Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Power Quality Monitoring of a 1.

1 MW
Photovoltaic Power Plant
Arash Anzalchi and Arif Sarwat
College of Electrical and Computer Engineering
Florida International University
Miami, Florida 33174
Email: asarwat@fiu.edu

Abstract—In 1982, IEEE standard 519 was first released and TABLE I
then updated in 2014. It sets some rules and steady state L OW- VOLTAGE S YSTEM C LASSIFICATION AND D ISTORTION L IMITS [5]
limitations on Total Harmonic Distortion (THD) with reference
to both current and voltage at the Point of Common Coupling Special General Dedicated
(PCC). However, exceeding these boundaries may be encountered Applications1 System System2
by transient conditions. IEEE Standard 1547 was published in Notch Depth 10% 20% 50%
THD (voltage) 3% 5% 10%
2003 and the latest amendment was issued in 2014. This standard
1- Special Applications include hospitals and airports.
contains power quality, response to unusual situations, and in- 2- A dedicated system is exclusively dedicated to the converter load.
stallation assessment. The specified requirements are essential for
interconnection of distributed resources (DR), including power
inverters/converters and synchronous generators. The standards TABLE II
are valid to all DR technologies, with combined capacity of M AXIMUM C URRENT D ISTORTION IN P ERCENT OF C URRENT [5]
10 MVA or less at the PCC, connected to secondary and/or
primary distribution voltages. This paper presents monitoring Individual harmonic order h (odd harmonics) Percent (%)
and assessment of a 1.1MW photovoltaic power plant at Florida h <11 4.0
11<h <17 2.0
International University, Miami, Florida. The assessment criteria 17 <h <23 1.5
were the IEEE 519 and 1547. Revolution power quality recorder 23 <h <35 0.6
and AlsoEnergy power track software captured the harmonics 35 <h 0.3
and voltage data with resolution on 1 minute. It concluded that at Total demand distortion (TDD) (up to 50 harmonic) 5.0
current level of photovoltaic penetration (16%), Current THDs
violates the 5% limit value at the Point of Common Coupling
(PCC). Moreover, except from a few short duration voltage
impulses, no voltage violation has been observed. reference to both current and voltage at the Point of Common
Coupling (PCC). However, exceeding these boundaries may
I. I NTRODUCTION be encountered by transient conditions. IEEE Standard 1547
The proliferation photovoltaic (PV) power generation sys- was published in 2003 and the latest amendment was issued
tems in the distribution power grid motivate utilities to monitor in 2014 [4]. This standard contains power quality, response to
the power quality (PQ) effects of these renewable power unusual situations, and installation assessment. The specified
generators in the electrical networks. The power quality may requirements are essential for interconnection of distribut-
cause voltage fluctuations and flicker, DC injection, harmon- ed resources (DR), including power inverters/converters and
ic emission, over voltages, and harmonics at the switching synchronous generators. The standards are valid to all DR
frequency [1], [2]. Nowadays most companies rely on sophis- technologies, with combined capacity of 10 MVA or less at
ticated equipment to be able to compete other competitors. the PCC, connected to secondary and/or primary distribution
This equipment could be affected some power quality issues voltages. The power quality concept has always been oversim-
which are undetectable by naked eyes. The benefits of high plified and misunderstood, but due to a significant increase
power quality of the power system are optimizing the relia- in the use of sensitive electronic devices and sophisticated
bility of the systems, early prediction of incipient problems, data management devices, the assessment of power quality
decreasing the energy expenditure, prevent power outages due has become an inevitable task.
to hidden disturbances, assurance of data integrity and reduced Many researchers have done power quality monitoring and
corrupt data in smart grids, etc. It is very difficult to quantify assessment. In [6] the effect of photovoltaic power generation
the power quality concerns since they are different by the on current harmonics and voltage variations were investigated.
interaction between susceptible equipment and power quality. This paper found a correlation between the generated power
When ”good” power quality for one equipment could be ”bad” and harmonic indices. A thorough power quality analysis for
for another one [3]. Therefore, the best assessment criteria three different PV power plants with 4 MW, 1 MW , and 5MW
are standards. In 1982, IEEE standard 519 was first released capacities has been carried out by [7]. In this study 3 years of
and then updated in 2014. It sets some rules and steady supply interruption and voltage dip data has been collected for
state limitations on Total Harmonic Distortion (THD) with three years and the observed disturbances compared to Grid-

