For Process Automation

CONTROL VALVES

ACTUATORS

INSTRUMENTS

FA・SYSTEMS

CHEMICAL PUMPS

PRODUCTION

1
ACCESSORIES FOR PNEUMATIC ACTUATORS Rotary Stem Motion type

EP800: Electro-Pneumatic Positioner


This series is for positioning of pneumatic actuator operated control valves. The input signal 4~20mA DC is changed
to air pressure. Accurate positioning is achieved by having valve position feedback from the valve stem.

PP800: Pneumatic-Pneumatic Positioner


Same series as EP800 but with a pneumatic signal (20~100Kpa). Also double acting and single acting types are available.

PRF300: Airfilter-Regulator
For regulating instrument air.
CL-420: Lock Valves
CL-523: Used for shut off, switching, or locking of instrumental air circuit (air relay).

CL-523 CL-420

EPA800 PPA800
EPB800 PPC800 PRF400 PRF300
EPC800

Specifications
EPA800 EPC800 EPB800
Type
for single acting for double acting 5200LAfor 5200LA actuator

Input signal / Characteriatic 4∼20, 4∼12, 12∼20 mA DC / Linear


Air supply 140∼700 KPa
Type Single acting type Double Acting type
Linearity/Hysteresis 1.0% / 0.5% 1.5% / 0.8%
Response level/Repeatability 0.1% / 0.2% 0.2% / 0.3%

Output air pressure(50%)


Air consumption
5 Nl/min. at Sup. 140 KPa[gaug] 15 Nl/min. at Sup. 400 KPa[gaug]

Output atomosphere
Max. capacity
175 Nl/min. at Sup. 140 KPa[gaug] 400 Nl/min. at Sup. 400 KPa[gaug]

Weather proof type, Explosion proof type


Enclosure
Intrisically safe explosion proof type

Air/Electric wiring connection Rc. 1/4 / G1/2


−20∼+60℃ (-4~+140OF),−50∼+60℃ (-58~+140OF),0∼+100℃ (32~+212OF)
Environment temp.
Standard type: −20∼+60℃ (-4~+140OF), Low temp.service:−50∼+60℃ (-58~+140OF), High Temp.service:0∼+100℃ (32~+212OF)

41