Professional Documents
Culture Documents
14240
14240
SECTION 14240
HYDRAULIC ELEVATOR
PART 1 GENERAL
1. Panoramic elevator.
2. Passenger car with doors and frames, hoistway entrances doors and frames.
J. Division 16 Electrical
1.03 REFERENCES
B. AISC – Specification for the Design, Fabrication and erection of structural steel for buildings.
G. ASTM A 6 Specification for General Requirements for Steel Plates and Pressure Vessels.
I. ASTM A 167 Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate,
Sheet, and Strip.
J. ASTM A 336 Specification for Steel Sheet, Carbon, Cold-Rolled, Commercial Quality.
K. ASTM A 568 Specification for Steel Sheet, Carbon and High Strength, Low Alloy, Hot
Rolled and Cold Rolled, General Requirements for.
M. ASTM B 221 Specification for Aluminum and Aluminum-Alloy Extruded Bar, Rod, Wire,
Shape, and Tube.
1. Clear plumb elevator hoistway with variations not to exceed 25 mm at any point.
2. Bevel cants (15 degrees from vertical) over any rear or side wall ledges and beams that
project or recess 50 mm or more into the hoistway. (Not required on hoistway divider
beams.)
3. Divider beams between adjacent elevators at each floor, pit and overhead. Car
intermediate rail supports where floor heights exceed 4250 mm.
11. Structural supports for jack unit, buffer impact and guide rail loads.
13. Protecting open elevator hoistways and entrances during construction per OSHA
Regulations.
14. Protecting cabs, door entrance assemblies and special metal finishes from damage after
installation.
15. Venting or other means to prevent accumulation of smoke and gas in case of fire, as
required by Local Building Code.
6. Fire extinguisher.
1. Lighting and GFCI convenience outlets in pit, machine room and overhead machinery
space.
2. Conduit from the closest hoistway of each elevator group to the fire control room and
elevator control panel. Coordinate size, number and location of conduits and elevator
control panel.
4. Single phase copper power feeder to each elevator controller for lighting and exhaust
blower with individual protected, lockable "off", disconnect switch located in machine
room.
5. Single phase power feeders to machine room elevator group control panel and VGA
with single-phase, protected, lockable "off", disconnect switch.
6. Public and Firefighters' telephone jack and announcement speaker in car with
connection to individual elevator control panels in elevator machine room and elevator
control panel in firefighters' control room.
8. Products-of-combustion sensor (NFPA 72, Chapter 5-3) in each elevator lobby, for
each group of elevators or single elevator and machine room to initiate firefighters'
return feature. Detector at top of hoistway if sprinklered. Provide means for service
access from outside the hoistway. Provide sensor signal wiring from hoistway or
machine room connection point to controller terminals.
9. Means to automatically disconnect power to affected elevator drive unit and controller
prior to activation of machine room overhead fire sprinkler system, and/or hoistway
overhead fire sprinkler system.
10. Power feeders to main control console and firefighters' control panel VGA.
11. Power feeder to elevator intercom amplifier located in the elevator machine room.
14. Security: Card readers, interface boards, security computer, monitor and keyboard for
encoding, overriding and monitoring restricted access floors on all elevators.
17. CCTV.
1. Standby power of the same voltage characteristics via normal electrical feeders to run
2. Conductors to signal power source, from the standby power transfer switch to the
single elevator control panel.
1.05 DEFINITIONS
A. Terms used are defined in the latest edition of the Safety Code for Elevators and Escalators,
ASME A 17.1.
B. Reference to a device or a part of the equipment applies to the number of devices or parts
required to complete the installation.
D. Door Opening Time: 2.8 seconds from start of opening to fully open.
E. The door closing times shall not be less than those permitted by the ASME A 17.1 Code,
Rule 112.4 and the kinetic energy of the hoistway door and all parts rigidly connected
thereto (includes the sum of the weights of the hoistway and car doors and related parts)
computed for the average closing speed shall not exceed 31 Newtons. The force necessary to
prevent closing of the hoistway door or car door from rest shall not exceed 13.5 kilograms.
F. Floor-to-Floor Performance Time: 14.0 Seconds from start of doors closing until doors are
3/4 open (1/2 open for side opening doors) and car level and stopped at next successive floor
under any loading condition or travel direction:
G. Pressure: Design and factory test fluid system components for 500 p.s.i. Do not exceed
operating pressure of 400 p.s.i.
