Professional Documents
Culture Documents
Chee 81 To 141
Chee 81 To 141
Chee 81 To 141
Applications
11.1 Introduction
The per unit system is a universal concept designed to ease the analysis and conceptualisation of electric
networks and systems. It makes it easier to judge whether values are within acceptable limits. For example,
even in a complex network involving transformers with varying transformation ratios, we can easily detect
abnormal or out-of-desired-range operation. If for example, we have a standard that voltages are not to be
outside ±10%, and we find a bus voltage of 1.2 per unit (p.u.), we can easily detect the abnormality because
we know that the voltage on any bus has to be a maximum of 1.1 p.u. and a minimum of 0.9 p.u.
281
reactances and voltage sources, i.e. into a standard electrical circuit then the analysis is simpler. The problem
can be solved in standard ways, we would save ourselves unnecessary effort and we would make less errors.
Being able to do this network conversion allows us to use other network analysis tools, for example to calculate
fault currents. Among the most useful tools would be the Norton and Thevenin equivalent circuits. The way to
achieve per unit conversion is quite straightforward. We will rely on the use of a few definitions and formulas.
T1 T2
G M1
Line
M2
V
Zbase = _
I
base
base
We are often concerned with circuits involving voltages in the kV rage and powers in the MVA range and
therefore voltage bases are frequently cited in kV and power bases in MVA. Note also that the base power
does not change throughout the system under study. The base voltage however will change from one side
of a transformer to another, i.e. it is dependent on the transformer ratio. This will become clearer when we do
examples involving transformers.
V
Zbase = _
base
(11.3)
Ibase
282
(V )2
=_
base
(11.4)
Sbase
(kV )2
=_
base
(11.5)
MVAbase
To find the actual values (usually this is the last step) we use:
Example 11.1
The generator in Figure 11.2 is supplying a load of ZF=R F +jX F
IL
impedance ZL through a feeder line ZF. The feeder
impedance is 1 + j2 or (2.24∠ 63.4) The load
impedance is 8 + j6 (or 10∠36.9). If the voltage
ZL VL
across the load is 120 V, use the per unit system to find EG
the real and reactive power supplied by the generator.
Use as base voltage, 120 V and as base VA, 1500.
= 1∠ 0 p.u.
V
Zbase = _
I
base
base
(Vbase)2
=_Sbase
(120)2
=_
1 500
= 9.6
Z
ZL p.u = _
Z
actual
base
= __
10∠ 36.9
9.6
p.u.
= 1.04∠36.9 p.u.
283
V
IL p.u = _
p.u.
Z
p.u.
Lp.u.
= __ 1∠0
1.04∠ 36.9
p.u.
Zƒ p.u = __
2.24∠63.4
9.6
p.u.
= 1.204∠4.8 p.u.
Since we know from Equation 11.6 that:
EG (volts) = 144.5∠4.8 V
Apparent power is:
SG = EGIL*
SG = (1.204∠4.8)(0.96∠– 36.9)
= 1.156∠41.7
= 0.863 + j0.769
From this, the per unit real power supplied is 0.863, and per unit reactive power supplied is +0.769.
By multiplying with base values, we find:
284
V% = _30
240
(100)
= 12.5%
The transformer is therefore as described in Figure 13.3. 1200 VA
Is/c = Irated = _
1 200 VA V%=12.5%
240 V
= 5A Figure 11.3: Short-circuit
voltage as a percentage.
Assuming negligible resistance
Zs/c = Z01
= Xs/c = X01 = _
30
5
=6
Therefore:
Zs/c = _
30
5
=6
This transformer is represented in Figure 11.4.
285
Choosing 1 200 as base VA and 240 as base voltage then the base impedance is:
2
(Vbase) 2
Zbase = _ = _
(240)
S 1 200
base
= 48
2
Z
Zp.u. = _
Z
=_6
48base
= 0.125 p.u.
Thus, we see that to convert transformer impedance from % to per unit, we simply divide by 100. It is also seen
that Vs/c expressed as a percentage also gives Z% and p.u. impedance, thus some manufacturers refer Z% as
percentage voltage.
We can apply the same reasoning to electrical machines. A machine such as a motor or generator with a
reactance of 20% has 0.20 p.u.
Note that Zpu can also be more directly calculated from:
S
Zpu = _
base
Z
2
(11.7)
(Vbase)
Z = Zpu1Zbase1 = Zpu2Zbase2
Zbase1
Zpu2 = Zpu1 _
Z base2
Vbase12/Sbase1
= Zpu1__
2
Vbase2 /Sbase2
Sbase2 Vbase1
( )
2
= Zpu1 _
S
_
V
base1 base2
Now Sbase1 is usually the rated or specified value of the equipment, so we may call it simply Sspec. Similarly,
Vbase1 is simply called, Vspec. It is also common practice to call Sbase2, simply Sbase and Vbase2, Vbase and we will
also call Zpu1, Zspec. We will proceed to name Zpu2, Zpu (new).
From the above formula, we note the following:
(a) If our chosen base MVA is higher that that on the nameplate, then the per unit value of the impedance
on the nameplate will increase proportionally. That is, we apply a factor of:
286
S( )
Sbase
Sk = _
spec
(11.8)
(b) For example, if for a transformer we have Sbase = 50 MVA, X% = 15 (0.15 p.u.) and the transformer
is rated at 25 MVA, then we should work with double the nameplate per unit value, i.e. a higher base
MVA increases the per unit value of the specified impedance.
(c) If our chosen base voltage is higher than that on the nameplate, then the per unit value of the impedance
on the nameplate will decrease but not in direct proportion. We apply a factor of:
( )
V 2
Vk = _
spec
V
(11.9)
base
It is very important to note that unlike Sbase and Sspec which may differ greatly, Vbase and Vspec and are expected
to be very close to one another, typically within 20% of one another unless there is an abnormality in the
system.
In real systems, the equipment specifications or ratings will differ for both S and V from our chosen base and
we often have to apply both Sk and Vk.
Therefore to translate a per unit impedance to a common base usable on a common system being studied, we
must apply this very important result:
( )( )
Sbase V 2
Zpu (new) = Zpu (spec) _ _spec
Sspec Vbase
(11.10)
Or:
Zpu (new) = (Sk)(Vk)(Zpu (spec))
M1
G1 Generator
Specifications:
SG=25MVA
XG=10%
VG=11 kV
287
Solution:
For this example, we have the freedom to choose bases. It would be convenient to choose values coinciding
with one of the items in the network. Generators are convenient, especially if they have several parameters.
It certainly makes sense to choose the base voltage from one of the ratings (Vspec ) of one of the items of the
system. A nominal busbar voltage is also convenient choice.
Lets then use Sbase = 20 MVA, and Vbase = 11 kV.
Then: VGpu = _ ( )
11 p.u. = 1 p.u., S
11 Gpu
= _( )
25
20
p.u. = 1.25 p.u.
Also, XGpu = _10
100
= 0.1 p.u.
Consider now transformer T1.
Using Equation 11.10:
= 0.08 p.u.
= 0.15 p.u.
Note that as the specified voltage and MVA coincide with base voltage and base MVA, there is no change
in the per unit value of this component. Also, we could have used 0.4 kV instead of 33 kV in applying the
formula.
