPORT CENTRE
CABLE.
E21 GENERAL INTERNAL INCORRECT SIGNAL IF THE MODULATION BOARD DOES NOT AUTOMATIC.
BOARD ERROR RECOGNITION BY THE RESET THE ERROR AUTOMATICALLY,
MODULATION BOARD REPLACE IT.
MICRO-PROCESSOR.
E35 RESIDUAL FLAME FAULTY DETECTION CLEAN IT OR REPLACE IT; MANUAL RESET
ELECTRODE; (PRESS THE RESET
‘ ’ KEY).
FAULTY DETECTION REPLACE IT;
ELECTRODE CABLE;
E40 SUPPLY VOLTAGE SUPPLY VOLTAGE OFF THE CHECK THE POWER SUPPLY AUTOMATIC.
OPERATION RANGE (d160 NETWORK (THE ERROR DEACTIVATES
VOLTS). AUTOMATICALLY AS SOON AS THE
SUPPLY VOLTAGE FALLS BACK WITHIN
THE REQUESTED LIMITS).
57
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
F07 CHIMNEY SWEEP ACTIVE YOU CAN ACTIVATE IT BY HOLDING FOR 7 SECONDS THE RESET ‘ ’ KEY AND YOU CAN
DEACTIVATE IT BY TURNING OFF THE BOILER. THIS FUNCTION BRINGS THE BOILER TO
ITS MAXIMUM HEATING PRESSURE FOR 15 MINUTES DEACTIVATING THE MODULATION
FUNCTION. GENERALLY USED FOR PERFORMING THE COMBUSTION TESTS.
SUPPORT CENTRE
F08 HEATING CIRCUIT ANTI-FREEZE IT ACTIVATES AUTOMATICALLY WHEN THE HEATING PROBE DETECTS A TEMPERATURE
OF 5°C. THE BOILER OPERATES AT MINIMUM GAS PRESSURE WITH THE DIVERTER
VALVE SET TO ‘WINTER’ MODE. IT DEACTIVATES WHEN THE HEATING PROBE DETECTS A
TEMPERATURE OF 30°C.
F09 D.H.W CIRCUIT ANTI-FREEZE THE FUNCTION IS AUTOMATICALLY ENABLED WHEN THE D.H.W SENSOR DETECTS A
TEMPERATURE OF 4 °C. THE BOILER OPERATES AT MINIMUM GAS PRESSURE WITH THE
DIVERTER VALVE IN THE ‘SUMMER’ POSITION. THE FUNCTION IS DISABLED WHEN THE
TEMPERATURE DETECTED BY THE SENSOR IS 8 °C IN THE D.H.W CIRCUIT.
F28 ANTI-LEGIONELLA THE FUNCTION IS ACTIVATED FOR THE FIRST TIME, 60 MINUTES AFTER THAT THE
BOILER HAS BEEN ELECTRICALLY POWERED.
STARTING FROM THAT MOMENT IT COMES AUTOMATICALLY INTO OPERATION EVERY
7 DAYS, BRINGING THE HOT WATER TEMPERATURE OF THE STORAGE CYLINDER UP
TO 60°C. THIS FUNCTION IS ENABLED INDEPENDENTLY FROM THE CONTACT TO THE
CYLINDER CLOCK, PROVIDING THAT THE RELATIVE PARAMETER (P15) IS ENABLED.
F33 SYSTEM AIR RELEASE CYCLE IT ACTIVATES AUTOMATICALLY AT FIRST BOILER START-UP, PERFORMING FOR 5
MINUTES A SERIES OF CYCLES DURING WHICH THE PUMP IS ACTIVATED FOR 40
SECONDS AND DEACTIVATED FOR 20 SECONDS. REGULAR OPERATION IS ALLOWED
ONLY AFTER THIS FUNCTION IS COMPLETED.
IT CAN ALSO ACTIVATE DURING NORMAL BOILER OPERATION, IF THE WATER PRESSURE
SWITCH CONFIRMATION IS MISSING, WHEN THE CONTACT IS RE-CLOSED, A 2 MINUTES 2Codicidisegnalazionefunzioniattive_accumulo_MIAH4_EN
RELEASE CYCLE WILL BE PERFORMED.
58
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
ATTENTION
Make sure that the gas adduction tube is
suitable for the new type of fuel with which the boiler
is supplied.
1 2
FOR TRANSFORMATION INTO METHANE GAS
PROCEED AS FOLLOWS:
SUPPORT CENTRE
G
V
› loosen the two screws ‘1’ (fig.1) from the 2
fastening bush, and remove the air suction tube;
fig. 1 2
› unscrew the tube coupling that connects the
gas valve to venturi;
59
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
2. MAINTENANCE
1 2
› unscrew the tube coupling that connects the
gas valve to venturi;
SUPPORT CENTRE
› adjust the CO2 combustion value as indicated in fig. 3 C 2 Trasformazione tipo gas_R2K 34_v.2_EN
chapter ‘CO2 VALUE CHECK AND CALIBRATION’.
3
60
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
1.
3. USER SECTION
The operations described in this section are addressed to
all those who will use the machine. The machine must be
3.1. USE
DANGER
DO NOT obstruct the air vents of the
location in which the gas device is installed to prevent
the formation of toxic explosive mixes.