A. Employ manufacturers who have been manufacturing similar lifts for at least 5 years.
6. Requirements of applicable Building Code and any other Codes, Ordinances and Laws
applicable within the governing jurisdiction.
C. Review Contract Documents for compatibility with the lift proposals. Review structural,
architectural, electrical and mechanical drawings and specification. The Contractor shall be
solely liable for any changes to structural, mechanical, electrical or other systems required to
accommodate Installer’s equipment if not identified sufficiently early.
1. Material and workmanship of the installation shall comply in every respect with
contract documents. Correct defective material or workmanship which develops within
one year from date of final acceptance of work to the satisfaction of the Engineer at no
additional cost, unless due to ordinary wear and tear, or improper use or care by
Purchaser. Perform maintenance in accordance with terms and conditions indicated in
attached Preventive Maintenance Contract.
2. Defective is defined to include, but not limited to; operation or control system failures,
performance below required minimum, excessive wear, unusual deterioration or ageing
of materials or finishes, unsafe conditions, the need for excessive maintenance,
abnormal noise or vibration, and similar unsatisfactory conditions.
C. Within 60 days after award of Contract and before beginning equipment fabrication, submit
shop drawings and required material for review as outlined in Division I.
1. Scaled or Fully Dimensioned Layouts: Plan of pit, hoistway and machine room
indicating equipment arrangement, elevation section of hoistway, details of car
enclosures, etc.
3. Power Confirmation Sheets: Include motor horsepower, code letter, starting current,
full-load running current, and demand factor for applicable motors.
D. Samples: Submit samples of finishing materials and components visible in finished work,
including of required signal fixtures, lights, graphics, Braille Plates and mounting
provisions.
B. Operation and Maintenance Data: Provide operation and maintenance data in accordance
with Section 01730 which will include but not be limited to the following.
C. Provide 2 sets of neatly bound written information necessary for proper maintenance and
adjustment of equipment at least 30 days before final acceptance tests.
3. Parts catalogs for all replaceable parts including ordering forms and instructions.
4. Diagnostic test device complete with access codes, adjusters manuals and set-up manuals
for adjustment, diagnosis and troubleshooting of elevator system and performance of
routine safety tests.
1. Submit the following information, at least 30 days before final acceptance tests of the
installation, for the Owner's file.
a. Wiring Diagrams: Three sets of "as installed" straight-line wiring diagrams showing
the electrical connections of all equipment and all modifications to control circuits.
One set of straight-line wiring diagrams shall be reproducible original. A legend sheet
shall be furnished with each set of drawings to provide the following information:
i) Name and symbol of each relay, switch or other apparatus.
ii) Location on drawings, drawing sheet number and area, and location of all
contacts.
b. Parts Catalog: Three sets of complete parts catalogs listing all replaceable parts
including Manufacturer's identifying numbers and ordering instructions.
c. Printed Instructions: Three sets of neatly bound instructions explaining all operating
features.
e. Diagnostic Test Equipment and Instructions: Provide all diagnostic test devices
together with one set of all supporting information necessary for interpretation of test
data and troubleshooting of system.
f. The elevator installation shall be a design that can be maintainable by any licensed
elevator maintenance company employing qualified mechanics, without the need to
purchase or lease additional diagnostic devices, special tools, or instructions from the
original equipment manufacturer.
ii) If the equipment for fault diagnosis is not completely self-contained within
the controllers but requires a separate, detachable device, that device shall be
furnished to the Owner as part of this installation. Such device shall be in
possession of and become property of the Owner.
iii) Installed equipment not meeting this requirement shall be removed and
replaced with conforming equipment at no cost to the Owner.
g. The Contractor is responsible for upgrades and/or revisions of software during the
progress of the work, warranty period and the term of the ongoing maintenance
agreement, between the Owner and the Contractor.
B. Store material in original protective packaging. Prevent soiling, physical damage, and
wetting.
C. Protect equipment and exposed finishes during transportation, erection, and construction
against damage and stains.
A. Obtain and pay for permits, licenses and inspection fees necessary to complete the elevator
installation.
B. Perform tests required by Consultant, Governing Authority and/or the ASME A 17.1 Safety
Code For Elevators And Escalators, with procedures described in ASME A 17.2.1
Inspectors' Manual for Elevators and Escalators, in the presence of Authorized
Representatives.
C. Supply personnel and equipment for tests and final reviews indicated in Part 3 at no added
cost.