Finally, lets consider the motor.
Again using Equation 11.10, we have:
= 0.20 p.u.
288
Notice how the base voltages have been shifting each time we move from one side of the transformer to
the other.
Lets combine all the information we have into one diagram (Figure 11.6).
XT1 XL1 XT2
0.092 0.15
0.096
0.08
XG1 0.20
XM1
VG1=1pu M1 M
Example 11.3
Example 11.2 was a ‘well behaved’ network, now lets make a p.u. diagram of a more complicated network
that makes sure we understand the importance of Equation 11.10. Consider the network of Figure 11.7.
T2
T1 Transformer Transformer
Specifications: Specifications M1 Motor
S=25 MVA : Specifications:
S=20 MVA S=10MVA
XT1=12% XT2=15%
12kV /33kV L1 35kV /0.4kV XM1= 10%
Line Spec: V=0.38 kV
j5 Ω
M
M1
G1 Generator
Specifications:
SG=25MVA
XG=10%
VG=11 kV
VG = _
11 p.u. = 0.92 p.u.
12
289
= 0.067 p.u.
Consider now transformer T1.
Using Equation 11.10:
XL1(pu) = _
20
2
(5)
(33)
= 0.092 p.u.
Next, we consider T2.
Using Equation 11.10:
= 0.169 p.u.
Finally, let us consider the motor.
Again using Equation 11.10, we have:
= 0.203
Notice how the motor voltage rating has changed from that of Example 11.2 and more significantly, how we
changed the base voltage on the motor side. We used the transformer ratio, so that:
= 0.377 kV
290
0.067
XG1 0.203
XM1
VG1=0.92pu M1 M
0.067
make certain investigations. What happens if there is a XG1
Fault 0.203
XM1
bolted three-phase fault (i.e. a short circuit of all lines to
M1
ground or together, also called a three-phase symmetrical VG1=0.92pu M
0.067
XG1 0.203
XM1
Xth
VG M1
j0.255 j0.372
Xth
j0.151
0.92
0.92 Isc (pu)=
j0.151
= -j6.09
291
2. A one-line impedance diagram for a power system is shown in Figure 11.11. The three-phase line-to-
line ratings are as follows:
Table 11.1 System ratings
Item Power Rating (MVA) Voltage (kV) Reactance (X p.u.)
Generator G 20 13.8 0.18
Motor M1 7 13.8 0.15
Motor M2 5 14.5 0.15
T1 25 13.2/161 0.1
T2 15 14/160 0.15
The line connecting T1 and T2 has a reactance of j80 (actual ohms).
Using a 100 MVA and a 161 kV transmission line voltage as bases, draw a per unit impedance
diagram for the system and calculate the predicted fault current at the secondary terminals
of transformer T2.
T1 T2
G M1
Line
M2
292
L2 L3
B4 T1 B6 B3
M
M
G FDR
L4
B5
SVC
In this chapter we shall summarise and consolidate the representations of the most important power system
components. As far as possible, the data format used in modern power system packages will be utilised.
293
Three-phase line A
A three-phase line in an equilateral triangle configuration shown in
Figure12.2 will have a line-to-neutral inductance given by: r
0 d
L=_8
[
1 + 4ln _(
d–r
r )]
H/m (12.2)
d
N
–7 ()
_
d
= (2)(10 )ln r for d >> r
The line-to-neutral inductance is important since in doing power C B
d
systems analysis, a single-phase representation is used.
Figure 12.2: Three-phase line,
If the configuration is not equilateral (such as three conductors in a
equilateral triangle configuration
plane as in Figure 12.3), d in equation 12.1 and 12.2 can be replaced
by a geometric mean distance between the conductors:
__
deq = √
3
dAB.dBC.dCA (12.3)
Substituting:
__
deq = √
3
(2.5).(2.5)(5) = 3.15 m
2.5m 2.5m
A B C
Figure 12.3: Three conductors, in-line configuration
Unsymmetrical spacing of the conductors can cause unacceptable uneven inductances and voltage drops as
well as induction of worrisome voltages in nearby communication lines.
For the reactance of the transmission line we obviously have to take into account the supply frequency. This
would be 60 Hz in the in the Americas and 50 Hz for other countries in the world.
Line resistance
For reasons of economy, aluminium and not copper is used for high voltage overhead cables. To achieve
mechanical strength, the stranded twisted aluminium conductors have a steel wire at the centre. They are
therefore called aluminium conductor steel reinforced conductor (ACSR). The cross-sectional area used for
these conductors is often based on what is called a copper equivalent and the constants given are those of this
copper equivalent. On this basis the area given is therefore smaller than that of the real aluminium conductor.
Figure 12.4 on the next page shows that overhead line data is dependent on circuit configuration.
294
Capacitance
The capacitance of a single-phase two-wire transmission line is given by the expression:
pe
C=_0
F/m (12.4)
ln[_]
d–r
r
Where d is the distance between the centres and r the radius of the conductors. A three-phase line on an
equilateral triangle configuration shown in Figure 12.2, will have a line to neutral capacitance given by:
2pe
C=_ 0
F/m (12.5)
ln[_
d–r
r ]
Charging current
Charging current is the current that flows through line capacitance. This can be calculated by dividing the
phase voltage by the reactance at line frequency.
Example 12.1
Consider the three-phase line of Figure 12.3. The geometric mean diameter, GMD or deq = D = 3.15 m. Let
the conductor radius be 0.006 m, the length of the line is 1 km. The line voltage is 220 kV, at 60 Hz.
