Professional Documents
Culture Documents
C22 OptimizationofWater-CooledChillerPlantSystemOperation
C22 OptimizationofWater-CooledChillerPlantSystemOperation
net/publication/288314596
CITATIONS READS
9 1,569
2 authors:
Some of the authors of this publication are also working on these related projects:
NSF: CRISP Type 1/Collaborative Research: A Human-Centered Computational Framework for Urban and Community Design of Resilient Coastal Cities View project
BIGDATA: Collaborative Research: IA: Big Data Analytics for Optimized Planning of Smart, Sustainable, and Connected Communities View project
All content following this page was uploaded by Wangda Zuo on 12 September 2018.
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 300
in either print or digital form is not permitted without ASHRAE’s prior written permission.
approach doesn’t need exact knowledge of the plant, where , is the temperature of chilled water
therefore, it is suitable to the condition when system leaving the chillers, is the chilled water flow rate,
model isn’t available. However, the performance of is the condenser water flow rate, and is the
their method highly depends on the transient pattern of cooling load. While can be expressed as
the controlled system. If the system cannot quickly
, , , , (3 )
respond to the change of control variable, it may lead to
long searching time. where is the wet bulb temperature.
In the previous studies, the focus was a plant with If , and , are constant (which is true
single chiller. A few studies on multiple chillers used for many chiller plants), then equations (2) and (3) can
idealized control that did not consider the detailed be simplified as
process for chiller sequencing. Since many chiller , , (4 )
,
plants are made of multiple chillers, it is necessary to
, , . (5 )
study the control optimization of multiple chillers by
using a plant model that can more realistically represent Combining equations (1), (4) and (5), we will get
the real control process. (6)
min , , , .
With a perception of higher optimization frequency
leading to more energy saving, we tend to optimize the The depends on the weather condition and
control parameters more frequently that requires more depends on user behavior and weather condition. Thus,
computing time. However, the relationship between the , is the only controllable variable in (6). Since
optimization frequency and energy saving is not well , can be controlled through , , we could
understood due to the lack of quantitative analysis. reformulate the optimization objective as:
To address the above issues, this study studied the min , , (7 )
model-based control of a chiller plant with three chillers with the constraints of:
and three cooling towers. The plant was modeled using m , (8 )
, ,
Modelica Buildings library (Wetter et al. 2014) and
m , (9 )
both the supervisory control with staging and local , ,
feedback-loop controls were modeled. The impact of , , , , (10)
frequency optimization on the energy saving and
computing time was also evaluated. The findings are where is the specific heat of the water.
presented in the following sections.
CASE STUDY
METHODOLOGY Case description
The conventional supervisor control usually fixes the The case study was performed for a real chiller plant in
condenser water temperature setpoint, , according Washington D.C.. The plant was the only cooling
to the design conditions. As a result, the cooling towers source for 3 office buildings nearby. Figure 1 shows the
could cool the condenser water lower than the schematic of the studied chiller plant. It has three
fixed , for most of the time. The chillers’ identical chillers, three condenser water pumps, three
efficiency increases when the temperature of condenser chilled water pumps and three cooling towers. One
water entering the chillers , decreases. On the cooling tower, one chilled water pump and one
other hand, reducing may increase the energy condenser water pump were coupled with one chiller. A
,
consumption of the cooling towers. Therefore, there is supervisor controller was used to control the chiller
status according to the cooling load. The control
an optimum , that the total energy consumption
sequence can be described by using a state graph
of the chillers and the cooling towers is minimum. (Figure 2). When the chiller plant system is started,
Accordingly, the objective function of the optimization there is only one chiller operating; when the cooling
is: load increases, the rest two chillers would be started
min min , (1 ) sequentially. A dead-band was used to avoid short
where and are the energy consumption by the cycling. In addition, a three-way valve was employed to
chillers and cooling towers, respectively. is a modulate the flow rate through the cooling towers so
function of multiple inputs: that overcooling can be avoided.
, , , , , , , (2 )
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 301
in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 1 Schematic of the condenser water loop
Figure 3 Diagram of the Modelica model for the plant
The capacity of each chiller was 2,799kW and the system
operation curve of Trane_CVHF_2799kW was adopted.
The temperature of chilled water leaving the chiller was Figure 4 shows the model for chiller sub-system. Three
set to = 6.67oC. For the cooling tower, the chillers were connected in parallel and each chiller can
,
nominal fan power was 37.285kW, nominal wet bulb be started separately.
temperature was 25oC, and the nominal approach
temperature was 1.11oC.
