Download as pdf or txt
Download as pdf or txt
You are on page 1of 111

SG3125HV

Turnkey Station
System Manual

SG3125HV-V11-SEN-Ver12-201807
Contents

1 About This Manual....................................................................1


1.1 Foreword ..................................................................................................... 1
1.2 Validity ......................................................................................................... 1
1.3 Content ........................................................................................................ 1
1.4 Target Group................................................................................................ 1
1.5 Symbols Explanation ................................................................................... 2
1.6 How to Use this Manual .............................................................................. 3
1.7 Terminology ................................................................................................. 3
2 Safety Instructions ...................................................................4
2.1 Intended Use ............................................................................................... 4
2.2 Important Safety Instructions....................................................................... 4
2.2.1 General Safety Rules .......................................................................... 4
2.2.2 Manual Storage ................................................................................... 5
2.2.3 PV Arrays Hazards .............................................................................. 5
2.2.4 Ground Fault Protection ...................................................................... 6
2.2.5 Live Line Measurement ....................................................................... 6
2.2.6 Measuring Instrument ......................................................................... 6
2.2.7 Voltage-free Operations ...................................................................... 6
2.2.8 ESD Protection.................................................................................... 7
2.2.9 LCD Parameter Setting ....................................................................... 7
2.2.10 Sand and Moisture Protection ........................................................... 7
2.2.11 Symbols on the Device Body ............................................................ 7
2.2.12 Safety Warning Signs ........................................................................ 7
2.2.13 Daily Operation and Maintenance..................................................... 7
2.2.14 Disposal of Waste ............................................................................. 8
2.2.15 Manual Description ........................................................................... 8
3 Product Description .................................................................9
3.1 Overall Design of the Turnkey Station ......................................................... 9
3.1.1 Turnkey Station Views ......................................................................... 9
3.1.2 Mechanical Parameter ...................................................................... 11
3.1.3 Ventilation Design .............................................................................12
3.2 Interior Design of the Turnkey Station .......................................................12

I
3.2.1 Internal Components ........................................................................ 12
3.2.2 Cable Entry Design .......................................................................... 13
3.2.3 Internal Devices of the Turnkey Station ........................................... 14
3.2.4 Operations on the DC and AC circuit breakers ................................ 15
3.2.5 Operations on the Protection Fuse inside the PMD ......................... 16
4 Delivery ................................................................................... 17
4.1 Scope of Delivery ..................................................................................... 17
4.2 Identifying the Turnkey Station ................................................................. 18
4.3 Checking for Transport Damages ............................................................. 18
4.4 Storage of the Turnkey Station ................................................................. 19
4.5 Removing Sealing Tapes .......................................................................... 19
5 Mechanical Installation .......................................................... 20
5.1 Transport .................................................................................................. 20
5.2 Hoisting the Turnkey Station ..................................................................... 21
5.2.1 Safety Precautions ........................................................................... 21
5.2.2 Hoisting ............................................................................................ 22
5.2.3 Fastening of Connectors .................................................................. 22
5.3 Foundation ................................................................................................ 23
5.3.1 Selection of Installation Site ............................................................. 23
5.3.2 Foundation Requirements ................................................................ 23
5.3.3 Recommended foundation construction plan ................................... 24
5.3.4 Other Precautions ............................................................................ 27
5.4 Clearance Requirement............................................................................ 27
6 Electrical Installation ............................................................. 28
6.1 Safety Instructions .................................................................................... 28
6.1.1 Generals rules .................................................................................. 28
6.1.2 Five Safety Rules ............................................................................. 29
6.2 Preparation before Electrical Connections ............................................... 30
6.2.1 Installation Tools ............................................................................... 30
6.2.2 Cable crimping ................................................................................. 30
6.2.3 Parts for Cabling............................................................................... 31
6.2.4 Opening the Turnkey Station door.................................................... 32
6.2.5 Checking the Cables ........................................................................ 32
6.2.6 During Connection ........................................................................... 33
6.3 Turnkey Station Circuit Diagram and Cable Connection .......................... 33
6.3.1 Circuit Diagram ................................................................................ 33
6.3.2 Cable Specifications ......................................................................... 33

II
6.4 DC Connection ..........................................................................................34
6.4.1 Checking before Connection .............................................................34
6.4.2 DC Cable Connection .......................................................................35
6.5 AC Connection ..........................................................................................36
6.5.1 Safety Notices ...................................................................................36
6.5.2 AC Cable Connection ........................................................................37
6.6 Ground Connection ...................................................................................38
6.7 Communication Connection ......................................................................40
6.7.1 RS485 communication solution ........................................................41
6.7.2 Ethernet Communication Solution ....................................................41
6.8 Power Supply Mode of the intelligent PMD ...............................................42
6.8.1 External Power Supply Mode ............................................................42
6.8.2 Internal Power Supply Mode .............................................................43
6.9 Finishing Electrical Connection .................................................................43
7 Commissioning .......................................................................44
7.1 Safety Instructions .....................................................................................44
7.2 Requirements for Commissioning .............................................................44
7.3 Checking before Commissioning ..............................................................45
7.3.1 Checking the Cable Connection .......................................................45
7.3.2 Checking the Turnkey Station Switches ............................................45
7.3.3 Checking PV Array ............................................................................45
7.3.4 Checking Grid Voltage ......................................................................46
7.4 Preparation before Starting .......................................................................46
7.5 Starting the Device ....................................................................................46
7.6 LCD Parameter Setting .............................................................................47
7.7 Completing Commissioning .......................................................................47
8 Starting/Stopping ....................................................................49
8.1 Starting ......................................................................................................49
8.1.1 Inspection before starting ..................................................................49
8.1.2 Start Steps .........................................................................................49
8.2 Stopping.....................................................................................................50
8.2.1 Normal Stop ......................................................................................50
8.2.2 Turnkey Station Stops when A Fault Occurs .....................................50
9 LCD Menu Operation ..............................................................51
9.1 LCD Touchscreen ......................................................................................51
9.2 Default Screen ...........................................................................................51
9.2.1 Initialization .......................................................................................51

III
9.2.2 Default Screen Introduction .............................................................. 51
9.2.3 Backlight and Screensaver .............................................................. 52
9.3 Overview of LCD Menu and Icon ............................................................. 52
9.3.1 Overview of Submenu and Icon ....................................................... 52
9.3.2 Layout of the submenus ................................................................... 52
9.4 Entering Password ................................................................................... 53
9.5 Language Setting ..................................................................................... 54
9.5.1 Conventional Way ............................................................................ 54
9.5.2 Shortcut ............................................................................................ 54
9.6 Date and Time Setting .............................................................................. 55
9.7 Running Information Checking ................................................................. 55
9.8 History Information Checking ................................................................... 56
9.8.1 History Event Checking .................................................................... 56
9.8.2 History Data Checking ..................................................................... 57
9.8.3 History Fault Checking ..................................................................... 57
9.8.4 History Alarm Checking .................................................................... 58
9.9 Present Fault Information Checking ......................................................... 58
9.10 Starting/Stopping ............................................................................. 59
9.11 Load Default ................................................................................... 59
9.12 Firmware Version Checking ............................................................ 60
9.13 Parameters of LCD ......................................................................... 60
9.13.1 Communication Parameters........................................................... 60
9.13.2 Running Parameters ...................................................................... 62
9.13.3 Protection Parameter ..................................................................... 66
10 Turnkey Station Functions .................................................... 71
10.1 Operation Mode .............................................................................. 71
10.1.1 Mode Change ................................................................................. 71
10.1.2 Operation Mode Description .......................................................... 71
10.2 Active Power Limitation .................................................................. 73
10.2.1 Introduction to Active Power Limitation .......................................... 73
10.2.2 How to Realize Power Limitation ................................................... 73
10.3 Reactive Power Adjustment ............................................................ 73
10.4 LVRT ............................................................................................... 75
10.5 High Voltage Ride Through (HVRT) ............................................... 76
10.6 Temperature Derating ..................................................................... 76
10.7 Altitude Derating Curve................................................................... 77
10.8 MPPT .............................................................................................. 77

IV
10.9 Intelligent Temperature-Control Technology ....................................78
10.10 Insulation Monitoring Function.........................................................78
10.10.1 Introduction ...................................................................................78
10.10.2 Simple Troubleshooting ................................................................78
10.11 Protection Function ..........................................................................78
10.11.1 DC over-voltage protection ...........................................................78
10.11.2 AC over/under-voltage protection .................................................79
10.11.3 Frequency anomaly protection ......................................................79
10.11.4 Islanding protection .......................................................................79
10.11.5 Reverse polarity protection ...........................................................79
10.11.6 Overload protection .......................................................................79
10.11.7 Ground protection .........................................................................79
10.11.8 Module over-temperature protection .............................................79
10.11.9 Internal over-temperature protection.............................................80
10.12 Firefighting .......................................................................................80
11 Troubleshooting......................................................................81
11.1 Safety Instructions ...........................................................................81
11.2 Fault Checking .................................................................................81
11.3 Fault and Troubleshooting on the LCD screen ................................82
11.4 LCD Display Alarm Information and Troubleshooting .....................86
11.5 Other Faults .....................................................................................87
12 Routine Maintenance..............................................................89
12.1 Safety Instructions ...........................................................................89
12.1.1 Safety Instructions...........................................................................89
12.1.2 Five Safety Rules ............................................................................89
12.2 Maintenance ....................................................................................90
12.2.1 Introduction .....................................................................................90
12.2.2 Maintenance Interval .......................................................................90
12.3 Cleaning the Turnkey Station...........................................................92
12.3.1 Introduction .....................................................................................92
12.3.2 Cleaning Interval .............................................................................92
12.3.3 Cleaning the Internal Dust ..............................................................93
12.3.4 Cleaning the Foundation .................................................................93
12.3.5 Filter checking and cleaning ...........................................................93
12.3.6 Cleaning the Surface of the Turnkey Station ..................................94
12.3.7 Checking the Lock and Hinge .........................................................94
12.3.8 Checking the Sealing Strip ..............................................................94

V
12.4 On-site painting make-up measures ............................................... 94
12.5 Replacement of the electrical components ..................................... 98
12.5.1 Replace DC fuses .......................................................................... 98
13 Appendix .............................................................................. 101
13.1 Turnkey Station System Parameter .............................................. 101
13.1.1 Input data (DC side) ..................................................................... 101
13.1.2 Output data (Grid side) ................................................................. 101
13.1.3 Mechanical parameters ................................................................ 101
13.1.4 System data ................................................................................. 101
13.2 Tightening Torques ....................................................................... 102
13.3 Exclusion of Liability ..................................................................... 102
13.4 Contact Information ...................................................................... 103

VI
1 About This Manual
1.1 Foreword
Thank you for purchasing the Turnkey Station from Sungrow Power Supply Co., Ltd.. We
hope that the device will meet your satisfaction. Your commands and feedbacks on the
performance and function of the device are important for our further improvement.

1.2 Validity
This manual is applicable to the Turnkey Station product of SG3125HV (hereinafter it will be
referred to as "Turnkey Station" unless otherwise specified).

1.3 Content
This manual contains the following information:
Content Description
Safety Safety instructions on the installation, operation, maintenance, and
instruction troubleshooting of the Turnkey Station
Product
The appearance and internal components of the Turnkey Station
Description
Delivery Delivery and inspection after receiving the Turnkey Station
Mechanical transport, installation, and electrical connection of the Turnkey
Installation
Station
Safety notices and commissioning process when the Turnkey Station is
Commissioning
powered on for the first time
Steps of starting and stopping the Turnkey Station internal devices during
Start/Stop
normal maintenance or troubleshooting
Operation on
Function and use of the Turnkey Station user interface
LCD Display
Functions Descriptions of the Turnkey Station main functions
Troubleshooting Simple troubleshooting of the Turnkey Station
Daily operation Instructions on and guides to the daily operation of the Turnkey Station

1.4 Target Group


This manual is for technical personnel who are responsible for the transport, installation
and other operations on the Turnkey Station. Only qualified personnel can perform the
installation, maintenance, and troubleshooting. Unauthorized persons should not perform
any operation to the Turnkey Station and should be away from the Turnkey Station to avoid
potential hazards. Qualified personnel are:
 Equipped with certain electrical wiring and mechanical knowledge and familiar with
electrical and mechanical principle diagram
 Familiar with the construction and working principle of the PV grid-connected power
generation system; and familiar with the construction and working principle of the
Turnkey Station upstream and downstream equipment
 Trained especially in the installation and commissioning of electrical devices

1
1 About This Manual System Manual

 Capable of coping with the dangerous and emergency situations during the installation
and commissioning
 Familiar with the country/regional standards and specifications
 Familiar with this manual

1.5 Symbols Explanation


This manual contains important safety and operational instructions that must be accurately
understood and respected during the installation and maintenance of the equipment.
To ensure the optimum use of this manual, note the following explanations of the symbols
used.

DANGER indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.

WARNING indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.

CAUTION indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.

NOTICE indicates a situation which, if not avoided, could result in equipment or property
damage.

NOTE indicates additional information, emphasized contents, or tips to help


you solve problems or save time.

The symbols below may be pasted on the electrical parts of the Turnkey Station or its
internal device. Make sure to read the following symbols and fully understand them before
installing the equipment.
Symbol Explanation

Lethal voltage inside! Do not touch!

Hot surface! Do not touch the hot surface of the device.

Protective earth. Earthing securely to ensure personal safety.

2
System Manual 1 About This Manual

1.6 How to Use this Manual


Read this manual and other related documents before transporting and installing the
Turnkey Station. Documents must be stored at hand and available at all times.
All rights reserved including the pictures, markings, and symbols used. Any reproduction or
disclosure, even partially, of the contents of this manual is strictly prohibited without prior
written authorization of Sungrow.
The contents of the manual will be periodically updated or revised as per the product
development. It is probably that there are changes of manual in the subsequent module
edition. The latest manual can be acquired via visiting the website at
www.sungrowpower.com.

Please read this manual and other related manuals before installing and
operating the devices inside the Turnkey Station.

1.7 Terminology
Name For short
Turnkey Station Turnkey Station
Module unit/ Inverter unit Unit
Intelligent power distribution cabinet Intelligent PMD or PMD
The foregoing devices are expressed in the abbreviation form in this document unless
otherwise specified.

3
2 Safety Instructions
2.1 Intended Use
The Turnkey Station, researched, developed, and manufactured by Sungrow, is mainly
applied to large-and-medium PV power station. The Turnkey Station can meet the modular
design and quick installation requirements of the large-and-medium PV power station and
can ensure the long-term, reliable, and safe power generation compliant with the grid.
The PV power generation system with the Turnkey Station is shown in the following figure.

A B C D E

Fig. 2-1 Application of Turnkey Station to the PV Power System


No. Name
A PV Array
B PV Array Combiner Box
C Turnkey Station
D Transformer
E Utility Grid

Installation of the Turnkey Station not in compliance with the description in this
manual or installation or modification of the device without authorization from
Sungrow may lead to personal injuries or device damages and may void pertinent
warranty claims from Sungrow.

2.2 Important Safety Instructions


Read the safety instructions carefully before installing the Turnkey Station. Refer to
corresponding manuals for the safety instructions on the internal devices.

2.2.1 General Safety Rules

Touching the terminals or contactors connected to the grid may lead to electric
shock!
 Do not touch the terminals or conductors connected to the grid.
 Respect all safety instructions on the grid connection.

4
System Manual 2 Safety Instructions

Lethal voltages are present inside the device!


 Pay attention to and follow the warning signs on the device.
 Respect all safety instructions in this manual and other pertinent documents.

Electric shock or fire may occur due to device damage or system fault.
 Visually inspect the Turnkey Station for device damages or other hazards.
 Check if the external devices and circuit connections are safe.
 Only operate the device when it is safe to do so.

All installations and operations on the Turnkey Station must be in full accordance
with the national and local regulations and standards.

2.2.2 Manual Storage


Product manuals are an indispensable part of the product. Important information about the
transport, installation, maintenance, and troubleshooting of the Turnkey Station is included
in this manual. All the descriptions in this manual, especially those safety-related items,
must be complied with. Please read all the instructions thoroughly prior to performing any
operation work on the Turnkey Station.

 Transport, install, maintain, and service the Turnkey Station strictly following the
descriptions in this manual. Device damage, personal injury, or property loss may
follow if otherwise.
 This manual and relevant documents should be available for relevant persons at all
times.

2.2.3 PV Arrays Hazards

DC high voltage! Electric shock hazards!


When exposed to sunlight, PV array will produce voltage, which is very high in
large-scale power Turnkey Station.
Death from burning and electric shock due to touching the PV array.
During installation, maintenance, and troubleshooting of the device, please ensure that:

 The Turnkey Station is disconnected from the PV array.


 Necessary warning signs are in place to prevent inadvertent reconnection.

5
2 Safety Instructions System Manual

2.2.4 Ground Fault Protection

If a ground fault occurs in the PV system, some parts that are supposedly
voltage-free may carry lethal voltage. Accidental touch may cause serious
damage. Make sure there is no system ground fault before performing operation
and take proper protective measures.

2.2.5 Live Line Measurement

High voltages are present inside the device. Death can result from burning and
electric shock due to touching the live components of the Turnkey Station. During
live line measurement,
 use suitable protective equipment, for example, dielectric gloves, and
 accompanied by other persons.

2.2.6 Measuring Instrument


The instrument for measuring the electrical parameters should meet the following
requirements:

 The instrument for measuring the electrical parameters should be a high-quality


instrument with sufficient measuring range.
 Make sure the connection and use of the instrument are correct to avoid arc and
other dangerous situations.
 Use suitable protective equipment, for example, dielectric gloves during live line
measurement.

2.2.7 Voltage-free Operations


Perform operations on the Turnkey Station only when all devices inside the Turnkey Station
are completely voltage-free.
 Avoid any inadvertent re-connections.
 Verify that no voltage or current is present with appropriate testing devices.
 Ground and short-circuit whenever necessary.
 Cover possible live parts to avoid inadvertent touch.
 Ensure sufficient escape room.
 After the Turnkey Station stops, wait at least 10 minutes before operating it.
 Ensure that the Turnkey Station is completely voltage-free.

6
System Manual 2 Safety Instructions

2.2.8 ESD Protection

Devices may be damaged irreversibly by electrostatic discharge (ESD).


 Avoid unnecessary touching of the PCB.
 Observe all the ESD-related safety instructions. Wear proper personal
protective equipment (PPE) such as wrist strap.

