A29-K-HVA-VA-015028-001 - 01A Schematic Diagram For MOS-029 HVAC-Default-000

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NOTES:

1. ALL AIR VOLUME ARE SHOWN IN CMH(CUBE


METER PER HOUR).
A29-ACCU-601 A29-AHU-601
2. THE REFRIGERANT PIPING SHALL BE IN
AIR COOLED CONDENSING UNIT AIR HANDLING UNIT
THE SCOPE OF AHU VENDOR SCOPE.
(100% x 1 SETS) TYPE : HORIZONTAL, DRAW THRU 3. VENDOR SHALL SUPPLY THE WHOLE HVAC
(100% x 1 SETS) SYSTEM, INCLUDING ALL THE EUIPMENTS,
INSTRUMENTS, FD, MFSD, MGD, MD, POWER
PANEL, CONTROL PANEL ETC..
M M M
A29-ACCU-602A/B
CONDENSER CONDENSER CONDENSER AIR COOLED CONDENSING UNIT A29-AHU-602A/B

AIR HANDLING UNIT


(100% x 2 SETS, ONE STAND-BY)
A29-ACCU-602A A29-ACCU-602B A29-ACCU-601
TYPE : HORIZONTAL, DRAW THRU

(100% x 2 SETS, ONE STAND-BY)


M M M
A29-EF-601/602/603 DX TYPE AIR FAN COIL UNIT
DX F DX

HANDLING UNIT
M

EXHAUST AIR FAN


M
(CEILING SUSPEND)

TYPE : IN-LINE A29-EDH-601~610

ELECTRICAL DUCT HEATER

TTEN CONSENT OF SAUDIARAM CO.


RL RG RL RG RL RG M

CONDENSER AIR COOLED


M INLINE EXHAUST FAN
TYPE : IN-LINE
M CONDENSER
A29-CFU-601
12000CMH TO PCS
MD CHEMICAL FILTRATION UNIT
(BY OTHERS) A29-STU-601 ELECTRIC DUCT
M TYPE : HORIZONTAL, DRAW THRU
+

SAND TRAP UNIT


SAND TRAP UNIT HEATER
(SUPPLY FAN-100%x2SETS, ONE STAND-BY)
TYPE : SELF CLEANING INERTIAL FILTER

M WALL MOUNTED FAN


SOUND ATTENUATOR
MD
CO LEL
A29-BF-601 M

M
A29-EF-604A/B
CENTRIFUGAL FAN
M MOTORIZED DAMPER
EXHAUST AIR FAN BLEED FAN
MGD-601
M TYPE : IN-LINE TYPE : CENTRIFUGAL, FLOOR MOUNTED
FIRE
MD M EXPLOSION PROOF AIR VOLUME DAMPER
DAMPER
DX F (100% x 2 SETS, ONE STAND-BY)
M

MOTORIZED FIRE/SMOKE
BACK DRAFT DAMPER
OA DAMPER

TT PRE-FILTER
A29-AHU-602A M A29-CFU-601 AIR INLET
(BY OTHERS) (BY OTHERS)

THOUT THE W RI
TO LFAP TO LFAP
A29-STU-601
VD AIR OUTLET F
FINAL-FILTER
PLENUM

PLENUM
NSA NSA
12000CMH FD-601
2210CMH 7220CMH
MD CONTROL LINE CHEMICAL FILTER
VD
M MD M
TT LOW EXPLOSIVE LEVEL
CO CO DETECTOR LEL
DETECTOR

F DUCT MOUNTED SMOKE


MD TT TEMPERATURE TRANSMITTER NSA DETECTOR

NG W I
MT
M

800CMH TEMPERATURE INDICATING


M M TIC MT MOISTURE TRANSMITTER
CONTROL

S DRAW I
TT A29-BF-601 PRESSURE DIFFERENTIAL
MOISTURE INDICATING
M MIC PDT
CONTROL TRANSMITTER
DX F
FD-624 FD-625 VA PRESSURE DIFFERENTIAL
MT VISIBLE ALARM PDI
- INDICATOR

NED FROM THI


AA PRESSURE DIFFERENTIAL
9790CMH FD-622 AUDIBLE ALARM PDLA
- LOW ALARM
A29-AHU-602B VD FD-642
PROCESS CONTROL PRESSURE DIFFERENTIAL
PCS PDHA
10560CMH SYSTEM HIGH ALARM
PLENUM
LEAK
FD-602 LOCAL FIRE ALARM
280CMH VD LFAP PSA POWER SYSTEM AUTOMATION
VD CONTROL PANEL
FD-605 VD VD

FD-612 MOTORIZED FIRE/SMOKE FIRE


1440CMH

N PART,SHALL BE OBTAI
MFSD FD DAMPER
DAMPER

FD-638 FD-608
VD MD MOTORIZED DAMPER VD VOLUME DAMPER
FD-610
A29-EDH-610 MOTORIZED GAS TIGHT
A29-EDH-608

+
BDD BACK DRAFT DAMPER MGD

+
A29-EDH-609 DAMPER

+
FD-626 FD-609 BF BLEED FAN EF EXHAUST FAN
FD-643

AIR COOLED CONDENSING


FD-639 AHU AIR HANDLING UNIT ACCU
A29-EF-604A UNIT
FD-606 FD-627 FD-641 FD-628 FD-611 A29-MD-601 M M

+
11650CMH FD-607
A29-EDH-605 860CMH CFU CHEMICAL FILTERING UNIT STU SAND TRAP UNIT
TT
M
VD RG REFRIGERANT GAS RL REFRIGERANT LIQUID
MD VD VD VD VD VD VD VD VD
VD
(BY OTHERS) (BY OTHERS)
M

