5TY.384.20015.1 of Active Part/ Transformer Bottom Side View Back Side View
2990 3375
of Active of Active Part/ Transformer
Part/ 3350
Transformer
F 51 F
1650 1293 1760
871.5 8
350 985
823
3649 635 100
585 530 636 500
871.5 185 65
360 80 285
90
90
285 1115
900
625
2313 1690
D 300 D
575 3140
240
1129
(Internal)
5X300(Pitch)=1500
4X300(Pitch)=1200
240
240
610 214
364
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
LV Side
2300 2300 1400
1150
185 B
880 880 225
HV Side 32
1500(Lifting & Jacking)
1165
Indent No.
Name Lower Tank Assembly
30 13 30
TBEA Energy (India) Pvt. Ltd.
Scale Page Size Mass (kg) Projection
T14135
10 1690 1690 10 01 06-Feb-19 Qty. of Item No. 12 revised Preetam Rinto Ashish "TBEA GREEN ENERGY PARK"
National Highway No.8, Material 0.025 A2 13355.2
00 06-Jan-19 First issue Preetam Rinto Ashish Village : Miyagam, Karjan,
C
SECTION A-A Rev. No. Date Description Prepared Checked Approved Gujarat - 391240. India Total Pages 2 Current Page 1
1 2 3 4 5 6 7 8
All dimensions are in millimeter unless otherwise specified.
1 2 3 4 5 6 7 8
5TY.384.20015.1
Technical Requirements:
01. Paint shall be same as painting procedure given by quality department.
02. For manufacturing instruction and Vacuum & Pressure test, refer final assembly drawing.
03. 200 NB pipe support shall be welded from vacuum block location to bottom plate before applying vacuum.
04. Outer Stopper shall be intermittent, 500mm long steel pieces shall be welded and 100mm space provided in
9 between two pieces. At the rim corners, stopper shall be blended with a suitable radius to maintain the
F distance between stoppers. F
47 05. After cutting the material; Burr & sharp edges must be grinded off & cleaned.
06. After welding, weld area shall be cleaned.
07. Min R10 fillet must be provided inside of the tank. All sharp edges must be rounded. No sharp edges are
23 permitted inside of the tank.
08. Box stiffener shall be blasted cleaned & full painted from inside before its weld to tank wall.
09. For tolerances refer tolerance document ISO 2768 – 2.
17 10. Lifting bollard and Jacking pad welding shall be DP tested.
11. Earthing plate (drawing code; 8TY.552.S5001.001) welding dimensions can be varied and it shall be welded
on nearest rim locking hole and it shall be in-line with cover assembly earthing plate.
12. Ative part center lines shall be marked on rim at all four locations with yellow paint.
27 13. Matching surfaces of components which are made of SS material like earthing bosses and earthing pads
shall not be painted
14. Tapped holes shall be capped to avoid entering of paint in holes.
38 15. Holes shall be drilled in cover assembly rim matching to lower tank rim holes.
16. Refer drawing ''5TY.384.A5001.2RF'' for Roller mounting details
17. Before welding inside oil channels, it shall be shot blasted & painted from inside same as tank inside paint
and all channel shall be leak proof.
18. Jacking welding shall be unpainted and covered with protection tapes during transportation.
19. All weld/corners inside the tank shall be smoothly grinded to 10mm radius. All external edges of fabricated
20 items to be rounded to 3mm radius for better paint adhesion.