2.2.9 LCD Parameter Setting


Certain LCD settable parameters are closely related to the operations of the Turnkey
Station and internal devices, therefore these parameters can only be set with reliable
evaluation of the system.

 Improper parameter setting may impair the functionality of the device.


 Only qualified personnel can set the parameters.

2.2.10 Sand and Moisture Protection


Do not open doors of the Turnkey Station on sandstorm, thunderstorm, strong wind or hail
days or when the ambient humidity is above 95%.

2.2.11 Symbols on the Device Body


Symbols on the device contain important information on safe operations of the Turnkey
Station and its internal devices. Do not tear or damage them!

Do not damage or tear the symbols.


 All symbols on the device body must be clearly legible.
 Replace the symbols once any damage or illegibility is detected.

2.2.12 Safety Warning Signs


During transport, installation, maintenance, and troubleshooting of the Turnkey Station,
keep unauthorized persons away.
 Post warning signs near the Turnkey Station upstream and downstream switches to
prevent inadvertent connection.
 Place necessary warning signs or barriers near the on-site operation areas.

2.2.13 Daily Operation and Maintenance


Make sure the doors of the Turnkey Station are closed and locked during daily operation to
prevent internal devices from damages caused by rain or rodents.
Regularly check and maintain the Turnkey Station and internal devices to ensure long-term
and reliable operation of the Turnkey Station.

7
2 Safety Instructions System Manual

Make proper insulation protection during live line operation. At least two persons
are required until the operation is done.
Proper filed rescue facilities are necessary since locations of most PV Turnkey
Stations are far away from the urban areas.
Take the followings into consideration during daily operation and maintenance:

 The nameplate is pasted on the Turnkey Station body. It contains important parameter
information of the devices. Protect the nameplate during all operations.
 Heating components may exist inside the Turnkey Station. When the device stops, the
heating components may be still hot. Wear proper gloves when working on them.
 Maintain the cooling fans inside the Turnkey Station only when the fans stop rotating.
 Wear proper PPE, such safety glasses, safety footwear, and safety gloves, if
necessary.
 All necessary auxiliary measures are advisable to ensure personal and device safety.

2.2.14 Disposal of Waste


When the Turnkey Station has come to the end of its service life, it cannot be disposed of
together with household wastes. Some inside components can be recycled while some
components can cause environmental pollution.
Please contact the local authorized collection point.

2.2.15 Manual Description

For user convenience, there are a large number of pictures in this manual.
These pictures are indicative only. For details about the device, please refer to
the actual product you receive.

Keep this manual at a convenient place near the device for future reference
during installation, operation, maintenance, and troubleshooting of the device.

All the descriptions in this manual are for the standard Turnkey Station. Please
inform us in the purchase order if you have specific requirements. The actual
product you receive may differ.
This manual may not cover all possible situations. Should a specific problem
not explained in this manual occur, please contact Sungrow.

8
3 Product Description
3.1 Overall Design of the Turnkey Station

3.1.1 Turnkey Station Views


View Description

Front view.
Front of the Turnkey Station; a pair of doors are
equipped.

Back view.
Back of the Turnkey Station; a pair of doors are
equipped.

Left view
Left of the Turnkey Station; a pair of doors are
equipped.

9
3 Product Description System Manual

View Description

Right view
Right side of the Turnkey Station.

Control and Monitoring Window


The Control and Monitoring window is located at the front door of the Turnkey Station. At
the upper part are LED indicators; at the middle part is the color liquid crystal touchscreen;
and at the lower part are the emergency stop button and maintenance interface. Please
refer to the figure below.

LCD

EMERGENCY MAINTENANCE
STOP INTERFACE

Fig. 3-1 Control and Monitoring window


There are three LED indicators at the upper part of the Control and Monitoring Window:
POWER indicates the power is on; OPERATION indicates the proper operation of the
Turnkey Station; FAULT indicates a fault.
The working status of the Turnkey Station can be acquired through these LEDs.
LED Color Description
POWER Green The control circuit power supply is supplying power.
White The Turnkey Station is in stop mode.
OPERATION Green The Turnkey Station is in grid-connected run mode.
Yellow The Turnkey Station is in alarm run mode.
A fault occurs and has not been removed.
FAULT Red
The LED will be off when the fault is cleared.

EMERGENCY STOP button


When an emergency occurs, the DC and AC circuit breakers are disconnected
automatically after pressing the emergency stop button.

The MAINTENANCE INTERFACE


The MAINTENANCE interface is the standard Ethernet port for maintenance only.

10
System Manual 3 Product Description

The cover plate of the LCD can only be opened by using a specific key.
Please remove the key and store it properly after the operation to the LCD.

3.1.2 Mechanical Parameter

Dimensions
External dimensions (without the flashings) are shown in the figure below.

Front view Side view

Height

Width Depth

Fig. 3-2 Appearance and dimensions of the Turnkey Station


Width Height Depth
2991mm 2591mm 2438mm

Weight
Approx. 6,000kg (with internal devices).

Clearance spaces
The clearance spaces around the Turnkey Station should be sufficient for at least the doors
when they are all open.
5309mm

5601mm

Fig. 3-3 The diagram of the required space when the door is opened for 90°

11
3 Product Description System Manual

3.1.3 Ventilation Design


The ventilation system is designed as the cool air is drawn from the bottom of the Turnkey
Station and hot air is exhausted from the top of the Turnkey Station.

Fig. 3-4 Air inlets and outlets of the Turnkey Station

3.2 Interior Design of the Turnkey Station

3.2.1 Internal Components


The figure below shows the top view of the major electrical components inside the Turnkey
Station:

A C D

Fig. 3-5 Turnkey Station internal devices layout


Devices in the above figure are:
Item Device Description
That includes fuses and DC switches. Cooper bars at the
A DC cabinet bottom of the DC cabinet are used for DC-side cable
connections.
B Module cabinet It converts the DC current into the AC current.
That includes AC contactors and AC switches. Cooper bars at
C AC cabinet the bottom of the AC cabinet are used for AC-side cable
connections.
The upper part of the cabinet integrates monitor function and
D Intelligent PMD the lower part of the cabinet integrates AC power distribution
function.

12
System Manual 3 Product Description

3.2.2 Cable Entry Design


For ease of cable connection in the field, all cables among the Turnkey Station internal
devices are connected before delivery.
All cables between the Turnkey Station and the external devices are routed through the
bottom of the Turnkey Station. All cables coming into or out of the Turnkey Station should
be protected properly, for example, using cable pipes to prevent damage from rodents.
After cable connection, all cable entries except for cable glands should be sealed with
fireproof mud or other appropriate materials.
The cable entries at the bottom of the Turnkey Station are shown below.

Hole-1

Hole-1

Hole-1
Hole-3

Hole-2

Fig. 3-6 Cable entries of the Turnkey Station


The function of each opening is shown below:
Item Name Note
DC cables are connected to the DC
Hole-1 DC cable inlets
cabinet through these 3 holes.
AC cables are connected to the grid
Hole-2 AC cable outlet
through this hole.
Communication & power distribution
Communication & power distribution
Hole-3 cables come inside the Turnkey Station
cable entry
through this hole.

Dimensions of the holes


425
570

55
570

180
800
55
570

120
275

Unit: mm

13
3 Product Description System Manual

3.2.3 Internal Devices of the Turnkey Station


The Turnkey Station contains the DC cabinet, the module cabinet, the AC cabinet, and the
PMD. The DC cabinet, the AC cabinet, and the PMD are all equipped with wiring terminals
and operation switches

DC cabinet

Item Name Description


Control the connection/disconnection on the DC side of the
A DC switches
Turnkey Station
The upper part of the copper bar is for positive cable
DC cable
B connection area while the lower part is for negative cable
connection area
connection

AC cabinet

Item Name Description


A AC switch Controls the connection/disconnection on the AC side
AC cable Three phases. Connect to L1 phase, L2 phase, and L3 phase
B
connection area from bottom to top

14
System Manual 3 Product Description

PMD

Item Name
A Electricity meter
B RS485 communication port
C Ethernet port
D* Micro circuit breaker and corresponding wiring terminal
E Protection fuse
Note: * The operation switch in the figure is for reference only and may differ from the
actual product.

3.2.4 Operations on the DC and AC circuit breakers


This Turnkey Station is equipped with electrically-controlled air circuit breakers on the DC
and AC sides. The appearance of the circuit breaker panels are shown in the figure below.

C
E B A

A B
DISCHARGED
SPRING CLOSED

C Push OFF Push ON


D

DC side AC side

Fig. 3-7 DC and AC circuit breakers


Item Name Description
Manual energy storage When the circuit breaker has no energy, you can
A
handle manually store energy through this button.
Circuit breaker state Display the present state of the circuit breaker, OPEN or
B
indicator CLOSED
C Push OFF button The breaker is switched off when this button is pressed
D Push ON button The breaker is switched on when this button is pressed
Energy storage state Display the present energy storage state, CHARGED
E
indicator SPRING or DISCHARGE SPRING

15
3 Product Description System Manual

The DC Switch can be used together with a micro-motor. When there is the
power supply on the Turnkey Station AC side, the energy can be stored to the
breaker through this motor; when there is no power supply on the Turnkey
Station AC side, you need to store the energy through the manual energy
storage handle.

The operation steps are briefly described by taking the DC switch as an example.

 Switch on
Press the Push ON button on the breaker panel to switch on the breaker.
Before switching on the breaker, you need to check if the energy storage state displayed on
the panel is CHARGED SPRING. If the state is DISCHARGED SPRING, you need to store
the energy manually by turning the manual energy storage handle down until the breaker
panel displays CHARGED SPRING.

DISCH CHARG
ARGED ED
SPRIN SPRIN
G G

After the breaker is switched on, the breaker panel displays CLOSED.

 Switch off
Press the Push OFF button on the breaker panel to switch off the breaker.
After the breaker is switched off, the breaker panel displays OPEN.

3.2.5 Operations on the Protection Fuse inside the PMD

Identify fuses states


The fuse inside the PMD is in closing or opening state.

(a) (b) (c)

Figure (a) shows the closing state


Figure (b) shows the opening state
The fuse is in the closing state by default.

16
4 Delivery
4.1 Scope of Delivery
The scope of delivery of the Turnkey Station is shown in the following table:

A B C D

E F G H

I J

No. Device Quantity Note


A Turnkey Station 1 -
Enclosed System manual, delivery inspection report,
B 1
documents certification, and warranty card
Door keys of
1 -
Turnkey Station
C
Keys to monitor
1 -
window
85 M16×55
D Bolt
12 M8×25
E Flat washer 170 φ 16

F Spring washer 85 M16


85 M16
G Nut 12 M8
5 M6
24 M8
H Washer
10 M6
I Disc springs 12 M8
10 M5×16
Cross recessed
J 60 M6×20
hexagon bolt
12 M4×16

17
4.Delivery System Manual

Note: The foregoing components and their quantities are based on the standard Turnkey
Station, and those of the actual product may differ.

4.2 Identifying the Turnkey Station


Identify the Turnkey Station from its nameplate. The nameplate contains the following
information: Turnkey Station model, major technical parameters, marks of certification
institutes, origins, and serial number.

Nameplate

Very important technical parameters and Turnkey Station-related parameters are


displayed on the nameplate.
Protect the nameplate at all times!

4.3 Checking for Transport Damages


The Turnkey Station has been strictly inspected and tested before delivery. Despite robust
packaging, the container or inside devices may be damaged during transport. Therefore,
once you receive the Turnkey Station, a detailed inspection is necessary.
If any damage is detected, contact the forwarding company or Sungrow immediately. A
relevant photo is desired. We will provide you with the fast and best service.
 Examine the contents of the shipment to check the scope of delivery described in 4.1
Scope of Delivery for completeness.
 Check to make sure the Turnkey Station and inner devices are of the same models as
those in your order;
 Check thoroughly the Turnkey Station and inner devices for any possible damages
during transport.

Install and commission the Turnkey Station only when it is technically faultless!
Make sure before installing the Turnkey Station that
 the Turnkey Station is intact without any damage; and
 all devices inside the Turnkey Station are intact without any damages.
Before commissioning of the Turnkey Station, make sure all the sealing tapes are removed
from the air inlets and outlets. Otherwise, there may not be sufficient fresh air for the normal
operation of the devices inside the Turnkey Station.

18
System Manual 4.Delivery

4.4 Storage of the Turnkey Station


If the Turnkey Station is not to be installed immediately after delivery, store it appropriately:
 Store the Turnkey Station indoors, for example, large warehouse or workshop, to
prevent possible condensation or damp.
If the Turnkey Station has to be stored outdoors, elevate the Turnkey Station base
according to the geological and ambient conditions. When the ambient temperature is
too low, heat the Turnkey Station internal devices.
 Temperature: -40°C~+70°C
Relative humidity: 0 to 95%, and non-condensation
Store the Turnkey Station on a dry, clean, and solid ground with sufficient load-bearing
capacity. The ground should be flat without water, bumps, or plantings.
 Lock the Turnkey Station internal devices and the Turnkey Station during storage.
 Take proper protective method to prevent the water and dust penetrating into the
Turnkey Station. Protect the Turnkey Station air inlets and outlets at least.
Regularly, once every half a month at least, check the Turnkey Station and internal devices.

4.5 Removing Sealing Tapes


To prevent sea-water or moisture penetrating into the Turnkey Station during ship transport,
the air inlets and outlets of the Turnkey Station are all sealed with sealing tapes.
The positions of the sealing tapes are shown by "A" in the following figure.

A A

A A A A

Front view Left view

A A A A

A A

A A

Back view
Fig. 4-1 Location of the sealing tapes

19
5 Mechanical Installation

Respect all local standards and requirements during mechanical installation.

5.1 Transport
All devices are installed inside the Turnkey Station before delivery. The Turnkey Station
should be transported as a whole. Transport the Turnkey Station by a crane with sufficient
load capacity.
The Turnkey Station is delivered to the user by the forwarding company. After unloading,
the Turnkey Station will be transported to the installation site by the plant staff.

Local standards and regulations on the transport and loading & unloading of the
container, especially those safety instructions, should be observed at all times.
 All the accessory appliances used during transport should be maintained
beforehand.
 The Turnkey Station must be transported by qualified personnel. Qualified
personnel are those who have relevant training experience, especially
safety-related experience.

Keep in mind the dimensions and total weight of the Turnkey Station at all times!
Ensure that the following requirements are met:

 All the doors are locked.


 Choose the appropriate crane or hoist to transport the Turnkey Station. The crane or
hoist must be sufficiently capable of bearing the Turnkey Station weight.
 An additional traction vehicle may be required when the road has a gradient.
 Anything, which may hinder the transport, like trees, cables (or the like), should be
removed.
 If possible, transport the Turnkey Station on fine weather days.
 Warning signs or barriers must be posted near the transport areas to avoid accidental
injuries.
Additionally, the following requirements should be met when the Turnkey Station is placed
on the ground:

 Place the Turnkey Station carefully and gently. Do not pull or push the Turnkey Station
on any surface.
 The place should be firm and flat with good drainage and no obstacles or outshoots.
The Turnkey Station should be supported by the four feet.

20
System Manual 5 Mechanical Installation

5.2 Hoisting the Turnkey Station

5.2.1 Safety Precautions

 Observe the safety operating rules of the crane at all times.


 Standing within 5 to 10 meters away from the hoisting areas is strictly
prohibited! Anybody standing under the boom or Turnkey Station is strictly
prohibited in the whole hoisting process.
 The hoisting work must be stopped on violent weather days. For example, in
strong wind, heavy rain, or thick fog conditions.
Please observe the following items:

 All safety requirements must be met.


 A professional instructor is required in the whole hoisting process.
 All the used slings must have the load-bearing capacity of at least 10t.
 The crane should have sufficient arm length and radius of gyration.
 All the connection point must be firmly connected.
 The length of the slings can be adjusted appropriately according to on-site conditions.
 Transport the Turnkey Station in a level, smooth, and steady way.
 Transport the Turnkey Station by connecting the four top corner fittings.
 Some accessories may be required to ensure the safety during hoisting.
The following figure illustrates the hoisting operations. Circle A describes the work areas of
the crane. Anybody standing inside the circle B is prohibited for safety considerations.

A
Inverter
Inverter

Crane

Fig. 5-1 Hoisting the Turnkey Station

21
5 Mechanical Installation System Manual

5.2.2 Hoisting
During the whole hoisting process, please observe the following rules:
 Hoist the Turnkey Station in a vertical manner. Do not drag or drop the Turnkey Station
on any surface.
 When the Turnkey Station has been hoisted for about 300mm away from the ground,
stop to check if all the connections are still firm. After confirmation, continue hoisting the
Turnkey Station.
 When transported to the final location, the Turnkey Station should be put down slowly
and steadily.
 The final location should be firm, level, and well-drained. The Turnkey Station is
supported by four bottom fittings on the ground.
The Turnkey Station should be hoisted by four top corner fittings as shown in the following
figure.

Fig. 5-2 Hoisting from top fittings

5.2.3 Fastening of Connectors


Use slings with hooks or U-hooks to hoist the Turnkey Station.
The lifting devices should be correctly connected to the Turnkey Station.

22
System Manual 5 Mechanical Installation

Lifting device Hook U-hook

Connections

Insert the hook from Lateral pin of the U-hook


Notice
inside to outside. should be tightened.

 National and local safety rules should be observed at all times.


 Violating relevant safety rules may void pertinent warranty claims from
Sungrow.

5.3 Foundation

5.3.1 Selection of Installation Site


When selecting the installation site, consider the following requirements at least:

 Ambient and geological conditions, such as stress wave emissions, the level of
underground water table and etc. should be taken into account.
 The ambient environment should be dry, well ventilated, and far away from inflammable
materials.
 The ground at the installation site must be compacted enough. Relative compaction of
the ground should be equal to or greater than 98%. Otherwise, take proper methods to
strengthen the ground.

5.3.2 Foundation Requirements

Pay attention to the high weight of the Turnkey Station. Check thoroughly the
conditions on the installation site (mainly the geographical and environmental
conditions) before designing and constructing the foundation.
Improper foundation construction may affect the placement of the Turnkey Station, open &
close of the door, and future maintenance. Therefore, the foundation must be designed and
constructed according to the related standard. The dimensions and weight of the Turnkey
Station, the cable route, and the future maintenance should be considered at all times.
The following conditions must be met:
 The bottom of the foundation should be firm enough.

