RTU Manual 8

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

E70-DOA-00x

6049-E70

Power Transmission
Power Generation & Distribution

Oil & Gas


Transmission & Distribution
Railway
Traction

E70-DOA-00x, part of Husky series RTU, is 16 / 8 channel potential free, normally open, digital
output card with an onboard 32 bit microcontroller. It is equipped with a feedback monitoring
circuit to provide accurate feedback for “Select Before Execute” commands. A dedicated “Hot
Swap Controller” is present on the card to allow fail safe hot swapping of cards without
affecting the backplane bus.
GENERAL TECHNICAL DESCRIPTION
DOA00x is a binary output card that provides isolated outputs, D O c a rd i s E M I / E M C
in groups of eight, for 16 process outputs. Following compliant as per standard
additional functionalities are provided: IEC60870-2-1, Level 3.
m 16 nos. Single Channel Output PROCESSING FUNCTIONS
m 8 nos. Double Channel Output DOA00x can execute following processing functions on the
m SBE or Non SBE Configuration output channels, depending upon the configuration:
m For Non SBE cards, individual channel selectable for Pulse m Double bit commands with automatic handling for latch
and Latch functionality outputs. Ensures that only one channel is triggered ON or
m Accepts SBE commands even for Non SBE configuration OFF at any given time.
for backward compatibility with systems m Dedicated feedback monitoring for SBE commands via
dedicated select and execute monitoring circuit. Detects
8 outputs form a single group with common supply. Groups
hardware malfunctions and reports them to CPU
are potentially isolated from one another as well as from
other logics. Each group is provided with a master relay along m Individual treatment of Pulse or latch per channel for non
with relays for individual channels. When command is SBE command
received from the CPU, it is routed to the output channel m Feedback monitoring for pulse commands
through selection of corresponding channel and master relay. m Pulse train with minimum duration of 50 ms.
In case of SBE output, the feedback is monitored before
Processing on the card is carried out by the on board
master relay is actuated.
microcontroller. The card communicates with the CPU over 1
Each channel has a corresponding Select and Execute LED on Mbps CAN bus. Configuration data is received from CPU and
the front plate of the card that is directly linked to the output. different processing functions are activated accordingly.
When output is triggered, corresponding LED is triggered to Upon receiving commands from CPU, command is processed
reflect the command status. and appropriate processing functions are applied. If proper
When powered on, the card carries out a self diagnostic feedback is not received, error is reported to the CPU.
procedure to determine the healthiness of critical hardware
components. Faults are reported via fault LED on the front plate.
TECHNICAL SPECIFICATIONS MODULE INDICATIONS

Processor 32 bit microcontroller LED Purpose


Points 16 / 8 Channels, 2 groups of 8, Potential PWR Indicates presence of input power PWR

CB1E
Free Outputs CB1E, CB2E Error in backplane IO bus CB2E

FAULT

Isolation 1KV between field and system FAULT Indicates presence of critical fault in module SEL EXE

Protection Surge 01 … 16 Output Status.


01
02

l Channel Selected. l Channel Executed.


03

Power Consumption 2.5W max 04


05

Operating Temperature 0-70 Degree C ORDERING INFORMATION 06


07
08
Relative Humidity 95% non condensing Order Code Specifications 09
10

I/O Connections 2x20 pin pluggable connector on chassis E70-DOA-001 16 Channels, Potential Free NO Contacts
11
12

backplane 13

E70-DOA-002 8 Channels, Potential Free NO Contacts 14

Dimensions 4U high x 4T wide, 1 slot width 15


16

DO CARD

You might also like