978-1-5386-7703-2/18/$31.00 ©2018 IEEE


1.4 MW Solar Canopy at FIU College of Engineering and
Computing. Point of
Common
Coupling
(Connected to
23Kv feeder)

Transformer
SMA Inverters
KVA 2000 -
Energy Main (Sunny Tripower
LV480V/277 -
Meter Disconnect 24000TL-US)
%Z 5.72

Combiner box
for the inverter

(a) (b) (c)

AC Disconnect
Box
Data Acquisition System
(DAS) with Capability of
Wireless Transmission of
Data

(d) (e) (f)


Fig. 1. PV Plant Components: a) 4460 PV modules of three different types but each with rated power around 315W, b) Transformer, Energy meter, and
Main dosconnect at the Point of Common Coupling(PCC), c) Smart field inverters, d) Revolution Wireless Power Quality Recorder, e) AC disconnect box
which is connected to the AC output of the inverter, f) DAS that measures the multivariate time-series data from inverters, meter and weather station and
securely stores in a cloud server.

Code requirements. Monitoring of power quality impacts of of solar panels are installed in this PV power plant. Fig. 1
a PV power generator has been conducted by [8]. Trends, represents the Point of Common Coupling (PCC), where the
waveforms and statistical analysis of the measurements was PV system is connected to the distribution feeder.
provided by this research. The power quality of transient
variation in high solar and load conditions was presented in Although the substation services eight feeders, this chapter
[9]. deals with the impact of the plant on the feeder that the
PV plant description and case study scope is This paper PV plant is connected to. The plant comprises: a) 4, 460 PV
presents monitoring and assessment of a 1.1MW photovoltaic modules of three different types, each with rated power around
power plant at Florida International University, Miami, Flori- 315W ; b) 46 smart string inverters, each of 24kW size, and
da. The assessment criteria were the IEEE 519 and 1547. Volt- related combiner boxes shown in Fig. 1 (d); c) a local weather
age and current distortion classifications are shown in Table station that records irradiance and both ambient as well as
I and II. Revolution power quality recorder and AlsoEnergy module temperature; d) one cluster controller for monitoring
power track software captured the harmonics and voltage data. the string inverters in real-time; e) an Elkor production meter
The rest of this paper is organized as follows. First, PV plant to record the plant’s net energy production (Fig. 1 (b));
components are described and case study scope is presented. f) Panel boxes for testing and disconnection, which have
Then, real results from the PV power plant are illustrated and different breakers for each inverter module along that column;
analyzed. The paper is concluded in the last section. g) a SCADA controller at the plant-level that interacts with
the cluster controller; h) Revolution Wireless
R Power Quality
II. T EST- BED D ESCRIPTION AND C ASE S TUDY Recorder connected to the lower side of transformer at PCC
In order to analyze the voltage profile and power quality and collects power quality data with a resolution of 1 minute
due to grid-tied PV, a comprehensive study was conducted from the plant including current and voltage THDs (Fig. 1
on a 1.1M W PV power plant, shown in Fig. 1 (a), tied to (d)); i) AC disconnect box connected to the AC output of the
a distribution feeder network in Miami, Florida. Three types inverter and has necessary protection devices like switch and
3W104
To feeder 8063
138 kV/ 0.3 Mile
23kV 3W116 1.7 Mile
56MVA
Feeder 8064

23 kV/480V
Δ Y 3W128

Y
To feeder 8063

YY
3W145
To feeder 8063

1.1 MW Solar
Flagami FPL Canopy at FIU
Substation

Fig. 2. Single Line Diagram of concerned system.

fuse (Fig. 1 (e)) ; and j) A Data Acquisition System (DAS)


that measures the multivariate time-series data from inverters,
meter and weather station and securely stores values in a cloud
server (Fig. 1 (f)). The plant is currently at a 15% penetration
into the grid, with a peak generation of 1.1M W on a clear,
bright and sunny day.
Effective voltage profile analysis and power quality study
are multi-step approaches which require reviewing the feeder
monitoring criteria recommended by grid code requirements
set by IEEE standard 1547.
Fig. 3. Current THD variation by Time and PV Power Production. (Data
A. Placement of Revolution imported from Provision Power Quality meter).

