MARATHON ELECTRIC

SYNCHRONOUS AC GENERATOR
SPECIFICATIONS & OPTIONS

STANDARDS VOLTAGE REGULATORS


MAGNAMAX® synchronous AC generators DVR®2000E+ — STANDARD
meet the main international standards and Provides 0.25% regulation; adjustable
regulations: NEMA MG1, IEC60034 and GB755. volts/hertz underspeed protection; single or
MAGNAMAX® generators are designed, three-phase RMS sensing; paralleling; loss of
manufactured and marketed in an ISO 9001 sensing protection; and over excitation
environment. protection. The regulator is conveniently
mounted in a low voltage control section within
APPLICATIONS the conduit box to facilitate external
MAGNAMAX® synchronous AC generators are
designed to be suitable for typical generator
applications, such as: PERMANENT MAGNET GENERATOR
■Agricultural ■Marine Ensurer 300% short circuit current during fault
conditions and provides the regulator with input
■Commercial ■Construction
power isolated from load distortions.
■Telecommunications ■Rental Markets

ELECTRICAL PERFORMANCE SHIELD HEAVY-DUTY BEARINGS


Optimized Electrical Design . . . Resist contamination and give a minimum B-10
brushless features, utilizes a 2/3 pitch winding life of 40,000 hours. Regreasing provisions are
to minimize harmonic distortion. The main rotor available on all generators.
provides exceptional waveshape and voltage
balance.
TERMINALS & TERMINAL BOX
Standard units with 4 leads (12 leads for simplify
Class H Insulation System . . . voltage reconnection is optional) and support
utilizes an unsaturated polyester varnish for lead termination.Provides ample space for easy
optimal insulation life and superior moisture connections and allows load line access from all
protection. An epoxy overcoat is added for sides, top, or bottom.
increased environmental protection. Field
windings are wet wound with epoxy and
designed to withstand overspeeds of 125%. EASY MOUNT SAE ADAPTERS
All windings are 100% copper with class H Provided with every generator, are designed
insulation. with easy drive disc access to simplify the
mounting to all popular engines. Generator foot
PROTECTION SYSTEM mounting location is unaffected by adapter
■ MAGNAMAX® is IP 21. changes. Special adaptations for automotive
■ Standard winding protection for clean engines are available.
environments with relative humidity ≤ 95%,
including indoor marine environments.
■Options:
- Dripcover on air outlet (IP 23)
- Filters on air inlet : derating 5%.
- Winding protection for harsh environments and
relative humidity greater than 95%.
- Space heaters.
- Thermal protection for stator windings.

Version:20150402 1
MARATHON ELECTRIC
SYNCHRONOUS AC GENERATOR
TYPICAL SUBMITTAL DATA
Model : MX-1030-4
Base Model : 742RSL4048 50Hz
Submittal Data: 0.8 P.F., 1500 RPM, 50 Hz, 3 Phase

Kilowatt ratings at 1500 RPM 50 Hertz 4 or 6 LEADS Standard 3 phase

kW (kVA) 3 Phase 0.8 Power Factor Dripproof or Open Enclosure


Class B Class F Class H
80ºC  105ºC② 105ºC ① 125ºC② 125ºC ①
90ºC  95ºC  130ºC  150ºC 
Voltage* Continu British Continuo British Continuo
Lloyds ABS Standby Standby
ous Standard us Standard us
415/208 745(931) 820(1025) 850(1063) 905(1131) 905(1131) 975(1219) 960(1200) 975(1219) 1040(1300)
400/200 800(1000) 880(1100) 870(1088) 960(1200) 960(1200) 1030(1288) 990(1238) 1030(1288) 1090(1363)
380/190 840(1050) 885(1106) 860(1075) 945(1181) 945(1181) 1010(1263) 1000(1250) 1000(1250) 1070(1338)
Rise by resistance method, Mil-Std-705, Method 680.1b. ②British Standard Rating per BS 5000

