GTX116-P+ Placement

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Process Color RGB: R=237 G=28 B=36 Process Color RGB: R=0 G=0 B=0

Web Safe: R=36 G=99 B=46 Web Safe: R=0 G=0 B=0

Hexadecimal color : #ED1C24 Hexadecimal color : #000000

GTx116-P+
HUE=0º Saturation=80% Brightness=100% HUE=344º Saturation=11% Brightness=0%

Advantage 3 GOLD SERIES


®

I-P Units
a measurable difference!
High-performance Airflow Measurement
with Temperature & Alarm Capability PLACEMENT
GUIDE
GTx116-P+ DUCTED AND PLENUM APPLICATION PLACEMENT GUIDE

Airflow A A Airflow Airflow A A Airflow Airflow A A Airflow


M M M M M M
D D D D D D

3D . 1.5D .
0.75D 0.75D 1.5D 0.75D

Unvaned Elbows Vaned Elbows Radius Elbows

AMD
Airflow

3D 0.5D 1.5D
Airflow

0.5D 0.5D
AMD
1D
0.5D 1.5D 0.5D 1.5D
A A A A
M Airflow M M Airflow
A A A A M
Airflow Airflow D D D D
M M M M
D D D D

Supply ‘T’ Fitting Return ‘T’ Fitting Reducing Transition Expanding Transition

2D A
A A Airflow M Airflow
Airflow Airflow A D
M M M
D D D
1D
1.5D 1D
Ducted Centrifugal and Ducted Centrifugal and
Supply Fan Plenum Return Fan Plenum Vane Axial Fan Discharge Vane Axial Fan Inlets

D = Simple Equivalent Diameter (Width + Height)


2

RECTANGULAR DUCT PROBE POSITIONING ROUND DUCT PROBE POSITIONING

Inside edge of duct


P_Probe_Duct_Plenum_Placement_R1E.vsd

# of # of
(including isulation) a b a
Probes Probes
a◦
a
Adj. Side (less internal ins.)

Probe 1

Probe 1
□ 1 ½X NA □ 1 NA
b
Probe Length

□ □
X=

2 ¼X ½X 2 90⁰
Probe(s) 2 to 4
Probe(s) 2 to 4

□ 3 ⅙X ⅓X □ 3 60⁰

Probe Length □ 4 ⅛X ¼X □ 4 45⁰

b = distance from probe 1 to 2, 2 to 3 and 3 to 4 a = angle from probe 1 to 2, 2 to 3 and 3 to 4


Note: # probes=2 shown for illustration
NOTES:
The GTx116-P+ sensor density will typically result in an installed accuracy of ±3% of reading or better over the entire calibrated range of airflow rates when loca-
tions meet or exceed EBTRON’s suggested guidelines.
Installed accuracy is the combined uncertainty of the measuring device and the sampling uncertainty that results from having a finite number of sensor nodes in
a velocity profile created by duct disturbances up and downstream of the measurement location.
EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com 1
GTx116-P+ OA HOOD, DAMPER AND LOUVER APPLICATION PLACEMENT GUIDE

Z
X Y

Damper
Probes A
M Damper
D

Intake Probes

Y
Hood AMD

Z
NOTES: X, Y = 6 in. MINIMUM
Airflow
Z = 12 in. MINIMUM NOTES:

X
X, Y = 6 in. MINIMUM
Z Airflow Z = 12 in. MINIMUM
12 in. Min
Z
X Y

X Y

A
Airflow M Damper
Probes
D
Airflow A
Probes M Damper
D

Fixed NOTES: X = 12 in. MINIMUM


Louver Y = 6 in. MINIMUM
P_Probe_Duct_Plenum_Placement_R1E.vsd

Z = 18 in. MINIMUM
Important: Actual plenum depth should be
determined based on louver data and maximum
KEY:
airflow rates to minimize water carry-over into the
X = Distance to upstream disturbance
intake system.
Y = Distance to downstream disturbance
NOTES: X, Y = 6 in. MINIMUM Z = Distance between disturbances
Fixed Louver Z = 18 in. MINIMUM

GTx116-P+ PROBE MOUNTING BRACKET STYLES

GTX116-P+_Placement_R1A

GTx116-P+ Probe with Insertion GTx116-P+ Probe with Stand Off GTx116-P+ Probe with Internal
Mounting Bracket Mounting Bracket Mounting Bracket

2 EBTRON • 1663 Hwy. 701 S., Loris SC 29569 • Toll Free: 800.2EBTRON (232.8766) • Fax: 843.756.1838 • Internet: EBTRON.com