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 302
in either print or digital form is not permitted without ASHRAE’s prior written permission.
available in the GenOpt library and they can be divided
into two categories: gradient-based and gradient-free
algorithms (Wetter and Wright 2004). To identify the
appropriate optimization algorithm for this study, we
first selected one algorithm from each category: Arm
(DiscreteArmijoGradient) for gradient-based algorithms
and GPS (GPSHookeJeeves) for gradient-free
algorithms.
A comparison was conducted to evaluate their
performance in terms of accuracy and computation
time. An exhaustive search was performed to provide
reference data. The input parameters were the cooling
load 390 ton and the wet bulb temperature T =
7.8 oC. The range for the independent variable ,
Figure 5 Diagram of subsystem model for the cooling was from 15.11 to 26.11oC with an interval of 1oC and
towers with bypass the start point was 15.11oC.
Numerical tests showed that the GPS predicted the
Figure 6 shows the diagram of tower models. An same optimal of 16.11oC as the exhaustive
,
Fluid.HeatExchangers.CoolingTowers.YorkCalc model
search while the prediction by the Arm was 15.93 oC.
(EnergyPlus Engineering Reference 2013) in the The GPS used only 7 steps while the Arm used 136
Buildings library were chosen to model the cooling steps. Therefore, the GPS was selected for the further
tower, which is described as following: study.
, ∙ , (12)
To study the impact of optimization frequency on
, , , , , (13) energy saving and computing time, the following
where is the air flow rate ratio. The , and scenarios were considered (Table 1):
are the nominal and actual power of the cooling tower, Table 1 Optimization scenarios
respectively.
To maintain , , a local controller was used to SCENARIO PERIOD FREQUENCY ALGORITHM
adjust the speed of the cooling tower fan according to Exhaustive Exhaustive
1 year 1 hour
Search Search
, , , Hourly GPS 1 year 1 hour GPS
(14)
max , , , , ,1 . Daily GPS 1 year 1 day GPS
Simulation Results
The model settings were the same as the one used in the
previous section except that the model inputs were
changed to actual hourly cooling load and wet bulb
temperature measured in 2012.
Figure 7 shows the measured cooling load. Due to the
load in the interior zones of the buildings, the chiller
plant had to provide cooling even in the winter season
(Nov-Feb). In addition, cooling load in the summer
season (Jun-Sept) was obviously larger than that in the
non-summer season (Oct-May). As shown in Figure 8,
in the summer was higher than that of in the non-
summer.
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 303
in either print or digital form is not permitted without ASHRAE’s prior written permission.
Table 2 Energy consumption for each scenario
ANNUAL SAVING
ENERGY RATIO
SCENARIO CONSUMPTION (COMPARED
(MWH) WITH
BASELINE)
Exhaustive Search 2,383.6 9.4%
Hourly GPS 2,383.7 9.4%
Daily GPS 2,387.6 9.2%
Baseline 2,630.3 N/A
Figure 9 shows the distribution of optimal condenser
temperature setpoints for each hour predicted by the
Hourly GPS. It can be found that the optimal setpoint
was less than the nominal value for most time.
Figure 7 Annul hourly cooling load
Figure 8 Annual hourly wet bulb temperature in Figure 9 The hourly optimal condenser water
Washington D.C. 2012 (National climatic data center) temperature setpoint distribution over the year
As shown in Table 2, about 9% energy savings can be As shown in the Figure 10, the major energy saving
anticipated by optimizing the condenser water was obtained from March to May and in September
temperature setpoint. The energy saving was mainly when the temperature was mild. The winter season has
due to reducing the condenser water temperature when the lowest energy saving since there was only a little
the wet bulb temperature was low. In the studied plant, usage.
the condenser water temperature setpoint was fixed as
26.11oC that led to high baseline energy consumption.
The energy saving potential may vary if the existing
control already allows the floating settings of condenser
water temperature setpoint.
The results of Hourly GPS and Exhaustive Search are
almost the same. The difference in results between
Hourly GPS and Daily GPS are also small (0.2%). This
indicates that optimization frequency only has tiny
impact on the energy performance in this case.
