CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-1

Tramos: 6.00 Vnom: 240.000 Vinic: 238.056 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
1.05 0.21 0.42 0.21 0.21 0.21 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
21.00 20.00 12.00 15.00 20.00 23.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 2.31 KW. LongTotal: 111.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 10.7818 5.9098 4.9375 2.9663 1.9794 0.9906 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0539 0.0513 0.0308 0.0385 0.0513 0.0590 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 0.5806 0.3031 0.1519 0.1141 0.1015 0.0584 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0125 0.0036 0.0015 0.0007 0.0004 0.0001 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 236.8944 236.2882 235.9843 235.7561 235.5531 235.4362 235.4362 235.4362 235.4362 235.4362 235.4362 235.4362
RegulacTramo: 0.487793 0.255889 0.128602 0.096700 0.086122 0.049606 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.294008 1.546586 1.673199 1.768282 1.852881 1.901567 1.901567 1.901567 1.901567 1.901567 1.901567 1.901567
Perdida-Acum: 0.0125 0.0160 0.0175 0.0182 0.0186 0.0187 0.0187 0.0187 0.0187 0.0187 0.0187 0.0187

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-2

Tramos: 5.00 Vnom: 240.000 Vinic: 238.056 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
0.63 0.21 0.84 0.63 0.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
21.00 20.00 12.00 35.00 43.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 2.52 KW. LongTotal: 131.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 11.7620 8.8687 7.9137 3.9650 0.9943 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0539 0.0513 0.0308 0.0898 0.1103 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 0.6334 0.4548 0.2435 0.3559 0.1096 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0149 0.0080 0.0038 0.0028 0.0002 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 236.7888 235.8791 235.3921 234.6804 234.4611 234.4611 234.4611 234.4611 234.4611 234.4611 234.4611 234.4611
RegulacTramo: 0.532138 0.384177 0.206478 0.302360 0.093432 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.337994 1.717030 1.919962 2.216517 2.307879 2.307879 2.307879 2.307879 2.307879 2.307879 2.307879 2.307879
Perdida-Acum: 0.0149 0.0229 0.0267 0.0295 0.0298 0.0298 0.0298 0.0298 0.0298 0.0298 0.0298 0.0298

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-3

Tramos: 4.00 Vnom: 240.000 Vinic: 238.056 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
0.84 0.21 0.21 0.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
84.30 40.00 40.00 40.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 1.47 KW. LongTotal: 204.30 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 6.8611 2.9776 1.9902 0.9969 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.2162 0.1026 0.1026 0.1026 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 1.4832 0.3054 0.2041 0.1023 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0203 0.0018 0.0008 0.0002 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 235.0892 234.4784 234.0701 233.8656 233.8656 233.8656 233.8656 233.8656 233.8656 233.8656 233.8656 233.8656
RegulacTramo: 1.246090 0.259834 0.174127 0.087367 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 2.046162 2.300679 2.470800 2.556008 2.556008 2.556008 2.556008 2.556008 2.556008 2.556008 2.556008 2.556008
Perdida-Acum: 0.0203 0.0221 0.0229 0.0231 0.0231 0.0231 0.0231 0.0231 0.0231 0.0231 0.0231 0.0231

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-4

Tramos: 5.00 Vnom: 240.000 Vinic: 238.056 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
0.84 0.21 0.21 0.21 0.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
84.30 20.00 40.00 40.00 40.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 1.68 KW. LongTotal: 224.30 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 7.8413 3.9773 2.9882 1.9973 1.0004 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.2162 0.0513 0.1026 0.1026 0.1026 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 1.6951 0.2040 0.3065 0.2049 0.1026 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0265 0.0016 0.0018 0.0008 0.0002 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 234.6654 234.2575 233.6445 233.2347 233.0295 233.0295 233.0295 233.0295 233.0295 233.0295 233.0295 233.0295
RegulacTramo: 1.424103 0.173849 0.261683 0.175372 0.087994 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 2.222732 2.392717 2.648138 2.818866 2.904380 2.904380 2.904380 2.904380 2.904380 2.904380 2.904380 2.904380
Perdida-Acum: 0.0265 0.0281 0.0299 0.0308 0.0310 0.0310 0.0310 0.0310 0.0310 0.0310 0.0310 0.0310

