Civil Engineering Architecture Transmission Load Worksheet Name

Transmission Loads
Surface R-Value U-Factor Area ΔT Basic Construction
1/R Square Feet Degrees F BTU/Hour
West Wall 14.13 0.070 128 61 547
East Wall 14.13 0.070 112 61 478
North Wall 14.13 0.070 114 61 487
South Wall 13.3 0.075 72 61 329
Roof 18.4 0.055 214.66 61 720
Door 1.65 0.599 42 61 1535
Window 0.88 1.136 16 61 1109
TOTAL TRANSMISSION LOAD 5205

Heating unit size requirement

Surface R-Value U-Factor Area ΔT Energy Efficient Design


1/R Square Feet Degrees F BTU/Hour
West Wall 14.13 0.070 128 61 547
East Wall 14.13 0.070 112 61 478
North Wall 14.13 0.070 114 61 487
South Wall 13.3 0.075 72 61 329
Roof 18.4 0.055 214.66 61 720
Door 1.65 0.599 42 61 1535
Window 0.88 1.136 16 61 1109
TOTAL TRANSMISSION LOAD 5205
Difference 0
Civil Engineering Architecture Transmission Load Worksheet Name

Transmission Loads
Surface R-Value U-Factor Area ΔT Additional Btu Basic Construction
450/person +
2000 Btu for
1/R Square Feet Degrees F equipment BTU/Hour
West Wall 14.3 0.070 128 -18 2900 2739
East Wall 14.3 0.070 112 -18 2900 2759
North Wall 14.3 0.070 114 -18 2900 2756
South Wall 13.28 0.075 72 -18 2900 2803
Roof 18.3 0.055 214.66 -18 2900 2687
Door 1.67 0.599 42 -18 2900 2447
Window 0.88 1.136 16 -18 2900 2573
TAL TRANSMISSION LOAD 18764
Difference

Size of A/C required to the nearest 1/2 ton

Surface R-Value U-Factor Area ΔT Additional Btu Energy Efficient Design


450/person +
2000 Btu for
1/R Square Feet Degrees F equipment BTU/Hour
West Wall 14.13 0.070 128 -18 2900 2739
East Wall 14.13 0.070 112 -18 2900 2759
North Wall 14.13 0.070 114 -18 2900 2756
South Wall 13.28 0.075 72 -18 2900 2803
Roof 18.3 0.055 214.66 -18 2900 2687
Door 1.67 0.599 42 -18 2900 2447
Window 0.88 1.136 16 -18 2900 2573
TAL TRANSMISSION LOAD 18764
Difference 0