1.12 MAINTENANCE
A. Interim:
1. When the elevator is near completion and declared ready for service, the Owner may
accept for interim use and place it in service.
B. Warranty Maintenance.
C. Contract (Ongoing Preventive Maintenance Program): Quote monthly cost for 5 year
maintenance agreement commencing on completion of the 12 month period in "B" above.
Submit quote based upon terms and conditions of the Owner's standard preventive
maintenance agreement. Submit with tender.
1.13 WARRANTY
B. Review Contract Documents for compatibility with the lift proposals. Review structural,
architectural, electrical and mechanical drawings and specification. The Contractor shall be
solely liable for any changes to structural, mechanical, electrical or other systems required to
accommodate Installer’s equipment if not identified sufficiently early.
PART 2 PRODUCTS
2.01 MANUFACTURERS
2.02 COMPONENTS
1. Number: 6
2. Capacity: 2000 kg
8. Stops: 3
25. Hall Lanterns: At First and Ground Floors With Chimes (Sound
Twice For Down Direction Travel)
31. Disabled Access: All call buttons, position indicators and publicly
accessible operating mechanism and shall be
compliant with ANSI 117.1 and ADAAG,
inclusive of mounting heights, colour, finish,
contrast and sound.
2.03 MATERIALS
A. Steel:
3. Structural Steel Shapes and Plates: ASTM A 6, ASTM A 36, and ASTM A 108.
B. Stainless Steel: Type 302 or 304 complying with ASTM A 167, with standard tempers and
hardness required for fabrication, strength and durability.
Apply mechanical finish on fabricated work in the locations shown or specified. (Federal
Standard and NAAMM nomenclature), with texture and reflectivity required to match
Engineer's sample. Protect with adhesive-paper covering.
1. No. 4: Bright directional polish (satin finish). Graining directions as shown or, if not
shown, in longest dimension or as shown on the Drawings.
C. Aluminum: Extrusions per ASTM B 221; sheet and plate per ASTM B 209.
D. Paint: Clean exposed metal of oil, grease, scale and other foreign matter and factory paint
one shop coat of Manufacturer's standard rust-resistant primer. After erection, provide one
finish coat of Industrial enamel paint. Galvanized metal need not be painted.
E. Prime Finish: Clean all surfaces receiving a baked enamel finish of oil, grease, scale, etc.
Apply one coat of rust-resistant mineral paint followed by a filler coat over uneven surfaces.
Sand smooth and apply final coat of mineral paint.
F. Baked Enamel: Prime per Clause E above. Apply and bake 3 additional coats of enamel in
the selected solid color.
2.04 OPERATION
A. Operate elevator without an attendant from buttons located at each floor and in car. When
elevator is idle, automatically start car and dispatch it to floor corresponding to registered
car or hall call.
Slow down and stop car automatically at floors corresponding to registered call. Hold car at
arrival floor for an adjustable time interval to allow passenger transfer.
Illuminate appropriate button to indicate call registration. Extinguish light when call is
answered.
B. Door Operation: Passenger open doors automatically when the car arrives at a floor to
permit transfer of passengers.
C. Automatic Stopping Accuracy: 2-way automatic with releveling feature stop car within 6
mm above or below the landing sill. Avoid overtravel, as well as undertravel, and maintain
D. Attendant Operation: Include provision for attendant control of door closing, car direction
and calls answered.
E. Independent Service: Provide controls for operation of the elevator from car buttons only.
Close doors automatically or with door close button. Open doors automatically upon arrival
at selected floor.
F. Low-Oil Control: In the event oil level is insufficient for travel to the top floor, provide
controls to return elevator to the main level and park until oil is added.
G. Motion Control: AC type with unit valve suitable for operation specified and capable of
providing smooth, comfortable acceleration, retardation and dynamic braking. Limit the
difference in speed between full load and no load to not more than ±10% of the contract
speed.
H. Firefighters' Service: as per Code, to operate and recall elevator to ground floor. Provide
sensor signal wiring from hoistway or machine room connection point to controller
terminals. Provide similar operation and fixtures on all elevators. Operate visual/audible
signal until return is complete or automatic operation restored.
I. Standby Lighting and Alarm: Car-mounted, battery unit with solid-state charger to operate
alarm bell and lighting, as per Code. Battery to be rechargeable with 5-year minimum-life
expectancy. Provide test button in service cabinet of car station which causes illumination of
standby lighting bulbs. Locate lights so they are part of normal car lighting system or not
exposed to view.
