Professional Documents
Culture Documents
NL02!17!0464 Control Philosophy
NL02!17!0464 Control Philosophy
Control philosophy
Vung Tau Vietnam Brewery – Control Philosophy
REVISION HISTORY
Revision Date Description Author
0.0 16-04-2018 First Issue [DRAFT] ETK
0.1 08-06-2018 First revision ETK
Page i
Vung Tau Vietnam Brewery – Control Philosophy
CONTENTS
Revision History .............................................................................................................................................................................. i
Contents ........................................................................................................................................................................................ ii
1 Introduction .......................................................................................................................................................................... 1
Project Participants ................................................................................................................................................................2
Used References ....................................................................................................................................................................3
Development Software ..........................................................................................................................................................4
Main Components..................................................................................................................................................................5
1.4.1 Compressors ....................................................................................................................................................................5
1.4.2 Condensers ......................................................................................................................................................................5
1.4.3 Pumps ..............................................................................................................................................................................5
Simple Process Diagram .........................................................................................................................................................6
Network Layout......................................................................................................................................................................7
Page ii
Vung Tau Vietnam Brewery – Control Philosophy
Page iii
Vung Tau Vietnam Brewery – Control Philosophy
Page iv
Vung Tau Vietnam Brewery – Control Philosophy
1 INTRODUCTION
This document will describe the control philosophy for the first phase of the new Greenfield cooling plant in Vung Tau, Vietnam.
Page 1
Vung Tau Vietnam Brewery – Control Philosophy
PROJECT PARTICIPANTS
Vietnam
Postal Address: ...
...
Vietnam
Phone: ...
Fax: ...
Page 2
Vung Tau Vietnam Brewery – Control Philosophy
USED REFERENCES
Drawing
Issue Description Source
Number
2042001-01 B Engineering diagram ammonia evaporator coolant freezing system JCI
2042002-01 B Engineering diagram ammonia evaporator coolant chilling system JCI
2042003-01 B Engineering diagram ammonia compressor coolant freezing system JCI
2042004-01 B Engineering diagram ammonia compressor coolant chilling system JCI
2042005-01 B Engineering diagram evaporative condensers JCI
2042006-01 B Engineering diagram liquid receiver JCI
2042007-01 B Engineering diagram ammonia coolant freezing system JCI
2042007-02 A Engineering diagram ammonia coolant freezing system JCI
2042008-01 B Engineering diagram ammonia coolant chilling system JCI
2042008-02 A Engineering diagram ammonia coolant chilling system JCI
2042009-01 A Engineering diagram ventilation / safety provision cooling plant JCI
2042010-01 A Engineering diagram softened water supply JCI
2042011-01 A Engineering diagram boiled feed water supply JCI
Page 3
Vung Tau Vietnam Brewery – Control Philosophy
DEVELOPMENT SOFTWARE
Note that the above mentioned development software is necessary to maintain the software on the cooling
plant. Customer to check with its software department if this software is available on-site and if the version
numbers correspond with the minimum requirements.
