Sample Structural Analysis
Sample Structural Analysis
OF
Prepared by:
Page 1 of 9
CONSTRUCTION OF PAL-LIM MANGO PACKAGING CENTER
PALUGSI-LAMINSANGAN, BAUANG, LA UNION
Owner: PRDP
DESIGN OF SLABS
A. DESIGN OF TWO-WAY SLAB (S-1)
Direct Design Method
Design Specifications
L1 = 4.00 m column size = 0.30m x 0.40m a1 = 1 (short direction)
L2 = 7.00 m beam size = 0.25m x 0.40m a2 = 1.25 (long direction)
Fy = 275 Mpa f'c = 20.7 Mpa cc = 25 mm
3 Design moments
Dead Load = W slab + W ceiling+finish = 4.53 Kpa L1 = 4 m
Live Load = 4.8 Kpa L2 = 7 m
f = 0.9
Long Span:
Mu = Wu L1 Ln2 /8 =
2
294.42 KN m; Mn = Mu/f = 327.13 KN m
Page 2 of 9
Column strip positive Mn = 100.59 KN m
Beam positive Mn = 85.50 KN m
Slab positive Mn = 15.09 KN m = 7.54 KN m /half strip
Short Span:
Mu = Wu L2 Ln1 /8 =
2
148.75 KN m; Mn = Mu/f = 165.28 KN m
By interpolation:
L2/L1 a1L2/L1
1 75 x x = 22.50 %
1.75 ? %M = 52.50 %
2 45
Code assigns 85% of the column strip moment to the beam
Column strip negative Mn = -56.40 KN m
Beam negative Mn = -47.94 KN m
Slab negative Mn = -8.46 KN m = -4.23 KN m /half strip
Page 3 of 9
DESIGN OF BEAMS
A. FLOOR BEAM, FB1
1 Design loads
TA = 40.00 m2 Slab Thickness = 150 mm
Beam size: b = 0.40 m Beam span L = 7 m
h= 0.35 m LL = 4800 Pa
d= 0.34 m
Dead loads: W slab = 141.24 KN
W c+f = 28.8 KN
W beam = 23.07
WDL = 193.11 KN = 27.59 KN/m
Live loads: WLL = 192 KN = 27.43 KN/m
Wu = 1.2DL + 1.6LL = 90.78 KN/m
2 Design Moments
Assuming fully restrained beam
Max. +Moment = WuL2/24 = 185.35 KN m
Max. -Moment = -WuL2/12 = -370.70 KN m
Max. Shear = WuL/2 = 317.74 KN
3 Reinforcement Design
At Support (Negative Moment)
Mu = -370.70 KN m f'c = 20.7 Mpa
Mn = Mu/0.90 = 411.89 KN m Fy = 275 Mpa
AǾ = 201.06 mm2
r = rmax = 0.75rbal
rbal = [0.85f'c b/Fy][600+(600+Fy)] = 0.037
rmax = 0.75rbal = 0.028
use r = 0.3rbal = 0.011
As1 = rbd = 1510.34 mm2
a = As1Fy/(0.85f'cb) = 59.01 mm
M1 = As1Fy(d-a/2) = 127.92 KN m < 370.70 KN m
Treat as doubly reinforced beam
No. of bars required (use 16 mmÆ)
n = As/AǾ = 7.5 say 8 pcs
Reinforcement:
8 pcs - 16mmǾ (Top bar)
2 pcs - 16mmǾ (Bottom bar)
4 Stirrup
Vu = 317.74 KN Vcr = Vu - Wu d = 287.10 KN
Shear capacity of beam
Page 4 of 9
Vc = √(f'c)bd/6 = 102.37 KN
Vn = fVc/2 = 43.51 KN < 287.10
Stirrup is needed
Vs = Vcr/f - Vn = 294.26 KN
Using 10mmǾ AǾ = 78.54 mm2
Spacing S = AǾFyd/Vs = 49.54 mm
Max S = d/2 = 168.75 mm
Use 10mmǾ stirrups spaced @: 3 @ 50mm; 2 @ 100mm; 2 rest @ 150mm
2 Design Moments
Assuming fully restrained beam
Max. +Moment = WuL2/24 = 80.32 KN m
Max. -Moment = -WuL2/12 = -160.65 KN m
Max. Shear = WuL/2 = 137.70 KN
3 Reinforcement Design
At Support (Negative Moment)
Mu = -160.65 KN m f'c = 20.7 Mpa
Mn = Mu/0.90 = 178.50 KN m Fy = 275 Mpa
AǾ = 201.06 mm2
r = rmax = 0.75rbal
rbal = [0.85f'c b/Fy][600+(600+Fy)] = 0.037
rmax = 0.75rbal = 0.028
use r = 0.25rbal = 0.009
As1 = rbd = 903.17 mm2
a = As1Fy/(0.85f'cb) = 56.46 mm
M1 = As1Fy(d-a/2) = 89.23 KN m < 160.65 KN m
Treat as doubly reinforced beam
No. of bars required (use 16 mmÆ)
n = As/AǾ = 4.5 say 5 pcs
Reinforcement:
5 pcs - 16mmǾ (Top bar)
2 pcs - 16mmǾ (Bottom bar)
Page 5 of 9
Reinforcement:
2 pcs - 16mmǾ (Top bar)
4 pcs - 16mmǾ (Bottom bar)
4 Stirrup
Vu = 137.70 KN Vcr = Vu - Wu d = 122.45 KN
Shear capacity of beam
Vc = √(f'c)bd/6 = 73.46 KN
Vn = fVc/2 = 31.22 KN < 122.45
Stirrup is needed
Vs = Vcr/f - Vn = 112.84 KN
Using 10mmǾ AǾ = 78.54 mm2
Spacing S = AǾFyd/Vs = 148.34 mm
Max S = d/2 = 193.75 mm
Use 10mmǾ stirrups spaced @: 3 @ 50mm; 2 @ 100mm; rest @ 150mm o.c.
