Heat load sum up table

Cooling Heating Heat load per area


Floor
Qty.
Sys area
Room name Fl of Indoor SH Total Selected Time Total Selected Humid. Time Cooling Heating
-tem
rooms
[W] [Hr] [W] [kg/h] [Hr] [m2] [W/m2]

TMDV 1-TANG 1 1 1 1 17128 20275 21289 9 76.1 279.7


TMDV 2-TANG 1 1 1 1 9744 12708 13343 9 68.5 194.8
TMDV 3-TANG 1 1 1 1 9443 12205 12815 9 68.1 188.2
TMDV 4-TANG 1 1 1 1 13808 17737 18624 9 94.5 197.1
NHA TRE- TANG 1 1 1 1 13445 24558 25786 15 62.5 412.6
BAN QUAN LY TOA NHA 1 1 1 2836 3775 3964 13 45.4 87.3
SHCD 1 1 1 8485 15359 16127 15 35.8 450.5
SANH DOI 1 1 1 9992 11717 12303 15 39.7 309.9
SANH DOI VAN PHONG 1 1 1 10502 12231 12843 15 61.0 210.5
TMDV1-TANG 2 1 1 1 5261 8912 9358 9 47.8 195.8
TMDV2-TANG 2 1 1 1 13454 22955 24103 15 122.1 197.4
TMDV 4-TANG 2 1 1 1 6595 11725 12311 13 65.5 188.0
NHA TRE TANG 2 1 1 1 6853 18566 19494 16 66.2 294.5
VP CHO THUE 1-T3~9 1 1 1 19002 24061 25264 9 125.0 202.1
VPCT 2 TANG 3~9 1 1 1 16309 22559 23687 9 143.3 165.3
VPCT 3-TANG 3~9 1 1 1 21444 28472 29896 9 177.3 168.6
VPCT4-T3~9 1 1 1 10900 14709 15444 15 84.7 182.3
VPCT5-T3~9 1 1 1 8868 12445 13067 15 88.4 147.8
VPCT 6 T3~9 1 1 1 21694 28506 29931 16 159.4 187.8

Peak load of building 19 206622 305058 320311 15 1631.3 196.4

SH : Sensible heat

-1-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

TMDV 1-TANG 1 1 1 1 Office 76.1 3.6 8 Summer 200.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 183 0 129 426 11774 94 452 448 608 1766 1800 0 16620 1060 1994 19674
* 9 32.5 69.2 285 0 162 532 12017 118 454 448 608 1766 1800 0 17128 1062 2085 20275
10 33.9 63.4 409 0 197 647 10403 143 444 448 608 1766 1800 0 15813 1052 2142 19007
11 35.0 58.8 533 0 224 737 8008 163 430 448 608 1766 1800 0 13679 1038 2163 16880
12 35.8 55.5 631 0 244 802 7341 177 417 448 608 1766 1800 0 13209 1025 2168 16402
13 36.1 54.3 693 0 251 827 7777 183 411 448 608 1766 1800 0 13745 1019 2168 16932
14 35.9 55.2 721 0 247 811 8322 179 417 448 608 1766 1800 0 14294 1025 2174 17493
15 35.4 57.2 719 0 234 770 8308 170 424 448 608 1766 1800 0 14215 1032 2169 17416
16 34.6 60.4 704 0 214 704 7405 155 435 448 608 1766 1800 0 13196 1043 2156 16395
17 33.6 64.4 678 0 189 622 5771 137 443 448 608 1766 1800 0 11411 1051 2120 14582
18 32.5 69.2 641 0 162 532 1932 118 454 448 608 1766 1800 0 7399 1062 2085 10546

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-2-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