Mil-Std-705B Mil-Std-705B
Method Description Value Method Description Value
301.1b Insulation Resistance >1.5 Meg 505.3b Overspeed 1875 RPM
302.1a High Potential Test 507.1c Phase Sequence CCW-ODE ABC
Main Stator 2000 Volts 508.1c Voltage Balance, L-L or L-N 0.20%
Main Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Total 5.0%
Exciter Stator 1500 Volts (Distortion Factor)
Exciter Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Single 3.0%
PMG Stator 1500 Volts 601.1c Deviation Factor 5.0%
401.1a Stator Resistance, Line to Line --- TIF (1960 Weightings) < 50
High Wye Connection 0.003 Ohms --- THF (IEC, BS & NEMA Weightings) < 2 %
Rotor Resistance 0.776 Ohms
Exciter Stator 22 Ohms
Exciter Rotor 0.043 Ohms --- Main Stator Capacitance to ground 0.047 mfd
PMG Stator 2.1 Ohms -- Cooling Air Volume 2875 CFM
427.1a T'd Transient Short Circuit 430.1a T'do Transient Open Circuit
Time Constant 0.162 sec. Time Constant 2.55 sec.
428.1a T''d Subtransient Short Circuit 432.1a Ta Short Circuit Time
Time Constant 0.011 sec. Constant of Armature Winding 0.027 sec.

380 V 400 V 415 V


410.1a No Load Exciter Field Amps 0.63 A DC 0.72 A DC 0.79 A DC
420.1a Short Circuit Ratio 0.442 0.514 0.617
421.1a Xd Synchronous Reactance 2.348 pu 2.183 pu 1.92 pu
422.1a X2 Negative Sequence React. 0.217 pu 0.202 pu 0.177 pu
423.1a X0 Zero Sequence Reactance 0.064 pu 0.06 pu 0.053 pu
425.1a X'd Transient Reactance 0.167 pu 0.155 pu 0.136 pu
426.1a X''d Subtransient Reactance 0.122 pu 0.113 pu 0.099 pu
-- Xq Quadrature Synch. React. 1.125 pu 1.046 pu 0.92 pu

* Voltages refer to wye (star) connection, unless otherwise specified.

Version:20150402 2
MARATHON ELECTRIC
SYNCHRONOUS AC GENERATOR
TYPICAL DYNAMIC CHARACTERISTICS
Model: MX-1030-4
Base Model: 742RSL4048 50Hz
Load Application (DVR2000E+)

20
% Voltage Dip

10

0
0 200 400 600 800 1000 1200
kW at 0.8 Power Factor

190/380V 200/400V 208/415V

Load Rejection (DVR2000E+)


20
% Voltage Rise

10

0
0 200 400 600 800 1000 1200
kW at 0.8 Power Factor

190/380V 200/400V 208/415V

Short-circuit Curves

Version:20150402 3
MARATHON ELECTRIC
SYNCHRONOUS AC GENERATOR
TYPICAL DYNAMIC CHARACTERISTICS
Model: MX-1030-4
Base Model: 742RSL4048 50Hz
Voltage Dip With Motor Starting (DVR2000E+)

30%

25%

20%
Percent Dip

15%

10%

5%

0%
0 400 800 1200 1600 2000 2400 2800 3200 3600 4000
Locked Rotor Kva
380V 400V 415V
Efficiency

100
97.0 96.6 96.2 96.9 96.6 96.2
95.9 95.9
93.7 93.6
% Efficiency

95.6 94.9 95.7 94.9 94.2


94.7 94.7
93.2 93.8 93.1
90

80
0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200
kW Output (380V) kW Output (400V)

0.8 pf 1.0 pf 0.8 pf 1.0 pf

100
96.8 96.5 96.1
95.8
93.5
95.7
% Efficiency

95.1 95.0 94.6


90 93.0

80
0 200 400 600 800 1000 1200
kW Output (415V)

0.8 pf 1.0 pf

Version:20150402 4
MARATHON ELECTRIC
SYNCHRONOUS AC GENERATOR
TYPICAL SUBMITTAL DATA
Model : MX-1030-4
Base Model : 742RSL4048 60Hz
Submittal Data: 0.8 P.F., 1800 RPM, 60 Hz, 3 Phase

Kilowatt ratings at 1800 RPM 60 Hertz 4 or 6 LEADS Standard 3 phase

kW (kVA) 3 Phase 0.8 Power Factor Dripproof or Open Enclosure


Class B Class F Class H
80ºC  105ºC② 105ºC ① 125ºC② 125ºC ①
90ºC  95ºC  130ºC  150ºC 
Voltage* Continu British Continuo British Continuo
Lloyds ABS Standby Standby
ous Standard us Standard us
480/240 1000 (1250) 1100 (1375) 1040 (1300) 1200 (1500) 1200 (1500) 1300 (1625) 1200 (1500) 1260 (1575) 1300 (1625)
440/220 1000 (1250) 1060 (1325) 1000 (1250) 1140 (1425) 1140 (1425) 1240 (1550) 1220 (1525) 1220 (1525) 1280 (1600)
416/208 950 (1188) 1010 (1263) 940 (1175) 1100 (1375) 1100 (1375) 1180 (1475) 1160 (1450) 1160 (1450) 1250 (1563)
Rise by resistance method, Mil-Std-705, Method 680.1b. ②British Standard Rating per BS 5000

