Professional Documents
Culture Documents
المبادل الحراري
المبادل الحراري
Fundamentals
Issue 7 and Volume 121.
7.12.17
By Brad Buecker
This article examines important cooling tower heat transfer fundamentals, and
modern methods for maintaining proper chemistry control in cooling systems.
A very important concept for understanding cooling tower heat transfer is that of
“wet bulb” temperature. Consider a warm summer day with 90°F shade
temperature at 40 percent relative humidity. A standard thermometer would
naturally read 90o, which is the “dry bulb” temperature. Now, attach another
thermometer alongside the dry bulb thermometer but with a soaked piece of cloth
around the bulb of the second thermometer, and put both on a swivel such that
the thermometers can be swirled very rapidly through the air. This simple and
common device is known as a sling psychrometer. After a while, the dry bulb
thermometer will still read 90°F but the other thermometer will read 71.2°F. This
latter reading is the wet bulb temperature, and is the lowest temperature that can
be achieved by evaporative cooling.
No matter how efficient, a cooling tower can never chill the recirculating water to
the wet bulb temperature, and at some point costs and space requirements limit
cooling tower size. The separation in temperature between the chilled water and
wet-bulb value is known as the approach. The data below show the relative size
of a cooling tower for a range of approach temperatures.
The table indicates that a “standard” sized cooling tower should approach the wet
bulb temperature within about 15°F. The curve becomes asymptotic as approach
temperatures narrow. Thus, for any cooling tower application at some point the
law of diminishing returns takes over. This data is only for general consideration,
as the approach temperature may be significantly influence by several factors
including the type of cooling tower fill, which will be explored later in greater
detail.
The data needed to calculate heat transfer by air cooling and evaporation has
been compiled in a graph known as a psychrometric chart.
All versions of psychrometric charts are “very busy” and at times difficult to
follow, but a psychrometric chart provides data for the following parameters.
If any two properties of air are known, all of the other properties can be
determined. Programs are available on-line that will calculate psychrometric
parameters with a few simple user inputs.
At this point, we will populate Figure 1 with some real-world data and calculate
the mass flow rate of air needed to cool 150,000 gpm of tower inlet water to the
desired temperature, and also calculate the water lost by evaporation.
The first step is to determine the energy balance around the tower.
ma = mass flow rate of dry air ha = enthalpy of dry air streams hw = enthalpy of
water streams
Utilizing algebra, the fact that ma1 = ma2, and that a mass balance on the water
flow is m4 = m3 – (w2 -w1)*ma, where w = humidity ratio; the energy balance
equation can be rewritten in the following form.
h2 = 52.5 Btu/lbm
So, with an inlet cooling water flow rate of 150,000 gpm (1,251,000 lb/min), the
calculated air flow is 1,248,000 lb/min, which by chance in this case is very close
to the cooling water flow rate. (Obviously, the air flow requirement would change
significantly depending upon air temperature, inlet water temperature and flow
rate, and other factors, and that is why cooling towers typically have multiple
cells, often including fans that have adjustable speed control.)
Utilizing the data above, m4 = 146,841 gpm. Thus, the water lost to evaporation
is, m3 – m4 = 3,159 gpm
This is due to the fact that the latent heat of evaporation at common atmospheric
conditions is close to 1,000 Btu/lbm. Thus, as water evaporates it carries away a
great deal of heat.
E = (f * R * DT)/1000, where
f = A correction factor that helps to account for sensible heat transfer, where
f (average) is often considered to be 0.65 to 0.85, but will rise in summer and
decline in winter.
The factor of 1,000 is, of course, the approximate latent heat of vaporization
(Btu/lb) of water. To check the general accuracy of this calculation, consider the
previous problem we solved in detail. Evaporation was 3,159 gpm with a
recirculation rate of 150,000 gpm and a range of 27°F. This gives a correction
factor of 0.78, which is quite in line with where ƒ should be for the conditions
shown.
Liquid-to-Gas Ratio
A very important factor with regard to cooling towers or other processes of this
type, including wet flue gas scrubbers, is the liquid-to-gas ratio (L/G). This
parameter can also be evaluated from Equation 1, where the enthalpy of the
water streams is simply the heat capacity of the water multiplied by the
temperature. Designating ma = G and mw = L from Equation 1 transforms it to:
Cp*L3*t3 + G*ha1 = Cp*L4*t4 + G*ha2 Eq. 5
We know that L4 = L3*G(w2 – w1), and using some simplifying algebra, elimination
of a negligible flow term, and that tw2 – tw1 is the “Range” between inlet and
outlet cooling water temperature, Equation 5 reduces to:
Thus, it can be seen that the heat transfer is significantly influenced by the liquid-
to-gas ratio. So, the more that liquid/gas interaction can be enhanced, the better
the heat transfer properties.
This explains the intensive past and continuing research into cooling tower fill
design. Most towers now are equipped with some variety of film fill.
As the name film fill implies, the material induces the incoming return water to
form a film that greatly increases its surface area. Critical to proper performance
of film fill are correct design and maintenance of the water distribution system
above the fill.
Also critical, and a subject that will be covered in a future article, is cooling water
chemical treatment to prevent fill fouling, especially from microbiological colonies
and silt. Not only will fouling inhibit heat transfer,
Author
Brad Buecker is a senior process specialist in the Water Technologies group of
Kiewit Engineering Group Inc.