J. Standby-Power Transfer: If normal power fails, adequate standby power will be supplied
through normal power feeders to start and run the elevator at rated speed.
1. Provide controls to automatically start and run the elevator nonstop to the ground floor
K. Standby-Power Source: In the event normal power fails, provide controls to automatically
lower the car nonstop to the lowest landing using DC battery power source installed in
machine room. Include solid-state charger and testing means mounted in a common metal
container. Provide rechargeable lead acid or nickel cadmium battery 10-year minimum life
expectancy. Provide switch in controller to disconnect unit during maintenance. Provide
operating instructions adjacent to switch.
Upon failure of normal power, lower elevator to ground floor, open doors automatically,
hold open until regular door time has expired, then close doors and shut elevator down.
Automatically resume normal operation when power is restored.
A. Arrange equipment in spaces shown on the Drawings. Provide identifying numbers on pump
unit, controller, and disconnect switch.
and manual-lowering functions, shut-off valve, oil reservoir with protected-vent opening, oil
gauge and outlet strainer, drip pan and connections all mounted on isolating pads. Provide
thermal unit or comparable means to maintain oil at operating temperature. Enclose with
removable sheet steel panels lined with sound-absorbing material.
D. Controller: Cabinet type, removable doors and adequate ventilation to dissipate heat. Wire
to identified terminal block studs. Identifying symbols or letters identical to those on wiring
diagrams permanently marked adjacent to each component on the controller. Provide
reduced-voltage Wye-Delta motor-starting circuits.
The car controller shall be equipped with plug compatible diagnostic ports, system
monitoring ports, and remote CRT drivers and plugs for integration into the elevator
monitoring and control system.
E. Muffler: Provide in discharge oil line near pump unit. Design to dampen and absorb
pulsation and noise in the flow of hydraulic fluid.
F. Piping and Oil: Provide piping, connections and oil for the system. Use isolating couplings
between the pump unit and oil lines.
G. Shut-Off Valve: Manual valve in line adjacent to pump unit. Provide second valve in pit
adjacent to jack unit. Provisions shall include continuously operated mechanical or electrical
monitoring devices.
2. Limit noise level relating to elevator equipment and its operation to no more than 60
dBa in elevator cars under any condition including door operation and exhaust blower
on highest speed.
A. Guide Rails: Planed steel T-sections suitable for elevator travel, car weight with brackets
for attachment to building structure. Provide backing and intermediate rail brackets to meet
Code requirements.
C. Cylinder: Seamless steel pipe. Design head to receive unit type packing and provide
automatic means to collect oil at cylinder head and return to oil reservoir.
D. Plunger: Polished seamless steel tubing or pipe. If plunger length exceeds 7 m, provide two
or more sections not exceeding 5 m in length, or coordinate installation of longer unit at the
jobsite. Join section by internal threaded couplings. Factory polish multiple section jack
units while assembled and mark for proper future reassembly.
E. Sheaves: Machined grooves with ball or roller bearings. Provide mounting means to jack
cylinder and pit structural members, etc. Provide drip pans under 2:4 pit sheaves and rope
guards on car sheaves, cylinder sheaves and pit sheaves.
G. Jack Support: Provide steel channels to support jack and transmit loads to building
structure.
H. Normal and Final Terminal Stopping Devices: In accordance with Code requirements.
1. Conductors and Connections: Copper throughout with individual wires coded and
connections on identified studs or terminal blocks. Use no splices or similar
connections in wiring except at terminal blocks, control cabinets, junction boxes, or
condulets. Provide 10% spare conductors throughout. Provide additional pairs of
shielded communication wires in addition to those required to connect specified items.
Run spare wires from car connection points to the elevator controllers in the machine
room. Tag spares so they can be identified in the machine room.
2. Conduit, Etc.: Painted or galvanized steel conduit and duct. Conduit size, 13 mm
minimum. Do not use flexible conduit exceeding 900 mm in length. Flexible
heavy-duty service cord may be used between fixed car wiring and car door switches
for door protective devices.
3. Traveling Cables: Flame and moisture-resistant outer cover. Prevent traveling cables
from rubbing or chafing against hoistway or elevator equipment within hoistway.
Provide CCTV traveling cable.
4. Life Safety: Connect smoke sensors, telephones, jacks and speakers to designated point
adjacent to hoistway or in machine room.