TMDV 2-TANG 1 1 1 1 Office 68.5 3.6 7 Summer 175.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 40 0 143 383 5372 85 451 392 532 1589 1600 0 9604 983 1901 12488
* 9 32.5 69.2 64 0 179 479 5335 106 452 392 532 1589 1600 0 9744 984 1980 12708
10 33.9 63.4 93 0 218 582 4387 129 444 392 532 1589 1600 0 8990 976 2030 11996
11 35.0 58.8 120 0 248 663 3098 146 431 392 532 1589 1600 0 7856 963 2049 10868
12 35.8 55.5 141 0 270 722 2724 160 419 392 532 1589 1600 0 7598 951 2053 10602
13 36.1 54.3 152 0 278 744 2694 164 414 392 532 1589 1600 0 7613 946 2052 10611
14 35.9 55.2 154 0 273 730 2482 161 419 392 532 1589 1600 0 7381 951 2059 10391
15 35.4 57.2 149 0 259 693 2169 153 426 392 532 1589 1600 0 7004 958 2055 10017
16 34.6 60.4 139 0 237 634 1741 140 435 392 532 1589 1600 0 6472 967 2042 9481
17 33.6 64.4 128 0 209 560 1221 124 443 392 532 1589 1600 0 5823 975 2010 8808
18 32.5 69.2 115 0 179 479 655 106 452 392 532 1589 1600 0 5115 984 1980 8079

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-4-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

TMDV 3-TANG 1 1 1 1 Office 68.1 3.6 7 Summer 175.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 34 0 0 381 5372 84 405 392 532 1580 1500 0 9343 937 1745 12025
* 9 32.5 69.2 55 0 0 476 5335 105 406 392 532 1580 1500 0 9443 938 1824 12205
10 33.9 63.4 79 0 0 579 4387 128 397 392 532 1580 1500 0 8645 929 1874 11448
11 35.0 58.8 103 0 0 659 3098 146 385 392 532 1580 1500 0 7478 917 1893 10288
12 35.8 55.5 120 0 0 718 2724 159 373 392 532 1580 1500 0 7193 905 1897 9995
13 36.1 54.3 130 0 0 740 2694 163 368 392 532 1580 1500 0 7199 900 1896 9995
14 35.9 55.2 132 0 0 725 2482 160 373 392 532 1580 1500 0 6971 905 1903 9779
15 35.4 57.2 127 0 0 689 2169 152 380 392 532 1580 1500 0 6609 912 1899 9420
16 34.6 60.4 119 0 0 630 1741 139 389 392 532 1580 1500 0 6101 921 1886 8908
17 33.6 64.4 110 0 0 557 1221 123 397 392 532 1580 1500 0 5483 929 1854 8266
18 32.5 69.2 99 0 0 476 655 105 406 392 532 1580 1500 0 4807 938 1824 7569

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-6-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

TMDV 4-TANG 1 1 1 1 Office 94.5 3.6 10 Summer 250.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 431 0 0 529 7419 117 562 560 760 2192 2200 0 13448 1322 2493 17263
* 9 32.5 69.2 681 0 0 661 7368 146 563 560 760 2192 2200 0 13808 1323 2606 17737
10 33.9 63.4 1000 0 0 803 6059 177 551 560 760 2192 2200 0 12991 1311 2678 16980
11 35.0 58.8 1317 0 0 915 4278 202 534 560 760 2192 2200 0 11664 1294 2705 15663
12 35.8 55.5 1578 0 0 996 3761 220 517 560 760 2192 2200 0 11507 1277 2709 15493
13 36.1 54.3 1740 0 0 1027 3720 227 511 560 760 2192 2200 0 11666 1271 2709 15646
14 35.9 55.2 1793 0 0 1007 3428 222 517 560 760 2192 2200 0 11402 1277 2718 15397
15 35.4 57.2 1762 0 0 956 2994 211 527 560 760 2192 2200 0 10875 1287 2712 14874
16 34.6 60.4 1665 0 0 874 2404 193 540 560 760 2192 2200 0 10088 1300 2695 14083
17 33.6 64.4 1539 0 0 773 1686 171 550 560 760 2192 2200 0 9121 1310 2649 13080
18 32.5 69.2 1389 0 0 661 905 146 563 560 760 2192 2200 0 8053 1323 2606 11982

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-8-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