Solution:
Now, the capacitance to neutral can be shown to be,
2e
C=_ 0
d–r
ln[_
r ]
2(8.854)(10–12)
C = __
3.15
ln_ 0.006
= 8.88 pF/m
Xc = ___
1
–12
M
2(60)(8.88)(10 )
= 298.6 M
__
220 _000
√3
Ic = __
(298.6)(106)
= 0.000425 A/m
For 1 km, therefore Ic = 1 000(0.000425)
= 0.425 A
295
13.3 2.159 2.159 0.474 0.491 0.503 0.520 0.534 8.7 0.604 7.6 0.615 7.4 0.624 7.3 0.649 7.0 0.633 7.2 0.668 6.8
15.3 1.877 1.877 0.469 0.486 0.498 0.515 0.529 8.8 0.598 7.7 0.610 7.5 0.619 7.4 0.644 7.1 0.628 7.3 0.662 6.9
21.2 1.356 1.356 0.457 0.474 0.486 0.503 0.516 9.0 0.586 7.8 0.598 7.7 0.606 7.6 0.632 7.2 0.616 7.4 0.650 7.0
23.9 1.201 1.201 0.452 0.469 0.481 0.498 0.511 9.1 0.581 7.9 0.593 7.8 0.601 7.6 0.627 7.3 0.611 7.5 0.645 7.1
26.2 1.093 1.093 0.449 0.466 0.478 0.495 0.508 9.2 0.578 8.0 0.590 7.8 0.598 7.7 0.624 7.3 0.608 7.5 0.642 7.1
28.3 1.025 1.025 0.423 0.440 0.452 0.469 0.483 9.4 0.552 8.2 0.564 8.0 0.572 7.8 0.598 7.5 0.582 7.7 0.616 7.3
33.6 0.854 0.854 0.439 0.456 0.468 0.485 0.499 9.4 0.569 8.1 0.580 7.9 0.589 7.8 0.614 7.5 0.598 7.7 0.633 7.2
37.7 0.765 0.765 0.392 0.409 0.421 0.438 0.452 9.7 0.521 8.4 0.533 8.2 0.541 8.1 0.567 7.7 0.551 7.9 0.585 7.4
42.4 0.677 0.677 0.431 0.447 0.460 0.477 0.490 9.6 0.560 8.3 0.572 8.1 0.580 7.9 0.606 7.6 0.589 7.8 0.624 7.3
44.0 0.652 0.652 0.384 0.400 0.413 0.429 0.443 9.9 0.513 8.5 0.525 8.3 0.533 8.2 0.559 7.8 0.542 8.0 0.577 7.5
47.7 0.604 0.604 0.383 0.400 0.412 0.429 0.443 9.9 0.513 8.5 0.524 8.3 0.533 8.2 0.558 7.8 0.542 8.1 0.576 7.6
51.2 0.563 0.564 0.380 0.397 0.409 0.426 0.440 10.0 0.510 8.6 0.521 8.4 0.530 8.2 0.555 7.9 0.539 8.1 0.573 7.6
58.9 0.489 0.490 0.375 0.392 0.404 0.421 0.435 10.1 0.505 8.7 0.516 8.5 0.525 8.3 0.550 7.9 0.534 8.2 0.568 7.7
63.1 0.455 0.455 0.416 0.432 0.445 0.462 0.475 9.9 0.545 8.5 0.557 8.3 0.565 8.2 0.591 7.8 0.574 8.0 0.609 7.5
Concise Higher Electrical Engineering
67.4 0.426 0.426 0.413 0.430 0.442 0.459 0.473 10.0 0.543 8.5 0.554 8.3 0.563 8.2 0.588 7.8 0.572 8.1 0.606 7.6
73.4 0.393 0.393 0.367 0.384 0.396 0.413 0.427 10.3 0.496 8.8 0.508 8.6 0.516 8.5 0.542 8.1 0.526 8.3 0.560 7.8
79.2 0.362 0.362 0.407 0.424 0.436 0.453 0.467 10.1 0.536 8.7 0.548 8.4 0.556 8.3 0.582 7.9 0.566 8.2 0.600 7.6
85.0 0.337 0.338 0.404 0.421 0.433 0.450 0.464 10.2 0.534 8.7 0.545 8.5 0.554 8.4 0.579 7.9 0.563 8.2 0.598 7.7
94.4 0.305 0.306 0.363 0.380 0.392 0.409 0.423 10.3 0.492 8.8 0.504 8.6 0.512 8.4 0.538 8.0 0.522 8.3 0.556 7.8
105.0 0.273 0.274 0.396 0.413 0.426 0.442 0.456 10.4 0.526 8.8 0.537 8.6 0.546 8.5 0.572 8.1 0.555 8.3 0.590 7.8
121.6 0.237 0.238 0.353 0.370 0.382 0.399 0.413 10.6 0.482 9.0 0.494 8.8 0.502 8.6 0.528 8.2 0.512 8.4 0.546 7.9
127.9 0.225 0.226 0.348 0.365 0.377 0.394 0.408 10.7 0.477 9.0 0.489 8.8 0.497 8.7 0.523 8.2 0.507 8.5 0.541 8.0
131.2 0.220 0.220 0.347 0.364 0.376 0.393 0.407 10.7 0.476 9.1 0.488 8.8 0.496 8.7 0.522 8.3 0.506 8.5 0.540 8.0
135.2 0.213 0.214 0.357 0.374 0.386 0.403 0.416 10.5 0.486 9.0 0.498 8.8 0.506 8.6 0.532 8.2 0.516 8.4 0.550 7.9
148.9 0.194 0.194 0.346 0.362 0.375 0.392 0.405 10.8 0.475 9.1 0.487 8.9 0.495 8.7 0.521 8.3 0.504 8.6 0.539 8.0
158.7 0.181 0.182 0.351 0.367 0.380 0.397 0.410 10.7 0.480 9.1 0.492 8.9 0.500 8.7 0.526 8.3 0.509 8.5 0.544 8.0
170.5 0.169 0.170 0.348 0.365 0.337 0.394 0.408 10.8 0.477 9.1 0.489 8.9 0.497 8.8 0.523 8.3 0.507 8.6 0.541 8.0
184.2 0.157 0.157 0.345 0.362 0.374 0.391 0.405 10.9 0.474 9.2 0.486 9.0 0.494 8.8 0.520 8.4 0.504 8.6 0.538 8.1
201.4 0.144 0.145 0.336 0.353 0.365 0.382 0.396 11.0 0.466 9.3 0.477 9.1 0.486 8.9 0.511 8.5 0.495 8.8 0.529 8.2
210.6 0.137 0.137 0.340 0.357 0.369 0.386 0.400 11.0 0.469 9.3 0.481 9.1 0.489 8.9 0.515 8.4 0.499 8.7 0.533 8.1
221.7 0.131 0.132 0.328 0.345 0.357 0.374 0.388 11.3 0.458 9.5 0.469 9.3 0.478 9.1 0.503 8.6 0.487 8.9 0.522 8.3
230.9 0.125 0.126 0.331 0.348 0.360 0.377 0.391 11.2 0.460 9.4 0.472 9.2 0.480 9.0 0.506 8.6 0.490 8.9 0.524 8.3
241.7 0.119 0.120 0.335 0.351 0.364 0.381 0.394 11.2 0.464 9.4 0.476 9.2 0.484 9.0 0.510 8.5 0.493 8.8 0.528 8.2
263.7 0.109 0.110 0.326 0.343 0.355 0.372 0.386 11.3 0.455 9.5 0.467 9.3 0.476 9.1 0.501 8.6 0.485 8.9 0.519 8.3
282.0 0.102 0.103 0.329 0.346 0.358 0.375 0.389 11.3 0.458 9.5 0.470 9.3 0.478 9.1 0.504 8.6 0.488 8.9 0.522 8.3
306.6 0.095 0.096 0.320 0.337 0.349 0.366 0.380 11.5 0.450 9.7 0.461 9.4 0.470 9.2 0.495 8.7 0.479 9.1 0.514 8.4
322.3 0.090 0.091 0.324 0.341 0.353 0.370 0.384 11.5 0.453 9.6 0.465 9.4 0.473 9.2 0.499 8.7 0.483 9.0 0.517 8.4
339.3 0.085 0.086 0.318 0.335 0.347 0.364 0.378 11.6 0.448 9.7 0.459 9.5 0.468 9.3 0.493 8.8 0.477 9.1 0.511 8.5
362.6 0.080 0.081 0.314 0.331 0.343 0.360 0.374 11.7 0.443 9.8 0.455 9.6 0.463 9.4 0.489 8.9 0.473 9.2 0.507 8.5
386.0 0.075 0.076 0.313 0.330 0.342 0.359 0.373 11.8 0.443 9.8 0.454 9.6 0.463 9.4 0.488 8.9 0.472 9.2 0.506 8.6
402.8 0.072 0.074 0.313 0.330 0.342 0.359 0.372 11.8 0.442 9.9 0.454 9.6 0.462 9.4 0.488 8.9 0.472 9.2 0.506 8.6
428.9 0.067 0.069 0.320 0.337 0.349 0.366 0.380 11.5 0.449 9.7 0.461 9.4 0.469 9.2 0.495 8.7 0.479 9.0 0.513 8.4
448.7 0.064 0.066 0.308 0.325 0.337 0.354 0.367 11.9 0.437 10.0 0.449 9.7 0.457 9.5 0.483 9.0 0.467 9.3 0.501 8.7
456.1 0.064 0.065 0.305 0.322 0.334 0.351 0.364 12.0 0.434 10.0 0.446 9.7 0.454 9.6 0.480 9.0 0.463 9.4 0.498 8.7