K. Templates, Forms, Sleeves and Guards: All templates, forms and sleeves for providing
necessary openings in the concrete slab over the hoistway or in the pit slab shall be provided
as part of this work. Sleeves for conduit and other small holes shall project 25 mm above the
concrete slab. Provide 25 mm steel angle guards around hoist cable or duct slots. Provide
approved rope and smoke guards for sheaves and cables.
L. Governor: Centrifugal type, car driven, with pull-through jaws. Provide electrical shutdown
switches and any overhead supports required which are additional to building structure.
M. Tie-Down Bolts, Templates, and Support Beams: Provide for securing mounted sheaves
and jack unit to the building tie-down supports and beams.
N. Entrance Equipment:
1. Door Hangers: 2-point suspension with upthrust adjustment. Tire rollers so that no
metal-to-metal contact exists.
2. Door Tracks: Bar or formed, cold-drawn steel with smooth hanger contact surface.
Provide removable tracks or track surface for replacement.
3. Interlocks: Provide type operable without retiring cam. Paint interlocks flat black.
A. Car Frame: Welded or bolted, rolled or formed steel channel construction. Isolate from jack
unit.
C. Guide Shoes: Solid guide shoes with removable phenolic (greaseless) liners.
F. Car Doors, Hangers and Tracks: Provide as specified for hoistway entrance doors, hangers
and tracks.
H. Car Door Electrical Contact: Arrange so that elevator cannot operate unless doors are
closed within tolerance allowed by Code.
I. Car Door Clutches: Heavy-duty clutches, linkage arms, drive blocks and pickup rollers or
cams to provide positive, smooth, quiet door operation. Design clutches so car doors can be
closed for maintenance purposes, while hoistway doors remain open.
J. Door Operator and Operation: Automatic medium-speed, heavy-duty, master door operator
capable of opening doors at no less than 0.30 m/s, and accomplishing reversal in no more
than 65 mm of door movement. Open doors automatically when car arrives at a floor to
permit egress of passengers. Close doors automatically after a timed interval.
1. Car Door Reversal Device: A solid-state electronically operated infrared door reversal
device shall be installed on the car doors. The device shall contain specially designed
electronic components enclosed in an insulated chassis. The device will create a criss-
cross matrix of invisible, infrared, light beams, minimum 32 beams, which shall scan
the car doorway and shall detect, through the breaking of any light beam, any opaque
object that may be placed in its path.
After a car stop is made, the door shall remain open for a predetermined interval before
closing. If, while the door is closing, the matrix of invisible light beams is interrupted
by a passenger or object entering or leaving the car, the door shall stop and reopen,
after which the door shall again start to close.
2. Door Open Timing Feature: Timing feature shall operate in conjunction with light rays
to provide adjustable, reduced, hold-open time once rays are broken and re-established.
In the event rays are broken beyond an adjustable time, a buzzer shall sound and doors
try to close at reduced speed (safety edge effective in stop but not reverse doors).
3. Nudging Action: In the event a light beam is continually obstructed, a safe edge held,
or the door hold button is continually activated, for a predetermined time interval (15-
20 seconds) after automatic door closing has been initialized, a buzzer shall sound and
the doors shall be closed at a gentle, reduced speed. Timers shall be individually
adjustable.
2. Suitably identify floor buttons, alarm button, door open button and emergency stop
switch Tactile symbols in accordance with ADAAG requirements including Braille.
Locate operating controls no higher than 1220 mm (front approach) above the car floor;
890 mm for stop switch and alarm button.
3. Provide 3.0 mm raised floor pushbuttons which illuminate to indicate call registration.
Include 16 mm designation of the floors served in face of button.
5. Provide red emergency stop switch or button at bottom of station to interrupt power
supply independently of regular operating devices. Maintain registered calls, if
emergency feature actuated, and continue normal service after power restored. Arrange
switch or button to sound control panel distress signal when actuated. Mark device to
indicate "run" and "stop" positions.
6. Provide door open button to stop and reopen closing doors. Make button operable while
car is stopped at landing, regardless of special operational features (except firefighters'
service).
7. Provide one firefighters' service key switch with engraved instructions per local
requirement, light jewel, buzzer and call cancel button.
9. Provide lockable service panel with recessed flush cover plate matching return panel.
Include the following controls with purpose and operating positions identified by
engraved letters painted black:
c. Light switch.
10. Provide black paint filled engraving with size and style approved by Engineer as
follows:
a. "Certificate of Inspection on File in Building Office" on main car station.