62
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
1 5
2 3 4
USER
KEY 6. DISPLAY
64
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
To view the boiler data from info menu you just have to press the INFO ‘ ’ key. The info code will be
displayed on the left side of the screen and its relative value will be displayed on the centre of the screen.
Use keys ‘ ’ and ‘ ’ of the heating circuit to scroll through the list of displayed data. To exit display
mode press the INFO ‘ ’ key.
d2 FAN SPEED
USER
d6 SOLAR BOILER TEMPERATURE (BOTTOM) [IF SOLAR BOARD INSTALLED] (SBSI)
65
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
Before starting the boiler make sure that it is In this mode the boiler meets the demands of
powered and that the gas tap below the boiler is heating and of domestic hot water.
open.
To switch the boiler to WINTER operating mode,
To start the boiler press the function key ‘ press the function key ‘ ’, the symbols ‘
’ and select the desired operating mode. If the and ’ will appear fixed on the display, indicating
symbol is displayed fixed, it means that the function that the function is enabled.
was activated.
Whenever heating energy and domestic hot water
are needed the automatic start-up system will
3.1.6. OPERATING MODE start the burner; this is indicated by displaying the
symbol ‘ e ’ blinking.
SUMMER MODE
ADJUSTING THE HEATING TEMPERATURE
In this mode the boiler meets only the demands of
domestic hot water. You can adjust the temperature using keys ‘ ’
and ‘ ’ of the heating circuit :
To switch the boiler to SUMMER operating mode,
press the function key ‘ ’, the symbol ‘ ’ · press key ‘ ’ to decrease the temperature.
will appear fixed on the display, indicating that the
function is enabled. · press key ‘ ’ to increase the temperature.
USER
Whenever hot domestic water is needed the The heating temperature adjustment field ranges
automatic start-up system will start the burner; from 30 °C to 80 °C (25 °C – 45 °C for floor systems).
this is indicated by displaying the symbol ‘ ’
blinking. DOMESTIC HOT WATER TEMPERATURE
ADJUSTMENT
ONLY HEATING MODE
You can adjust the temperature using keys ‘ ’
In this mode the boiler meets only the demands of and ‘ ’ of the domestic circuit :
heating. 3Accensione_Modalitàdfunzi
· press key ‘ ’ to decrease the temperature.
To switch the boiler to ONLY HEATING operating
mode, press the function key ‘ ’, the symbol ‘ · press key ‘ ’ to increase the temperature.
’ will appear fixed on the display, indicating that
the function is enabled. The hot domestic water temperature adjustment
i onamento_Antigelo_MIAH4_MIAH6_EN
66
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
› contact the Technical support centre that will › the pressure of the system is proper;
empty the water system, where no anti-freeze
is intended, and will cut off the power, water and › the boiler is not blocked.
gas supply.
USER
that the anti-freeze function may activate.
3Accensione_Modalitàdfunzi
i onamento_Antigelo_MIAH4_MIAH6_EN
67
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
fig. 2
3Riempimentodell'impianto_MIAH4_R2KA_.20_EN
68
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
The boiler might signal some faults by displaying a code. Below you have a list of the codes and of the
operations to be performed in order to unlock the boiler.
E01 FLAME BLOCK MAKE SURE THAT THE BOILER AND CONTACTOR GAS VALVES
ARE OPEN.
E02 SAFETY THERMOSTAT (95 °C) PRESS THE RESET ‘ ’ BUTTON ON THE CONTROL PANEL TO
RESET THE FAULT, AS SOON AS THE ERROR CODE DISAPPEARS
FROM THE DISPLAY, THE BOILER WILL START AUTOMATICALLY.
USER
CENTRE.
E03 FUMES SAFETY THERMOFUSE (102 °C) CONTACT THE TECHNICAL SUPPORT CENTRE.
E04 WATER MISSING IN THE SYSTEM IF THE SYSTEM PRESSURE IS BELOW 1.2 BAR, FILL THE SYSTEM
AS DESCRIBED IN CHAPTER “SYSTEM FILLING”.
69
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
E21 GENERAL INTERNAL BOARD ERROR CUT OFF THE POWER SUPPLY FROM THE MAIN SWITCH AND
THEN RESTORE IT, AS SOON AS THE ERROR CODE DISAPPEARS,
THE BOILER WILL RESTART AUTOMATICALLY.
E22 PARAMETERS PROGRAMMING CUT OFF THE POWER SUPPLY FROM THE MAIN SWITCH AND
REQUEST THEN RESTORE IT, AS SOON AS THE ERROR CODE DISAPPEARS,
THE BOILER WILL RESTART AUTOMATICALLY.
E35 RESIDUAL FLAME PRESS THE RESET ‘ ’ BUTTON ON THE CONTROL PANEL TO
RESET THE FAULT, AS SOON AS THE ERROR CODE DISAPPEARS
FROM THE DISPLAY, THE BOILER WILL START AUTOMATICALLY.
3Codicidisegnalazioneanomalie_combi_MIAH4_EN
70
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
USER
3Codicidisegnalazionefunzioniattive_accumulo_MIAH4_EN
71
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
3. USE
3.1.11. MAINTENANCE
WARNING
DO NOT use abrasive or powder detergents
as they might damage the plastic cover and control
elements.
3.1.13. DISPOSAL
USER
72
R2KA 34 /20 - RAD - ING - Manuale - 1507.1_PM
RADIANT BRUCIATORI s.p.a.