483.4 0.060 0.062 0.306 0.323 0.335 0.352 0.366 12.0 0.435 10.0 0.447 9.8 0.455 9.6 0.481 9.0 0.465 9.4 0.499 8.7
494.4 0.058 0.060 0.305 0.322 0.334 0.351 0.365 12.1 0.435 10.0 0.446 9.8 0.455 9.6 0.480 9.0 0.464 9.4 0.980 8.7
510.5 0.057 0.059 0.303 0.320 0.332 0.349 0.362 12.1 0.432 10.1 0.444 9.8 0.452 9.6 0.478 9.1 0.462 9.4 0.496 8.7
523.7 0.055 0.057 0.303 0.320 0.332 0.349 0.363 12.1 0.432 10.1 0.444 9.8 0.452 9.6 0.478 9.1 0.462 9.4 0.496 8.7
Figure 12.4: Dependence of Overhead Line data on configuration (Source Network Protection and Application Guide, AREVA T&D)
2009/10/15 01:01:25 PM
Chapter 12 Modelling and Analysis of Power Systems
C R C R
Long lines
The parameters of a long line are distributed over the entire length of the line and the voltage V at any point,
x from one end is given by:
_
d2V
= 2V
dx2
Where:
_
= √yz = the propagation constant
And y is the shunt admittance per unit length and z the series impedance per unit length.
Short line
r L
Vs VR
297
Vs = AVR + BIR
IS = CVR + DIR
When expressed in matrix form these equations rend themselves to easy solutions.
Example 12.2
Calculate the sending-end voltage and current for a 100 km transmission line. The receiving line to line
voltage is 132 kV. The line parameters are R = 0.3 per km per phase, inductive reactance 0.55 per
km per phase. The capacitive susceptance is 400 μS. The current at the receiving end is 400 A at 0.8 power
factor lagging. Use the nominal -line model.
Solution:
The sending end voltage and current can be expressed in matrix form:
Receiving phase voltage:
VR = (_
132 _000
).
√3
In phasor form:
VR = (76 210 + j0) V
298
299
The inter-conductor capacitance, C2 is shown in Figure 12.9. Figure 12.8: Single conductor cable
The effective capacitance is: components
C1
C2 C2
C1 C1
C2
300
Figure 12.11 shows an oscillogram of a previously unloaded generator subjected to a short circuit. Only one
half (the positive part) has needed to be drawn because the other half is a mirror image. Observing Figure
12.11 we see the effect of the short circuit on machine reactances. The period immediately following the short
circuit is the sub-transient period and the highest short-circuit current occurs during this period. However, the
current decreases more rapidly here than in the following period, designated the transient period.
|Eƒ| ov
|I″| =_=_ _ (12.10)
X″d √2
X″d is called the sub-transient reactance (ov is marked in the figure).
X″d
_
X ratio = _ (12.11)
R Rg
Where Rg is the generator stator resistance.
|Eƒ| ou
|I′| =_=_ _ (12.12)
X′d √2
X′d is called the transient reactance (ou is marked in the figure).
301
P=_
VE
X
sin G
s
For constant load G remains constant, assuming a new increased value for increased demand. There is a limit
however beyond which G must not go. This is the stability limit. Instability means loss of synchronism (the
machine will run out of step out with other connected machines and may have to be taken out of service).
Disturbances in a power system cause even more serious stability problems.
Steady-state stability
Steady-state stability relates to a machine’s response to a gradually increasing load or small disturbance. A
machine with steady-state stability will return to initial operating state after a small disturbance. For machines
connected to an infinite busbar the stability limit is the maximum power limit which is reached for 90o load
angle for cylindrical rotor machines and about 80o for salient pole machines.
Dynamic stability
Dynamic stability relates to a machine’s response following a small disturbance with operating angles
beyond 90o. Dynamic stability depends on a machine’s inertia, damping, reactance and its control system. A
dynamically stable machine will have oscillations of successively decreasing amplitude. If the amplitudes of
the oscillations keep on increasing then the machine is dynamically unstable.
Transient Stability
This concerns large disturbances: such as a loss of a major load or generating unit, or severe fault. This may
cause large changes in rotor speeds, power angles or power transfers.
Assessment of stability requires us to study the angular motion of the rotor, or its acceleration. The rotor will
change its position when the power input, Pi exceeds the electromagnetic power output Pe. The stability of
the machine depends very much on its inertia. If J is the polar moment of inertia of the machine, and the
synchronous angular velocity, then the kinetic energy stored in it is:
302
GH = _21J s2 (12.14)
We know from physics, that M, the momentum of the machine is Jws
We can re-write 12.14 as,
GH = _21 Jwsws
We know from physics, that M, the momentum of the machine is Jws
GH = _21 J wsws
or GH = Mws
therefore,
M=_
2GH
w [12.15]
s
Neglecting damping effects and the influence of any installed control system, the equation of motion of the
rotor in p.u. can then be given by,
Net torque Ti − Te = J
and accelerating power,
dw
P − P = P = w (T − T ) = w J
= M _r
i e a s i e s dt
where Pi is shaft power and Pe is electromagnetic power
dw d 2
Since we can write, _r = _
dt
dt2
dw d 2
M_ _= P − P = _ _
2
r d 2H
= M w = Pi − Pe = Pa [12.16a]
dt dt 2 i e s dt
2
d 2 _ ws
_ = (P − Pe) [12.16b]
dt2 2H i
This equation, in forms [12.14a] or [12.14b] is known as the swing equation. Its solution gives the rotor angle
with respect to time.