23
5 Mechanical Installation System Manual

 The foundation should be at least 820mm higher than the ground level on site to
prevent the rain from damaging the base or penetrating into the Turnkey Station.
 Sufficient cross-sectional area and depth of the foundation should be maintained. The
depth is designed according to local soil conditions.
 Cable route should be taken into account.
 According to the cable design of Turnkey Station and for easy electrical
connection, please establish cable trenches on the bottom of the Turnkey
Station, i.e. reserve the cable trenches inside the foundation and pre-bury the
wire pipes.
 The dirt dug out should be cleared immediately.

5.3.3 Recommended foundation construction plan


The foundation construction plan includes concrete foundation plan and strip foundation
plan.

Plan 1: Concrete foundation

The foundation plan described in this chapter is for reference only. Please consult
on-site professional project personnel before construction.

This section clearly specifies the foundation construction plan for reference as shown
below (unit: mm). For details, refer to the final civil drawing issued by the design institute.
The recommended foundation construction plan is described as follows:

Channel steel pre-


embedding
300
500

300
2600

300
700 225
500

500

4914

 A maintenance platform should be built for the convenience of maintenance and repair
work.
 The position of cable inlets and outlets are at the bottom of the Turnkey Station. In the
construction of the foundation, adequate space is reserved for AC/DC side cable trench

24
System Manual 5 Mechanical Installation

and perforating pipes are pre-embedded. The specification and quantity of the
perforating pipes are determined according to the cable model and cable quantity.
 20# channel steel is pre-embedded on the front and back side of the foundation surface
so that the foundation of the Turnkey Station can be welded with the foundation after
the mechanical installation. The pre-embedded channel steel must be level with the
rest part of foundation upper surface; and the pre-embedded steel sheet must be firm
and reliable.
 According to the on-site actual conditions, drainage system is designed and
constructed at the bottom of the foundation to avoid water immersion.
 In the construction of the foundation, the grounding body is pre-embedded. One end of
the grounding body is welded with the main grounding network of power plant while the
other end is welded with the pre-embedded channel steel in the foundation to ensure
firm welding quality. The embedded grounding pole must be in accordance with the
installation codes.
 The maintenance entry is designed on the foundation; if necessary, the operators can
enter the foundation to perform required operations.
 It is recommended to build up steps at the inlet of the Turnkey Station for convenient
access. The step width and level are appropriately selected according to the actual
on-site conditions.
 For convenience of future maintenance and repair work, a proper maintenance area is
constructed around the foundation according to the actual on-site conditions. The
maintenance area has an adequate bearing capacity and levelness and complies with
the local standard/code.
 Both ends of all the pre-embedded pipes are temporarily blocked to prevent impurities.
Otherwise, it is inconvenient to lay cables in the future.
 Upon connection of all the electrical cables, the cable inlet, outlet, and joint are sealed
by refractory mud or other appropriate materials to prevent pests and mice from entry.
 For the rest recommended dimensions, please refer to the mentioned drawing and
other related drawings.

Pre-bury grounding units according to relevant standards of the country/region


where the project is issued.

Fixing the Turnkey Station


Check to ensure that the foundation construction has met all the local standards and other
relevant requirements.
Hoist the Turnkey Station onto the foundation after the foundation is dry enough.

25
5 Mechanical Installation System Manual

Foundation

Inverter bottom

Plan 2: Concrete pillar


The following conditions must be fulfilled:
 The bottom of the foundation should be firm enough.
 The foundations must be suitable for the weight of the Turnkey Station.
 The foundation should be at least 100mm higher than the pea gravel ground on site to
prevent the rain from damaging the base or penetrating into the Turnkey Station.
 Each foundation has the following width: 500mm to 600mm.
 The length of each foundation must be at least 200 mm longer than the width of
Turnkey Station on each side.
 Sufficient cross-sectional area and depth of the foundation should be maintained. The
depth is designed according to local soil conditions.
 Cable route should be taken into account.
Overall construction effect of Plan 2 is shown below.

Front view Left view

A B C A A B A

26
System Manual 5 Mechanical Installation

No Name
A Foundation
B Pea gravel ground
C Solid ground, e.g. gravel

5.3.4 Other Precautions

A drainage system should be designed on the installation site to prevent the


Turnkey Station from being immersed in water during heavy rainfalls.

Do not plant any trees near the Turnkey Station installation site to prevent the
damage of the Turnkey Station caused by tree leaves or stems.

5.4 Clearance Requirement


On site, if two Turnkey Stations are placed side by side, the minimum reserved clearances
around the Turnkey Stations are shown in the following figure.

C B

D
A

Fig. 5-3 Requirements for clearances around the Turnkey Station


A* B* C* D*
4000mm 4000mm 4000mm 4000mm
Note: A is the minimum distance away from the front doors.
* The distance illustrated in this table is the minimum values. More space is recommended
for better ventilation and higher conversion efficiency of the Turnkey Station.

27
6 Electrical Installation
6.1 Safety Instructions

6.1.1 Generals rules

High voltage! Electrical hazards!


 Do not touch the live components of the device.
 Make sure the AC and DC sides are voltage-free before installation.
 Never put flammable materials in the vicinity of the Turnkey Station.

If a ground fault occurs to the PV system, some parts that were voltage-free
before may contain lethal voltage. Accidental touch may cause serious damage.
Make sure there is no system ground fault before operation and take proper
protective measures.

 Observe all the country-specific standards and regulations.


 Connect the Turnkey Station to public grid only after receiving authorization
from the local network operator.

Only professional electricians can perform the operations described in this


chapter.
Observe all the instructions to connect the wires.

Disconnect all AC and DC Switches before electrical connection.

Sand and moisture penetration may affect the performance of electric devices
inside the Turnkey Station!
 Do not perform electrical connection in sandy season or when the ambient
relative humidity is above 95%.
 Perform electrical connection on fine weather days.

28
System Manual 6 Electrical Installation

Improper torque used may cause a fire to the connection point!


Fix the bolts by strictly following the torque requirements in this manual during
electrical connection.

Too small bending radius or excessive intertwine may damage the fiber!
When selecting fiber as the communication cable, please follow the related
requirements of the fiber manufacturer about the min. allowable bending radius.

Only professional electricians can perform the electrical connection. Professional


electricians should meet the related requirements listed in 2 Safety Instructions in
this manual. Sungrow should hold no liability for any personal injury or property
loss caused by ignorance of the safety instructions.

Ensure the electrical insulation is satisfied before laying the cables. Follow the
EMC regulation and lay the power cable and communication cable in different
layers. Provide support and protection to the cables to reduce the stress of the
cables when necessary.

Strictly follow all the instructions when connecting the cables.

 The installation and design of the Turnkey Station must fulfill national and local
standards and regulations.
 Sungrow should hold no liability for the Turnkey Station or system fault caused
by ignorance of the description in this manual.

Select optical fibers as the external communication cable to lower the signal
interference.

6.1.2 Five Safety Rules


During electrical connections and other operations on the inside device, observe the
following Five Safety Rules:

 Disconnect all the external connections and disconnect the Turnkey Station internal
power supply
 Avoid any inadvertent re-connections.
 Verify that no voltage or current is present with appropriate testing devices.

29
6 Electrical Installation System Manual

 Ground and short-circuit whenever necessary.


 Cover possible live parts to avoid inadvertent touch.

6.2 Preparation before Electrical Connections


Cables inside the Turnkey Station have been connected before delivery. You need to
connect the cables of the Turnkey Station to the external devices, i.e. the DC input cable
connection, the AC output copper bus connection, the communication connection, and the
communication cabinet cable connection.

6.2.1 Installation Tools


Prepare the following tools before installation:

 Torque wrench
 Screwdriver
 Wire stripper
 Terminal crimping device
 Alcohol blast burner (or hot air blower)
 Allen wrench
 Meg-ohmmeter or multimeter
 Other auxiliary tools or spare parts

6.2.2 Cable crimping


You need to crimp the cables as follows before the electrical connection.
Step 1 Strip off the insulation cover of the cable with a stripped length of 5mm longer than the
depth of the cable lug;

L=D+5mm
D

Cable
lug

Step 2 Crimp the cable lug.


1. Insert the stripped cable into the cable lug;
2. Tighten the cable lug with relevant tools. The crimping number should be more than
two.

30
System Manual 6 Electrical Installation

Step 3 Insert the heat-shrinkable tubing;


1. A tubing with a length of 2cm longer than the depth of the cable lug is recommended;
2. Insert the heat-shrinkable tubing into the cable lug;
3. Shrink the tubing with a hot air blower.

Cable protectors are advisable in the cable crosses if the multi-core


cables are used.

6.2.3 Parts for Cabling

Incorrect connection of power cables will cause fires. Follow the sequence when
connecting the power cables.
Ensure the fastness of the connection parts. Poor contact or oxidation of the
contact surface may cause a fire.

NOTICE
 Long bolts may impair the insulation and may cause a short circuit.
 Remove the heat-shrinkable tubing between the cable lug and the copper bar if
necessary. Poor contact or over-heating may follow if otherwise.

Clean the connection terminals before cable connection. Do not touch the
terminal after cleaning.

The spare parts required for connecting power cables, such as the screws, are within the
scope of delivery. Please respect the description in this chapter during connection.

31
6 Electrical Installation System Manual

Copper Wire Connection


If copper wires are used, connect the spare parts as described below:

A
E E
D D
F C

Fig. 6-1 Copper wire terminal connection sequence of single-hole cable connection
A B C D E F
Copper Bus Cable Lug Bolt Spring washer Flat washer Nut

Aluminum Wire Connection


When the aluminum wire is selected, a copper-aluminum composite terminal is needed as
shown below:

A
E E
D D
F C

Fig. 6-2 Copper-aluminum composite terminal of single-hole cable connection


A B C D E F
Copper copper-aluminum composite Bolt Spring Flat Nut
Bus terminal washer washer

6.2.4 Opening the Turnkey Station door


All the Turnkey Station doors are standard container doors. Open the doors before cable
connection.

6.2.5 Checking the Cables

Check to ensure the intactness and insulation of all cables before electrical
connection. Poor insulation or damages of the cables may cause potential
hazards. Replace them if necessary.

32
System Manual 6 Electrical Installation

6.2.6 During Connection

 Make sure the polarities of the DC cables and AC cables and the phase
sequence of the AC cables are correct before connection.
 Do not pull the cables hard during electrical connection.
 Make sure there is enough wire bending space for all connection cables.
 Take proper methods to reduce the stress of cables.
 Check carefully for the correctness and fastness of the connections.

6.3 Turnkey Station Circuit Diagram and Cable Connection

6.3.1 Circuit Diagram

Turnkey Station

E F G

=
A B
3~

C
D K

Fig. 6-3 Turnkey Station main circuit diagram


Devices in the above figure are:
Item Name
A DC input
B AC output
C External communication port
D External 3-phase power supply port
E DC cabinet
F Module cabinet
G AC cabinet
K Intelligent PMD

6.3.2 Cable Specifications


Choose cables according to the rules below:
 All the cables must have sufficient ampacity. The ampacity of the conductor can be
influenced by environmental conditions, conductor insulation materials, laying, wire
materials , cross-sectional areas and etc.

33
6 Electrical Installation System Manual

 All the cables must be chosen according to the maximum current on the AC and DC
sides of the Turnkey Station, and enough allowance is required.
 Cables for one side should be of the same type and specification.
 Flame-retardant and fire-resistant cables are recommended.

Overloading operation of cables is strictly prohibited.

6.4 DC Connection
6.4.1 Checking before Connection
Check the following items before cable connections.

 Check the open-circuit voltage of the PV array to ensure the open-circuit voltage is
within the max. DC voltage of the Turnkey Station.
 Mark the negative and positive polarity of the cable.
 Check the PV array for possible ground fault.

 Open-circuit voltage of the PV array should not exceed the max. DC voltage of
the Turnkey Station. The Turnkey Station may be damaged if otherwise.
 If the ground fault is found, it must be removed before any DC connection.

Strictly follow all the instructions when connecting the cables.

Observe all the safety rules required by the PV array manufacture.


Start the DC connection only when all checks and measurements meet requirements.

34
System Manual 6 Electrical Installation

6.4.2 DC Cable Connection

50

Φ17

277 420(6*70) 135 420(6*70) 205 420(6*70) DC + 80

684 DC -

Dimensions of copper bar

Front view of the left- door side of the inverter

4 191

270

Top view of the left- door side of the inverter

Fig. 6-4 The location and size (in mm) of the wiring copper bar on the DC side
Item Description
A DC positive cable connection area
B DC negative cable connection area

Cable requirements:
 21 input cables can be connected to the DC side
 The maximum cross-sectional area of the aluminum/copper cable is 400mm2
 Recommended copper lug mode: DT-400 or BL400-16
 Fasten the wiring terminal with the bolts of M16×55 in the scope of delivery
 The fastening torque is 119~140Nm

Cable connection steps


Step 1 Make sure the switch upstream of the combiner box is in the OFF position.
Step 2 Strip off the insulation cover of the cable with a stripped length of 5mm longer than the
depth of the cable lug.
Step 3 Crimp the cable lug.
1. Insert the stripped cable into the cable lug.
2. Tighten the cable lug with relevant tools. The crimping number should be more than
two.
Step 4 Insert the heat-shrinkable tubing.
1. A tubing with length of 2cm longer than the depth of the cable lug is recommended.
2. Insert the heat-shrinkable tubing into the cable lug.

35
6 Electrical Installation System Manual

3. Shrink the tubing with a hot air blower.

Cable protectors are recommended in the cable crosses if the multi-core cables
are used.
Step 5 Connect the cable.
1. Select bolts matching with the cable lug.
2. Attach the cable lug to the DC connection copper bar following the sequence in the
following figure.
3. Fasten the bolts with a screwdriver or spanner.

 Incorrect connection sequence may cause a fire. Please pay much attention to
the connection sequence.
 Ensure the firmness of the cable connection. Poor connection or oxidation of
the surface may cause over-heating or a fire.

NOTICE
 Long bolts may impair the insulation and may cause a short circuit.
 Remove the heat-shrinkable tubing between the cable lug and the copper bar if
necessary. Poor contact or over-heating may follow if otherwise.
Step 6 Confirm that all cable connections are secure.
Connect the DC cables according to the above steps.

6.5 AC Connection

6.5.1 Safety Notices

Incorrect AC connection may cause damages to the Turnkey Station.

Electrical hazards!
 Do not touch the live components.
 Disconnect the AC switches and ensure all terminals are voltage-free.
 The connection to the public grid must be carried out only after receiving
approval from the distribution utility as required by national and state
interconnection regulations.

Strictly follow all the instructions when connecting the cables.

36
System Manual 6 Electrical Installation

Strictly follow all instructions on the device when closing/opening the AC


switches.

6.5.2 AC Cable Connection

Φ17

L3
80
L2
L1 85

700(10*70) 70
410 618
Dimensions of copper bar

Inverter front side-front view

8
8 92
85
8 278

Inverter front side-top view

Fig. 6-5 The location and size (in mm) of the wiring copper bar on the AC side

Cable requirements:
 A maximum of 11 three-phase cables can be connected to the AC side
 The maximum cross-sectional area of the aluminum/copper cable is 400mm2
 Recommended copper lug mode: DT-400 or BL400-16
 Fasten the wiring terminal with the bolts of M16×55 in the scope of delivery
 The fastening torque is 119~140Nm

Cable connection steps


Step 1 Disconnect the downstream grid-side switches of the Turnkey Station.
Step 2 Check to ensure the AC connection sequence is correct.
Step 3 Strip off the insulation cover of the cable with a stripped length of 5mm longer than the
depth of the cable lug. Use cable lug based on the cable specification.
Step 4 Crimp the copper cable lug.
1. Insert the stripped cables into the cable lug.
2. Tighten the cable lug with proper tools. The crimping number should be more than two.
Step 5 Install the heat-shrinkable tubing.
1. Select tubing with dimensions matching with the cables. Tubing length should be 2cm
longer than the cable lug.
2. Insert the heat-shrinkable tubing into the cable lug.
3. Shrink the tubing with a hot air blower.

37
6 Electrical Installation System Manual

If multi-core cable is used, install cable protection stall at the forks.


Step 6 Connect the cable.
1. Select bolts matching with the cable lug.
2. Crimp the cable lug into the AC copper bar.
3. Fasten the bolts with screwdriver or spanner

 Incorrect connection sequence may cause a fire. Please pay much attention to
the connection sequence.
 Ensure the firmness of the cable connection. Poor connection or oxidation of
the surface may cause over-heating or fire.

NOTICE
 Long bolts may impair the insulation and may cause a short circuit.
 Remove the heat-shrinkable tubing between the cable lug and the copper bar if
necessary. Poor contact or over-heating may follow if otherwise.
Step 7 Check to ensure the connection is secure.
Connect the AC cables according to the above steps.

6.6 Ground Connection


Brief Introduction
Generally, the ground connection includes equipotential connection of internal devices and
external grounding.

B D

Front door side


Item Description
A DC cabinet
B AC cabinet
C Module cabinet
D Intelligent PMD

Equipotential connection of Turnkey Station internal devices


The grounding copper bar inside the Turnkey Station is located at the right side of the
Turnkey Station, as shown in the following figure A.

38
System Manual 6 Electrical Installation

The main internal electrical devices have been connected to the ground copper bar before
delivery.

External grounding
Two external grounding points are located at the bottoms on the left side and right side of
the Turnkey Station.
Illustrations Description

Left-side view of the Turnkey Station.


The external grounding point is located at B in the
figure.

Right-side view of the Turnkey Station.


The external grounding point is located at B in the
figure.

The external grounding points of the Turnkey Station can be grounded in the following two
manners:
 Connect the grounding cable to the external grounding points with M10 bolts, where the
recommended cable is of 50 mm2 to 95 mm2.
 Weld the grounding steel flat onto the external grounding point, after which
anti-corrosion processing needs to be performed.
It is recommended that two points of the Turnkey Station should be connected to the
ground system of the PV plant.

39
6 Electrical Installation System Manual

The Turnkey Station needs to be grounded on site. The following operations


should also be conducted on site:
Measure the electrical conductivity between the device ground terminals and
the total equipotential connection copper bar to ensure the effectiveness of the
internal ground connection.
Perform the external grounding according to on-site situation and instructions of
the plant staff.
The grounding resistance should be no more than 4Ω.

The grounding resistance should be determined according to local standards


and regulations.