E E
11 53 8TY.576.20015.560 Earthing Nut 40 SS304 0.1 2.7
52 8TY.325.20015.501 Sludge Removal Flange 1 E250 2.8 2.8
51 8TY.310.T0300.3 CT Terminal Blanking Plate 1 E250 1.0 1.0
30 50 8TY.310.T0100.50 50NB-Cover Plate 1 E250 DN50 1.0 1.0
49 8TY.310.T0100.25 25NB-Cover Plate 10 E250 DN25 0.5 4.6
48 8TY.310.T0100.150 150NB-Cover Plate 2 E250 DN150 2.9 5.7
47 8TY.310.T0100.125 125NB-Cover Plate 1 E250 2.2 2.2
46 8TY.310.T0100.100 100NB-Cover Plate 1 E250 1.7 1.7
45 8TY.310.20015.534 Cover Plate 3 E250 3.7 11.1
44 8TY.310.20015.503 Sludge Removal Blanking 1 E250 0.3 0.3
43 8TY.130.20015.952 Gusset 12 E250 t= 20 1.1 12.7
15
42 8TY.130.20015.946 Gusset 1 E250 t= 32 6.4 6.4
3 41 8TY.130.20015.944 Gusset 1 E250 t= 32 1.3 1.3
40 8TY.130.20015.943 Gusset 1 E250 t= 32 19.0 19.0
D 39 8TY.130.20015.942 Gusset 1 E250 t= 32 36.6 36.6 D
41
38 8TY.130.20015.941 Gusset 1 E250 t= 32 22.2 22.2
37 8TY.130.20015.939 Gusset 1 E250 t= 32 9.0 9.0
37 36 8TY.130.20015.938 Gusset 1 E250 t= 32 13.6 13.6
35 8TY.130.20015.936 Gusset 1 E250 t= 32 11.1 11.1
18 34 8TY.130.20015.935 Gusset 2 E250 t= 32 10.0 20.1
33 31 33 8TY.130.20015.934 Gusset 4 E250 t= 32 16.0 64.1
6
22 32 8TY.130.20015.932 Gusset 4 E250 t= 32 14.2 56.7
34 28 31 8TY.130.20015.822 Box Stiffener 3 E250 26.7 80.1
35
36 30 8TY.130.20015.821 Box Stiffener 2 E250 98.5 197.0
43 16 53 12 25 26 2 14 24 5 29 29 8TY.130.20015.819 Box Stiffener 2 E250 92.3 184.6
28 8TY.130.20015.818 Box Stiffener 2 E250 73.2 146.4
27 8TY.130.20015.592 Gusset 1 E250 29.8 29.8
26 8TY.130.20015.513 Stiffening Plate 4 E250 t= 25 21.5 86.1
25 8TY.130.20015.512 Stiffening Plate 4 E250 t= 32 19.6 78.6
C 24 8TY.102.20015.500 Cup 4 Seamless Pipe OD=245, H=65, t=10 3.8 15.1 C
23 8TY.100.20015.860 Post insulator supporting 3 E250 t= 10 2.8 8.3
Bracket
22 8TY.100.20015.522 Plate 4 E250 28.1 112.5
21 8TY.064.20015.501 Earthing Pad 1 SS304 LxWxT= 160x80x16 1.5 1.5
20 8TY.059.20015.604 Base Plate for R&D Plate 6 E250 t= 6 0.7 4.0
19 8TY.059.20015.601 Base Plate (Name Plate) 1 E250 100 X 25 X 2 0.1 0.1
18 8TY.059.20015.501 Base Plate 1 E250 1620.0 1620.0
45
17 8TY.051.20015.531 N Side Wall 1 E250 224.6 224.6
16 8TY.051.20015.530 IV Side Bottom Wall 1 E250 207.6 207.6
15 8TY.013.20015.603 Cylinder Clamp 2 STEEL 0.7 1.5
14 5TY.793.20015.852 Magnetic Shield 1 CRGO 119.0 119.0
13 5TY.793.20015.851 Magnetic Shield 1 CRGO 92.0 92.0
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Product Type
A
Drawing
Code 5TY.384.20015.1 A
OSFSZ-100000/220TH
Indent No.
Name Lower Tank Assembly
TBEA Energy (India) Pvt. Ltd.
49 48 32 7 1 10 39 Scale Page Size Mass (kg) Projection
T14135
01 06-Feb-19 Qty. of Item No. 12 revised Preetam Rinto Ashish "TBEA GREEN ENERGY PARK"
National Highway No.8, Material 0.035 A2 13355.2
00 07-Jan-19 First issue Preetam Rinto Ashish Village : Miyagam, Karjan,