By integration of the swing equation, we can arrive at the equation for the angular velocity of the rotor. As part
of the integration process, we multiply both sides by _
d
dt
, thus :
_
2H _d 2 _
d _
d
ws dt 2 dt = Pa dt
or integrating both sides,
_ d 2 _
_
∫ dt = ∫ Pa _
d
2H ddt
ws 0 dt 2 dt
0 dt
303
òu(x).u′(x)dx = _21[u(x)]2 + C
and therefore
_
2H _1 _
( )
ws 2 dt = ∫ Pa d
d 2
__ 0
ws
_
d
dt H √
= _∫ Pa d
__
0
_
√
= _∫ Pa d
d 2ƒ
dt H
[12.17a]
0
∫ Pa d = 0
[12.17b]
0
Equation 12.15b summarises the equal area criterion, which says that for stability the area between the P-
curve and the line representing the power input must be zero. To illustrate this consider a P versus is a
sinusoidal as in Figure 12.11aa. The machine is originally operating at power level Pi0 (operating point p0)
and equilibrium is maintained with input power and electromagnetic powers being equal. If through a sudden
increase of demand the requirement is Pi1, then the rotor angle will change, overshooting to 2 before, hopefully,
resting at p1, corresponding to angle 1. According to the equal area criterion, 2 cannot just be any value, its
maximum will be such that A2=A1. Inspecting Figure 12.11a we have:
G1 G2
∫ (Pi – Pmaxsin G)dG = ∫ (PmaxsinG – Pi) dG
G0 G1
leading to:
Pi(G1 – G2) + Pmax (cos G1 – cos G0) = Pi (G1 – G2) + Pmax(cos G1 – cos G2)
since Pi = PmaxsinG1
The equation becomes:
(G1 – G0) sin G1 + (cos G1 – cos G0) = (G1 – G2) sin G1 + (cos G1 – cos G2)
or
(G2 – G0) sin G1 + cos G2 – cos G0 = 0 (12.17a)
304
Figure 12.11aa
Example 12.3
A synchronous generator develops
a maximum power of 450 MW and
operates at a power angle of 10o.
How much more power can be added
suddenly without loss of stability?
Refer to Figure 12.11b.
305
Solution:
The initial operating point is with 0=10°. So that Peo=450sin(10)=78.1 MW
max = – 1
( − 1 − 0) sin 1 + cos ( – 1) – cos 0 = 0
= ( – 1 – 0) sin 1 – cos 1 = cos 1 = 0
with 0 = 10° = 0.174 radians,
(3.142 − 1 − 0.174) sin 1 − cos 1 − 0.985 = 0
(2.96 − 1) sin 1 − cos 1 − 0.985 = 0 [12.16]
In Equation 12.16 1 cannot be explicitly obtained but can be readily solved using, for example the Newton
Raphson, algorithm (described fully in section 12.12) as follows.
ƒ(1) = (2.96 − 1) sin 1 − cos 1 − 0.985 = 2.96 sin 1 − 1 sin 1 − cos 1 − 0.985 and
dƒ( )
ƒ′(1) = _1
= 2.96 cos 1− (1 cos 1 − sin 1) − sin 1
d1
= 2.96 cos 1 − 1 cos 1
let 0 = 1 radian, the initial guess for 1 then 1, nearer to the correct answer, is,
ƒ( )
1 = 0 − _1
ƒ′(1)
1 = 1 − _
0.124
1.6
= 0.922
Then substitute 1 = 0.922 radian, the better solution for 1 then, 2, nearer to the correct
answer, is,
ƒ( )
2 = 1 − _1
ƒ′(1)
2 = 0.922 − _
0.0347
1.7885
= 0.903
Finally with just one more iteration convergence is reached with, 1 = 0.897 radians, i.e. 51.4°. With this
angle,
Pe1 = 450 sin 1
= 450 sin 51.4
= 351.1MW
With the initial power at 78.1 MW, the additional power is (351.1-78.1)=273 MW.
306
P0 = Pa sin G′2
P
sin G′2 _0
Pa
G′2 = sin–1 _ ()
P0
Pa
G2 = 180 – G′2
()
P0
Note, for _
Pa
= 0.5, for example, there are two solutions, sin30o and sin(180 − 30)o .
Here we are interested in the second solution.
P0
G0 = sin–1 _ (P )
max
Inspecting Figure12.11c:
G1
A1 = ∫ (P0 – Pƒ sin G)dG
G0
G2
A2 = ∫ (Pa sin G – P0)dG
G1
307
So that:
G1 G
[P0G + Pƒ cos G]G 0
+ [P0G + Pa cos G]G2 = 0
1
Example 12.4
Before a fault, a generator previously delivering a maximum of 300 MW is connected to an infinite busbar
through a double line. A fault occurs and the power is reduced to a maximum of 80 MW. After the fault the
maximum power is 250 MW and the operating point is 200 MW. Calculate the critical clearing angle.
Solution:
Pmax = 300 MW, Pƒ = 80 MW,
G0 = sin–1 _
200
(300)
= 41.8°
P
G2 = 180 – sin–1 _0 (P )
a
= 180 – 53.1
= 127°
308
From which:
P0 (G0 – G2) + Pƒ cos G0 – Pa cos G2
cos G1 = ____
Pƒ – Pa
cos G1 = _____
200(0.73 – 2.214) + 80(0.7454) – (250) (–0.6)
80 – 250
= 0.513
G1 = 59.1°
These results are shown in Figure 12.11c.
Transformers
Standard single-phase and three-phase transformers have straight-forward models for power system study
purposes. They are usually represented by the R-X model of Figure 12.12.
R X
V1 V2
Three-winding transformers (Figure 12.13), however require extra care, as we need to specify three voltages
(primary, secondary & tertiary) and three impedances. The impedances may be entered as Z% and R% or in
the form of corresponding % impedance voltages. Both forms can readily be transformed into the per unit form,
as we saw in Chapter 11.
Primary
Secondary
Tertiary
309
Z1 = _21 (Z12 + Z13 – Z23), Z2 = _21 (Z12 + Z23 – Z13), Z3 = _21 (Z13 + Z23 – Z12)
3
11kV
1
220kV
220kV
11kV
66kV
66kV
Induction motors
There are several models used to represent the induction motor, such as the and the T-configuration. Figure
12.15 shows the IEEE model. In this model, the core losses are not accounted for by a shunt resistor, Rc. These
losses are lumped with the friction and windage losses.
R1 X1 R2 ' X 2'
V ph=V L Im
Xm R2 '(1-s)
3 s
In Figure 12.15, the parameters have been referred to the stator. Other power systems analysis packages may
have implementations with parameters referred to the rotor. They may also use different symbols.
310
311
Iteration method
Consider Figure 12.16
Z12
V1 V2
S2 = V2I*12 (12.19)
V1 = V2 + Z12I12 (12.20)
Eliminate I, then:
V2 = V1 – Z12I12
S*
V2 = V1 – Z12_2* (12.21)
V2
In the iterative method we can assume a value of V2 on the right hand side of Equation 12.21. Lets call this V2(0)
(we will use its complex conjugate). We will then get a revised value of V2 on the left, call it V2(1).
Then:
S2*
V2(1) = V1 – Z12_ (12.22)
V2(0)
*
In the next iteration, we substitute replace V2(0) on the right with the newly evaluated V2(1), to obtain a better
estimate for the bus 2 voltage, call this V2(2), that is:
S2*
V2(2) = V1 – Z12_
V2(1)
*
We can generalise this to any number of iterations. For iteration, k, for example:
S2*
V2(k) = V1 – Z12_ (12.23)
V2(k – 1)
*
312
Example 12.5
In Figure 12.16, let Z12=0.04+j0.03, S2=1.0+j0.5 and V1=1∠0 p.u. Find V2 and sending end power, S1.