MD SA SUPPLY AIR

N FULL,OR I
A29-MD-602 A29-MFSD-604 RA RETURN AIR
TO LFAP TO LFAP EA
1140CMH
M
BOD BOTTOM OF DUCT OA OUTDOOR AIR
NSA NSA
M

1440CMH 1340CMH 590CMH 690CMH 3300CMH 3260CMH 4300CMH 5060CMH 160CMH 260CMH 100CMH 150CMH VD
COP EL. CENTER OF PIPE
M COU CENTER OF UNIT
ELEVATION
G05 G02 G03
DX F G04
40CMH
CONTROL ROOM ENGINEERING ROOM
G01
LIBRAY
G27
A29-EF-604B REFERENCE DRAWINGS
PLENUM

PLENUM

5010CMH TELECOM ROOM RACK ROOM BATTERY CHARGING

ON I
ELECTRICAL ROOM
VD SWITCH
DWG. CONTROL FOR J.O.10-01525-0004-018
TT MT TT MT MT TT MT TT
TT
790CMH RH=50% 10% RH=50% 10% RH=50% 10% RH=50% 20% RH=50% 20% G28 BATTERY ROOM HVAC LEGEND VA-014969
VD

N ARE THE SOLE PROPERTY OF SAUDIARAM CO.NO REPRODUCTI


TT TT

EQUIPMENT SCHEDULE VA-015027


100CMH
A29-AHU-601 100CMH 720CMH 100CMH 50CMH VB-015029
EQUIPMENT LAYOUT
MT MT
AIR DUCT LAYOUT VB-015030
110CMH 100CMH 100CMH 100CMH 100CMH 100CMH VA-015031
VD 50CMH
DETAIL DRAWING
460CMH
VD
G10 G09
G08 TT MT
OPERATION LEARNING/
VD MAINT STORE TT MT TT MT
VD G06 MAINT COORD SUPERVISOR MEETING
OPERATION STORE OFFICE G13 OFFICE G14
1730CM H

G15 G26
MECHANICAL ROOM RH=50% 20% RH=50% 20%
RH=50% 20% RH=50% 20% RH=50% 20% RH=50% 20% RH=50% 20%
110CMH 350CMH 250CMH 130CMH 90CMH 320CMH 220CMH 320CMH 220CMH 260CMH 360CMH 750CMH 850CMH

HVAC CONTROL PANEL HVAC CONTROL PANEL


TT
A29-HVA-LCP-601 A29-HVA-LCP-602

FD-603 FD-604 FD-623

VD VD VD VD VD VD VD VD VD VD VD VD VD

FD-629
FD-632 FD-640 FD-631 FD-630 FD-637

5860CMH 40CMH TO
+

+
A29-EDH-607 MAINTENANCE SHOP
A29-EDH-604

FD-613 FD-614
2180CMH

FD-615 FD-617

A29-EDH-606

NED HEREI
+

8800CMH
SCALE: N.T.S
+

VD VD A29-EDH-601
FD-635 FD-619 FD-620 FD-616

A29-EDH-602
REVISION VALIDATION
+

A29-EDH-603 FD-633 FD-634 FD-636 FD-621 FD-618


+

VD VD VD

ON CONTAI
MFSD-603 THIS REVISION NO. 01A IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
MFSD-601 REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
M
M MFSD-602 M
10-01525-0004-019
VD VD VD VD VD VD VD VD VD VD VD VD VD VD VD VD VD
M DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
BDD M M (DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
2220CMH BDD
1600CMH

NFORM ATI
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
A29-EF-602 BDD
1730CMH JL.Zhao B.ANDERS
580CMH 80CMH 530CMH A29-EF-601
VD A29-EF-603 04/28/19 04/28/19
VD VD
REV.NO. DATE REVISION DESCRIPTION
LEAK
01A 04/28/19 ISSUED FOR CONSTRUCTION
280CMH
2460CMH 470CMH 370CMH 310CMH 410CMH 320CMH 220CMH 170CMH 110CMH 1080CMH 1180CMH 390CMH 290CMH 790CMH 890CMH 470CMH 470CMH 940CMH
1020CMH G23 G24 G25 JOB ORDER/EWO NO.

NG AND THE I
G12 G17 G16 G18 G21 G22 G19 THIS REVISION IS NOT TO BE USED FOR
10-01525-0004 CONSTRUCTION UNTIL CERTIFIED AND DATED
AIR LOCK OFFICE G20 OPERATION CREW PRAYER ROOM CORRIDOR LOCKER ROOM HEAT ROOM TOILET
G11 MAINTENANCE SHOP MAINT CREW MAINT SUPV COFFEE ROOM

PDT TT MT TT MT TT MT
PDT SAUDI ARABIAN OIL COMPANY
RH=50% 20% RH=50% 20% RH=50% 20% RH=50% 20% RH=50% 20% RH=50% 20% RH=50% 20% DRAWING TYPE
RH=50% 20% RH=50% 20% RH=50% 20% RH=50% 20%
HVAC LAYOUT/PLN/DETAIL/DIAGRAM HVA
HVA
LEAK SCHEMATIC DIAGRAM FOR MOS-029 HVAC
40CMH FROM MAINT STORE 100CMH 100CMH 100CMH 1620CMH 100CMH 100CMH 100CMH 2220CMH 1120CMH 80CMH 1200CMH

S DRAW I
280CMH
LEAK
ELECTRICAL POWER DISTRIBUTION & INT
80CMH

JAZAN SAUDI ARABIA


PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
A29 K VA-015028 001 01A
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-01