NHA TRE- TANG 1 1 1 1 Office 62.5 3.6 31 Summer 775.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 435 0 0 350 1693 77 371 1736 2356 1450 1500 0 7241 2727 7728 17696
9 32.5 69.2 639 0 0 437 2213 97 373 1736 2356 1450 1500 0 8072 2729 8079 18880
10 33.9 63.4 911 0 0 531 2675 117 365 1736 2356 1450 1500 0 8920 2721 8301 19942
11 35.0 58.8 1213 0 0 605 2980 134 353 1736 2356 1450 1500 0 9618 2709 8383 20710
12 35.8 55.5 1492 0 0 659 3154 146 342 1736 2356 1450 1500 0 10137 2698 8400 21235
13 36.1 54.3 1707 0 0 679 4037 150 338 1736 2356 1450 1500 0 11259 2694 8400 22353
14 35.9 55.2 1864 0 0 666 5367 147 342 1736 2356 1450 1500 0 12730 2698 8426 23854
*15 35.4 57.2 1979 0 0 632 6008 140 349 1736 2356 1450 1500 0 13445 2705 8408 24558
16 34.6 60.4 2054 0 0 578 5656 128 357 1736 2356 1450 1500 0 13102 2713 8351 24166
17 33.6 64.4 2089 0 0 511 4515 113 364 1736 2356 1450 1500 0 11914 2720 8213 22847
18 32.5 69.2 2064 0 0 437 941 97 373 1736 2356 1450 1500 0 8225 2729 8079 19033

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-10-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

BAN QUAN LY TOA NHA 1 1 1 Office 45.4 3.6 2 Summer 50.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 0 0 35 254 0 56 270 112 152 1053 1000 0 2510 422 499 3431
9 32.5 69.2 0 0 44 318 0 70 271 112 152 1053 1000 0 2597 423 521 3541
10 33.9 63.4 0 0 54 386 0 85 265 112 152 1053 1000 0 2690 417 535 3642
11 35.0 58.8 0 0 61 440 0 97 256 112 152 1053 1000 0 2763 408 541 3712
12 35.8 55.5 0 0 67 479 0 106 249 112 152 1053 1000 0 2817 401 542 3760
*13 36.1 54.3 0 0 69 493 0 109 245 112 152 1053 1000 0 2836 397 542 3775
14 35.9 55.2 0 0 67 484 0 107 249 112 152 1053 1000 0 2823 401 543 3767
15 35.4 57.2 0 0 64 459 0 101 253 112 152 1053 1000 0 2789 405 542 3736
16 34.6 60.4 0 0 58 420 0 93 259 112 152 1053 1000 0 2736 411 539 3686
17 33.6 64.4 0 0 52 371 0 82 264 112 152 1053 1000 0 2670 416 529 3615
18 32.5 69.2 0 0 44 318 0 70 271 112 152 1053 1000 0 2597 423 521 3541

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-12-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

SHCD 1 1 1 Office 35.8 3.6 18 Summer 450.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 25 0 118 200 1411 44 236 1008 1368 831 850 0 4487 1604 4888 10979
9 32.5 69.2 31 0 147 250 1844 55 236 1008 1368 831 850 0 5016 1604 5092 11712
10 33.9 63.4 41 0 179 304 2229 67 232 1008 1368 831 850 0 5509 1600 5221 12330
11 35.0 58.8 56 0 204 347 2483 77 225 1008 1368 831 850 0 5856 1593 5269 12718
12 35.8 55.5 74 0 222 378 2628 83 219 1008 1368 831 850 0 6074 1587 5278 12939
13 36.1 54.3 91 0 229 389 3364 86 216 1008 1368 831 850 0 6848 1584 5278 13710
14 35.9 55.2 113 0 224 381 4473 84 219 1008 1368 831 850 0 7964 1587 5293 14844
*15 35.4 57.2 135 0 213 362 5006 80 223 1008 1368 831 850 0 8485 1591 5283 15359
16 34.6 60.4 158 0 195 331 4713 73 228 1008 1368 831 850 0 8159 1596 5250 15005
17 33.6 64.4 176 0 172 293 3762 65 231 1008 1368 831 850 0 7157 1599 5170 13926
18 32.5 69.2 185 0 147 250 784 55 236 1008 1368 831 850 0 4110 1604 5092 10806

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-14-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

SANH DOI 1 1 1 Office 39.7 3.6 4 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 36 0 257 222 1764 49 261 224 304 921 900 0 4373 565 1087 6025
9 32.5 69.2 45 0 321 278 2305 61 262 224 304 921 900 0 5055 566 1132 6753
10 33.9 63.4 59 0 390 337 2786 75 257 224 304 921 900 0 5692 561 1161 7414
11 35.0 58.8 80 0 444 384 3104 85 250 224 304 921 900 0 6142 554 1171 7867
12 35.8 55.5 105 0 485 419 3242 92 243 224 304 921 900 0 6388 547 1173 8108
13 36.1 54.3 130 0 499 431 4090 95 240 224 304 921 900 0 7290 544 1173 9007
14 35.9 55.2 159 0 490 423 5748 93 243 224 304 921 900 0 8958 547 1177 10682
*15 35.4 57.2 191 0 465 402 6800 89 247 224 304 921 900 0 9992 551 1174 11717
16 34.6 60.4 225 0 425 367 6718 81 252 224 304 921 900 0 9861 556 1167 11584
17 33.6 64.4 254 0 376 325 5700 72 257 224 304 921 900 0 8772 561 1149 10482
18 32.5 69.2 273 0 321 278 1065 61 262 224 304 921 900 0 4043 566 1132 5741