Solution:
Then, using Equation, 12.16, start with V2(0)=1+j0
S1 = V1I*
S*
I=_2
V* 2
= __
1 − j0.5
0.94147 + j0.01
= 1.0676 − j0.5197
S1 = V1I*
= (1)(1.0676 + j0.5197)
= 1.0676 + j0.5197
= 1.187∠26
313
[] [ ][ ]
I1 Y11 Y12 Y13 V1
I2 = Y21 Y22 Y23 V2 (12.24)
I3 Y31 Y32 Y33 V3
Where:
Y11 = y10 + y12
Y22 = y20 + y12 + y23
Y33 = y30 + y23
Y12 = Y21 = –y12
Y13 = Y31 = – y13 = 0
Y23 = Y32 = –y23
REFERENCE
314
Example 12.6
Obtain the admittance matrix for Figure 12.17a, and solve for V1 and V2.
–j2
V1 V2
–j3 –j5
4∠30
4∠0
Solution:
Y11 = –j3 – j2 = –j5
Y22 = – j2 – j5 = – j7
Y12 = Y21 = j2
[–j5 j2 ]
Ybus = j2 –j7
[ 4∠30
4∠0
] = [–j5j2 j2 _
][ ]
V1
–j7 V2
[]
V1
V2
= [
1.134∠96.5°
0.878∠111.6°
p.u. ]
Names of buses
A bus (or busbar) is a connection point for one or more components of an electrical network. From a power
system analysis point of view, we define three buses:
(i) A load or PQ bus. On this bus the net active (P) and reactive power (Q) are constant and specified. The
magnitude of the voltage and its angle G (or T) are unknowns.
(ii) A generator or PV bus. On this bus the net active power (P) and voltage (V) are known and the net
reactive power Q and G (or T) are to be found.
(iii) A slack or swing bus. This is a generator or bus on which voltage and angle G (or T) are known and P
and Q to be found. Since it is not possible to know in advance the losses of the system, one generator
315
is chosen by the analyst to take up the ‘slack‘. The voltage is usually chosen to 1 p.u. and the angle
chosen to be 0.
Example 12.6a
A 100 MW, 60 MVar load (bus 2) is connected to a generator (bus 1) through a line with z=0.02+0.06 p.u.
There is a capacitor of susceptance j0.3 at bus 2. At each bus, take note of the effect of line capacitance
represented by a suspectance of j0.08. Calculate the voltage at bus 2, assuming that the voltage of the
generator is 1 p.u.
Solution:
We will use:
( )
Pk – jQk n = N
Vk = _
Y
1 _ – ∑ YknVn
kk Vk * n=1
n¹k
V2 = _
Y
1 _
22
[
P2 – jQ2
– (y21V1)
V2* ]
We note that the number of buses is 2, but n cannot have a value of 2, the same as k (2nd bus). So for a
2-bus n can only have a value of 1, and therefore we have V1 only in the above equation. Note: for a 3-bus
system n can have K–1 (i.e. 3–1=2) values; if solving for bus 2 of a 3-bus system, the values will be 1 and 3.
Note also that instead of Y21, –y21 has been used (see explanations after Equation 12.24, from which
Y12=Y21=–y12=–y21).
We shall use the generator convention, that S is the power into the bus. For a load then we have –S.
y12=1/z12=(1/0.02+j0.6)=6.9–j17.24
Y22=6.9–j17.24+j0.08+j0.3=6.9–16.9
Substituting:
V2(1) = __ 1 __
[
–1 + j0.6
6.9 – j16.9 1 + j0
– (–6.9 + j17.24)(1 + j0) ]
= 0.9639 – j0.0445
316
V2(2) = __ 1 __
[–1 + j0.6
6.9 – j16.9 0.9639 + j0.0445
– (–6.9 + j17.24)(1 + j0) ]
= 0.9644 – j0.0451
V2(3) = __ 1 __
[–1 + j0.6
6.9 – j16.9 0.9644 + j0.0451
– (–6.9 + j17.24)(1 + j0) ]
= 0.9644 – j0.0451
S2 = P2 + jQ2 = V2I*2
So that:
P – jQ
I2 = _
2
*
2
V2
Using Kirchoff’s Law:
P2 – jQ2
_
*
= Y21V1 + Y22V2 + Y23V3 (12.25)
V2
Solving for V2:
V2 = _
Y
P2 – jQ2
1 _
22
* [– (Y21V1 + Y23V3)
V2 ] (12.26)
For node 1:
V1 = _
Y
P1 – jQ1
1 _
11
* [– (Y21V2 + Y23V3)
V1 ] (12.27)
( )
Pk – jQk n = N
Vk = _
Y
1 _ – ∑ YknVn (12.28)
kk Vk * n=1
n¹k
To solve for the voltage for a particular node, k, we assume values Vk (except for the slack bus which is already
known) on the right hand side of the equation and proceed as in the example of the two-bus case already
described. In the three-bus example we only need to calculate V2 and V3. This is the Gauss-Seidel method.
317
ƒ(xr + 'xr) = 0
Expanding the left side we have:
( ) ( )
r
dƒ r _ d2ƒ
ƒ(xr) + 'xr _ + 21('xr)2 _ +…=0 (12.29)
dx dx2
(dx )
dƒ r
ƒ(xr) + 'xr _ ≈0 (12.30)
From the above equation, we can solve for an approximate value of the error:
ƒ(xr)
'xr = – _ (12.31)
(dx )
dƒ r
_
Example 12.7
Using the NR method, solve:
ƒ(x) = x2 + x – 12 = 0
Solution:
Here:
¶ƒ(x)
_ = 2x + 1
¶x
318
Starting with an initial guess of 2, and repeatedly applying Equation 12.32, we have the results in
Table 12.2.
Multi-dimensional NR algorithm
The NR algorithm can be extended to the general multi-dimensional case of:
ƒ(X) = 0, where X is the vector [x1, x2, x3, ….xn].
Instead of an error, Δxr, we have an error matrix, ΔXr. Further, the function _
dƒ
dx ( )
is now also replaced by a
matrix, called a Jacobian. The corresponding multi-dimensional NR algorithm can be written thus;
[X(r + 1)] = [X(r)] – [J(r)]–1 [F(X(r))] (12.33)
In other words if we start with an initial guess [X(0)], then [X(1)], is more accurate, and can be determined from:
Example 12.8
Use the NR algorithm to solve:
ƒ1 = x12 + x22 – 9 = 0
ƒ2 = x1 – x2 + 1 = 0
319
Solution:
Form the Jacobian:
[ ][
¶ƒ1
_ ¶ƒ1
_
[J] =
¶x1
¶ƒ2
_
¶x2
¶ƒ2
_
2x 2x
= 1 1 –12 ]
¶x1 ¶x2
Starting with X(0) = [30] and the mismatch or error is ƒX = [04] (0)
With
With
X(2) = [ 1.857
2.857 ]
, ƒ(X(2)) = [ 2.6
0]
(real improvement).