The country-specific regulations and standards must be observed at all times!

If you have any doubts during the ground cable connection, please contact the
related technical personnel in time. Any installations not following the standards
or the installation and alternation without permission may lead to safety incidents
or damage to the devices. Sungrow shall hold no liability for the damages caused.

6.7 Communication Connection


All communications between the Turnkey Station and the external devices are based on the
intelligent PMD inside the Turnkey Station.
As shown in the following figure, the RS485 port and the Ethernet port are designed in the
intelligent PMD.

Item Description
A RS485 communication port
B Ethernet port

40
System Manual 6 Electrical Installation

6.7.1 RS485 communication solution


The A5B5 port is connected to the PC.
A6B6 to A9B9 are standby ports and can be connected to the detection and control device
of the transformer, the combiner box, the environmental detector, and the like. For details,
refer to the actual configuration.

PC
PIN3:TXD PIN2:RXD
Inverter

RS485A
TX+/RX+ 5 4 3 21
9 8 7 6
RS485B TX-/RX-
A5B5
RS485/232 converter

PC RS232

Connection steps
Step 1 Strip off the insulation covers at the ends of two cables that need to be connected to the
same terminal.
Step 2 Insert the bare copper wires into the cold-pressed terminal and crimp them with the
crimping tool.
Step 3 Connect the cold-pressed terminal to the communication terminal.
Step 4 Twist shield layers of the two cables into one and insert it into the cold-pressed terminal
after heat shrink via heat-shrinkable tubing
A B FG

Fig. 6-6 Schematic diagram of terminal crimping

 To ensure communication quality, the RS485 communication connection


cable should be the shielded twisted pair. (Recommended: the shielded
twisted pair of RVVP-2*1.0.)
 After the shield layers of the shielded cable is connected, single point
grounding is adopted at the monitoring terminal.

6.7.2 Ethernet Communication Solution


Connect the Ethernet port inside the PMD to the PC by using the network cable
(EIA/TIA568B)

41
6 Electrical Installation System Manual

PC

Ethernet port

6.8 Power Supply Mode of the intelligent PMD


The power supply mode includes internal power supply mode (default) and external power
supply mode.
 Internal power supply mode: powered by the AC current that is output from the AC
cabinet inside the Turnkey Station, where cables for the internal power supply have
been connected before delivery.
 External power supply mode: connect the external auxiliary power port and the external
three-phase power supply to supply power.

6.8.1 External Power Supply Mode


The power distribution area, including the wiring terminal and the micro circuit breaker, is
located at the bottom of the PMD. The internal power distribution area of the PMD is shown
in the following figure.

42
System Manual 6 Electrical Installation

The external auxiliary power supply needs to be the three-phase 380V AC current, and the
cross-sectional area of the connected cable is 6.6mm2.
The maximum distribution power of the PMD is 15kW.
Item Description Description
Port of the external
C Corresponding micro circuit breaker is Q2
three-phase power supply
D Protection fuse -

Operation before cable connection

Disconnect the protection fuse at the bottom of the PMD before closing the
external power supply switch Q2. For details, refer to the section "3.2.5
Operations on the Protection Fuse inside the PMD".

6.8.2 Internal Power Supply Mode


Cables for the internal power supply have been connected before delivery.
During normal operation of the Turnkey Station, the control switch of the internal power
supply mode automatically connects and disconnects without manual operations.

In the internal power supply mode, close the protection fuse at the bottom of the
PMD. For details, refer to the section "3.2.5 Operations on the Protection Fuse
inside the PMD".

6.9 Finishing Electrical Connection

After the electrical connection, check the connection of all cables. Make sure all
the connections are correct and firm.
After ensuring that all connections are correct and firm,

 Check the bottom of the Turnkey Station and seal the gaps between the cables with
fireproof mud. If cable glands are used, make sure they are tightened. Seal the unused
terminal.
 Reassemble the protective grid removed.
 Water-proof processing should be done on the foundation of the Turnkey Station.

43
7 Commissioning
7.1 Safety Instructions

High voltage! Electric shock!


 Wear proper protective equipment before performing any operations on the
device.
 Do not touch the live terminals or conductors.
 Respect all safety instructions inside the device and in this manual.
 Respect all safety instructions prescribed by the manufacturer of devices
connected to the Turnkey Station.

Grid-connection of the Turnkey Station can only be done by qualified persons


after receiving approval from the local utility grid company.

When the Turnkey Station is operating, make sure there are no flammable
materials within at least 5m around the installation site.
Local/national standards about the min. electric clearance around the Turnkey
Station should be respected.

Make sure the installation is correct and no spare parts or tools are left inside the
device.

Close the doors of the Turnkey Station and the internal devices if the
commissioning process is stopped.

7.2 Requirements for Commissioning


Before commissioning, installation of the DC cabinet and AC cabinet inside the Turnkey
Station should be checked thoroughly.
 Ensure all cable connections are secure and all bolts are fixed properly.
 Ensure DC side voltage meets the Turnkey Station requirements and the polarity is
correct.

44
System Manual 7 Commissioning

 Ensure AC side voltage meets the Turnkey Station requirements.


 Ensure all cable connections meets related standards and requirements.
 Ensure the system is properly grounded. Ground resistance is so important for the
whole system that before the commissioning, make sure the ground resistance is less
than 4Ω

NOTICE
All operations during the commissioning must be performed by qualified
personnel only.

Commission the device when it is sunny and the environmental conditions are
stable to ensure successful commissioning.

7.3 Checking before Commissioning

7.3.1 Checking the Cable Connection


 Check cables for any possible damages or cracks.
 Check that all cables are connected securely according to the cable connection
diagram. Adjust the cable connection if necessary.
 Ensure all cable connections are firmly enough. Fix the bolts if necessary.
 Check the PE equipotential connection. Ensure PE ground point of the internal devices
has been connected to the equipotential connection point in the Turnkey Station and
properly grounded. The ground resistance should be no more than 4Ω.

7.3.2 Checking the Turnkey Station Switches


 Ensure that all DC, AC, and micro switches in the Turnkey Station are in the “OFF”
position.
 Ensure that the emergency stop button is released.
 Check and ensure the Turnkey Station and switches upstream and downstream meet
the requirements and flexible enough.

7.3.3 Checking PV Array

Ensure the measuring devices are connected and used correctly. Otherwise, there
will be an electric arc.

DC side voltage should be no more than the Turnkey Station max. input DC
voltage.
Too high DC voltage may damage the Turnkey Station even cause safety incident.

45
7 Commissioning System Manual

To ensure the system reliability and device operation, the Turnkey Station DC
side should employ PV cells of the same manufacturer and numbers of PV cells
in each string should be the same.
Check the PV arrays before grid-connection. The voltage of each DC main cables should
be the same and no more than the max. allowable DC voltage. Check carefully the polarity
of each DC main cable. Once the polarity in one DC main cable is incorrect, the PV arrays
may be damaged.
Make sure the environmental condition is stable since the voltage of PV array may change
with the solar radiation and the temperature of the PV cells. Use the U-I curve to record the
PV array situation. Commission the device when the PV array output situation is stable.

The PV field circuit fault (module fault or module numbers deviation in certain
array), cable damages or connection looseness may cause the voltage
deviation exceeding 3% at stable environmental conditions.
 Record the environmental parameters (temperature and radiation, etc.).
 Measure the resistance of cables (between the terminal box and the Turnkey Station).
 Record accurately all the measured data.

7.3.4 Checking Grid Voltage


 Measure accurately the grid 3-phase line-to-line voltage: L1-L2, L1-L3, and L2-L3.
Measured data should not exceed the grid permissible voltage and the three phases
are balanced.

Adjust the transfer ratio of the transformer by qualified personnel if the grid
voltage deviation is large.
 Measure and record the grid frequency. Measured data should not exceed the grid
permissible frequency.
 Measure the THD and check the curve if possible. The Turnkey Station will stop
running if the THD is serious.
 Record accurately all the measured data.

7.4 Preparation before Starting


 Place the disassembled protection grills to their original positions and ensure the
connection is secure.
 Clean the device site. Make sure the position is clean without flammable or explosive
materials.
 Ensure the ventilation of the installation place.
 Recheck to ensure the Turnkey Station and switches upstream and downstream meet
the requirements and are flexible enough.

7.5 Starting the Device


If all tests and measurements have been performed, and all measured values lie within the
acceptable range, the device can be switched on for the first time. Proceed as follows to
start the Turnkey Station:

46
System Manual 7 Commissioning

Step 1 Check again for the polarity on the internal DC side of the Turnkey Station.
Step 2 Close the upstream and downstream switches of the Turnkey Station.
Step 3 Manually close the auxiliary power supply switch inside the Turnkey Station and wait the
touchscreen to be powered on.
Step 4 Stop the Turnkey Station through the touchscreen.
Step 5 Turn off “Trip Enable” and “Door-protect enable” through the touchscreen.
Step 6 Set output power limitation to 5% through the touchscreen.
Step 7 Manually close all AC switches inside the Turnkey Station.
Step 8 Manually close all DC switches inside the Turnkey Station.
Step 9 Perform the start operation through the touchscreen, and the Turnkey Station starts
grid-connected operation.
Step 10 Increase output power limitation gradually to the maximum value.

To ensure the Turnkey Station normal operation for the first time, please
measure the Turnkey Station DC input voltage beforehand. When the DC side
voltage meets the start-up requirement, i.e. DC voltage is steadily higher than
DC start-up voltage. Start the Turnkey Station for the first time.

7.6 LCD Parameter Setting


When the LCD is on, set the LCD display language, data and time, communication
parameters, and active power limitation etc. according to Chapter 9: LCD Operation in this
manual. You can also view the Turnkey Station running information and perform pertinent
operation.

7.7 Completing Commissioning


If all the start-up procedures have been performed, check the operating condition of the
Turnkey Station.

 Check whether there are anomalies of the Turnkey Station: abnormal noise,
overheating, smoking, or unusual odor.
 Check the Turnkey Station grid-connected voltage, current, and THD for unstableness.
 Check the grounding of the Turnkey Station enclosure.
 Check the functionality of the LCD display.
 Record accurately the Turnkey Station operation data during commissioning.
The duration of commissioning depends on the plant scale, plant location, on-site
environmental conditions, and on the like. Usually, if on-site condition is stable, the
commissioning can last for 1 week, i.e. 168 hours.
The commissioning of the Turnkey Station is completed. The Turnkey Station operates
normally.
After commissioning, plant starts power generation and enters daily maintenance process.

47
7 Commissioning System Manual

When the Turnkey Station is operating, make sure there are no flammable
materials or other materials within at least 5 meters around the installation site.
Local/national standards about the min. electric clearance around the Turnkey
Station should be respected.

The Turnkey Station needs no manual control in daily operation. Open the cabinet
door only for maintenance or troubleshooting and by qualified personnel only.
Keep the door closed and locked and store the keys of the door by appointed
personnel during normal operation.

48
8 Starting/Stopping
8.1 Starting

8.1.1 Inspection before starting


After the maintenance or service work, you may start the Turnkey Station. Inspect the
following requirement before starting the Turnkey Station:

 All connections are done by strictly following the relevant manual and circuit diagram.
 The coverings of the internal devices are fixed and secured.
 The emergency stop button is released.
 Make sure, via suitable instruments, that there is no ground fault of the PV array.
 Measure the DC and AC voltage with multi-meter to check if they meet the Turnkey
Station startup conditions and ensure that there is no overvoltage hazard.
 Measure the DC voltage with multi-meter, and check if the polarity is correct.

If the Turnkey Station has been stored for more than half a year in the required
storage environment, a thorough and careful inspection is necessary before the
Turnkey Station is powered on.

8.1.2 Start Steps


When the foregoing conditions are met, proceed as follows to start the Turnkey Station:
Step 1 Close the upstream and downstream switches of the Turnkey Station.
Step 2 Manually close the auxiliary power supply switch inside the Turnkey Station and wait the
touchscreen to be powered on.
Step 3 Stop the Turnkey Station through the touchscreen.
Step 4 Turn off “Trip Enable” and “Door-protect enable” through the touchscreen.
Step 5 Manually close all AC switches inside the Turnkey Station.
Step 6 Manually close all DC switches inside the Turnkey Station.
Step 7 Perform the start operation through the touchscreen, and the Turnkey Station starts
grid-connected operation.
After startup, the Turnkey Station will automatically check if parameters of the DC and AC
side meet the grid-connection requirements. If the requirements are met, and the set time
has been reached, the Turnkey Station will turn to the OPERATION mode and feed the
generated AC current to the grid.

 The Turnkey Station needs no manual control in daily operation. Open the
cabinet door only for maintenance or troubleshooting and by qualified
personnel only.
 Keep the door closed and locked and store the keys of the door by appointed
personnel during normal operation.

49
9 Starting/Stopping System Manual

8.2 Stopping
Turnkey Station stops during normal maintenance and service work or when a fault occurs.

8.2.1 Normal Stop


Proceed as follows to stop the Turnkey Station during normal maintenance and service
work:
Step 1 Stop the Turnkey Station through the stop operation on the LCD panel.
Step 2 Disconnect the DC, AC, and Auxiliary power supply switches.
Step 3 Disconnect the Turnkey Station downstream switches.
Step 4 Disconnect the Turnkey Station upstream switches.
Step 5 The Turnkey Station stops.

During normal operation, disconnection of AC or DC switch is strictly prohibited.


Otherwise, the switch can be damaged and the Turnkey Station may also be
damaged.

8.2.2 Turnkey Station Stops when A Fault Occurs


Proceed as follows to stop the Turnkey Station when a fault or an emergency occurs:
Step 1 Press the emergency stop button.
Step 2 Disconnect the DC, AC, and Auxiliary power supply switches.
Step 3 Disconnect the Turnkey Station downstream switches.
Step 4 Disconnect the Turnkey Station upstream switches.
Step 5 The Turnkey Station stops.

 Use the emergency stop button only when an emergency or a fault occurs.
Under normal conditions, stop the Turnkey Station by performing the stop
command in the LCD panel.
 Press the emergency stop button directly in case of crisis to ensure a timely
response.

The emergency stop button will stay in lock state once you press it. Use a key to
unlock the button.

50
9 LCD Menu Operation
9.1 LCD Touchscreen
The LCD touchscreen, located at the eye-level inside the monitoring window on the front
side of the Turnkey Station is used for viewing the data and related set parameters by the
user.

For user convenience, there are a large number of pictures about the LCD
interface in this chapter. The parameters and other details in those pictures are
indicative only. The actual product you receive may differ.

If the time shown on the LCD panel is different from the actual local time after
time calibration, please check the button cells on the back of the LCD panel and
replace them if necessary.

9.2 Default Screen

9.2.1 Initialization
The LCD is initialized and then enters into the starting menu. The initialization screen
appears every time the Turnkey Station is powered on. After initialization, the default screen
follows.

9.2.2 Default Screen Introduction


G H Item Description
B Yield data. The first line from the top is the
A
present active power; and the work state
A
C D is the transient state of the Turnkey
Station.
Today’s active power curve indicating the
B power percentage (power value/the
E
F Turnkey Station nominal power value).
DC side voltage and current of the
C
Turnkey Station
AC side line-to-line voltage and phase
D
current
Language selection button. Click it to
E change languages among English,
Chinese, French, and Italian.
F Present date and time
The success rate of the Turnkey Station
G
internal communication
The success rate of communication
H
between the Turnkey Station and PC
Accessing to submenus mentioned below starts from the default menu.

51
9 LCD Menu Operation System Manual

LCD screen contains lots of parameters pertinent to the Turnkey Station


operation. All parameters must be set by appointed personnel. Do not modify any
parameters before you fully understand this manual or consult the staff from
Sungrow.

9.2.3 Backlight and Screensaver


If there is no operation on the screen for more than 5 minutes, the backlight will be off.
Activate the backlight by tapping the screen and the screen will r display the menu
operated previously.

9.3 Overview of LCD Menu and Icon

9.3.1 Overview of Submenu and Icon


There are three buttons on the lower left side of the touch panel for the user to operate

“Start/Stop” , “Home”, , “Function” . The logical structures of these


menus are shown below:
Main Menu First sub-menu Second sub-menu Third sub-menu
Start/Stop Start - -
Stop - -
Home - - -
Function Run-information Real-Time Data -
Power curve -
E-histogram -
History-information His-event
His-fault -
His-data -
His-alarm
Start/Stop Start -
Stop -
Set-parameter Sys-parameter Language & Firmware
Ver.
Time
Remote/Local control
Load default
Run-parameter -
Pro-parameter -
Com-parameter Serial port param.
Network param.

9.3.2 Layout of the submenus


The layout of submenus is the same as that shown below except for the default menu.

52
System Manual 9 LCD Menu Operation

Item Description
Title bar
The first line from the top is the present success rate of communication.
A
The left side of the second line is the name of the present page, while the right
side is the present date and time.
B Data display or parameter configuration.
From left to right: the three main icons; the return button to return to the previous
C
menu by tapping it.
For convenience, the operations on the menus are referred to as the menu name with

quotation marks. For example, the menu will be referred to as “Set-parameter”.

9.4 Entering Password


Turnkey Station parameters are protected by the password. The user can enter the
“Set-parameter” sub-menu only after entering the correct password. Proceed as follows to
enter the password:
Step 1 Tap “Function” on the default menu;
Step 2 Tap “Set-parameter”, and the password entering window pops out;

Step 3 Tap the white edit box, and a keypad pops out.
Step 4 Enter the password through the keypad.
Button Function
← backspace key, delete the digit input
Clr clear the digitals input
Esc escape and close the keypad
Enter confirm the password input
the maximum and minimum value that can be entered; digital beyond this
Max./Min.
range is invalid

53
9 LCD Menu Operation System Manual

If the entered password is 1111, the user can enter the normal parameter setting page and
set system parameters, running parameters, protection parameters, and communication
parameters.
Step 5 Press “Enter” to confirm the entered password.
Step 6 If the entered password is incorrect, an “Error password” window will appear. Tap “Enter”
and re-enter the password.

9.5 Language Setting


The user can set the language by either of the following two ways:

9.5.1 Conventional Way


Step 1 Tap “Function” on the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password;
Step 4 Tap “Language & Firmware Ver.” and enter the language and firmware version sub-menu;

Step 5 Select the target language.

9.5.2 Shortcut
The language setting shortcut (A) is at the lower right side of the Home menu. Select either
language by tapping the language button.
By tapping the button, the language can be switched among English, Chinese, French, and
Italian.
The language on the button is the present language on the display.