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-16-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

SANH DOI VAN PHONG 1 1 1 Office 61.0 3.6 4 Summer 100.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 34 0 51 341 1644 75 363 224 304 1415 1500 0 5284 667 998 6949
9 32.5 69.2 42 0 64 427 2148 94 364 224 304 1415 1500 0 5914 668 1043 7625
10 33.9 63.4 56 0 77 519 2597 114 356 224 304 1415 1500 0 6502 660 1072 8234
11 35.0 58.8 76 0 88 591 2893 130 345 224 304 1415 1500 0 6917 649 1082 8648
12 35.8 55.5 100 0 96 643 3022 142 334 224 304 1415 1500 0 7142 638 1084 8864
13 36.1 54.3 124 0 99 663 3813 146 330 224 304 1415 1500 0 7984 634 1084 9702
14 35.9 55.2 151 0 97 650 5357 143 334 224 304 1415 1500 0 9537 638 1088 11263
*15 35.4 57.2 181 0 92 617 6337 136 340 224 304 1415 1500 0 10502 644 1085 12231
16 34.6 60.4 213 0 84 564 6261 125 349 224 304 1415 1500 0 10386 653 1078 12117
17 33.6 64.4 240 0 75 499 5312 110 355 224 304 1415 1500 0 9375 659 1060 11094
18 32.5 69.2 259 0 64 427 993 94 364 224 304 1415 1500 0 4976 668 1043 6687

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-18-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

TMDV1-TANG 2 1 1 1 Office 47.8 3.6 10 Summer 250.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 222 0 147 0 1791 59 284 560 760 1109 1200 0 5088 1044 2493 8625
* 9 32.5 69.2 356 0 184 0 1778 74 285 560 760 1109 1200 0 5261 1045 2606 8912
10 33.9 63.4 514 0 224 0 1462 90 279 560 760 1109 1200 0 5159 1039 2678 8876
11 35.0 58.8 667 0 255 0 1032 102 270 560 760 1109 1200 0 4925 1030 2705 8660
12 35.8 55.5 781 0 277 0 908 111 262 560 760 1109 1200 0 4946 1022 2709 8677
13 36.1 54.3 844 0 286 0 898 115 258 560 760 1109 1200 0 5012 1018 2709 8739
14 35.9 55.2 857 0 280 0 828 112 262 560 760 1109 1200 0 4946 1022 2718 8686
15 35.4 57.2 825 0 266 0 723 107 267 560 760 1109 1200 0 4790 1027 2712 8529
16 34.6 60.4 775 0 243 0 580 98 273 560 760 1109 1200 0 4565 1033 2695 8293
17 33.6 64.4 711 0 215 0 407 86 278 560 760 1109 1200 0 4288 1038 2649 7975
18 32.5 69.2 641 0 184 0 218 74 285 560 760 1109 1200 0 3986 1045 2606 7637

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-20-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

TMDV2-TANG 2 1 1 1 Office 122.1 3.0 24 Summer 600.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 207 0 180 0 3026 126 670 1344 1824 2833 2800 0 10516 2494 6518 19528
9 32.5 69.2 321 0 225 0 3391 157 672 1344 1824 2833 2800 0 11071 2496 6790 20357
10 33.9 63.4 459 0 273 0 3413 191 659 1344 1824 2833 2800 0 11313 2483 6962 20758
11 35.0 58.8 599 0 311 0 3204 218 640 1344 1824 2833 2800 0 11309 2464 7025 20798
12 35.8 55.5 711 0 339 0 3207 237 622 1344 1824 2833 2800 0 11471 2446 7038 20955
13 36.1 54.3 782 0 349 0 3841 244 615 1344 1824 2833 2800 0 12193 2439 7038 21670
14 35.9 55.2 818 0 342 0 4742 239 622 1344 1824 2833 2800 0 13118 2446 7058 22622
*15 35.4 57.2 821 0 325 0 5104 227 633 1344 1824 2833 2800 0 13454 2457 7044 22955
16 34.6 60.4 808 0 297 0 4703 208 647 1344 1824 2833 2800 0 12993 2471 7001 22465
17 33.6 64.4 780 0 263 0 3698 184 658 1344 1824 2833 2800 0 11902 2482 6893 21277
18 32.5 69.2 735 0 225 0 904 157 672 1344 1824 2833 2800 0 8998 2496 6790 18284