Proceeding:
X(3) = [ 1.857
2.857 ] [ 1 –1 ] [2.60 ] = [1.58
2.58 ]
–1
– 3.714 5.714
With
X(3) = [ 1.58
2.58 ]
, ƒX((3)) = [ 0.158
0 ]
(much reduced error, suggests quick convergence)
Finally with:
X(4) = [ 1.561
2.561 ]
, ƒX((4)) = [ 0.004
0 ]
Thus the solution is, X1 = 1.561 and X2 = 2.561
320
x= T PQ and PV nodes
V PQ nodes only
This means that we need to find T for every PQ node and every PV node and V for all the PQ nodes. How many
unknown variables? Iƒ the number oƒ PQ buses is Npq and the number oƒ PV busbars is NPV, then the
number oƒ unknown variables is 2Npq + Npv.
This will also enable us to establish the size of the Jacobian.
The apparent power at bus i, with neighbouring buses k is:
Si = Pi + jQi (12.35)
n
= Vi ∑ Yi*kV*k
k=1
n
= ∑ ViVk(cos Tik + sin Tik)(Gik – jBik)
k=1
Where: Tik = Ti – Tk
Separating real and imaginary parts, we can find the net real and reactive at any bus I, (Generation, Gi, less loads
connected there, Li) as follows:
n
Pi = ∑ |Vi||Vk|(Gik cos Tik + jBik sin Tik)= PGi – PLi (12.36)
k=1
n
Qi = ∑ |Vi||Vk|(Gik sin Tik – jBik cos Tik)= QGi – QLi (12.37)
k=1
321
Qi = k = –BiiVi2(i = k) (12.39)
Separating the i = k case from the i ¹ k case, Equations 12.36 and 12.37 can therefore be written as:
n
Pi = GiiVi2 + ∑ |Vi||Vk|(Gikcos Tik + jBik sin Tik)
k=1
k¹1
Example 12.9
Consider a two-bus example (Figure 12.18). The line impedance is per unit, and the load S = 100 + j80. In the
diagram it has been converted to a 100 MVA base. We wish to find the voltage magnitude and phase angle at
the PQ bus 2. In the solution and subsequent treatment it will also be implied that |Vi| or |Vk| may be written
simply as Vi or Vk.
Load
V 1 =1 p.u. (1+ j0.8 ) p.u.
1=0 2
j0.2
2 -j5 j5
G X = V , YBus=
2 j5 -j5
322
Solution:
We note that there is one PQ (NPQ = 1) busbar and no PV (NPV = 0) busbars, thus there are two variables in our
equation.
The balance equations for bus 2, using equations 12.35 and 12.36 are:
PG2 = 0, PLi = 1
Noting that G22 = 0:
[ ][
¶P2(X)
_ ¶P2(X)
_
_
¶T2
¶Q 2
(X) _
¶V2
¶Q 2
(X)
5V cos T
2 2
5 sin T2
= 5V2 sin T 2 10V – 5 cos
2
T2 ]
¶T2 ¶V2
X(0) = [ VT] = [ 01 ]
Then:
[
ƒ(X(0)) =
5V2sin T2 + 1
–5V2cos T2 + 5V22 + 0.8 ]
1
= 0.8 [ ]
J(X ) = [ ]
5V2cos T2 5sin T2
(0)
5V2sin T2 10V2 – 5cos T2
= 50 05 [ ]
Now:
= [ 01] – [ 0.2
0 0.2 ] [ 0.8 ] = [ 0.84 ]
0 1 –0.2
323
ƒ(X(1)) = [–5(0.84)5(0.84)
cos (–0.2) + 5(0.84) + 0.8 ] [ 0.2117 ]
sin (–0.2) + 1
2 = 0.1656
= [ –0.8344 3.4997 ]
4.1163 –0.9933
ƒ(X(2)) =[–5(0.7656)5(0.7656)
cos(–0.2581) + 5(0.7656) + 0.8 ] [ 0.0296 ]
sin(–0.2581) + 1
2 = 0.0225
) = [ 5(0.7656) cos(–0.2581)
5(0.7656) sin(–0.2581) 10(0.7656) – 5 cos (–0.2581) ]
5 sin (–0.2581)
J(X(2)
= [ –0.9774 2.8217 ]
3.7011 –1.2767
= [ –0.2581
0.7656 ] [ –0.97748 2.8217 ] [0.0225
0.0296 ]
–1
– 3.7011 –1.2767
= [ –0.2692
0.7513 ]
ƒ(X(3)) = [–5(0.75135(0.7513
cos(– 0.2692) + 5(0.7513) + 0.8 ] [ 0.00105 ]
sin (–0.2692 + 1
2 = 0.0092
At the third iteration, we find that V2 = 0.7512 p.u., and T2 = − 0.2692 radians (− 15.4 degrees).
Figure 12.19 shows the network solved by a power system analysis package (NEPLAN) with the results in
Table 12.4. The results are, V2 = 0.7507, and T2 = -15.5 degrees. With quite good convergence at just three
iterations, this shows the power of the NR method.
324
Figure 12.20 shows a load flow performed on a computerised analysis package, with the results in
Table 12.5.
325
Overloads
Nodes %
(lower)
N440 75.07
326
A
B Load
4. Use a power system analysis package to compare the results you obtained in question 3.
5. Use a power system analysis package to produce a load flow for Figure 12.22 (see page 326). The
base MVA is 100, all other parameters are in per unit. Compare with the solution given in Figure 12.23
(see page 327).
327
328
329
13.1 Introduction
When the currents and voltages in a three-phase circuit are unbalanced, it is not easy to analyse the circuit.
Unbalanced systems arise due to faults and uneven loading. The method of symmetrical components is a
useful analytical tool to solve such circuits and networks. It involves converting a three-phase unbalanced
network into a set of three balanced networks, which are then easier to solve. Through this conversion we
are also able to discover ‘hidden’ information about the network and we will be able to take appropriate
action if necessary.
330
N-Eye Vc2
Va1
P-Eye
Negative Sequence
Vb2
Va0
Vb0
Vb1 Vco
Vc1
Zero Sequence
Positive Sequence
We can re-create the unbalanced sets of currents in Figure 13.1 by adding the sequences in Figure 13.2 as
follows:
Va = Va0 + Va1 + Va2 (13.5)
Vb = Vb0 + Vb1 + Vb2 (13.6)
Vc = Vc0 + Vc1 + Vc2 (13.7)
The above also works for unbalanced currents as follows:
Ia = Ia0 + Ia1 + Ia2 (13.8)
Ib = Ib0 + Ib1 + Ib2 (13.9)
Ic = Ic0 + Ic1 + Ic2 (13.10)
We note in the above equations that from our definitions, Ia0 = Ib0 = Ic0 so we can replace Ib0 and Ic0 with Ia0.
We can also replace, Ib1 with a2Ia1 and Ic1 with aIa1. Similarly, we can replace Ic2 with a2Ia2 and Ib2 with aIa2.
This is shown diagrammatically in Figure 13.3.
331
Ia1
Va1
Ib1 =a2I
a1
Ic1 =aIa1
Vb1=a2V
a1
Vc1 =aV a1 Ia2
Note that all the unbalanced currents have now been expressed in terms of the sequence components of
phase a. Thus once the sequence components of one phase (usually phase a, or the RED phase) are known
(Figure 13.3), the other phase currents can easily be determined from the above equations.
