VCB Manual Oper.

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

PRODUCT VHA PANEL WITH

PRESENTATION
HPA12 CIRCUIT
BREAKER


© ABB Ltd. - 1
01-04-06 -
VHA 12 PANEL

 Designed and type tested to


meet requirements of IEC 298
& 694 / IS:3427
 Air insulated indoor switchgear
 Metal clad construction
 Internal arc tested
 IP4X degree of protection
externally and IP2X between
compartments
 Independent exhaust vents for
all HT compartments


© ABB Ltd - 2
VHA 12 PANEL

 Integral Earthing Switch


optional
 Normal service conditions: Min
ambient temp:-5oC, Max
ambient temp:+40oC
 Up to 3000A in panel without
forced cooling
 Quality System Certification-
ISO 9001
 Environmental Management
System- ISO 14001


© ABB Ltd - 3
BREAKER COMPARTMENT

 Cassette mounted breaker


with isolated position on
cubicle front door
 Racking in/out of breaker from
test to service position and
vice-versa with cubicle door
closed only
 Mechanical interlock to
prevent racking in/out of
breaker, when breaker is in
closed position
 Live parts covered by
automatic shutters when
breaker is racked out


© ABB Ltd - 4
METERING COMPARTMENT

 Metering compartment with


numerical/static/electro-
magnetic relays, indicating
meters, lamp and control
switches
 Protection and measuring
apparatus customized as per
requirement


© ABB Ltd - 5
CABLE AND CT COMPARTMENT

 Spacious construction to
accommodate 1 set of CTs
and 2 runs of cables
 Option of rear extension to
accommodate extra CTs or
cables
 Adequate height for cable
termination


© ABB Ltd - 6
PT COMPARTMENT

 Withdrawable line PT provided


in the breaker panel
 Removable fuses mounted on
the PT
 Safety shutters between PT &
Cable compartment close
automatically on PT
withdrawal


© ABB Ltd - 7
BUSBAR COMPARTMENT

 Spacious busbar compartment


for adequate air clearances
 Option for busbar insulation
available
 Option for shrouds on joints
available


© ABB Ltd - 8
HPA BREAKER

 The HPA type circuit breaker


is designed and tested to meet
requirements of IEC 56 / IS :
13118
 SF6 gas used as insulation
and arc interruption medium
 Arc control and extinction
achieved by puffer principle
 Capable of interrupting small
magnetizing and capacitive
currents


© ABB Ltd - 9
HPA BREAKER

 Features of operating
mechanism
 O-C-O operation without
recharging
 Closing spring charged by
motor in less than 15secs
 Electrical anti-pumoing
 Provision for manual
recharging
 Synchronisation and fast auto
reclosure duty


© ABB Ltd - 10
HPA BREAKER

 The HPA series of CB are designed and type tested to meet the
requirements of IEC-60056 / IS:1318

 The HPA series of CB use SF6 gas as insulating and arc


interruption medium

 Arc interruption and control are achieved by puffer principle

 Short arc duration followed by rapid dielectric recovery

 Long electrical life, as the interruption system develops low arc


energy and contact wear is minimal

 Long mechanical life with study and proven operating


mechanism

- 10000 operations at no load



© ABB Ltd - 11

- 10000 operations at rated current


HPA BREAKER

 Operationally safe and reliable in wide range of operating


temperature
-5o to +40o c
 Capable of interrupting small magnetizing and capacitive currents
 Compact design with relatively light weight construction
 Features of operating mechanism
− O-C-O operation without recharging
− closing spring charged by motor in less than 15 secs.
− electrical anti-pumping
− provision for manual recharging
− synchronization and fast auto-reclosure duty


© ABB Ltd - 12
VHA PANEL CROSS SECTIONAL DWG


© ABB Ltd - 13
VHA 12 PANEL
TECHNICAL DETAILS

Description Unit Rating


Voltage kV 12
Frequency Hz 50
Current A 630, 1250, 1600, 2000,
2500, 3000, 4000
Short time withstand kA 40
current (for 3 secs)
Peak withstand current kAp 100
Insulation level kVrms/kVp 28/75
WidthxDepthxHeight mm 800x1370x2340
Weight with breaker (approx.) kg 1000
Degree of Protection-Enclosure IP4X


© ABB Ltd - 14
HPA12 CIRCUIT BREAKER
TECHNICAL DETAILS

Description Unit Rating


Voltage kV 12
Frequency Hz 50
Current A 1250, 1600, 2000, 2500, 3150
Breaking capacity kA 40
Short time withstand kA 40
current (for 3 secs)
Peak withstand current kAp 100
Insulation level kVrms/kVp 28/75
Operating sequence O-3min-CO-3min-CO/
O-0.3secs-CO-3min-CO
Weight (approx.) kg 190-225


© ABB Ltd - 15
INSTALLATIONS

OVER 25,000 PANELS INSTALLED


MAJOR
INSTALLATIONS AT:
 POWER PLANTS
 DISTRIBUTION UTILITIES
 STEEL PLANTS
 CEMENT PLANTS
 REFINERIES
VARIOUS INDUSTRIES & IN-
FRASTRUCTURE PROJECTS


© ABB Ltd - 16
SUCCESFULL INSTALLATIONS IN GENEARATIONS

Major installations of VHA 12S +HPA

POWER PLANT LOCATION SF6 SWGR INSTALLED


 MSEB ( CHANDRAPUR UNIT IV V &VII ,KORADI) (1989,95,99)- 593
 NTPC ( VINDHYACHAL 500MW)(1995) - 248
 NTPC ( TALCHER 4 X 500MW) (1999) - 451
 APSEB ( RAYALSEEMA 2 X 210 MW) (1998) - 235
 BSES DAHANU ( 2 X 250MW) (1994) - 163
 MPEB SGTPS (1997) - 179
 GIPCL (2 X 125 MW) (1996) - 110

Total SF6 panels installed in Generations in India - 4100Nos


ABB’s market share in Generation is 70% !!!

© ABB Ltd - 17
HPA – Arc Interruption principle

BBBBBBBB


© ABB Ltd - 19