The most critical question to define compliance with IEEE


519 is, ”Where is the best point to take the most precise
measurements?” As said by the standard, the point of common capacity). As it can be seen that the total current THD is highly
coupling (PCC) is the best place to take all the measurements, sensitive to changes in irradiance but the total voltage THD
since this is the nearest utility side point of the customer’s does not maintain such a strong relation with the same (Fig.
service where a new utility is or could be supplied, usually 4). During the period of Feb 28, 2017 to July 27, 2017 voltage
at a substation or transformer. If the power quality meter THD was always within the IEEE standards limit. However,
is going to be installed at a transformer, the PCC can be some violations, less than 0.3% noticed between March 15 and
on either the secondary or the primary side. However, as March 17, 2017. Nevertheless, these events happen at night
the secondary is close to the inverters and renewable power time, when no PV generation is available, or in the morning,
generators that are main sources of distortion, it is suggested when the PV power output is still too low without any high
that all measurements be read from the secondary to confirm fluctuations.
compliance.
B. Voltage Measurement
III. R ESULTS AND A NALYSIS The PV plant has been operational from July 19, 2016, and
Based on the review of grid code requirements different has since generated a cumulative energy of more than 1GW h.
feeder monitoring criteria were elicited. It is noteworthy that The top graph in Fig. 5 shows the 60 cycle average of
the concerned feeder, which serves 700 residential and 200 voltage variations by Time and PV power production for Feb
commercial customers, has three capacitor banks, one voltage 28, 2017 to July 27, 2017. The lower graph is the side view
regulator, and two transformers. Following subsections look at of the top graph. It can be seen that voltage does no exceed
harmonics and voltage profile analysis. limits by when PV power output is beyond 800 kW. This is
opposite of what expected in high PV penetration. Therefore
A. Recording Harmonics the voltage violations are not because of PV installation.
THD is not the best measure of PV-induced harmonics, A time-series profile of the plant’s current and voltage from
since the fundamental current is reduced by PV generation, July 31, 2016 to July 29, 2017 is shown in Fig. 7, from
making harmonics larger by comparison and consequently which a seasonal pattern can be estimated. Immediately after
increasing THD values. The top graph in Fig. 3 shows the its commissioning, the plant experienced device failure issues
current THD variations by Time and PV power production due to which the data obtained was not of good quality (that is,
for Feb 28, 2017 to July 27, 2017. The lower graph is the it lacked consistency and accuracy). Hence, the initial few days
side view of the top graph. It can be further noted that the of operation, from July 19 through 31, 2016, were removed
current THD has an inverse relationship with the power output. from this analysis. It can be observed that the plant experiences
Furthermore, there are no current THD violations when the a higher generation between the months of April and Septem-
PV generation exceeds 451 kW (41% of nominal installed ber, while it showcases a lower production profile during the
Total Voltage
Distortion THD Limit
(IEEE 519)

April 2017

Fig. 5. Voltage variation by Time and PV Power Production. (Data imported


from Provision Power Quality meter).

Phase A Phase B Phase C

March 17, 2017 Friday 8:06 AM 8:57 AM


Short duration impulses

Prohibited Region
Fig. 4. Voltage THD variation by Time and PV Power Production. (Data
imported from Provision Power Quality meter).

winter months between November and January.The voltage


No Interruption Region (0.9 – 1.1 pu)
profile analysis under grid-integrated PV scenarios is examined
in this section. As shown in the left graph in Fig. 7, except No Damage
Region
from June 21, 2017 to July 13, 2017, the voltage profile was in
the IEEE 1547 ±5% limits (456V − 504V ). By a closer look
at selected days of that period (07/01/2017 − 07/13/2017), Fig. 6. ITIC (CBEMA Curve) of Photovoltaic power plant at FIU.
it has been concluded that the voltage violations happened at
the night time, therefore they are not due to PV generations.
The main cause of these fluctuations are the load profile of
the feeder. When the working hour ends around 18 : 00 and
problems for sensitive electronic devices or computers, but
employees start turning off the loads as computers, lights, air
not to the distribution feeder.
conditioners, etc. the voltages start increasing and reaches to
the maximum of 510 volts around 4 : 00. Then around 8 : 00 Voltage regulation can be a challenge when faced with PV
in the morning, when the employees go to their work places, systems producing variable amounts of power. Fig. 8shows the
the load increases and voltage starts decreasing. In another voltage profile considering the voltage regulator operations in
study the ITIC (Information Technology Industry Council) FIU PV Power plant on a weekday on March 2017. Keeping
and CBEMA (Computer Business Equipment Manufacturers track of tap changers and other voltage regulation devices is
Association) curve were generated to clearly represent Voltage important in the face of PV arrays that can increase the voltage
events. These curves define different regions based on the down-stream of the substation. At current 16% penetration
sensitivity of computer equipment to the input voltage. As operation of voltage regulators are related to load rather than
illustrated in Fig. 6, voltage events at the PCC may cause PV installation.
515 Voltage 4000
Current
5% limit (456-291 V) Voltage at PCC 510 3500
by P1547™/D4.0 V Current at PCC 3000
505

DC Bus Voltage (V)

AC Current (A)
2500
500
2000
495

07/10/2017

07/11/2017

07/12/2017

07/13/2017
1500
490
1000
485 500

480 0

0:00
3:45
7:30

2:15
6:00
9:45

0:45
4:30
8:15

3:00
6:45
11:15
15:00
18:45
22:30

13:30
17:15
21:00

12:00
15:45
19:30
23:15

10:30
14:15
18:00
21:45
Fig. 7. Photovoltaic Power Plant Voltage and Current at the PCC (By AlsoEnergy DAS).