Also, if we assume that phase a is always the reference, then we can simplify the subscripts as follows:
Ia0 = I0; Ia1 = I; Ia2 = I2 (13.11)
We can then express the equation as follows:
Ia = I0 + I1 + I2 (13.12)
Ib = I0 + a2I1 + aI2 (13.13)
Ic = I0 + aI1 + a2I2 (13.14)
This can be expressed in matrix form as follows:
[] [ ][ ]
Ia 1 1 1 I0
Ib = 1 a2 a I1 (13.15)
Ic 1 a a2 I2
The above expression allows us to synthesise sequence values into phase values. Sometimes we need to
decompose a phase value into its sequences. We can do this by inverting the above matrix.
[] [ ] []
I0 1 1 1 –1 Ia
I1 = 1 a2 a Ib (13.16)
I2 1 a a2 Ic
332
That is:
[] [ ][ ]
I0 1 1 1 Ia
I1 = _
1
1 a a2 Ib (13.17)
3
I2 1 a2 a I
c
Or, alternatively:
Example 13.1
The phases of a Y-connected generator are as follows, related to the neutral:
Va = 240∠0°
Vb = 240∠–120°
Vc = 240∠120°
Find the symmetrical components of phase a.
Solution:
[] [ ][ ]
V0 1 1 1 Va
V1 = _
1
1 a a2 Vb
3
V2 1 a2 a V
c
[] [ ][ ]
V0 1 1 1 240∠0
V1 = _
1
1 a a2 240∠–120
3
V2 1 a2 a 240∠120
333
Example 13.2
The phases of a generator are as follows:
Ia = 15∠–90°
Ib = 20∠–114°
Ic = 14∠0°
Find the symmetrical components of phase a.
Solution:
Using:
[] [
1 1 1 Ia
][ ]
I0
I1 = _
1
1 a a2 Ib
3
I2 1 a2 a I
c
Ia0 = 11.26∠–80°
Ia1 = 9.39∠–62.8°
Ia2 = 7.67∠144.6°
Example 13.3
Find the symmetrical components of phase a. Given:
Ia = 0∠0°
Ib = 20∠–120°
Ic = 15∠36°
Solution:
Ia0 = 2.92∠–75.9°
Ia1 = 8.74∠–34.7°
Ia2 = 11.11∠135.3°
Notice in the above example that even when Ia is zero, it has sequence components. Also the line currents
into a delta connection do have a zero sequence component, since the line currents must add to zero
I0 = _31(Ia + Ib + Ic). Similarly, if the line currents are flowing into a Y-connected load without a neutral wire
and with ungrounded neutral, the line current will have no zero sequence component (Kirchoff’s Junction
Law).
334
Example 13.4
The following was determined for a three-phase cable. Investigate the fault on the cable (find the line
currents and determine the type of fault). Given:
Ia0 = 0∠0°
Ia1 = –j500°
Ia2 = j500°
Solution:
[] [ ][ ]
Ia 1 1 1 I0
Ib = 1 a2 a I1
Ic 1 a a2 I2
[] [ ][ ]
Ia 1 1 1 0
Ib = 1 a2 a –j500
Ic 1 a a2 j500
Ia = [0 – j500] = 0
Ia = 0, Ib = 866∠–180, Ic = 866∠0.
Phase a current is 0, and this is a b-c fault.
335
• a zero sequence
• a positive sequence
• a negative sequence network.
To simplify the analysis, it is better to reduce these networks into their Thevenin equivalents as in Figure 13.4.
336
sequence network. These positive sequence impedances are the same ones we are familiar with and they form
the basic data for transmission lines and electric motors among other components.
EA
If
ZF
N
EB
EC
Ib =0
Ic =0
337
Thus:
I
I0 = _31 (Ia + Ib + Ic) = _
3
a
Ia
I1 = _31 (Ia + a2Ib + aIc) = _
3
Ia
I2 = _31 (Ia + aIb + a2Ic) = _
3
And:
I
I0 = I1 = I2 = _
3
a
Since the magnitude and direction of all the sequence currents of Ia are the same, we can deduce that the
sequence voltages behind them are in series. Remember that in the positive sequence network, the source
generator is present and we can represent this network as in Figure 13.6 (a). The negative and zero sequence
networks consist only of Z2 and Z0 respectively (Figure 13.6 (b) and (c)).
I1
I2
Ea1=E a I0
Z1 Z2 Z0
Va1 Va2
Va0
Next, we connect all the networks in a series circuit carrying the same current as in Figure 13.7.
For transmission lines, Z2, the negative sequence impedance, is equal to the positive sequence impedance.
The calculation of sequence impedances for lines is usually complicated by mutual inductance effects.
The combined network is shown in Figure 13.7.
Vf = Va = Ia Zf,
But Ia = 3I1, therefore:
Vf = 3I1Zf = I1(3Zf).
Therefore, the fault impedance can be represented as 3Zf.
338
I1
Ia
3
EA
Z1
3Z f
Va =V f
Va1
Z2
Va2
Z0
Va0
Ea = I1(Z1 + Z2 + Z0) + Vƒ
If the generator is grounded through a neutral impedance Zn and has zero sequence impedance Zgo, then we
can combine them in Z0 using:
Z0 = Zgo + 3Zn
So that Equation 13.22 becomes:
3E
Ia = ____
a
(13.22a)
(Z1 + Z2 + Zg0) + 3(Zn + Zƒ)
If the fault occurs at a significant distance from the generator terminals such that we have to include line
impedance, Zl, can be added to Zf. The factor of 3 arises from examining Figure 13.8 where we observe
(Kirchoff’s Current Law) that the diagram on the left can be replaced with the one on the right.
339
Ia0
I0
Ib0
Ic0
Zn 3Zn
V=3Ia0Zn V=I03Zn
Example 13.5
A resistive 0.05 : single line-to-ground (SLG) fault occurs on three-phase system supplied by an 11 kV
(line-to-line) generator. The parameters of the generator are as follows, Z1 = 0 + j0.5, Z2 = 0 + j0.2,
Zg0 = 0 + j0.1. The neutral is grounded with Zn = 0 + j0.2.
Calculate the fault current.
Solution:
This is a direct application of Equation 13.22a. Assuming that phase a is faulted then:
3E
Ia = ___
a
Z1 + Z2 + Zg0 + 3(Zn + Zƒ)
3_
11_
Ia = ____
3 √
kA
j0.5 + j0.2 + j0.1 + 3(j0.2 + 0.05)
= 13.6∠ – 84 kA
340
Ia
A
Ea
Ec Eb
Ib
B
C
Ic
Figure 13.9: Generator with a b-c fault
For this fault, Ia = 0 and Ib = -Ic, which are substituted in Equation 13.17 to form:
[] [ ][ ]
I0 1 1 1 0
I1 = _
1
1 a a2 Ib
3
I2 1 a2 a –Ib
From which:
I0 = 0
Ib
I = j_ _
1 √3
I
I2 = – j__
b
(13.23)
√3
From which, I1 = –I2.
Substituting in Equation 13.15:
[] [ ][ ]
Ia 1 1 1 0
Ib = 1 a2 a I1
Ic 1 a a2 –I1
From which:
_
Ib = – jI1√3 = –Ic (13.24)
Where:
Ea
I1 = _
Z +Z
(13.25)
1 2
341