M. Car Top Control Station: As per Code. Provide with minimum 1220 mm long, permanently
attached, extension cord for remote operation.
O. Work Light and Duplex Plug Receptacle: Top and bottom of elevator car. Provide lights
with on-off switch and bulb guard.
P. Communication Systems:
1. "Push-to-Talk" telephone instruments and telephone cabinet in each car with shielded
wiring to machine room controller.
Engrave inside face of box cover with elevator number, building name and address.
Mount cover recessed and flush, with hairline joints.
2. Firefighters' telephone jack in each car and firefighters' panel, with 4 shielded source
wires extended to machine room junction box for firefighters' 2-way communication
system.
3. Install remote speakers provided by Life Safety Contractor in each car canopy behind
front return panel with shielded wiring extended to machine room junction box for life
safety public address system source wiring.
C. Hoistway Access Switches: Mount in entrance frame side jamb at terminals. Provide fixture
without faceplate as shown on the Drawings. (Alternately, locate in sight guard of terminal
floor hoistway doors.)
2.09 SIGNALS
B. Car Position Indicator: Metal box mounted behind the panels containing digital-type
fluorescent, active dot matrix or electroluminescent display representing the floor served and
the direction of car travel. When a car leaves or passes a floor, sound an audible signal of
minimum 20db and a maximum frequency of 1500 Hz. (Locate in each elevator cab front
return panel above each car operating station.)
C. Lobby Position Indicator: Digital-type with directional arrows mounted as shown on the
Drawings.
D. Low-Oil Indicator: Provide indicator light adjacent to ground floor hoistway entrance to
indicate parked car results from low oil.
PART 3 EXECUTION
A. Prior to beginning installation of equipment, examine hoistway and machine room areas.
B. Do not proceed with installation until work in place conforms to project requirements.
3.02 INSTALLATION
A. Install each equipment item in accordance with Manufacturer's direction, referenced codes,
and specifications.
B. Install machine room equipment with clearances in accordance with referenced codes and
specifications.
C. Install items so they may be easily removed for maintenance and repair.
D. Install items so that access for maintenance is safe and readily available.
E. Clean the following items of oil, grease, scale, and other foreign matter, and apply one coat
of field-applied machinery enamel.
1. All exposed equipment and metal work installed as part of this work which does not
have architectural finish.
3. Neatly touch up damaged factory painted surfaces with original paint and color. Protect
machine-finish surfaces against corrosion.
A. Work at the jobsite will be checked during the course of installation. Full cooperation with
reviewing personnel is mandatory. Accomplish corrective work required prior to performing
further installation.
B. Have Code Authority acceptance inspection performed and complete corrective work.
3.04 ADJUSTMENTS
A. Align guide rails vertically with tolerance of 1.6 mm in 30 m. Secure joints without gaps
and file any irregularities to a smooth surface.
D. Adjust motors, pumps, valves, controllers, leveling switches, limit switches, stopping
switches, door operators, interlocks and safety devices, etc., to achieve required performance
levels.
E. Fabricate and assemble various parts in shop to minimize field assembly. Assemble parts
which require close field fit in the shop and mark for field erection.
3.05 CLEANING
B. Keep work areas orderly and free from debris during progress of project. Remove packaging
materials on a daily basis as equipment is installed.
D. Clean machine room equipment and floor of dirt, oil and grease.
E. Clean hoistways, cars, car enclosures, entrances, operating and signal fixtures, and trim of
dirt, oil, grease, and fingermarks.
A. General: Furnish labor, materials, and equipment necessary for tests. Notify Elevator
Consultant 5 days in advance when ready for final review of each elevator unit or group.
(Final acceptance of installation will be made only after all field-quality control reviews
have been completed, identified deficiencies have been corrected, all submittals and
certificates have been received, and the following items have been completed to satisfaction
of Owner and Elevator Consultant's satisfaction.)
a. In all test conditions, obtain specified speed, performance times, floor accuracy
without releveling, and ride quality to satisfaction of the Owner and Elevator
Consultant.
b. Temperature rise in windings limited to 50 degrees Celsius above ambient.
Conduct a full-capacity, one-hour running test, stopping at each floor for 10
seconds in up and down directions, if equipment performance is questionable in
Elevator Consultant's opinion.
2. Perform work and furnish labor, materials and equipment necessary to meet specified
operation and performance.
3. Perform and assume cost for retesting required by Governing Code Authority and
Owner to verify specified operation and/or performance.
END OF SECTION 14240