Regulator renewable energy systems,” IEEE Transactions on Industry Applications,


Voltage Voltage Adjust vol. PP, DOI 10.1109/TIA.2017.2712783, no. 99, pp. 1–1, 2017.
Decrease increase [2] A. Anzalchi, M. Moghaddami, A. Moghaddasi, A. I. Sarwat, and A. K.
Rathore, “A new topology of higher order power filter for single-
phase grid-tied voltage-source inverters,” IEEE Transactions on Industrial
Regulator Electronics, vol. 63, DOI 10.1109/TIE.2016.2594222, no. 12, pp. 7511–
Adjust 7522, Dec. 2016.
[3] C. SANKARAN, Power Quality. Library of Congress Cataloging-in-
Publication Data: CRC PRESS, 2002.
[4] A. Anzalchi and A. Sarwat, “Overview of technical specifications for grid-
connected photovoltaic systems,” Energy Conversion and Management,
vol. 152, DOI https://doi.org/10.1016/j.enconman.2017.09.049, no.
Supplement C, pp. 312 – 327, 2017. [Online]. Available:
Fig. 8. Voltage profile considering the voltage regulator operations in FIU http://www.sciencedirect.com/science/article/pii/S0196890417308737
PV Power plant on a weekday on March 2017. [5] “Ieee draft recommended practice for establishing methods and proce-
dures that provide supplemental support for implementation strategies
for expanded use of ieee standard 1547,” IEEE P1547.8/D8, July 2014,
pp. 1–176, Jun. 2014.
IV. C ONCLUSION [6] N. Golovanov, G. C. Lazaroiu, M. Roscia, and D. Zaninelli, “Power
This paper presents power quality monitoring results of an quality assessment in small scale renewable energy sources supplying
distribution systems,” Energies, vol. 6, DOI 10.3390/en6020634,
1.1 MW Photovoltaic power plant installed at Florida Interna- no. 2, pp. 634–645, 2013. [Online]. Available: http://www.mdpi.com/
tional University. Site description and list of components are 1996-1073/6/2/634
provided. Base on the analysis, steady state voltage violations [7] A. Honrubia-Escribano, T. Garcia-Sanchez, E. Gomez-Lazaro, E. Muljadi,
has been occurred on Jun 20 to Jul 16 (Over-voltages). How- and A. Molina-Garcia, “Power quality surveys of photovoltaic power
plants: characterisation and analysis of grid-code requirements,” IET
ever, some spikes happen during the period of study, which Renewable Power Generation, vol. 9, DOI 10.1049/iet-rpg.2014.0215,
were not because of PV installation. Based on ITIC curves no. 5, pp. 466–473, 2015.
momentary voltage spikes can cause problems for sensitive [8] A. R. Oliva, J. C. Balda, D. W. McNabb, and R. D. Richardson, “Power-
electric devices and computers, but not to the grid.Voltage quality monitoring of a pv generator,” IEEE Transactions on Energy
THD Violation only happens on phase and they were below Conversion, vol. 13, DOI 10.1109/60.678984, no. 2, pp. 188–193, Jun.
1998.
5.3%. Voltage THDs may not cause major problems in the
[9] S. Patra, N. Kishor, S. R. Mohanty, and P. K. Ray, “Power quality
Feeder. However, current THD has an inverse relationship assessment in 3-phase grid connected pv system with single and dual
with PV power production. When PV production is lower than stage circuits,” International Journal of Electrical Power & Energy
451kW, current THDs exceed 5% limit the IEEE 1547. Systems, vol. 75, DOI http://dx.doi.org/10.1016/j.ijepes.2015.09.014, pp.
275 – 288, 2016. [Online]. Available: http://www.sciencedirect.com/
R EFERENCES science/article/pii/S0142061515003968

[1] A. Anzalchi, M. Moghaddami, A. Moghadasi, M. M. Pour, and A. Sarwat,


“Design and analysis of a higher order power filter for grid-connected

You might also like