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-22-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

TMDV 4-TANG 2 1 1 1 Office 65.5 3.0 13 Summer 325.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 435 0 0 0 1996 67 359 728 988 1520 1500 0 6246 1347 3531 11124
9 32.5 69.2 691 0 0 0 1981 84 360 728 988 1520 1500 0 6504 1348 3678 11530
10 33.9 63.4 1008 0 0 0 1630 102 354 728 988 1520 1500 0 6488 1342 3771 11601
11 35.0 58.8 1321 0 0 0 1151 117 343 728 988 1520 1500 0 6337 1331 3805 11473
12 35.8 55.5 1567 0 0 0 1012 127 334 728 988 1520 1500 0 6454 1322 3812 11588
*13 36.1 54.3 1716 0 0 0 1000 131 330 728 988 1520 1500 0 6595 1318 3812 11725
14 35.9 55.2 1757 0 0 0 922 128 334 728 988 1520 1500 0 6555 1322 3823 11700
15 35.4 57.2 1714 0 0 0 805 122 339 728 988 1520 1500 0 6389 1327 3815 11531
16 34.6 60.4 1616 0 0 0 647 112 347 728 988 1520 1500 0 6123 1335 3792 11250
17 33.6 64.4 1490 0 0 0 454 99 353 728 988 1520 1500 0 5791 1341 3733 10865
18 32.5 69.2 1343 0 0 0 243 84 360 728 988 1520 1500 0 5418 1348 3678 10444

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-24-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

NHA TRE TANG 2 1 1 1 Office 66.2 3.0 33 Summer 825.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 388 0 0 0 0 68 328 1848 2508 1536 1500 0 5340 2836 8226 16402
9 32.5 69.2 566 0 0 0 0 85 329 1848 2508 1536 1500 0 5535 2837 8601 16973
10 33.9 63.4 805 0 0 0 0 104 322 1848 2508 1536 1500 0 5793 2830 8838 17461
11 35.0 58.8 1072 0 0 0 0 118 312 1848 2508 1536 1500 0 6074 2820 8924 17818
12 35.8 55.5 1322 0 0 0 0 128 302 1848 2508 1536 1500 0 6334 2810 8942 18086
13 36.1 54.3 1517 0 0 0 0 132 298 1848 2508 1536 1500 0 6533 2806 8942 18281
14 35.9 55.2 1670 0 0 0 0 130 302 1848 2508 1536 1500 0 6684 2810 8969 18463
15 35.4 57.2 1782 0 0 0 0 123 308 1848 2508 1536 1500 0 6789 2816 8950 18555
*16 34.6 60.4 1856 0 0 0 0 113 315 1848 2508 1536 1500 0 6853 2823 8890 18566
17 33.6 64.4 1892 0 0 0 0 100 321 1848 2508 1536 1500 0 6876 2829 8742 18447
18 32.5 69.2 1855 0 0 0 0 85 329 1848 2508 1536 1500 0 6824 2837 8601 18262

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-26-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

VP CHO THUE 1-T3~9 1 1 1 Office 125.0 3.3 13 Summer 325.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 301 0 183 0 11094 142 681 728 988 2900 3000 0 18348 1669 3241 23258
* 9 32.5 69.2 463 0 229 0 11505 177 683 728 988 2900 3000 0 19002 1671 3388 24061
10 33.9 63.4 662 0 279 0 10244 215 669 728 988 2900 3000 0 18028 1657 3481 23166
11 35.0 58.8 864 0 317 0 8233 245 647 728 988 2900 3000 0 16287 1635 3515 21437
12 35.8 55.5 1028 0 346 0 7691 267 627 728 988 2900 3000 0 15960 1615 3523 21098
13 36.1 54.3 1135 0 356 0 8385 275 619 728 988 2900 3000 0 16779 1607 3522 21908
14 35.9 55.2 1192 0 349 0 9466 270 627 728 988 2900 3000 0 17905 1615 3534 23054
15 35.4 57.2 1203 0 332 0 9836 256 639 728 988 2900 3000 0 18255 1627 3526 23408
16 34.6 60.4 1195 0 303 0 9003 234 655 728 988 2900 3000 0 17363 1643 3502 22508
17 33.6 64.4 1165 0 268 0 7185 207 667 728 988 2900 3000 0 15453 1655 3444 20552
18 32.5 69.2 1116 0 229 0 2101 177 683 728 988 2900 3000 0 10251 1671 3388 15310