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-5

Tramos: 5.00 Vnom: 240.000 Vinic: 237.944 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
0.21 0.21 0.21 0.21 0.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
42.00 40.00 20.00 20.00 40.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 1.05 KW. LongTotal: 162.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 4.9031 3.9400 2.9651 1.9793 0.9905 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.1077 0.1026 0.0513 0.0513 0.1026 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 0.5281 0.4041 0.1521 0.1015 0.1016 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0052 0.0032 0.0009 0.0004 0.0002 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 236.8883 236.0800 235.7758 235.5728 235.3696 235.3696 235.3696 235.3696 235.3696 235.3696 235.3696 235.3696
RegulacTramo: 0.443863 0.341204 0.128829 0.086108 0.086256 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.296561 1.633341 1.760066 1.844658 1.929323 1.929323 1.929323 1.929323 1.929323 1.929323 1.929323 1.929323
Perdida-Acum: 0.0052 0.0083 0.0092 0.0096 0.0098 0.0098 0.0098 0.0098 0.0098 0.0098 0.0098 0.0098

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-6

Tramos: 4.00 Vnom: 240.000 Vinic: 237.944 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
0.21 0.21 0.42 0.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
22.00 40.00 40.00 40.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 1.05 KW. LongTotal: 142.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 4.9031 3.9316 2.9588 0.9888 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0564 0.1026 0.1026 0.1026 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 0.2766 0.4033 0.3035 0.1014 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0027 0.0032 0.0018 0.0002 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 237.3912 236.5846 235.9776 235.7748 235.7748 235.7748 235.7748 235.7748 235.7748 235.7748 235.7748 235.7748
RegulacTramo: 0.232500 0.339759 0.256560 0.085961 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.087008 1.423075 1.675984 1.760503 1.760503 1.760503 1.760503 1.760503 1.760503 1.760503 1.760503 1.760503
Perdida-Acum: 0.0027 0.0059 0.0077 0.0079 0.0079 0.0079 0.0079 0.0079 0.0079 0.0079 0.0079 0.0079

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-7

Tramos: 6.00 Vnom: 240.000 Vinic: 237.944 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
0.21 0.21 0.21 0.21 0.21 0.21 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
5.40 38.00 40.00 38.00 40.00 40.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 1.26 KW. LongTotal: 201.40 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 5.8837 4.9065 3.9410 2.9659 1.9821 0.9928 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0138 0.0974 0.1026 0.0974 0.1026 0.1026 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 0.0815 0.4781 0.4042 0.2890 0.2033 0.1018 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0010 0.0047 0.0032 0.0017 0.0008 0.0002 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 237.7815 236.8252 236.0167 235.4387 235.0321 234.8284 234.8284 234.8284 234.8284 234.8284 234.8284 234.8284
RegulacTramo: 0.068482 0.402141 0.341385 0.244906 0.172709 0.086654 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 0.924395 1.322819 1.659688 1.900530 2.069956 2.154816 2.154816 2.154816 2.154816 2.154816 2.154816 2.154816
Perdida-Acum: 0.0010 0.0056 0.0088 0.0105 0.0113 0.0115 0.0115 0.0115 0.0115 0.0115 0.0115 0.0115

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-8

Tramos: 5.00 Vnom: 240.000 Vinic: 237.944 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 8.36 ( 8 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 2.56433 W/Km 2.55577 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
0.21 0.21 0.42 0.21 0.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
18.00 40.00 40.00 38.00 40.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 1.26 KW. LongTotal: 176.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 5.8837 4.9143 3.9482 1.9809 0.9921 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0462 0.1026 0.1026 0.0974 0.1026 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 0.2716 0.5041 0.4050 0.1930 0.1018 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.0032 0.0049 0.0032 0.0008 0.0002 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 237.4012 236.3931 235.5831 235.1971 234.9935 234.9935 234.9935 234.9935 234.9935 234.9935 234.9935 234.9935
RegulacTramo: 0.228272 0.424663 0.342635 0.163872 0.086532 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.082817 1.502882 1.840367 2.001224 2.086024 2.086024 2.086024 2.086024 2.086024 2.086024 2.086024 2.086024
Perdida-Acum: 0.0032 0.0081 0.0113 0.0121 0.0123 0.0123 0.0123 0.0123 0.0123 0.0123 0.0123 0.0123

