Parameters configuration
SN Parameter Default Configured Note
1 System Time Zone GMT8 GMT1
2 System Time Actual time
3 Battery capacity 150 Actual capacity
4 Work Mode Save Safe
5 Battery charge coefficient 0.15C 0.10C
6 LLVD1 45 44.4
7 BLVD 44 43.2
0.10C10
44.4
43.2
9, Measure battery voltage, each cell battery voltage should be varied within 0.1V.
10, No alarms in the CSU monitor unit before leaving.
2, “Batt.T.Invalid”
Cause: Battery temperature sensor not connected or broken.
To check whether the corresponding battery temperature sensor connected or not.
Or whether the battery capacity configure, follow the Step 3 “Battery Capacity” to check the
actual connection.