M-3425A All Setpoints

Software Version: D-0345V10.01.09


Relay Firmware Version: D-0150V01.14.00
Serial Number: 5082
BECKWITH ELECTRIC CO.
M-3425A

Setup System
Setup
CT Type: 5A Frequency Type: 60Hz
Phase Rotation: ABC Expanded I/O: Disabled
Nominal Voltage: 69.0 (V) Nominal Current: 2.92 (A)
Delta-Y Transform: Delta-AB VT Configuration: Line to Ground
59/27 Magnitude Select: RMS 50DT Split Phase Differential: Disable
V.T. Phase Ratio: 137.5 (:1) V.T. Neutral Ratio: 66.7 (:1)
V.T. VX Ratio: 1.0 (:1) C.T. Phase Ratio: 2400 (:1)
C.T. Neutral Ratio: 1 (:1)
I/O Settings
Latched Outputs: Pulsed Outputs:
Active Inputs (Open): Active Inputs (Close): 1, 2, 3, 4, 5, 6
Sealin Time
Output 1: 60 (Cycles) Output 2: 60 (Cycles)
Output 3: 60 (Cycles) Output 4: 60 (Cycles)
Output 5: 60 (Cycles) Output 6: 60 (Cycles)
Output 7: 60 (Cycles) Output 8: 60 (Cycles)

21: Phase Distance


21 #1
Blocking Inputs: FL, 1 Outputs: 2, 4
Circle Diameter: 3.1 (Ohm) Offset: 0.0 (Ohm)
Impedance Angle: 89 (Degree) Time Delay: 60 (Cycles)
Out of Step Block: Disabled
21 #2 (Disabled)
21 #3 (Disabled)

24: Volts/Hz Overexcitation


24 DT #1
Blocking Inputs: Outputs: 2, 4
Pickup: 124 (%) Time Delay: 300 (Cycles)
24 DT #2 (Disabled)
24 IT
Blocking Inputs: Outputs: 2, 4
Pickup: 110 (%) Curve: 3
Time Dial: 2.0 Reset Rate: 200 (sec)

25: Sync Check

27: Phase Undervoltage


27 #1 (Disabled)
27 #2 (Disabled)
27 #3 (Disabled)

27TN: Third Harmonic Undervoltage, Neutral

03/10/2017 Page 1 of 5
27TN #1 (Disabled)
27TN #2 (Disabled)

32: Directional Power


32 #1
Blocking Inputs: FL, 1 Outputs: 2, 4
Pickup: -0.080 (PU) Time Delay: 600 (Cycles)
Target LED: Enabled Power Selection: Overpower
32 #2 (Disabled)
32 #3 (Disabled)

40: Loss of Field


40 #1
Blocking Inputs: FL, 1 Outputs: 2, 4, 7
Circle Diameter: 23.8 (Ohm) Offset: -2.2 (Ohm)
Time Delay: 5 (Cycles)
40 #2
Blocking Inputs: FL, 1 Outputs: 2, 4, 7
Circle Diameter: 39.5 (Ohm) Offset: -2.2 (Ohm)
Time Delay: 30 (Cycles)
40 VC#1 (Disabled)
40 VC#2 (Disabled)
Setting
Voltage Control: 180 (V) Directional Element: 0 (Degree)

46: Negative Sequence Overcurrent


46 DT (Disabled)
46 IT
Blocking Inputs: Outputs: 2, 4
Pickup: 8 (%) Time Dial: 10
Maximum Time: 30000 (Cycles) Reset Time: 1 (Seconds)

49: Stator Overload Protection


49 #1 (Disabled)
49 #2 (Disabled)

50: Instantaneous Phase Overcurrent


50 #1 (Disabled)
50 #2 (Disabled)

50/27: Inadvertent Energizing


50/27
Blocking Inputs: Outputs: 2, 4
Overcurrent Pickup: 0.50 (A) Undervoltage Pickup: 48 (V)
Pick-up Delay: 120 (Cycles) Drop-out Delay: 60 (Cycles)

50BF: Breaker Failure


50BF
Blocking Inputs: Outputs: 3, 4
Phase Current: 0.50 (A) Time Delay: 10 (Cycles)
Input Initiate: 2 Output Initiate: 1, 2, 4

03/10/2017 Page 2 of 5
50DT: Definite Time Overcurrent
50DT #1 (Disabled)
50DT #2 (Disabled)

50N: Instantaneous Neutral Overcurrent


50N (Disabled)

51N: Inverse Time Neutral Overcurrent


51N (Disabled)