54
System Manual 9 LCD Menu Operation

9.6 Date and Time Setting


Step 1 Tap “Function” on the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Sys-parameter” after entering the correct password;
Step 4 Tap “Time” and enter the date and time setting sub-menu;

Step 5 Set the “Year”, “Month”, “Date”, “Hour”, “Minute” and “Second”. Tap the corresponding cell
and the keypad will appear;
Step 6 Set the time and date by tapping the keypad and confirm the setting by tapping “Enter”.

9.7 Running Information Checking


Running information contains all data pertinent to the Turnkey Station operation:

Real-time data
The real-time running information can be checked.
The output power, DC voltage & current, power factor, reactive power, efficiency,
daily/monthly/annual power yields, internal temperature, positive/negative insulation
resistance to the ground, running time, amount of CO2 reduction, grid frequency, AC
phase/line voltage, module temperature, AC & DC switches states, bypass switches/fuse
state, power supply mode are included.

Power curve
The output power curve shows the percentage of the power yield to the nominal power on
that particular day. The data are updated every several seconds and the total diagram data
will be cleared at the beginning of a new day.

55
9 LCD Menu Operation System Manual

E-histogram
The power yields of the present day in the histogram.
Proceed as follow to view the running information:
Step 1 Tap “Function” on the default menu;
Step 2 Tap “Run-information” and switch among “Real Time Data”, “Power curve” and
“E-histogram”. The default display is “Real Time Data”;

Step 3 Tap “Power curve” and enter the power curve sub-menu;

Step 4 Tap “E-histogram” and enter the electricity histogram sub-menu.

The display value is directive only and must not be used as a basis for charging.

9.8 History Information Checking


There are four kinds of history information: History event, history fault, history data, and
history alarm.

9.8.1 History Event Checking


Step 1 Tap “Function” on the default menu.
Step 2 Tap “History-information” and enter the history information sub-menu.

56
System Manual 9 LCD Menu Operation

Step 3 Tap “His-event” and enter the history event sub-menu.

A maximum ofA maximum of 200 history events can be viewed via this sub-menu, and a
maximum ofa maximum of 5 records can be displayed on one page. The upper left side of
the event table is the total number of the current event records. Tap “Prev” or “Next” to turn
pages up or down.

9.8.2 History Data Checking


The system can record the Turnkey Station running information of the latest 90 days with
the records updated every 15 minutes per day.
History data displays the data related to the power yields and the electric quantity of the
Turnkey Station. Proceed as follows to check the history information:
Step 1 Tap “Function” on the default menu.
Step 2 Tap “History-information” and enter the history information sub-menu.
Step 3 Tap “His-data” and enter the history data sub-menu.

Tap “Prev” or “Next” to turn pages up or down.

9.8.3 History Fault Checking


When a fault occurs in the Turnkey Station, the user can view the present fault via the LCD
screen and the history fault records as follows:
Step 1 Tap “Function” on the default menu.
Step 2 Tap “History-information” and enter the history information sub-menu.
Step 3 Tap “His-fault” and enter the history fault sub-menu.

57
9 LCD Menu Operation System Manual

A maximum of 200 history faults can be viewed from this sub-menu, with a maximum of 5
records can be shown on one page. The upper left side of the event table is the total
number of the current fault records. Tap “Prev” or “Next” to turn pages up or down.

9.8.4 History Alarm Checking


Proceed as follows to check the history warn information:
Step 1 Tap “Function” on the default menu.
Step 2 Tap “History-information” and enter the history information sub-menu.
Step 3 Tap “his-alarm” and enter the history alarm sub-menu.

A maximum of 200 history alarms can be viewed from this sub-menu, with a maximum of 5
records can be shown on one page. The upper left side of the event table is the total
numbers of the current warn records. Tap “Prev” or “Next” to turn pages up or down.

9.9 Present Fault Information Checking


The module cabinet inside the Turnkey Station includes three module units(inverter unit).
There may be one or more faults occur in the inverter units inside the Turnkey Station at the
same time, and the fault can be viewed on the LCD screen. Follow the description in this
chapter to view the fault information when the faults occur.

Fault

If there is a fault, the “Work State” will


show “Fault”. Tap the “Fault” cell.

58
System Manual 9 LCD Menu Operation

The state column of the module unit that


has fault will display “Fault". As shown in
the left figure, a fault occurs to inverter
unit 1. Tap the fault cell of inverter unit 1
to check the present fault.

The fault interface of inverter unit 1 will


appear with the fault item in red.

9.10 Starting/Stopping

Usually, the Turnkey Station will start automatically when the grid-connected
requirements are met.
Follow either of the two ways below to start/stop the Turnkey Station through the LCD
screen:
 Tap “Start/Stop” on the default menu.
 Tap “Start/Stop” from the Function menu.

Start or stop the Turnkey Station by tapping the start/stop button on the screen.
A confirm operation interface will appear after tapping the corresponding buttons. The
instruction is effective after confirmation; and cancel the operation by tapping “Cancel”.

9.11 Load Default


Proceed as follows to perform the load default:
Step 1 Tap “Function” on the default menu.
Step 2 Tap “Set-parameter”.
Step 3 Tap “Sys-parameter” after entering the correct password.
Step 4 Tap “Load default” and the password inputting window appears.

59
9 LCD Menu Operation System Manual

The password is “1111”. The system will be reset after entering the password.

9.12 Firmware Version Checking


The user can view the firmware version of the LCD and DSP as follows:
Step 1 Tap “Function” on the default menu.
Step 2 Tap “Set-parameter”.
Step 3 Tap “Sys-parameter” after entering the correct password.
Step 4 Tap “Language & Firmware Ver.” and enter the language and firmware version sub-menu.

Step 5 The firmware version of LCD and DSP is displayed at the bottom of the page.

9.13 Parameters of LCD

9.13.1 Communication Parameters

Improper communication parameter configuration may lead to communication


failure!
Follow strictly the instructions of the plant staff to configure the communication
parameters.
There are RS485 communication and Network communication. The user can set the
communication address and protocol through the LCD screen when the hardware
connection is complete and the device is energized.
Proceed as follows to set the communication parameters:
Step 1 Tap “Function” on the default menu.
Step 2 Tap “Set-parameter”.
Step 3 Tap “Com-parameter” after entering the correct password.

60
System Manual 9 LCD Menu Operation

 Set parameter from the Serial Port Parameter interface for RS485 serial
communication.
 Set parameter from the Network Parameter interface for Network communication

Serial Port Parameter Setting


Click “Serial port param” to enter the following interface.

Two parameters pertinent to RS485 serial port communication can be set according to the
parameter range shown on the display.
“Address” is prescribed by the plant staff and the address for each device must be unique
when there is more than one device. “Baud” is selected according to the communication
method adopted on site.

Network Parameter Setting


Click Network Parameter to enter the following interface.

Six parameters pertinent to the Network communication can be set. DNS address 1 and
DNS address 2 can be set to the default value. Other parameters are assigned by plant
staff.
Set parameter via the pop-up keypad.

61
9 LCD Menu Operation System Manual

9.13.2 Running Parameters

Setting Running Parameters


Step 1 Tap “Function” on the default menu.
Step 2 Tap “Set-parameter”.
Step 3 Tap “Run-parameter” after entering the correct password.

Step 4 Set the running parameter by tapping the pop-up keypad and tap ENTER to confirm the
setting. Tap “Prev” or “Next” to turn pages up or down.

Description of Running Parameters


Parameter Description
Vmppt-max (V) Maximum MPPT voltage
Vmppt-min (V) Minimum MPPT voltage
T-start-wait (s) The time from the AC/DC parameters meet the
grid-connection conditions to the Turnkey Station begins
to generate power.
T-stop-delay (s) The time from the LCD display or upper computer sends
stop command to Turnkey Station performs the stop
command
stop slope (%/s) Active power decline rate from the time at which Turnkey
Station performs stop command to the time at which
Turnkey Station stops
start slope (%/s) Active power rise rate from the time at which the Turnkey
Station performs the start command to the time at which
the Turnkey Station completes the startup
Limit Power (%) Percentage that the active power output accounted for
the nominal output power (%)
Pf cosφ
Q-limit (%) Percentage that the reactive power rise accounted for the
nominal power (%)
Q-adjust switch -
Power-off saved (Pf) If the power factor setting can be saved when the LCD
screen is powered off
Power-off saved (P-limited) If the limit power(%) setting can be saved when the LCD
screen is powered off
SVG switch If the reactive power compensation is activated or
deactivated
T-recover (s) Automatic recovery time when fault occurs
P-rise rate (%/s) Rate of rise of the active power
P-decline rate (%/s) Rate of decline of the active power
Q-rise rate (%/s) Rate of rise of the reactive power
Q-decline rate (%/s) Rate of decline of the reactive power
Trip Enable Trip the DC main switches of two modules
FW func enable To enable/Disable the FW function
FW output change base The standard of active power change caused by
frequency change

62
System Manual 9 LCD Menu Operation

Parameter Description
50Hz OF decrease start(Hz) For 50Hz grid type, refer to f1i in Fig.9-1 The relation
curve between the active power and the frequency
50Hz OF decrease end(Hz) For 50Hz grid type, refer to f2i in Fig.9-1 The relation
curve between the active power and the frequency
60Hz OF decrease start(Hz) For 60Hz grid type, refer to f1i in Fig.9-1 The relation
curve between the active power and the frequency
60Hz OF decrease end(Hz) For 60Hz grid type, refer to f2i in Fig.9-1 The relation
curve between the active power and the frequency
OF decrease slope Refer to K1 in Fig.9-1 The relation curve between the
active power and the frequency
OF decrease limit (%) Refer to ΔP1 in Fig.9-1 The relation curve between the
active power and the frequency
FW input type The input frequency type of the FW function.
The max./min value of the real-time frequency or during
frequency change
FW enable power(%) After the FW function is enabled, the FW function is
started when the percentage of the actual output active
power is bigger than the set value
50Hz UF increase start(Hz) For 50Hz grid type, refer to f1s in Fig.9-1 The relation
curve between the active power and the frequency
50Hz UF increase end(Hz) For 50Hz grid type, refer to f2s in Fig.9-1 The relation
curve between the active power and the frequency
60Hz UF increase start(Hz) For 60Hz grid type, refer to f1s in Fig.9-1 The relation
curve between the active power and the frequency
60Hz UF increase end(Hz) For 60Hz grid type, refer to f2s in Fig.9-1 The relation
curve between the active power and the frequency
UF increase slope Refer to K2 in Fig.9-1 The relation curve between the
active power and the frequency
UF increase limit(%) Refer to ΔP2 in Fig.9-1 The relation curve between the
active power and the frequency
QU enable power(%) In QU mode, the QU function will be enabled when the
actual output active power percentage is bigger than the
set value
QU operation mode In QU reactive power mode, the method to set the
reactive power value
QU input type QU function input voltage type; the max./min value of the
real-time grid voltage or during grid voltage change
QU ind var limit (%) Refer to Qmax in Fig.9-2 The relation curve between the
reactive power and the voltage
QU cap var limit (%) Refer to Qmin in Fig.9-2 The relation curve between the
reactive power and the voltage
QU PF limit (%) The Turnkey Station compensation power factor min. and
max. value caused by grid voltage change; setting is
available when the QU operation mode is TanPhiadj or
CosPhiadj
QU volt rise start(%) Refer to U1i in Fig.9-2 The relation curve between the
reactive power and the voltage.
QU volt rise end(%) Refer to U2i in Fig.9-2 The relation curve between the
reactive power and the voltage.
QU volt drop start(%) Refer to U1s in Fig.9-2 The relation curve between the
reactive power and the voltage
QU volt drop end(%) Refer to U2s in Fig.9-2 The relation curve between the
reactive power and the voltage
V auto-adj ref(%) When the reactive regulation switch is V auto-adj, the grid
regulation reference is set according to the percentage of
nominal voltage

63
9 LCD Menu Operation System Manual

Parameter Description
V auto-adj hysteresis(%) When the reactive regulation switch is V auto-adj, the
allowable plus or minus error of the regulation voltage
and it is set according to the percentage of nominal
voltage
Q(P) upper PF Power factor of point P1 in Fig. 9-3 Q(P) mode curve
Q(P) lower PF Power factor of point P2 in Fig. 9-3 Q(P) mode curve
Q(P) upper power(%) Output power of point P2 in Fig. 9-3 Q(P) mode curve
Q(P) lower power(%) Output power of point P1 in Fig. 9-3 Q(P) mode curve

The relation curve between the active power and the frequency is shown in the figure
below.
P/kW

Pn

△P2 k2
P0

△P1 k1

f/Hz
f2s f1s fn f1i f2i
Fig. 9-1 The relation curve between the active power and the frequency
The relation curve between the reactive power and the voltage is shown in the figure below.
Q

Qmax

U2s U1s
U
U1i U2i

Qmin

Fig. 9-2 The relation curve between the reactive power and the voltage

64
System Manual 9 LCD Menu Operation

Q(P) mode curve is shown in following figure.

Upper PF P1
Cap

Upper Power
P/Pn
Lower Power

Lower PF
Ind P2

Fig. 9-3 Q(P) mode curve


Running parameter range and default value are shown in the following table.
Parameter Range Default
Vmppt-max (V) 875~1300 1300
Vmppt-min (V) 875~1300 875
T-start-wait (s) 0~600 60
T-stop-delay (s) 0~600 0
Stop slope (%/s) 0.1~100 100
Start slope (%/s) 0.01~100 100
Limit Power (%) 0~115 110
Pf -0.8~-1/0.8~1 1
Q-limit (%) -100~100 0
Q-adjust switch Close/Pf/Q-limit/QU mode/ Pf
V auto-adj/QP mode
Power-off saved (Pf) Save/Not save Save
Power-off saved (P-limited) Save/Not save Not save
SVG switch Enable/Disable Disable
T-recover (s) 20~600 60
P-rise rate (%/s) 0.01~100 10
P-decline rate (%/s) 0.01~100 10
Q-rise rate (%/s) 0.01~100 10
Q-decline rate (%/s) 0.01~100 10
Trip Enable Enable/Disable Disable
FW func enable Enable/Disable Disable
FW output change base Rated-P/Pre-derate-P Pre-derate-P
50Hz OF decrease start(Hz) 50~55 50.2
50Hz OF decrease end(Hz) 50~55 51.2
60Hz OF decrease start(Hz) 60~65 60.2
60Hz OF decrease end(Hz) 60~65 61.2
OF decrease slope 0~2 0.4
OF decrease limit (%) 0~115 30
FW input type RT-F/Record-F Record-F
FW enable power(%) 0~115 0
50Hz UF increase start(Hz) 45~50 49.8
50Hz UF increase end(Hz) 45~50 48.8
60Hz UF increase start(Hz) 55~60 59.8
60Hz UF increase end(Hz) 55~60 58.8
UF increase slope 0~2 0.4
UF increase limit(%) 0~115 30
QU enable power(%) 0~100 0

65
9 LCD Menu Operation System Manual

Parameter Range Default


QU operation mode Var PCT adj/ Var PCT adj
TanPhi adj/
CosPhi.adj
QU input type RT volt/Record volt RT volt
QU ind var limit (%) 0~100 50
QU cap var limit (%) 0~100 50
QU PF limit (%) 0.8~1 0.9
QU volt rise start(%) 100~110 108
QU volt rise end(%) 100~110 110
QU volt drop start(%) 90~100 92
QU volt drop end(%) 90~100 90
V auto-adj ref(%) 90~110 100
V auto-adj hysteresis(%) 0~10 1
Q(P) upper PF 0.9~1 1
Q(P) lower PF 0.9~1 0.9
Q(P) upper power(%) 50~100 100
Q(P) lower power(%) 0~50 50
Note: * non-settable
** at night when the Turnkey Station enters standby mode (but does not enter the deeper
standby mode with lower power consumption), the SVG function needs to be activated: first,
stop the Turnkey Station by the LCD button, and then start; set the SVG switch to “Enable”.
The SVG is an optional function of this Turnkey Station.

Please refer to the LCD screen for the specific setting ranges of these
parameters.

9.13.3 Protection Parameter

Setting Protection Parameter


Step 1 Tap “Function” on the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Pro-parameter” after entering the correct password.

Set the protection parameter by tapping the pop-up keypad and tap ENTER to confirm the
the setting. Tap “Prev” or “Next” to turn pages up or down.
Description of Protection Parameters
Parameter Description
Ⅰ_Vgrid-max(%) Set the grid over-voltage protection Ⅰ value. Protection is
activated when voltage exceeds this value.
Ⅱ_Vgrid-max(%) Set the grid over-voltage protection Ⅱ value. Protection is
activated when voltage exceeds this value.