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-28-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

VPCT 2 TANG 3~9 1 1 1 Office 143.3 3.3 15 Summer 375.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 262 0 279 0 7726 162 865 840 1140 3325 3500 0 16094 2005 4073 22172
* 9 32.5 69.2 420 0 348 0 7673 203 867 840 1140 3325 3500 0 16309 2007 4243 22559
10 33.9 63.4 607 0 423 0 6309 247 851 840 1140 3325 3500 0 15251 1991 4352 21594
11 35.0 58.8 787 0 482 0 4455 281 826 840 1140 3325 3500 0 13670 1966 4391 20027
12 35.8 55.5 922 0 525 0 3917 306 804 840 1140 3325 3500 0 13335 1944 4399 19678
13 36.1 54.3 997 0 541 0 3874 315 794 840 1140 3325 3500 0 13392 1934 4399 19725
14 35.9 55.2 1012 0 531 0 3570 309 804 840 1140 3325 3500 0 13087 1944 4411 19442
15 35.4 57.2 975 0 504 0 3119 293 817 840 1140 3325 3500 0 12556 1957 4402 18915
16 34.6 60.4 915 0 461 0 2504 268 835 840 1140 3325 3500 0 11813 1975 4375 18163
17 33.6 64.4 840 0 407 0 1756 237 849 840 1140 3325 3500 0 10905 1989 4308 17202
18 32.5 69.2 757 0 348 0 942 203 867 840 1140 3325 3500 0 9915 2007 4243 16165

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-30-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

VPCT 3-TANG 3~9 1 1 1 Office 177.3 3.3 18 Summer 450.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 838 0 0 0 10085 201 966 1008 1368 4113 4500 0 20745 2334 4487 27566
* 9 32.5 69.2 1269 0 0 0 10303 251 969 1008 1368 4113 4500 0 21444 2337 4691 28472
10 33.9 63.4 1828 0 0 0 8841 305 948 1008 1368 4113 4500 0 20595 2316 4820 27731
11 35.0 58.8 2419 0 0 0 6633 348 918 1008 1368 4113 4500 0 19021 2286 4868 26175
12 35.8 55.5 2936 0 0 0 5912 378 890 1008 1368 4113 4500 0 18847 2258 4877 25982
13 36.1 54.3 3303 0 0 0 6081 390 878 1008 1368 4113 4500 0 19395 2246 4877 26518
14 35.9 55.2 3529 0 0 0 6020 382 890 1008 1368 4113 4500 0 19552 2258 4892 26702
15 35.4 57.2 3633 0 0 0 5595 363 907 1008 1368 4113 4500 0 19212 2275 4882 26369
16 34.6 60.4 3639 0 0 0 4704 332 929 1008 1368 4113 4500 0 18296 2297 4849 25442
17 33.6 64.4 3576 0 0 0 3439 293 946 1008 1368 4113 4500 0 16929 2314 4769 24012
18 32.5 69.2 3406 0 0 0 1468 251 969 1008 1368 4113 4500 0 14746 2337 4691 21774

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-32-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