DESIGN OF COLUMNS
A. EXTERIOR COLUMNS (C1)
Trial Section
b = 300 mm Ag = 120000 mm2
h = 400 mm Ast = 2513.2741 mm2
Ǿbar = 20 mm Ǿtie = 10 mm
n = 8 pcs
Design Specifications
f'c = 20.7 MPa ǿ = 0.7
Fy = 275 MPa β = 0.85
1 Axial loads
PDL = 96.55 kN PLL = 96.00 kN
Pu = (1.2DL + 1.6LL)x1.5 = 404.20 kN (for one side only)
PuTotal = Pu x no. of sides x no. of floors = 2425.19 kN
4 Lateral ties
s = 16 (Ǿbar) = 320 mm
s = 48 (Ǿtie) = 480 mm
s = least dimension = 300 mm
Thus: Use 8 - 16mm dia bar with 10mm dia lateral ties @ 200mm o.c.
Page 6 of 9
Design Specifications
f'c = 20.7 MPa ǿ = 0.7
Fy = 275 MPa β = 0.85
1 Axial loads
PDL = 96.55 kN PLL = 96.00 kN
Pu = (1.2DL + 1.6LL)x1.5 = 404.20 kN (for one side only)
PuTotal = Pu x no. of sides x no. of floors = 1616.79 kN
4 Lateral ties
s = 16 (Ǿbar) = 256 mm
s = 48 (Ǿtie) = 480 mm
s = least dimension = 300 mm
Thus: Use 8 - 16mm dia bar with 10mm dia lateral ties @ 200mm o.c.
DESIGN OF FOOTING
A. INTERIOR FOOTING (F1)
Design Specifications
f'c = 20.7 MPa H = 1500 mm
Fy = 275 MPa h = 300 mm
Ǿbar = 16 mm qall = 190 kPa (assume)
σconc = 23.5 kN/m3 σsoil = 15.7 kN/m 3
(assume)
colb = 300 mm cc = 100 mm
colh = 400 mm ǿ = 0.85
1 Service loads
PT = PDL + PLL = 1155.33 kN
2 Base dimensions
qnet = qall - [ hσconc + Hσsoil ] = 159.40 kPa
Areqd = PT / qnet = 7.25 m2
B2 = Areqd B = 2.69 m
Trial section:
B = 2 m Aact = 4 m2
Page 7 of 9
ǿVc = 0.33ǿ bo d √f'c = 561.53 kN
since: ǿVc < Vu → UNSAFE
6 Design of reinforcement
x2 = (B - colb)/2 = 0.85 m
Mu = qu B x /2
2
2
= 292.03326 kN m
Mu = ǿf'c Bd ω (1-0.59ω)
2
ω2 - 1.69ω + 0.33211 = 0
ω = = 0.227
ρ = ωf'c/Fy = 0.017
n = Ast/AǾ = 10.13
say 8 pcs
Thus: Use 8 16mm dia bar on both sides of footing.
1 Service loads
PT = PDL + PLL = 770.22 kN
2 Base dimensions
qnet = qall - [ hσconc + Hσsoil ] = 175.10 kPa
Areqd = PT / qnet = 4.40 m2
B2 = Areqd B = 2.10 m
Trial section:
B = 1.2 m Aact = 1.44 m2
Page 8 of 9
5 Check beam shear
x1 = (B - colb - 2d)/2 = 0.25 m
Vu = q u B x1 = 224.55 kN
6 Design of reinforcement
x2 = (B - colb)/2 = 0.45 m
Mu = qu B x22/2 = 90.944613 kN m
Mu = ǿf'c Bd2 ω (1-0.59ω)
ω2 - 1.69ω + 0.17237 = 0
ω = = 0.109
ρ = ωf'c/Fy = 0.008
n = Ast/AǾ = 6.08
say 7 pcs
Thus: Use 7 16mm dia bar on both sides of footing.
Page 9 of 9