66
System Manual 9 LCD Menu Operation

Parameter Description
Ⅲ_Vgrid-max(%) Set the grid over-voltage protection Ⅲ value. Protection is
activated when voltage exceeds this value.
Ⅳ_Vgrid-max(%) Set the grid over-voltage protection Ⅳ value. Protection is
activated when voltage exceeds this value.
Ⅴ_Vgrid-max(%) Set the grid over-voltage protection Ⅴ value. Protection is
activated when voltage exceeds this value.
Recover_Vgrid-max(%) The Turnkey Station recovers normal operation when grid voltage
is below this value
Ⅰ_T-Vhigh trip(ms) Grid over-voltage protection Ⅰ trip time
Ⅱ_T-Vhigh trip(ms) Grid over-voltage protection Ⅱ trip time
Ⅲ_T-Vhigh trip(ms) Grid over-voltage protection Ⅲ trip time
Ⅳ_T-Vhigh trip(ms) Grid over-voltage protection Ⅳ trip time
Ⅴ_T-Vhigh trip(ms) Grid over-voltage protection Ⅴ trip time
Ⅰ_Vgrid-min(%) Set the grid under-voltage protection Ⅰ value. Protection is
activated when voltage is below this value.
Ⅱ_Vgrid-min(%) Set the grid under-voltage protection Ⅱ value. Protection is
activated when voltage is below this value.
Ⅲ_Vgrid-min(%) Set the grid under-voltage protection Ⅲ value. Protection is
activated when voltage is below this value.
Ⅳ_Vgrid-min(%) Set the grid under-voltage protection Ⅳ value. Protection is
activated when voltage is below this value.
Ⅴ_Vgrid-min(%) Set the grid under-voltage protection Ⅴ value. Protection is
activated when voltage is below this value.
Recover_Vgrid-min(%) The Turnkey Station recovers normal operation when grid voltage
is above this value
Ⅰ_T-Vlow trip(ms) Grid under-voltage protection Ⅰ trip time
Ⅱ_T- Vlow trip(ms) Grid under-voltage protection Ⅱ trip time
Ⅲ_T- Vlow trip(ms) Grid under-voltage protection Ⅲ trip time
Ⅳ_T- Vlow trip(ms) Grid under-voltage protection Ⅳ trip time
Ⅴ_T- Vlow trip(ms) Grid under-voltage protection Ⅴ trip time
Ⅰ_Fgrid-max(Hz) Set the grid over-frequency protection I value. Protection is
activated when frequency exceeds this value
Ⅱ_Fgrid-max(Hz) Set the grid over-frequency protection II value. Protection is
activated when frequency exceeds this value
Ⅲ_Fgrid-max(Hz) Set the grid over-frequency protection Ⅲ value. Protection is
activated when frequency exceeds this value
Ⅳ_Fgrid-max(Hz) Set the grid over-frequency protection Ⅳ value. Protection is
activated when frequency exceeds this value
Ⅴ_Fgrid-max(Hz) Set the grid over-frequency protection Ⅴ value. Protection is
activated when frequency exceeds this value
Recover_Fgrid-max(Hz) The Turnkey Station recovers normal operation when grid
frequency is below this value
Ⅰ_T-Fhigh trip(ms) Set the grid over-frequency I tripping time

Ⅱ_T-Fhigh trip (ms) Set the grid over-frequency II tripping time

Ⅲ_T-Fhigh trip(ms) Set the grid over-frequency Ⅲ tripping time


Ⅳ_T-Fhigh trip (ms) Set the grid over-frequency Ⅳ tripping time
Ⅴ_T-Fhigh trip(ms) Set the grid over-frequencyⅤ tripping time

67
9 LCD Menu Operation System Manual

Parameter Description
Ⅰ_Fgrid-min(Hz) Set the grid under-frequency protection I value. Protection is
activated when frequency exceeds this value
Ⅱ_Fgrid-min(Hz) Set the grid under-frequency protection II value. Protection is
activated when frequency exceeds this value
Ⅲ_Fgrid-min(Hz) Set the grid under-frequency protection Ⅲ value. Protection is
activated when frequency exceeds this value
Ⅳ_Fgrid-min(Hz) Set the grid under-frequency protection Ⅳ value. Protection is
activated when frequency exceeds this value
Ⅴ_Fgrid-min(Hz) Set the grid under-frequency protection Ⅴ value. Protection is
activated when frequency exceeds this value
Recover_Fgrid-min(Hz) The Turnkey Station recovers normal operation when grid
frequency is above this value
Ⅰ_T-Flow trip(ms) Set the grid under-frequency I tripping time

Ⅱ_T-Flow trip (ms) Set the grid under-frequency II tripping time

Ⅲ_T-Flow trip(ms) Set the grid under-frequency Ⅲ tripping time


Ⅳ_T-Flow trip (ms) Set the grid under-frequency Ⅳ tripping time
Ⅴ_T-Flow trip (ms) Set the grid under-frequency Ⅴtripping time
LVRT switch Enable or disable the LVRT switch
LVRT T1(ms) Refer to T1 in Fig. 10-3 Lower voltage withstand requirements
LVRT T2(ms) Refer to T2 in Fig. 10-3 Lower voltage withstand requirements
LVRT voltage1(%) Refer to U1 in Fig. 10-3 Lower voltage withstand requirements
LVRT voltage2(%) Refer to U2 in Fig. 10-3 Lower voltage withstand requirements
LVRT dynamic Var Kf Ratio of reactive power compensation and voltage dropping depth
factor during LVRT
HVRT switch Enable or disable the HVRT switch
HVRT T1(ms) Refer to T1 in Fig. 10-4 High voltage withstand requirements
HVRT T2(ms) Refer to T2 in Fig. 10-4 High voltage withstand requirements
HVRT voltage1(%) Refer to U1 in Fig. 10-4 High voltage withstand requirements
HVRT voltage2(%) Refer to U2 in Fig. 10-4 High voltage withstand requirements
The grid under-/over-voltage and under-/over-frequency
Recover T-grid(s) protection is enabled. When the grid turns normal and the set time
is reached, the fault will be removed.
Active Islanding Enable or disable the islanding protection function
I leakage-pro(A) Leakage current protection setting value
Door-protect enable Enable or disable the door control protection
Manual fault restart. If this function is enabled, the Turnkey
Fault manual restart Station can reconnect to the grid only after the fault is removed
manually.
Negative Vgrid protect
Protection value of negative voltage to ground
value(V)
Grid_V-unbalanced
3-phase grid voltage unbalance protection threshold value
protect value(%)
Grid_V-unbalanced 3-phase grid voltage unbalance time reaches to the set value.
protect time(S) Protection is activated
If Anti-PID mode is enabled, you may set the Anti-PID mode
Anti-PID mode
(Invalid, Suppression and Repair)
Ins monitor measure
Insulation monitoring time
time(S)
Ins monitor protect
Insulation monitoring protection threshold value
threshold(K)
Insulation monitoring startup voltage. When the DC voltage
Ins monitor Vdc-start(V)
reaches to this set value, the insulation monitoring enables.

68
System Manual 9 LCD Menu Operation

Protection parameter range and default value are shown in the following table.
Parameter Range Default
Ⅰ_Vgrid-max(%) 105~150 115

Ⅱ_Vgrid-max(%) 105~150 130

Ⅲ_Vgrid-max(%) 105~150 130

Ⅳ_Vgrid-max(%) 105~150 130

Ⅴ_Vgrid-max(%) 105~150 130


Recover_Vgrid-max(%) 105~150 110
Ⅰ_T-Vhigh trip(ms) 40~600000 2000

Ⅱ_T-Vhigh trip(ms) 40~600000 100

Ⅲ_T-Vhigh trip(ms) 40~600000 100

Ⅳ_T-Vhigh trip(ms) 40~600000 100

Ⅴ_T-Vhigh trip(ms) 40~600000 100

Ⅰ_Vgrid-min(%) 10~95 80

Ⅱ_Vgrid-min(%) 10~95 50

Ⅲ_Vgrid-min(%) 10~95 50

Ⅳ_Vgrid-min(%) 10~95 50

Ⅴ_Vgrid-min(%) 10~95 50
Recover_Vgrid-min(%) 10~95 90
Ⅰ_T-Vlow trip(ms) 40~600000 2000

Ⅱ_T- Vlow trip(ms) 40~600000 100

Ⅲ_T- Vlow trip(ms) 40~600000 100

Ⅳ_T- Vlow trip(ms) 40~600000 100

Ⅴ_T- Vlow trip(ms) 40~600000 100

Ⅰ_Fgrid-max(Hz) 50.2~55/60.2~65 50.5/60.5

Ⅱ_Fgrid-max(Hz) 50.2~55/60.2~65 50.5/60.5

Ⅲ_Fgrid-max(Hz) 50.2~55/60.2~65 50.5/60.5

Ⅳ_Fgrid-max(Hz) 50.2~55/60.2~65 50.5/60.5

Ⅴ_Fgrid-max(Hz) 50.2~55/60.2~65 50.5/60.5


Recover_Fgrid-max(Hz) 50.2~55/60.2~65 50.2/60.2
Ⅰ_T-Fhigh trip(ms) 40~600000 160

Ⅱ_T-Fhigh trip (ms) 40~600000 160

Ⅲ_T-Fhigh trip(ms) 40~600000 160

Ⅳ_T-Fhigh trip (ms) 40~600000 160

Ⅴ_T-Fhigh trip(ms) 40~600000 160

Ⅰ_Fgrid-min(Hz) 45~49.8/55~59.8 47.5/57.5

Ⅱ_Fgrid-min(Hz) 45~49.8/55~59.8 47.5/57.5

Ⅲ_Fgrid-min(Hz) 45~49.8/55~59.8 47.5/57.5

Ⅳ_Fgrid-min(Hz) 45~49.8/55~59.8 47.5/57.5

Ⅴ_Fgrid-min(Hz) 45~49.8/55~59.8 47.5/57.5


Recover_Fgrid-min(Hz) 45~49.8/55~59.8 47.5/57.5
Ⅰ_T-Flow trip(ms) 40~600000 160

69
9 LCD Menu Operation System Manual

Parameter Range Default


Ⅱ_T-Flow trip (ms) 40~600000 160

Ⅲ_T-Flow trip(ms) 40~600000 160

Ⅳ_T-Flow trip (ms) 40~600000 160

Ⅴ_T-Flow trip (ms) 40~600000 160


LVRT switch Enable/Disable Enable
LVRT T1(ms) 2500~3500 3000
LVRT T2(ms) 500~1500 1000
LVRT voltage1(%) 50~90 90
LVRT voltage2(%) 5~50 20
LVRT dynamic Var Kf
0~4 1.5
factor
HVRT switch Enable/Disable Enable
HVRT T1(ms) 100~20000 10000
HVRT T2(ms) 100~5000 500
HVRT voltage1(%) 110~120 110
HVRT voltage2(%) 120~140 130
Recover T-grid(s) 1~600 10
Active Islanding Enable/Disable Disable
I leakage-pro(A) 1~10 5
Door-protect enable Enable/Disable Disable
Fault manual restart Enable/Disable Disable
Negative Vgrid protect
20~200 50
value(V)
Grid_V-unbalanced
3~20 5
protect value(%)
Grid_V-unbalanced
0.1~600 60
protect time(S)
Anti-PID mode Invalid/Suppression/Repair Invalid
Ins monitor measure
30/150/300/600 150
time(S)
Ins monitor protect
15~100 50
threshold(K)
Ins monitor Vdc-start(V) 220~780 220

Improper parameter configuration may affect the normal operation of the Turnkey
Station!
Only authorized personnel can configure these parameters.
Should there be any question or doubt, please contact Sungrow.

Please refer to the LCD screen for the specific setting ranges of these
parameters.

70
10 Turnkey Station Functions
10.1 Operation Mode

10.1.1 Mode Change


After being energized, the Turnkey Station will switch among different modes as shown in
the figure below.
Unrecoverable fault
Stop Stop and repair the Station Fault

Fault cleared and


Station is energized Fault
setting time reached
occurred
All the grid-
connected Idc ≈ 0A for 10 minutes
Initial requirements met
Startup Run Standby
standby Upv>UpvStart and
setting time reached

Stop the Station via LCD panel


Alarm
removed
Alarm Run
Station restarts
Key-stop Turn the Start/Stop switch to “Stop” or
Stop the Station via LCD panel push down the Emergency stop button

Station restarts
Emergency-
stop
Turn the Start/Stop switch to “Stop” or push
down the Emergency stop button

Fig. 10-1 Operation modes change

Upv is the DC input voltage of the Turnkey Station.


UpvStart is the DC side startup voltage of the Turnkey Station.

10.1.2 Operation Mode Description

Stop
This is the initial state of the Turnkey Station. The Turnkey Station DC and AC switches are
in the “OFF” position; and the upstream and downstream connections are disconnected.
The Turnkey Station is therefore electricity-free.

Initial Standby
When switches of the upstream and downstream devices are closed and the AC & DC
switches of the Turnkey Station are in the “ON” position, the Turnkey Station turns to the
Initial Standby mode.
The Turnkey Station will continuously check if the PV array and the grid meet the
grid-connection requirements. If the Turnkey Station DC input voltage is higher than the
Turnkey Station startup voltage, the startup time is reached, and the requirements for the
grid side parameter are satisfied, the Turnkey Station will turn from the Initial Standby
mode into the Startup mode.

71
10 Turnkey Station Functions System Manual

Startup
This is the transient process between the Initial Standby mode and the Run mode. Once
the Startup mode is activated, the Turnkey Station will start feeding power to the grid.

Run
In this mode, the Turnkey Station converts the DC energy into AC energy and feeds it to the
grid by way of MPPT.
The Turnkey Station tracks the PV arrays’ maximum power point (MPP) to maximize the
output energy.

Standby
In Run mode, the Turnkey Station will enter the Standby mode if the DC side current is as
low as 0A for a while.
The Turnkey Station will continuously check if the PV array meets the grid-connection
requirements. If the DC startup voltage of the Turnkey Station and the startup time are
reached, it will turn into the Run mode.

Fault
If a fault occurs during operation, the Turnkey Station will enter the Fault mode. LCD panel
will display the fault type with the “Fault” indicator on until the fault is removed and the
Turnkey Station turns into the Run mode.
If the fault is unrecoverable, the Turnkey Station must be stopped to perform maintenance
work. It will automatically check if the fault is recoverable.

When there is a DSP fault or module fault, restart of the Turnkey Station through
the LCD is strictly prohibited. A power-off check is required before reenergizing
the Turnkey Station. Otherwise, the machine may be damaged.

Emergency-stop
Stop the Turnkey Station by pressing the emergency stop button inside the monitoring
window when a fault or an emergency occurs.
The emergency stop button is used to disconnect the AC switch, the DC switch, and the
auxiliary switch. Release the emergency stop button by using the specific key.

Key-stop
In the Run mode, the Turnkey Station will enter the Key-stop mode when stop instruction
is sent via the LCD panel if the user needs to conduct maintenance or service work

Alarm Run
In Alarm Run mode, the Turnkey Station can keep running but send alarm signal. The user
can check the present alarm information through the Working state on the LCD default
screen or check the latest 200 history alarm information through Function/History
information/his alarm. The Turnkey Station automatically turns to the Run mode when the
alarm is removed.

72
System Manual 10 Turnkey Station Functions

10.2 Active Power Limitation

10.2.1 Introduction to Active Power Limitation


Situations, needing power limitation, are listed below:
 Potential threatens to the Turnkey Station safety operation
 Over-load of the grid branch connected to the Turnkey Station
 Islanding
 Factors affecting the stability of the static grid status and dynamic grid status
 Frequency rising affects the system stability
 Grid maintenance
 Grid management

10.2.2 How to Realize Power Limitation

Improper parameter configuration may affect the normal operation of the Turnkey
Station!
Only authorized personnel can configure these parameters.
Should there be any question or doubt, please contact Sungrow.
The user can adjust the Turnkey Station active power output through the LCD display:
Step 1 Tap “ Function” on the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Run-parameter” after entering the correct password;
Step 4 Set the “Limit Power (%)” parameter by tapping the pop-up keypad;
Step 5 Tap “Enter” to confirm the setting.

Parameters related to power limitation (P-rise rate and P-decline rate) are also
included in the running parameter setting sub-menu and can be set accordingly.

10.3 Reactive Power Adjustment


The Turnkey Station can provide reactive power output. The user can open or close the
reactive power adjustment switch and set the reactive power output through the LCD
screen.
Reactive power limitation is performed through the running information sub-menu as
follows:
Step 1 Tap “Function” on the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Run-parameter” after entering the correct password;

73
10 Turnkey Station Functions System Manual

Step 4 Turn the page down to select the “Q-adjust switch”. Tap the pull-down list and there are six
options:

 Close: reactive power cannot be adjusted


 Pf: adjust the reactive power by setting power factor
 Q-limit: adjust the reactive power by setting reactive power percentage
 QU mode: the reactive power changes with the grid voltage
 V auto-adjust: Voltage automatic adjusting: by setting the voltage adjusting benchmark
and hysteresis, reactive power can be dynamically adjusted and the actual voltage
tracking setting benchmark can be controlled.
 QP mode: the PF changes with the output power of the Turnkey Station
Step 5 If "Pf" is selected, the "Pf" can be set on the running parameter interface;
if "Q-limit" is selected, the "Q-limit" can be set on the running parameter interface;
if "QU mode" is selected, QU-related parameter can be set on the running parameter
interface, where the parameter name begins with "QU", for example, QU operation mode;
and
if "V auto-adjust" is selected, the "voltage automatic adjusting benchmark" and "voltage
automatic adjusting hysteresis" can be set on the running paramter interface.

P-Q Capability
The Turnkey Station can support the grid by supplying the reactive power in different ways. The
shaded area in the figure below shows the Turnkey Station’s P-Q capability.

P=115%Pn P (kW)
P=110%Pn 3593kVA
P=100%Pn @PF=0.80
92% Pn
88% Pn 25℃
80% Pn
45℃

50℃

Q (VAR)
-69% -66%-60% 60% 66% 69%
Ind. Cap.

Fig. 10-2 The P-Q Capability of Turnkey Station


The Pmax=3593KW, Pn=3125KW , Smax=3593KVA.

The Max. Q is ±2155Kvar, when the power factor is ±0.8,at 25℃;

The Q is ±1566Kvar, when the power factor is ±0.9,at 25℃.

74
System Manual 10 Turnkey Station Functions

Improper parameter configuration may affect the normal operation of the Turnkey
Station!
Only authorized personnel can configure these parameters.
Should there be any question or doubt, please contact Sungrow.

10.4 LVRT
Technical Requirements for Connecting Photovoltaic Power Station to Power System
requires medium-and-large PV plant should be equipped with Low Voltage Ride Through
(LVRT) ability.
LVRT requires: PV plant can operate normally within certain voltage drop range and
duration when the voltage of the grid-connected point drops due to the power system
failure or disturbance; PV plant can provide the dynamic reactive power support during the
period.

Active power recovery


If the power station still connects to the grid during power system failure, the active power
will recover on the moment the fault is removed at the speed of at least 30% of nominal
power/second.

Dynamic reactive current support


During LVRT, power station should feed reactive current to the power system as per
requirements. For a station whose 500kV or 750kV voltage is stepped up from the 220kV or
330kV voltage and then connects to the power station group, it should feed reactive current
to the grid when a short-circuit occurs and the voltage drops.

Zero voltage ride through


When the grid-connection point voltage drops to zero, the power station can operate
normally for 1 second.
UT/Upu

U1

Power station
operates normally Power station can
disconnect from the grid

U2

Time (s)
1(T2) 3(T1)
Fig. 10-3 Lower voltage withstand requirements
Note: UT is the grid-connection point voltage; Upu is the grid-connection point nominal
voltage.
Sungrow’s Turnkey Station meets the abovementioned requirements.

