Fan Data
Specifications FIRE EXHAUST
Motor Data
Start currents (sc) are DOL other than for motors of 3kW and above which are Star Delta (T).
speed Q [m3/h] Pe [Pa] Pd [Pa] Pt [Pa] Wm [kW] c [m/s] dB(A) 63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
1 106293.750 133.220 153.585 286.805 9.486 24.060 SPL(A) 88.4 68.6 70.6 80.6 84.0 83.2 77.8 75.4 65.0
2 53146.875 33.305 38.396 71.701 1.186 12.030 SPL(A) 73.3 53.6 55.6 65.5 68.9 68.2 62.8 60.3 50.0
SWL(A) 105.9 86.2 88.1 98.1 101.5 100.8 95.3 92.9 82.5
SWL(A) 90.9 71.1 73.1 83.1 86.4 85.7 80.3 77.9 67.5
Data obtained under ISO 5801:1997, type D and air density 1.2kg/m3. Sound pressure levels quoted are average dBA radiated at 3m distance over a sphere, under free field conditions and are presented
for comparative purposes only.
F G H I J
1315 16x22,5 0 0 0
K L M N
0 0 0 0
Optional Accessories -
Optional Electrical -
Accessories