VPCT4-T3~9 1 1 1 Office 84.7 3.3 9 Summer 225.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 119 0 351 0 1404 96 511 504 684 1965 2000 0 6439 1195 2444 10078
9 32.5 69.2 149 0 438 0 1835 120 513 504 684 1965 2000 0 7011 1197 2547 10755
10 33.9 63.4 197 0 533 0 2218 146 503 504 684 1965 2000 0 7563 1187 2611 11361
11 35.0 58.8 268 0 607 0 2471 166 488 504 684 1965 2000 0 7981 1172 2634 11787
12 35.8 55.5 351 0 661 0 2615 181 475 504 684 1965 2000 0 8277 1159 2640 12076
13 36.1 54.3 435 0 681 0 3347 186 469 504 684 1965 2000 0 9118 1153 2639 12910
14 35.9 55.2 536 0 668 0 4451 183 475 504 684 1965 2000 0 10307 1159 2647 14113
*15 35.4 57.2 643 0 634 0 4981 173 483 504 684 1965 2000 0 10900 1167 2642 14709
16 34.6 60.4 751 0 580 0 4689 159 494 504 684 1965 2000 0 10648 1178 2626 14452
17 33.6 64.4 840 0 512 0 3743 140 502 504 684 1965 2000 0 9704 1186 2584 13474
18 32.5 69.2 882 0 438 0 780 120 513 504 684 1965 2000 0 6689 1197 2547 10433

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-34-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

VPCT5-T3~9 1 1 1 Office 88.4 3.3 9 Summer 225.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 55.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 303 0 162 0 4091 100 482 504 684 2051 0 0 7211 1166 2243 10620
9 32.5 69.2 450 0 202 0 4505 125 483 504 684 2051 0 0 7837 1167 2346 11350
10 33.9 63.4 644 0 246 0 4302 152 473 504 684 2051 0 0 7899 1157 2411 11467
11 35.0 58.8 855 0 280 0 3709 173 458 504 684 2051 0 0 7572 1142 2434 11148
12 35.8 55.5 1049 0 305 0 3456 189 444 504 684 2051 0 0 7554 1128 2439 11121
13 36.1 54.3 1196 0 314 0 3870 194 438 504 684 2051 0 0 8129 1122 2439 11690
14 35.9 55.2 1300 0 308 0 4377 191 444 504 684 2051 0 0 8731 1128 2446 12305
*15 35.4 57.2 1368 0 293 0 4471 181 452 504 684 2051 0 0 8868 1136 2441 12445
16 34.6 60.4 1401 0 268 0 4000 166 463 504 684 2051 0 0 8390 1147 2425 11962
17 33.6 64.4 1408 0 237 0 3073 146 472 504 684 2051 0 0 7419 1156 2384 10959
18 32.5 69.2 1364 0 202 0 921 125 483 504 684 2051 0 0 5167 1167 2346 8680

F/A : Fresh air


SH : Sensible heat
LH : Latent heat

-36-
CHUNG CU OPAL

Table of room heat load


Room name Floor System Rooms Usage Fl area(m2) Height(m) No of person F/A volume(m3/h)

VPCT 6 T3~9 1 1 1 Office 159.4 3.3 16 Summer 400.0/Winter ----

[Cooling load] Condition of indoor design temprature & humidity: 26.0(CDB) 50.0(%RH) [W]

F/A cond. Roof Infiltration Human body Equipments Indoor heat Total
Outer Inner Light Fresh
Time & Floor Window Heat
Wall Wall -ing air
CDB %RH Ceiling SH LH SH LH SH LH SH LH Load

8 31.2 74.4 415 0 207 0 2717 181 962 896 1216 3698 3500 0 11614 2178 4345 18137
9 32.5 69.2 519 0 259 0 3549 226 965 896 1216 3698 3500 0 12647 2181 4527 19355
10 33.9 63.4 685 0 314 0 4291 274 946 896 1216 3698 3500 0 13658 2162 4642 20462
11 35.0 58.8 933 0 358 0 4779 312 919 896 1216 3698 3500 0 14476 2135 4683 21294
12 35.8 55.5 1224 0 390 0 4993 340 894 896 1216 3698 3500 0 15041 2110 4693 21844
13 36.1 54.3 1514 0 402 0 6299 351 883 896 1216 3698 3500 0 16660 2099 4692 23451
14 35.9 55.2 1854 0 394 0 8852 344 894 896 1216 3698 3500 0 19538 2110 4706 26354
15 35.4 57.2 2228 0 374 0 10471 326 909 896 1216 3698 3500 0 21493 2125 4696 28314
*16 34.6 60.4 2614 0 342 0 10345 299 929 896 1216 3698 3500 0 21694 2145 4667 28506
17 33.6 64.4 2937 0 302 0 8778 264 945 896 1216 3698 3500 0 20375 2161 4595 27131
18 32.5 69.2 3134 0 259 0 1640 226 965 896 1216 3698 3500 0 13353 2181 4527 20061