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-9

Tramos: 2.00 Vnom: 240.000 Vinic: 239.444 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 33.62 ( 2 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 0.68695 W/Km 0.66601 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
6.00 6.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
40.00 40.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 12.00 KW. LongTotal: 80.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 55.6846 28.2027 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0275 0.0275 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 1.5301 0.7750 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.1652 0.0424 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 236.3838 234.8339 234.8339 234.8339 234.8339 234.8339 234.8339 234.8339 234.8339 234.8339 234.8339 234.8339
RegulacTramo: 1.278044 0.655675 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.506750 2.152546 2.152546 2.152546 2.152546 2.152546 2.152546 2.152546 2.152546 2.152546 2.152546 2.152546
Perdida-Acum: 0.1652 0.2076 0.2076 0.2076 0.2076 0.2076 0.2076 0.2076 0.2076 0.2076 0.2076 0.2076

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-10

Tramos: 2.00 Vnom: 240.000 Vinic: 239.444 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 53.48 (1/0 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 0.45945 W/Km 0.42979 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
6.00 6.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
80.00 41.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 12.00 KW. LongTotal: 121.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 55.6846 28.3265 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0368 0.0188 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 2.0467 0.5336 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.2132 0.0283 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 235.3505 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833
RegulacTramo: 1.709579 0.453451 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.937285 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951
Perdida-Acum: 0.2132 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-11

Tramos: 2.00 Vnom: 240.000 Vinic: 239.444 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 53.48 (1/0 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 0.45945 W/Km 0.42979 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
6.00 6.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
80.00 41.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 12.00 KW. LongTotal: 121.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 55.6846 28.3265 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0368 0.0188 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 2.0467 0.5336 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.2132 0.0283 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 235.3505 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833 234.2833
RegulacTramo: 1.709579 0.453451 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 1.937285 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951 2.381951
Perdida-Acum: 0.2132 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415 0.2415

Reforma N° 708, Col. Rovirosa


Villahermosa, Tab. (993) 315 7508.
Ing. Matusalén Martínez Hernández
Ingeniero Electricista, U.J.A.T. Ced. Prof. 1616745 CIME-Tab 138.

CALCULO DE REGULACION Y PERDIDAS


RED DE ALUMBRADO PUBLICO SUBTERRANEO, 2F-2H+t; 240 V.
CIRCUITO: E4-12

Tramos: 2.00 Vnom: 240.000 Vinic: 239.444 F.P. 0.90 Fases: 2.00 CableACSR:
Cable THW: 53.48 (1/0 AWG) Cable XLP: ZImped/Km: Resist/Km:
DATOS

( * AWG) 0.45945 W/Km 0.42979 W/Km


KWTram01: KWTram02: KWTram03: KWTram04: KWTram05: KWTram06: KWTram07: KWTram08: KWTram09: KWTram10: KWTram11: KWTram12:
6.00 6.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LongTram01: LongTram02: LongTram03: LongTram04: LongTram05: LongTram06: LongTram07: LongTram08: LongTram09: LongTram10: LongTram11: LongTram12:
142.00 41.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CargaTotal: 12.00 KW. LongTotal: 183.00 Mts.

R E S U L T A D O S
Tramo 01 Tramo 02 Tramo 03 Tramo 04 Tramo 05 Tramo 06 Tramo 07 Tramo 08 Tramo 09 Tramo 10 Tramo 11 Tramo 12
CorrienteFase: 55.6846 28.7136 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
ZImped/Tramo: 0.0652 0.0188 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CaidaVoltFase: 3.6330 0.5409 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Pérdid-Tramo: 0.3785 0.0291 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Voltaje Recib: 232.1781 231.0963 231.0963 231.0963 231.0963 231.0963 231.0963 231.0963 231.0963 231.0963 231.0963 231.0963
RegulacTramo: 3.034502 0.465928 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000 0.000000
Regul Acum: 3.259139 3.709881 3.709881 3.709881 3.709881 3.709881 3.709881 3.709881 3.709881 3.709881 3.709881 3.709881
Perdida-Acum: 0.3785 0.4075 0.4075 0.4075 0.4075 0.4075 0.4075 0.4075 0.4075 0.4075 0.4075 0.4075