75
10 Turnkey Station Functions System Manual

10.5 High Voltage Ride Through (HVRT)


Technical Requirements for Connecting Photovoltaic Power Station to Power System
requires that the PV plant can operate as required within certain voltage range.
Grid-connection pint voltage Requirements
1.1Upu<UT<1.2Upu Operate for at least 10s
1.2Upu≤UT≤1.3Upu Operate for at least 0.5s
Note: UT is the grid-connection point voltage; Upu is the grid-connection point nominal
voltage.
UT/Upu
1.4
U2
1.3
Power station can disconnect from the grid
1.2
Power station operates normally U1
1.1

1.0
Grid fault and voltage increases

0.5
-2 0 0.5(T2) 2 6 10(T1) 14 Time (s)

Fig. 10-4 High voltage withstand requirements


Sungrow’s Turnkey Station meets the abovementioned requirements.

10.6 Temperature Derating


P/Pn
1.15
1.1
1.0

0.8

0.6

0.4

0.2

-35 -30 -20 0 20 25 30 40 45 50 60


Ambient Temperature [℃]

Fig. 10-5 Turnkey Station temperature derating function

76
System Manual 10 Turnkey Station Functions

10.7 Altitude Derating Curve


P/Pn
1.2
1.15

1.0
0.9
0.85

0.7

0.6

0.4

0.2

Altitude [m]
0 1000 2000 3000 4000 5000

Altitude H Turnkey Station operation state


The Turnkey Station can run in the state of 1.15 times of overload for
H≤2000m
a long time
The Turnkey Station can run in the state of 1 time of overload for a
2000m<H≤3000m
long time
3000m<H≤4000m The Turnkey Station can run in derating state

10.8 MPPT
Maximum Power Point Tracking (MPPT) is a technique that the Turnkey Station uses to get
the maximum power from the PV arrays. PV arrays have a complex relationship between
solar irradiation, temperature and total resistance that produces a non-linear output
efficiency known as the I-V curve.

PMPP
ISC
“I-V”Curve
IMPP
Current(A)

Power(W)

“P-V”Curve

UMPP Uoc

Voltage(V)
Fig. 10-6 MPPT

77
10 Turnkey Station Functions System Manual

10.9 Intelligent Temperature-Control Technology


The Turnkey Station will continuously detect the IGBT temperature and adjust the fan
speed accordingly. When the module temperature is low, the Turnkey Station will decrease
the fan speed to lower the device noise and decrease the device operation consumption.
As the module temperature increases, the Turnkey Station will increase the fan speed for
good ventilation.
The intelligent temperature-control technology can synchronize the speed of fan and
temperature of the IGBT module and thus optimize the module temperature and other
conditions.

10.10 Insulation Monitoring Function

10.10.1 Introduction
Insulation resistance is an important parameter related to safety operation. If the insulation
resistance is low, the direct contact protection and indirect contact protection may be failed;
meanwhile, the fault current against the ground and the short circuit caused by low
insulation resistance may lead to an electric fire, device damage, or even physical hazards.
Sungrow’s Turnkey Station is equipped with insulation resistance monitoring function to
detect the system insulation resistance in real time. If low resistance is detected, it will send
alarm at the first time to remind the user and prevent potential hazards.

10.10.2 Simple Troubleshooting


Regardless of the Turnkey Station setting, when the insulation resistance is below the
threshold (can be set on the LCD display), the Turnkey Station will send alarm signal and
the Operation LED will turn to yellow. After receiving the “low insulation resistance” alarm
signal, the user should stop the device and check the specific insulation resistance via the
LCD screen “Function/Run-information/Real time data”.

 If the insulation resistance recovers to be normal, the fault loop is on the AC side.
 If the insulation resistance is still low, the fault loop is on the DC side.
 No matter the fault is on the DC side or on the AC side, a thorough checking and
troubleshooting after the system is powered down is necessary.

10.11 Protection Function


The Turnkey Station has complete protection functions to protect itself when input voltage
or grid is abnormal. After the anomaly is removed, the Turnkey Station can operate
normally.

10.11.1 DC over-voltage protection


When the DC voltage of the PV array exceeds the max. DC voltage, the Turnkey Station
will stop operating, send warning signal, and display the fault type on the LCD screen.
The Turnkey Station can detect the abnormal voltage and respond quickly.

78
System Manual 10 Turnkey Station Functions

10.11.2 AC over/under-voltage protection


When the Turnkey Station AC output voltage exceeds the allowable range, the Turnkey
Station will stop feeding the grid, send warning signal, and display the fault type on the LCD
screen.
The Turnkey Station can detect the abnormal voltage and respond quickly.

10.11.3 Frequency anomaly protection


When the grid frequency exceeds the allowable range, the Turnkey Station will stop feeding
the grid, send warning signal, and display the fault type on the LCD screen.
The Turnkey Station can detect the abnormal frequency and respond quickly.

10.11.4 Islanding protection


Islanding is a case that can occur if the utility grid is disconnected while the Turnkey Station
is operating and the local load of the Turnkey Station is similar to the present output power.
“Islanding” is a potential threaten to devices and operators.
− If the Turnkey Station continues supplying power after the grid is out of power
supply, death or injury may occur to the maintainers during maintenance.
− When power grid fails, the Turnkey Station continues supplying power. Once the
grid resumes, a surge current may occur and damage devices.

The Turnkey Station is equipped with anti-islanding protection function.

In anti-islanding protection state, high voltage is still present. Disconnect the


main switch and discharge before testing or maintenance.

10.11.5 Reverse polarity protection


When the PV array inputs’ polarities are connected reversely, the Turnkey Station will stop
and protect itself against damage, and the Turnkey Station operate normally after the
connection is corrected.

10.11.6 Overload protection


When the PV array output power exceeds the Turnkey Station permissible maximum input
power, the Turnkey Station will limit the power yield at maximum AC power point. If the
temperature exceeds the permissible value, the Turnkey Station will automatically stop
operating unless the the temperature recovers to be normal.

10.11.7 Ground protection


The grounding cables are equipped with the leakage current sensor. When it is detected
that the leakage current exceeds the setting value, the system will send an instruction to
stop the Turnkey Station and display the fault type on the LCD screen.

10.11.8 Module over-temperature protection


IGBT modules inside the Turnkey Station use a high-precision thermal sensor with to
monitor the real-time module temperature. Once high module temperature is detected,
DSP will send instruction to stop the Turnkey Station.

79
10 Turnkey Station Functions System Manual

10.11.9 Internal over-temperature protection


The Turnkey Station is equipped with high-precision thermal sensor to monitor the internal
temperature of the Turnkey Station. Once the over-temperature is detected, the DSP will
help to maintain the safe operation of the Turnkey Station by sending an instruction to stop
the Turnkey Station.

10.12 Firefighting
The Turnkey Station is equipped with the smoke detector and temperature & humidity
sensor. Both the two detectors should be inspected and maintained regularly.
When the smoke concentration and the temperature inside the turnkey station reach the
set values, temperature anomaly or over temperature occurs. Correspondingly, the tripping
of the DC and AC switches is triggered, so as to protect personal and property safety.
The foregoing alarm information is displayed on the external LCD of the inverter.
After eliminating the alarm, the user needs to remove the alarm signal manually.

80
11 Troubleshooting
11.1 Safety Instructions

Lethal voltages are present inside the Turnkey Station when a fault occurs.
 Only qualified personnel can perform troubleshooting described in this chapter.
Qualified personnel are those who have relevant training experience, especially
safety-related experience.
 Do not perform any troubleshooting other than that specified in this manual.
 Respect all safety instructions during troubleshooting.

The electrical components inside the Turnkey Station must be replaced by the
same components from the same manufacturer and of the same model.
The model can be found on the marking of the Turnkey Station or the component
itself. If otherwise, please contact Sungrow.

If the components need to be replaced with products from other manufacturers or


of different model on site, a prior analysis and confirmation by Sungrow is
required.
Failure to follow this procedure may lead to physical injury or death and void all
warranty from Sungrow.

Disconnect all AC and DC switches before troubleshooting.

11.2 Fault Checking


If any power output anomaly is detected, you may check the following items before
contacting Sungrow.

 Open-circuit voltage of the PV arrays


 State of the emergency stop button
 Power limitation state
Should there be any questions or doubts that are not covered by this manual, please
contact us.
If you provide our customer service assistant the following information, it will be of great
help for us to diagnose and solve the problem in your system:

81
11 Troubleshooting System Manual

 Type and serial number of the Turnkey Station and internal devices
 Manufacturer, model, and configuration of the PV arrays and upstream & downstream
combiner devices connected to the Turnkey Station
 Turnkey Station communication solution
 Fault and brief description of the fault phenomenon
 A picture of the fault if necessary

11.3 Fault and Troubleshooting on the LCD screen


This section is dedicated to the faults shown on the LCD, possible reasons and
troubleshooting. In case the fault cannot be removed following the instructions in this
section, please contact Sungrow.
Fault Vdc-high
Possible DC voltage exceeds the max. DC voltage
reason
Measure Check the configuration of the PV array and reduce the open-circuit voltage of
the PV array
Remark Please contact the installers of the PV arrays

Fault Vac-high
Possible The grid voltage is above the max. grid voltage
reason
Measure Check the grid voltage (or check if the grid-connected wire is too thin)
Remark The Turnkey Station automatically reconnects to the grid once the grid voltage
recovers to be normal

Fault Vac-low
Possible The grid voltage is below the min. grid voltage
reason
Measure Check the grid voltage
Check if the AC cables are securely connected.
Remark The Turnkey Station automatically reconnects to the grid once the grid voltage
recovers to be normal

Fault Cntr-flt
Possible Contactor connected to the gird failure
reason
Measure Check the contactor after the device is voltage-free
Remark Stop the Turnkey Station if this fault occurs 5 times per day

Fault No grid
Possible Islanding detected
reason
Measure The Turnkey Station enters into anti-islanding protection state automatically
Remark The Turnkey Station automatically reconnects to the grid once the grid becomes
normal

82
System Manual 11 Troubleshooting

Fault F-fault
Possible The grid frequency is beyond the permitted range
reason
Measure Check grid frequency
Check if the AC cables are securely connected.
Remark The Turnkey Station automatically reconnects to the grid once the grid voltage
recovers to be normal

Fault PDP-pro
Possible Internal fault
reason
Measure Wait 5 minutes for device auto-reconnection or disconnect first and then connect
the AC main switch
Contact Sungrow if the fault insists
Remark Stop the Turnkey Station if this fault occurs 5 times per day

Fault Gnd-flt
Possible The Turnkey Station AC side leakage current to the ground exceeds the set
reason value
Measure -
Remark The Turnkey Station automatically reconnects to the grid once the leakage
current recovers

Fault Iac-high
Possible Internal short-circuit or internal components damages
reason
Measure Check the AC side cable connection and the control circuit board.
Remark Contact Sungrow

Fault Meter-com-flt
Possible Measurement board communication abnormal. This inversion module stops.
reason
Measure Stop the device to check and service the measurement board of the inversion
module.
Remark Contact Sungrow

Fault GFDI-pro
Possible GFDI fault
reason
Measure Stop the device to check and service the grounding part.
Remark Contact Sungrow

Fault Temp-flt
Possible The Turnkey Station internal temperature exceeds the permitted value
reason
Measure Check functionality of fan after the device is voltage-free
Remark Stop the Turnkey Station if this fault occurs 10 times per day

83
11 Troubleshooting System Manual

Alarm RISO-flt
Possible The Turnkey Station DC side insulation resistance is lower than the set value.
reason
Measure Check the PV panel insulation to the ground when the Turnkey Station is
voltage-free
Remark Only alarm display. The Turnkey Station can operate normally.

Fault PM-high
Possible Module temperature exceeds the permitted value
reason
Measure Check the module and ventilation after the device is voltage-free
Remark Stop the device if this fault occurs 5 times per day

Fault I leakage pro


Possible The ground protection is activated when the Turnkey Station AC leakage current
reason to the ground is more than 5A (value can be set through the LCD).
Measure -
Remark The Turnkey Station can automatically reconnect to the grid and start operation
when the leakage current to the ground recovers to be normal.

Fault Overload pro


Possible Capacity of the DC side panel is overload
reason
Measure It is advisable to stop the device and disconnect half of the DC switches.
Remark Contact Sungrow

Fault Soft Start flt


Possible A fault occurs during the soft start process.
reason
Measure Stop the device to check and service it.
Remark Contact Sungrow

Fault T&H-com flt


Possible Temperature and humidity sensor communication fault.
reason
Measure Stop the device to check and service the temperature and humidity sensor and
the cable connection.
Remark Contact Sungrow

Fault AC switch breaking


Possible This fault is reported when the AC circuit breaker is in trip-off state.
reason
Measure -
Remark -

Fault L over-temp
Possible Reactor temperature exceeds the permitted value
reason
Measure Check the reactor after the device is voltage-free
Remark -

84
System Manual 11 Troubleshooting

Fault PV pol-rev
Possible The positive and negative polarities of the DC side are connected reversely.
reason
Measure Check the DC connection to for reverse connection after the Turnkey Station
voltage-free
Remark -

Fault Ctrol power supply-flt


Possible CPS (Control power supply) inside the Turnkey Station cannot work normally
reason
Measure -
Remark The Turnkey Station automatically reconnects to the grid once the CPS reverts
to normal and the grid-connection requirements are fulfilled

Fault AC SPD flt


Possible AC SPD tripping, over-voltage protection
reason
Measure Replace the SPD with the same model after the device is voltage-free
Remark Contact Sungrow

Fault DC SPD flt


Possible DC SPD tripping, over-voltage protection
reason
Measure Replace the SPD with the same model after the device is voltage-free
Remark Contact Sungrow

Fault Grid-V-unbalanced
Possible AC side 3-phase voltage unbalance
reason
Measure Stop the device to check the AC side voltage
Remark -

Fault Encoding repeat


Possible Different modules have the same address
reason
Measure Check the dipswitch on the module control board, whether different modules
have the same address. If yes, correct it.
Remark Contact Sungrow

Fault Vdc-samp-flt
Possible DC voltage sampling fault
reason
Measure Stop the device to check and service.
Remark Contact Sungrow

Fault Fan1-flt
Possible Correspond to the fault of the Turnkey Station module fan 1 (left side fan from
reason the front view)
Measure Check the functionality of fan after the device is voltage-free
Remark Contact Sungrow

85
11 Troubleshooting System Manual

Fault Fan2-flt
Possible Correspond to the fault of the Turnkey Station module fan 2 (right side fan from
reason the front view)
Measure Check the functionality of fan after the device is voltage-free
Remark Contact Sungrow

Alarm AC breaker flt


Possible AC side circuit breaker is abnormal
reason
Measure Check the AC circuit breaker when the Turnkey Station is voltage-free
Remark Before device stops, the Turnkey Station can operate in grid-connection
normally

Fault Driver board fault


Possible Driver board fault
reason
Measure Stop the device to check and service the driver board.
Remark Contact Sungrow

Fault Carrier synch flt


Possible Carrier synchronization fault
reason
Measure The carrier synchronization cable is loose or broken.
Remark Contact Sungrow

Fault DC switch fault


Possible DC cabinet switch fault
reason
Measure Stop the device to check and service the DC cabinet switch
Remark Contact Sungrow

11.4 LCD Display Alarm Information and Troubleshooting


During alarm running state, the Turnkey Station can operate normally and send warning
signal. The user can check the alarm information through the Work state on the default
menu or through the Function->History-information->His-alarm interface to check the latest
200 history alarm information. The module will recover to normal operation once the alarm
is removed.
Alarm GFRT Run
Possible Grid voltage below 0.9Un with LVRT function enabled or above 1.1Un with
reason HVRT function enabled
Measure Alarm will disappear automatically when grid voltage recover to be normal
Remark -

Alarm CT Unbalanced
Possible Current transformer (CT) on the Turnkey Station control cabinet is abnormal
reason
Measure Check and service the CT on the measuring board when the module is
voltage-free
Remark Operation LED will keep green when this alarm occurs

86
System Manual 11 Troubleshooting

Alarm DC Sensor-err
Possible The Turnkey Station DC sensor abnormal
reason
Measure Check and service the DC sensor when the Turnkey Station is voltage-free
Remark -

Fault DC switch anomaly


Possible DC switch is abnormal
reason
Measure Stop the device to check and service the DC switch
Remark Contact Sungrow

Alarm IDM-com-flt
Possible The Turnkey Station internal communication abnormal
reason
Measure Check the IDM when the Turnkey Station is voltage-free
Remark -

Alarm Branch rev-Idc-high


Possible The detected reverse current of the branch on the DC side exceeds the
reason permissible range
Measure Check the abnormal branch when the Turnkey Station is voltage-free
Remark Before the device stops, the non-abnormal branches can work normally and the
Turnkey Station can operate in grid-connected mode normally

Alarm Branch fwd-Idc-high


Possible The detected forward current of the branch on the DC side exceeds the
reason permissible range
Measure Check the abnormal branch when the Turnkey Station is voltage-free
Remark Before the device stops, the non-abnormal branches can work normally and the
Turnkey Station can operate in grid-connected mode normally

Alarm Branch breaker flt


Possible The circuit breaker of the branch on the DC side is abnormal and this branch
reason cannot work normally
Measure Check the abnormal circuit breaker when the Turnkey Station is voltage-free
Remark Before the device stops, the non-abnormal branches can work normally and the
Turnkey Station can operate in grid-connected mode normally

11.5 Other Faults


Fault The Turnkey Station shuts down shortly after start-up
Possible DC input voltage just reaches the Turnkey Station start-up voltage. The voltage
reason will decrease and the Turnkey Station will stop when it is under load.
Measure Design the serial and parallel connection in accordance with the open circuit
voltage; increase the input DC voltage; and avoid adopting the critical voltage
Remark -

87
11 Troubleshooting System Manual

Fault LCD Display Cannot Start or Stop the Turnkey Station


Possible Communication malfunction between the LCD display and the DSP; and LCD
reason power supply malfunction
Measure Check the connection between the LCD display and the DSP when the Turnkey
Station is voltage-free
Remark -

Fault Communication Failure with PC


Possible
Possible reasons are various. Please refer to the Measure for troubleshooting
reason
Measure  Check if the address and the Baud rate of the LCD are the same as that of
PC
 Check to ensure the circuits are properly connected and if the RS485
communication is adopted, the A and B ports are connected correctly
 Check if the communication converters are matched. Communicate again
after replacing the converter
 The monitor disk is installed incorrectly. It is recommended to reinstall the
disk
 If all the above-mentioned items are correct and this fault still exists, please
replace the PC communication module on the LCD display
Remark The monitor disk might be incompatible with the antivirus software and thus
cannot be installed correctly. You are recommended to disable the antivirus
software and then install the monitor software.
If the fault still occurs, please contact Sungrow

88
12 Routine Maintenance
12.1 Safety Instructions
Due to the effect of ambient temperature, humidity, dust, and vibration, the Turnkey Station
and the inner components will be aging and worn out. To ensure the system safety and
maintain the efficiency of the Turnkey Station, it is necessary to carry out routine and
periodic maintenance.
All measures, which can help the Turnkey Station work in good conditions, are within the
maintenance scope.