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 304
in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 10 Averaged daily energy saving by Hourly
GPS for each week Figure 12 Hourly cooling loads on June 28th and
October 9th
The ratio of energy saving ratio was around 5 to 20%
(Figure 11).The highest ratio appeared in spring and Figure 13 shows the energy consumption by using
fall. The lowest ratio was in summer. different optimization algorithms in the hot day. For
that day, the energy saving by optimization was small
because the high wet bulb temperature left little space
for optimizing the condenser water temperature setting
point.
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 305
in either print or digital form is not permitted without ASHRAE’s prior written permission.
Figure 14 Predicted , for different scenarios on
June 28th Figure 16 Predicted , for different scenarios on
October 9th
Figure 15 shows the energy consumption during a mild
day on October 9th. Compared to the hot day, Based on the above observation, it can be found that
significant energy saving was achieved by optimizing is the key impact factor of the energy saving effect
the condenser water temperature setpoint because the by optimizing , : higher leads to less energy
low wet bulb temperature allowed lower condenser saving.
water temperature setpoint. Table 3 Computing time for each scenario
OPTIMIZATION
SCENARIO COMPUTING EFFICIENCY
TIME (hours) (SEC/HOUR)
Exhaustive
18.8 7.7
Search
Hourly GPS 11.6 4.8
Daily GPS 1 0.4
(Optimization efficiency is defined as computing time divided by the
actual operation time)
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 306
in either print or digital form is not permitted without ASHRAE’s prior written permission.
result shows that about 9% energy saving could be Component Models." ASHRAE Transactions
achieved by optimizing the condenser water AC-02-9-1.
temperature setpoint. The GPS can provide an optimal Hydeman, M. and G. Zhuo 2007. "Optimizing chilled
solution comparable to Exhaustive Search but with water plant control." ASHRAE Journal.
significantly less computing time. We also found Daily Li, X., Y. Li, et al. 2012. "Extremum Seeking Control
GPS optimization could achieve similar results as of Cooling Tower for Self-optimizing Efficient
Hourly GPS, but with much less computing time. Operation of Chilled Water Systems " 2012
American Control Conference.
ACKNOWLEDGEMENTS Lu, L., W. Cai, et al. 2004. "HVAC system
The research was supported by the U.S. Department of optimization––condenser water loop." Energy
Defense under the ESTCP program. Conversion and Management.
The authors thank Michael Sohn, Marco Bonvini, Ma, Z., S. Wang, et al. 2009. "An optimal control
Michael Wetter, Mary Ann Piette, Jessica Granderson, strategy for complex building central chilled
Oren Schetrit, and Rong Lily Hu for the support water systems for practical and real-time
provided through the research. applications." Building and Environment
44(6): 1188-1198.
NOMENCLATURE Perez-Lombard, L., J. Ortiz, et al. 2008. "A review on
buildings energy consumption information."
T: Temperature
Energy and Buildings 40(2008): 394–398.
: Cooling load Westphalen, D. and S. Koszalinski 2001. "Energy
Consumption Characteristics of Commercial
: Mass flow rate Building HVAC Systems Volume I : Chillers,
E: Energy or power Refrigerant Compressors and Heating
Systems."
Cp : Specific heat Wetter, M. 2005. "BuildOpt—a new building energy
simulation program that is built on smooth
SUBSCRIPTS models." Building and Environment 40(2005):
cw : Condenser water 1085–1092.
Wetter, M. and J. Wright 2004. "A comparison of
chw : Chiller water deterministic and probabilistic optimization
ent : Entering chiller algorithms for nonsmooth simulation-based
optimization." Building and Environment
lea : Leaving chiller 39(2004): 989–999.
wb : Wet bulb Wetter, M., W. Zuo, et al. 2014. "Modelica Buildings
library." Journal of Building Performance
app : Approach Simulation 7: 253-270.
nom : Nominal condition Yao, Y., Z. Lian, et al. 2004. "Optimal operation of a
large cooling system based on an empirical
ch : Chiller model." Applied Thermal Engineering 24(16):
tw : Cooling tower 2303-2321.
REFERENCES
"EnergyPlus Engineering Reference."
F.W.Yu and K.T.Chan 2008. "Optimization of water-
cooled chiller system with load-based speed
control." Applied Energy.
Hydeman, M. and K. L. Gillespie 2002. "Tools and
Techniques to Calibrate Electric Chiller
© 2014 ASHRAE (www.ashrae.org). For personal use only. Reproduction, distribution, or transmission 307
in either print or digital form is not permitted without ASHRAE’s prior written permission.