Design Calculations for External Supports for Spray System and

Foam System of Tankage Area

1.0 Load Calculation


1.1 Dead Load
Self Weight

1.2 Pipe Empty Weight

For 1 Inch Pipe


Contributory Length L = 6.392 m
Diameter of Pipe d = 33.4 mm
Thickness of Pipe t = 3.38 mm
Density of pipe ρst = 7854 Kg/ M3

Pipe Empty Load (1") = π d t L ρst = 0.1781 KN

For 3 Inch Pipe


Contributory Length L = 6.392 m
Diameter of Pipe d = 76.1 mm
Thickness of Pipe t = 4 mm
Density of pipe ρst = 7854 Kg/ M3

Pipe Empty Load (3") = π d t L ρst = 0.4802 KN

1.3 Pipe Operating Load

For 1 Inch Pipe


Contributory Length L = 6.392 m
Diameter of Pipe d = 33.4 mm
Thickness of Pipe t = 3.38 mm
Density of Fluid ρw = 1000 Kg/ M3

Pipe Operating Load (1") = (π /4) x d2 x L x ρw = 0.0560 KN

For 3 Inch Pipe


Contributory Length L = 6.392 m
Diameter of Pipe d = 76.1 mm
Thickness of Pipe t = 4 mm
Density of Fluid ρw = 1000 Kg/ M3

Pipe Empty Load (3") = (π /4) x d2 x L x ρw = 0.2908 KN

1.4 Seismic Load

Dead Load+Operating Load = 0.48 + 0.29 = 0.771 KN


From this seismic weight horizontal base shear will be calculated

Length of Building in x Direction = 1.0 m


Length of Building in y Direction = 1.0 m

Design Calculation for STR1


File : Support Design Calculations.xls
Design Calculations for External Supports for Spray System and
Foam System of Tankage Area
Height of Building in y Direction = 12.0 m

Zone Factor z = 0.36


Importance Factor I = 1
Response Reduction Factor R = 5

From Staad Tx = 0.56 sec Sa/g = 1.9


From Staad Tz = 0.77 sec Sa/g = 1.75
`
W = 4.560 KN Calculated
Ahx = 0.07 Vbx = 0.312 KN
Ahz = 0.06 Vbz = 0.287 KN

Ah = (Z I/2R) x ( Sa/g)

Support Reaction (Dead Load + Operational Load)

Horizontal Vertical Horizontal Moment


Node
Force - X KN Force - Y KN Force - Z KN Moment X KNm Moment Y KNm Moment Z KNm
11 0 0.771 0 0 0 0
8 0 0.771 0 0 0 0

Node Wi hi Wi x Qix Qiz


11 WEIGHT 0.771 11.7 136.89 105.53 0.2125 0.1958
8 WEIGHT 0.771 8 64 49.34 0.0994 0.0915

Qi = Vb x ((Wi x )/(∑Wi x ))

JOINT LOAD JOINT LOAD


11 Fx 0.220 Fz 0 0.2
8 Fx 0.100 Fz 0 0.1

1.5 Wind Load

Wind Data
Location of Structure = Geleki
Basic Wind Speed = 50 m/s
Terrain Category = Category - 1
Class of Structure = Class A
Life of Structure = 50

k1 = 1
k2 = 1.09
k3 = 1
Design Wind Speed
Vz = k1 x k2 x k3 x Vb = 54.5 m/s

Design Wind Pressure Pz = 1782.15 N/m2

Design Calculation for STR1


File : Support Design Calculations.xls
Design Calculations for External Supports for Spray System and
Foam System of Tankage Area
Pz = 0.6 x Vz X Vz = 1.78 KN/m2

P = Cpe x Pz x Contributory Length x Dia. Of Pipe


Cpe = 0.7

P (For 1 inch Ring Pipe)


Contributory Length L = 6.392 m
Diameter of Pipe d = 33.4 mm
P (For 1 inch Ring Pipe) P = 0.266 KN

P (For 3 inch Ring Pipe)


Contributory Length L = 6.392 m
Diameter of Pipe d = 76.1 mm
P (For 3 inch Ring Pipe) P = 0.607 KN

P (For 1 inch Riser Pipe)


Contributory Length L = 1.67 m
Diameter of Pipe d = 33.4 mm
P (For 1 inch Riser Pipe) P = 0.070 KN

P (For 6 inch Riser Pipe)


Contributory Length L = 1.67 m
Diameter of Pipe d = 76.1 mm
P (For 6 inch Riser Pipe) P = 0.159 KN