12.1.1 Safety Instructions

Lethal voltage inside the Turnkey Station!


After the Turnkey Station stops, wait at least 10 minutes before opening the
cabinet door. Make sure the internal device is completely voltage-free before
performing any work on the Turnkey Station.

Only qualified personnel can perform the work described in this chapter.
Do not leave any screws, washers, or other metallic parts inside the Turnkey
Station to avoid damages to the Turnkey Station.

Sand and moisture penetration may affect the performance of electric devices
inside the Turnkey Station!
 Do not perform electrical connection in sandy season or when the ambient
relative humidity is above 95%.
 Perform electrical connection on fine weather days.

Disconnecting the AC & DC switches never means that the cable connection
terminals inside the AC and DC cabinets are voltage-free. To avoid the risk of
electric shock, before maintenance work,
 Disconnect the AC & DC switches;
 Disconnect the upstream and downstream switches of the Turnkey Station.

12.1.2 Five Safety Rules


Respect the following five rules during maintenance or service on the Turnkey Station to
ensure the safety of the maintainer.

89
12 Routine Maintenance System Manual

 Disconnect the Turnkey Station from all the external connections and internal power
supplies.
 Ensure that the Turnkey Station will not be started inadvertently.
 Verify that the Turnkey Station interior discharges completely with a multimeter.
 Necessary ground and short circuit connection.
 Cover the adjacent electrical components with insulation cloth during operation.

12.2 Maintenance

12.2.1 Introduction
With IP54 protection degree, the Turnkey Station can be installed outdoors. Harsh
environmental condition or long-time operation, however, may cause aging and damage to
the Turnkey Station. Check and maintain the Turnkey Station periodically and replace the
aged components, which can effectively prolong the service life and improve the
performance of the devices inside the Turnkey Station.

Unscheduled maintenance is also required, esp. when the system performance


is poor.

12.2.2 Maintenance Interval


Maintain the Turnkey Station and internal electric devices periodically to ensure the good
performance of the Turnkey Station.
The maintenance interval described in this chapter is indicative only. The actual interval
depends on the on-site environment condition. If the Turnkey Station is located in harsh
environment place, for example, desert areas, the maintenance interval shall be shortened.
Esp. the cleaning of the Turnkey Station outside and anti-corrosion & anti-rust work should
be more frequent.
If the Turnkey Station is installed in the desert areas, it is recommended to check the
Turnkey Station thoroughly and clean it carefully after sand storm.

Check the module fans inside the Turnkey Station and the fans on top of the
cabinet periodically for abnormal operation and abnormal noise due to dust
penetration. Stop the Turnkey Station and clean the dust if necessary.
Wait at least 10 minutes after the Turnkey Station discharge completely. Before
cleaning, make sure, with the multimeter, the Turnkey Station internal is
discharged completely to avoid electric shock.

Almost all maintenance work needs the internal protective grid to be removed.
Make sure to reassemble the grid and fasten all the screws after the maintenance
work.
Make sure all bolts are securely fixed.

90
System Manual 12 Routine Maintenance

Once any anomaly is found during routine maintenance of the Turnkey Station
and internal devices please make correction immediately. If there are any doubts,
please contact Sungrow.
Item Method Interval
Make correction immediately once the
following items are found:
 Check if there are flammable materials on
top of and around the Turnkey Station; and if
External checking there are other factors that may impair the Every quarter
system operation
 Check if the Turnkey Station and the
foundation are firmly connected and if there
is rust
 Check the Turnkey Station and internal
devices for deformation and damages
 Check the Turnkey Station and internal
devices for abnormal noise
 Check if the temperature of the Turnkey
Station interior and device enclosure is
System states and
too high Once a month
cleaning
 Check if the Turnkey Station internal
humidity and dust deposition are too
heavy. Clean the Turnkey Station.
 Check if the air inlet and outlet are
blocked;
 Check if the circuit board and the From every six
component are clean; months to annually
 Check the temperature and dust of the depending on the
heat-sink. Use a vacuum cleaner to clean dust deposits.
Module cleaning
the module if necessary;
 Replace the air filter if necessary
 Notice! Check the air inlet and outlet. The
device may be damaged by overheating.
 Check if the warning labels are clearly
Warning labels Once per year
visible. Replace them if necessary
Check the cable connection after the Turnkey
Station and internal devices are voltage free.
Make correction once unconformity is found.
 Check if all cable entries are sealed
properly;
 Check if there is water leakage inside the
Turnkey Station; check if Turnkey Station
windows and doors can close and open
flexibly; check if the sealing strip is sealed
Cable connection Once per year
properly
 Check if the power cable connections are
loose. Retighten them with the torque
specified in the manual if necessary
 Check if the power cables and control
cables, especially the surface in contact with
the metal are damaged;
 Check if the wrap belt of the connection
terminals is strip-off
Check if the air inlet filter and ventilation ducts Every six months
of the Turnkey Station and internal devices or maintain
Air inlet/outlet
are normal according to real
Clean or replace the filter situation

91
12 Routine Maintenance System Manual

Check the running state of the fan inside the


Every six months
Turnkey Station
or maintain
Fan Check if there is a crack in the fan blade
according to real
Check if there is abnormal noise during the
situation
running of the fan;
Device maintenance  Routine check the corrosion of the metal From every six
components (once six months) months to annually
 Annually check the contactors (auxiliary
switches and micro-switches) to ensure the
optimal operation
 Check the running parameters (esp.,
voltage and insulation)
Safety function  Check the emergency stop button and the From every six
LCD stop function; months to annually
 Simulation shutdown
 Check the warning labels and other
markings for damage or unclearness.
Replace them if necessary
Software  Optimize software From every six
maintenance  Check each parameter setting months to annually
LCD time display  Check if the time displayed on the LCD From every six
display is correct; months to annually
 Replace the button cells on the back of the
LCD panel if time is incorrect after
calibration.
Follow related
Check the functionality of the firefighting regulation where
Firefighting device
devices the project is
located
Other devices Replace the damaged lighting devices in time When necessary

The maintenance operations could be more frequent according to the


environmental conditions at the place where the Turnkey Station is suited, plant
capacity, and on-site situations.
The maintenance interval should be shortened if the sand or dust deposition
around the operation site is serious.

12.3 Cleaning the Turnkey Station


12.3.1 Introduction
Cleaning the surrounding areas of the Turnkey Station and the Turnkey Station interior is
important maintenance work.
Due to the effect of ambient temperature, humidity, dust, and vibration, there may be dust
deposition inside the Turnkey Station blocking the air entries and penetrating inside the
Turnkey Station internal devices. There may be potential faults of the Turnkey Station
internal devices and the service life of the internal devices as well as the power yields may
be affected.
During device normal operation, check and clean the device periodically to make sure the
internal devices are in a relatively good condition.

12.3.2 Cleaning Interval


The cleaning interval of the Turnkey Station depends on the operation conditions of the
Turnkey Station, for example, the weather condition and etc.. It is recommended to check
the Turnkey Station once every one or two months to make sure the Turnkey Station

92
System Manual 12 Routine Maintenance

exterior and interior areas are clean. If the operation conditions are severe, in desert area
for instance, the cleaning interval shall be once every half a month or even shorter. The
cleaning of the internal devices and the air inlet and outlet shall be more frequent.

12.3.3 Cleaning the Internal Dust


For cleaning the dust inside the Turnkey Station, please use a vacuum cleaner instead of a
broom.

The vacuum cleaner can get power supply from the backup socket inside the
intelligent power distribution cabinet. For the marking of the backup socket,
please refer to the circuit diagram inside the cabinet door of the intelligent
power distribution cabinet.

12.3.4 Cleaning the Foundation


The foundation is designed with maintenance entry. You should enter the foundation to
check the cleanness periodically. Use a vacuum cleaner to clean the foundation if
necessary.

12.3.5 Filter checking and cleaning

It is recommended to check and clean the Turnkey Station filter at least every
six months.
The maintenance interval should be shortened to once every three months or
shorter if the dust deposition is heavy.
The air inlets located on the front and back sides of the Turnkey Station are entrances of
cool air. Periodically clean and replace the filter cotton and filter screen to ensure air
circulation and appropriate temperature inside the Turnkey Station.
Cleaning and replacing operations are performed on the air inlet window outside the
Turnkey Station:
Step 1 Push the two spring lock catches toward the middle of the air inlet window to open the
outside shutters of air inlet window.

Step 2 Remove the air filter cotton inside the air inlet window , and shake the dust off.

93
12 Routine Maintenance System Manual

Filter cotton

Filter screen

Step 3 Clean the filter screen with warm water and degreaser and then dry it in the air if necessary.
Step 4 If the filter is broken, replace it. Put a proper new one when the old filter is removed.
Step 5 When the filter cotton and screen are clean and dry, reassemble them in reverse order.

Do not pull hard during cleaning and replacing the filter cotton and filter screen.
Otherwise the cotton and the screen may be damaged.
Contact Sungrow to order the filter. You can cut proper filters out of the larger
filter.

12.3.6 Cleaning the Surface of the Turnkey Station


If there is corrosion on the surface of the Turnkey Station, clean it with abrasive paper or
brush.
If the dust deposition is serious on the surface of the Turnkey Station, use a mop or big rag
to clean the surface of the Turnkey Station. It is recommended to clean the Turnkey Station
top first and then clean the Turnkey Station side. You can clean it directly or wash with
water.

12.3.7 Checking the Lock and Hinge


Check the functionality and state of the lock and hinge of the Turnkey Station after the
cleaning work. Lubricate the lock and hinge if necessary.

12.3.8 Checking the Sealing Strip


The sealing strip is used to prevent the water from penetrating insider the Turnkey Station.
Check it carefully for damages. Replace the damaged sealing strip in time.

12.4 On-site painting make-up measures


Check for the damages of the Turnkey Station appearance:
Situation 1: smudginess on the surface caused by water and dust that can be cleaned
Situation 2: smudginess on the surface & damage to the finishing coat that cannot be
cleaned
Situation 3: the undercoat is damaged and the primer is revealed

Maintenance and operation steps for situation 1:


Materials:

94
System Manual 12 Routine Maintenance

 Rag
 Water
 Alcohol or other non-corrosiveness detergents
Step Figure Description
Clean the smudginess on the surface by rag
1
(or other cleaning tools) with water

If the smudginess cannot be cleaned by


water, use 97% alcohol until the surface is
2 clean enough to accept. (Or try other local
commonly used non-corrosiveness
detergent)

Maintenance and operation steps for situation 2:


Materials:
 Abrasive paper
 Rag
 Water
 Alcohol
 Hairbrush
 Oil paint

95
12 Routine Maintenance System Manual

Step Figure Description

Polish the rough oil paint surface or the scratched


1 parts by abrasive paper until the surface is
smooth

Clean the target parts by rag with water or use


2
97% alcohol

When the surface is clean and dry, paint the


abraded parts of the oil paint by banister brush
3
and make sure the painting is as uniform as
possible

Maintenance and operation steps for situation 3:


Materials:

 Abrasive paper
 Rag
 Water
 Alcohol
 zinc primer
 Hairbrush
 Oil paint

96
System Manual 12 Routine Maintenance

Step Figure Description

Polish the damaged parts of the oil paint to remove


1
the surface rust or other roughness

Clean the target parts by rag with water or use 97%


2
alcohol to clean the surface dust and dirty

When the surface is clean and dry, paint the base


material revealed parts with zinc primer (or other
3 local primers with the same function) for protection.
The paints should cover the revealed primer
completely

Paint the abraded parts by banister brush when the


4 primer is dry, and make sure the painting is as
uniform as possible

97
12 Routine Maintenance System Manual

Check the protective paint on the Turnkey Station surface for peeling off. Please
re-paint the Turnkey Station surface if necessary.
Re-spray the protective paint once every 3-5 years to the Turnkey Station
surface.

12.5 Replacement of the electrical components

The electrical components inside the Turnkey Station must be replaced by the
same components from the same manufacturer and of the same model.
The model can be found on the marking of the Turnkey Station or the component
itself. If otherwise, please contact Sungrow.

If the components needs to be replaced with products from other manufacturers


or of different model on site, a prior analysis and confirmation by Sungrow is
required.
Failure to follow this procedure may lead to physical injury or death and void all
warranty from Sungrow.

12.5.1 Replace DC fuses

Safety instructions

Strictly observe the instructions in this chapter to replace the fuse.


Any personal injury or property damage caused by the disobedience of this
chapter may void pertinent warranty claims from Sungrow.

Only qualified technical persons who have fully understood the description in this
chapter can perform the operations in this chapter.

DC fuse area
The DC cabinet inside the Turnkey Station is equipped with DC fuses. The DC fuse area is
shown in the following figure A.

98
System Manual 12 Routine Maintenance

Before replacing the fuses, remove protective grid installed at the DC fuse area at the
bottom of the DC cabinet.

Operations before replacement


Follow the procedure below to replace the fault fuse.
Step 1 Stop the Turnkey Station via the stop instruction on the LCD screen.
Step 2 Disconnect DC output switches of all PV array combiner boxes upstream.
Step 3 Disconnect the DC and AC side switches of the Turnkey Station and auxiliary power supply
switches, and perform Step 4 about 5 minutes later when the capacitor inside the machine
discharges completely.
Step 4 Use a multimeter with a measuring range of 1500Vdc to check whether voltages of the
connection terminal on the DC side of the Turnkey Station are zeros, where the voltages
include the voltage between the positive and negative poles, the positive to ground voltage,
and the negative to ground voltage.
Step 5 Open the left door with the key and remove the protective grid in the DC fuses area.
Step 6 Measure each DC input voltage by using the multimeter, and perform the next step after
ensuring the wiring terminal is completely voltage-free.
Step 7 Replace the fault fuse.

Replacement of the fault fuse

The fuse must be replaced with one of the same model and from the same
manufacturer.
Obtain the model from the marking on the fuse. Contact us if otherwise.

99
12 Routine Maintenance System Manual

Without our confirmation, do not replace the fuse with the one from another
manufacturers or of a different model.
Otherwise, Sungrow shall not be responsible for any possible personal injury or
property damage.

Proceed as follows to replace the fuses if necessary.


Descriptions Figure
1. As shown in the right figure, identify the
faulty fuse.

2. Remove the micro-switch (A in the figure)


attached to the fuse and use the fuse
extractor (not in the scope of delivery) to
remove the fuse.

3. Mount the new fuse.

100
13 Appendix
13.1 Turnkey Station System Parameter

13.1.1 Input data (DC side)


Parameter Specification
Max. DC voltage 1500 V
MPPT voltage range under full load 875 V ~ 1300 V
Min. DC voltage 875 V
Max. input current 4178 A

13.1.2 Output data (Grid side)


Parameter Specification
Nominal output power 3125 kW
Maximum output apparent power 3593 KVA
Max. AC output current 3458 A
Nominal grid voltage 600 V
Grid voltage range 480 V ~ 690 V
Nominal grid frequency 50 Hz / 60 Hz
Grid frequency 45 ~ 55 Hz / 55 ~ 65 Hz
THD <3% at nominal power
DC current injection <0.5% at nominal output current
Power factor 0.8 (leading)~0.8 (lagging)

13.1.3 Mechanical parameters


Parameter Specification
Dimensions(W×H×D) 2991 mm x 2591 mm x 2438 mm
Weight 6,000 kg

13.1.4 System data


Parameter Specification
Max. efficiency 99 %
European efficiency 98.7 %
Protection degree IP54
Night self-consumption 500 W
Operating ambient temperature range -35℃~+60℃ (> 50℃ derating)
Cooling method Temperature controlled forced air cooling
Relative humidity 0~95% (non-condensing)
Max. working altitude 4000 m (> 3000m derating)
RS485/Modbus, Ethernet(communication distance of
Communication port/protocol RS485 ≤1000m; communication distance of Ethernet
≤100m)

101
13 Appendix System Manual

13.2 Tightening Torques


Tighten the cable with proper torque shown below to prevent the poor contact, high contact
resistance, or fire caused by the looseness of cable lugs:
Screw size M3 M4 M5 M6 M8 M10 M12 M16
Torque (N·m) 0.7~1 1.8~2.4 4~4.8 7~8 18~23 34~40 60~70 119~140
Secure the cable in proper place to reduce the pressure of cable lug.

13.3 Exclusion of Liability


The content of these documents is checked and revised whenever necessary. Please call
us or visit our website at www.sungrowpower.com for the latest information. No guarantee
is made for the completeness of these documents. Please contact our company or
distributors for the latest version.
Guarantee or liability claims for damages of any kind are excluded if they are caused
 Improper or inappropriate use or installation of the product
 Install or operate the product in unpredictable environment
 Install or operate the product without observing relevant local safety regulations
 Ignore the safety warnings or instructions contained in all documents relevant to the
product
 Install or operate the product under incorrect safety or protection conditions
 Alter the product or supplied software without perimission
 Product malfunctions due to operation attached or neighboring devices running out of
the allowed limit values
 Unforeseen calamity or force majeure
The use of supplied software produced by Sungrow Power Supply Co., Ltd. is subject to the
following conditions:

 Sungrow Power Supply Co., Ltd. assumes no liability for direct or indirect damages
arising from the use of SolarInfo software. This also applies to the provision or
non-provision of support activities.
 SolarInfo software used for commercial purposes is prohibited.
 Decompiling, decoding or destroying the original program, including SolarInfo software
and the embedded software, is prohibited.

102
System Manual 13 Appendix

13.4 Contact Information


Should you have any questions or queries about this product, please contact us through
the following information. We will be more than happy to assist you!
Company: Sungrow Power Supply Co., Ltd.
Website: www.sungrowpower.com
Email: Info@sungrow.cn
No.1699 Xiyou Rd., New & High Technology Industrial Development Zone,
Address:
Hefei, P. R. China.
Zip: 230088
Telephone: +86 551 6532 7834, +86 551 6532 7845
Fax: +86 551 6532 7856

103

You might also like