Mil-Std-705B Mil-Std-705B
Method Description Value Method Description Value
301.1b Insulation Resistance >1.5 Meg 505.3b Overspeed 2250 RPM
302.1a High Potential Test 507.1c Phase Sequence CCW-ODE ABC
Main Stator 2000 Volts 508.1c Voltage Balance, L-L or L-N 0.20%
Main Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Total 5.0%
Exciter Stator 1500 Volts (Distortion Factor)
Exciter Rotor 1500 Volts 601.4a L-L Harmonic Maximum - Single 3.0%
PMG Stator 1500 Volts 601.1c Deviation Factor 5.0%
401.1a Stator Resistance, Line to Line --- TIF (1960 Weightings) < 50
High Wye Connection 0.003 Ohms --- THF (IEC, BS & NEMA Weightings) < 2 %
Rotor Resistance 0.776 Ohms
Exciter Stator 22 Ohms
Exciter Rotor 0.043 Ohms --- Main Stator Capacitance to ground 0.047 mfd
PMG Stator 2.1 Ohms -- Cooling Air Volume 3430 CFM
427.1a T'd Transient Short Circuit 430.1a T'do Transient Open Circuit
Time Constant 0.162 sec. Time Constant 2.55 sec.
428.1a T''d Subtransient Short Circuit 432.1a Ta Short Circuit Time
Time Constant 0.011 sec. Constant of Armature Winding 0.027 sec.

416 V 440 V 480 V


410.1a No Load Exciter Field Amps 0.55 A DC 0.64 A DC 0.79 A DC
420.1a Short Circuit Ratio 0.419 0.485 0.637
421.1a Xd Synchronous Reactance 2.686 pu 2.513 pu 2.181 pu
422.1a X2 Negative Sequence React. 0.253 pu 0.237 pu 0.205 pu
423.1a X0 Zero Sequence Reactance 0.075 pu 0.07 pu 0.061 pu
425.1a X'd Transient Reactance 0.195 pu 0.182 pu 0.158 pu
426.1a X''d Subtransient Reactance 0.142 pu 0.133 pu 0.115 pu
-- Xq Quadrature Synch. React. 1.313 pu 1.229 pu 1.066 pu

* Voltages refer to wye (star) connection, unless otherwise specified.

Version:20150402 5
MARATHON ELECTRIC
SYNCHRONOUS AC GENERATOR
TYPICAL DYNAMIC CHARACTERISTICS
Model: MX-1030-4
Base Model: 742RSL4048 60Hz
Load Application (DVR2000E+)

20
% Voltage Dip

10

0
0 500 1000 1500
kW at 0.8 Power Factor

208/416V 220/440V 240/480V

Load Rejection (DVR2000E+)


20
% Voltage Rise

10

0
0 500 1000 1500
kW at 0.8 Power Factor

208/416V 220/440V 240/480V

Short-circuit Curves

Version:20150402 6
MARATHON ELECTRIC
SYNCHRONOUS AC GENERATOR
TYPICAL DYNAMIC CHARACTERISTICS
Model: MX-1030-4
Base Model: 742RSL4048 60Hz
Voltage Dip With Motor Starting (DVR2000E+)

30%

25%

20%
Percent Dip

15%

10%

5%

0%
0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400
Locked Rotor Kva
416V 440V 480V
Efficiency

100
96.0 96.8 96.0 95.2 96.6 96.3 95.8
95.6
93.7 93.2
% Efficiency

95.0 95.0 94.7 95.2 94.593.8


94.0
90 92.9 92.9 92.5

80
0 500 1000 1500 0 500 1000 1500
kW Output (416V) kW Output (440V)

0.8 pf 1.0 pf 0.8 pf 1.0 pf

100
96.4 96.596.3
95.2
92.7
% Efficiency

95.3 95.094.6
94.4
90 92.1

80
0 500 1000 1500
kW Output (480V)

0.8 pf 1.0 pf

Version:20150402 7