51V: Inverse Time Phase Overcurrent


51V (Disabled)

59: Phase Overvoltage


59 #1
Blocking Inputs: Outputs: 2, 4
Pickup: 83 (V) Time Delay: 900 (Cycles)
Input Voltage Selection: Phase Voltage
59 #2 (Disabled)
59 #3 (Disabled)

59D: Third Harmonic Voltage Differential


59D (Disabled)

59N: Neutral Overvoltage


59N #1
Blocking Inputs: Outputs: 1, 4
Pickup: 7.1 (V) Time Delay: 60 (Cycles)
59N #2 (Disabled)
59N #3 (Disabled)
Setting
20Hz Injection: Disabled

59X: Multi-purpose Overvoltage


59X #1 (Disabled)
59X #2 (Disabled)

60FL: VT Fuse-Loss Detection


60FL
Blocking Inputs: Outputs: 4, 8
Three Phase Fuse Loss
Time Delay: 2 (Cycles) Detection: Disabled
Input Initiate: FL

64F/B: Field Ground Protection

64S: 100% Stator Ground Protection by Low Frequency Injection

67N: Residual Directional Overcurrent

03/10/2017 Page 3 of 5
67N DT (Disabled)

78: Out of Step


78
Blocking Inputs: 1 Outputs: 2, 4
Circle Diameter: 13.1 (Ohm) Offset: -8.8 (Ohm)
Impedance Angle: 90 (Degree) Blinder Impedance: 2.1 (Ohm)
Pole Slip Counter: 1 Pole Slip Reset Time: 120 (Cycles)
Time Delay: 5 (Cycles) Trip on MHO Exit: Enabled

81: Overfrequency/Underfrequency
81 #1
Blocking Inputs: 1 Outputs: 2, 4, 5
Pickup: 57.50 (Hz) Time Delay: 600 (Cycles)
81 #2
Blocking Inputs: 1 Outputs: 1, 4, 5
Pickup: 56.39 (Hz) Time Delay: 6 (Cycles)
81 #3
Blocking Inputs: Outputs: 2, 4, 5
Pickup: 61.51 (Hz) Time Delay: 36010 (Cycles)
81 #4
Blocking Inputs: Outputs: 1, 4, 5
Pickup: 62.11 (Hz) Time Delay: 600 (Cycles)

81A: Frequency Accumulation


81A #1 (Disabled)
81A #2 (Disabled)
81A #3 (Disabled)
81A #4 (Disabled)
81A #5 (Disabled)
81A #6 (Disabled)

81R: Rate of Change of Frequency


81R #1 (Disabled)
81R #2 (Disabled)

87: Phase Differential Current


87 #1
Blocking Inputs: Outputs: 1, 4, 6
Pickup 0.20 (A) Percent Slope 10 (%)
Time Delay: 1 (Cycles)
87 #2 (Disabled)
Setting
Phase CT Correction: 1.00

87GD: Ground Differential Current


87GD (Disabled)

BM: Breaker Monitoring


BM (Disabled)

03/10/2017 Page 4 of 5
TC: Trip Circuit Monitoring
TC (Disabled)

IPS
IPSlogic #1 (Disabled)
IPSlogic #2 (Disabled)
IPSlogic #3 (Disabled)
IPSlogic #4 (Disabled)
IPSlogic #5 (Disabled)
IPSlogic #6 (Disabled)

Setup Oscillograph Recorder


Setup
Triggered Inputs: Triggered Outputs: 1, 2
Partitions: 6 Post Delay: 25 (%)

Setup Sequence of Events Recorder


Setup
21 #1, 21 #2, 24 DT #1, 24 IT, 27TN #1, 27TN #2, 32 #1, 32 #2, 40 #1, 40 #2, 46 IT, 50BF, 59 #1, 59 #2, 59 #3, 59D, 59N #1,
Function Pickup: 59N #2, 60FL, 78, 81 #1, 81 #2, 81 #3, 81 #4, 87 #1, 87 #2

21 #1, 21 #2, 24 DT #1, 24 IT, 27TN #1, 27TN #2, 32 #1, 32 #2, 40 #1, 40 #2, 46 IT, 50BF, 59 #1, 59 #2, 59 #3, 59D, 59N #1,
Function Trip: 59N #2, 60FL, 78, 81 #1, 81 #2, 81 #3, 81 #4, 87 #1, 87 #2

Function Dropout:

Inputs Pickup: Outputs Pickup:


Inputs Drop: Outputs Drop:

03/10/2017 Page 5 of 5