Page 4
Vung Tau Vietnam Brewery – Control Philosophy
MAIN COMPONENTS
1.4.1 COMPRESSORS
Process
# Description Type Capacity Remark
Number
1 Compressor Sabroe SAB-233LME C 99.111.01 1477,7 [kW] Coolant Freezing System
2 Compressor Sabroe SAB-233LME C 99.112.01 1477,7 [kW] / Swing Compressor
1955,0 [kW]
3 Compressor Sabroe SAB-233LME C 99.113.01 1477,7 [kW] / Swing Compressor
1955,0 [kW]
4 Compressor Sabroe SAB-233LME C 99.114.01 1955,0 [kW] Coolant Chilling System
5 Compressor Sabroe SAB-233LME C 99.115.01 1955,0 [kW] Coolant Chilling System
1.4.2 CONDENSERS
Process Spray
# Description Type Fan Remark
Number Pump
1 Condenser Baltimore CXV-D876L A 95.111.01 2x DOL 1x FRQ
2 Condenser Baltimore CXV-D876L A 95.112.01 2x DOL 1x FRQ
3 Condenser Baltimore CXV-D876L A 95.113.01 2x DOL 1x FRQ
4 Condenser Baltimore CXV-D876L A 95.114.01 2x DOL 1x FRQ
1.4.3 PUMPS
Process Electric
# Description Type Remark
Number Power
1 Pump P 95.111.01 5,5 [kW] Evaporative condensers
2 Pump P 95.111.02 5,5 [kW] Evaporative condensers
3 Pump P 95.112.01 5,5 [kW] Evaporative condensers
4 Pump P 95.112.02 5,5 [kW] Evaporative condensers
5 Pump P 95.113.01 5,5 [kW] Evaporative condensers
6 Pump P 95.113.02 5,5 [kW] Evaporative condensers
7 Pump P 95.114.01 5,5 [kW] Evaporative condensers
8 Pump P 95.114.02 5,5 [kW] Evaporative condensers
9 Pump P 95.120.01 ?,? [kW] Biocide
10 Pump P 95.120.02 ?,? [kW] Corrosion / Scaling
11 Pump KSB ETN 200-150-250 GG P 96.111.01 37 [kW] Coolant Freezing Primary
12 Pump KSB ETN 200-150-250 GG P 96.111.02 37 [kW] Coolant Freezing Primary
13 Pump KSB ETN 200-150-250 GG P 96.111.03 37 [kW] Coolant Freezing Primary
14 Pump KSB ETN 200-150-250 GG P 96.121.01 37 [kW] Coolant Chilling Primary
15 Pump KSB ETN 200-150-250 GG P 96.121.02 37 [kW] Coolant Chilling Primary
16 Pump KSB ETN 200-150-250 GG P 96.121.03 37 [kW] Coolant Chilling Primary
17 Pump KSB ETN 050-032-1601 GG P 96.151.01 4,0 [kW] Make-up
18 Pump LUTZ P 96.151.02 ?,? [kW] Drum
19 Pump KSB ETN 200-150-315 GG P121.111.01 75 [kW] Coolant Freezing Distribution
20 Pump KSB ETN 200-150-315 GG P121.111.02 75 [kW] Coolant Freezing Distribution
21 Pump KSB ETN 200-150-315 GG P121.111.03 75 [kW] Coolant Freezing Distribution
22 Pump KSB ETN 200-150-315 GG P121.121.01 75 [kW] Coolant Chilling Distribution
23 Pump KSB ETN 200-150-315 GG P121.121.02 75 [kW] Coolant Chilling Distribution
24 Pump KSB ETN 200-150-315 GG P121.121.03 75 [kW] Coolant Chilling Distribution
25 Pump KSB AMA Drainer 415 P307.100.01 1,6 [kW] Gutter pump
Page 5
A.99.29.01 A.99.27.01 A.99.26.01 A.99.25.01 A.99.28.01 A.95.10.01 A.95.11.01
EVC1 EVC2 EVC3 EVC4 EVC5 EVC6 EVC7
C.99.20.01 C.99.22.01 C.99.24.01 C.99.21.01 C.99.21.02 C.99.23.01 C.99.23.02 C.99.11.01 C.99.10.01 C.99.12.01
A.95.20.01
LIQ CMP1 CMP2 CMP3 CMP4 CMP5 CMP6 CMP7 CMP8 CMP9 CMP10
A.97.12.01
ECO1
A.97.11.01 A.97.10.01
SEP1 SEP2
P.96.10.01
TT TT TT
.02 PROCESS WATER
RETURN
FT TT PT TT FT
.03 A.114.01.01 TT TT TT
TT TT TT
FT FT FT
TT
CWT
P.114.01.01
Make-Up
A.96.11.02 Tank
STT
.02 PT
CELLAR DAW PLANT
P.96.11.01 P.121.10.01 TT
FT
FT
.02 BREWHOUSE 1
WORT COOLER
TT PT
BREWHOUSE 2 BREWHOUSE 1
P.121.11.??
.03
.??
PACKAGING WORT COOLER
BREWHOUSE 2
TT
Page 6
Vung Tau Vietnam Brewery – Control Philosophy
NETWORK LAYOUT
Page 7
Vung Tau Vietnam Brewery – Control Philosophy
INTRODUCTION
First the general features and operating strategy are explained. Hereafter is a detailed instruction on how to operate the plant. For
this instruction the print-outs of the actual screens are used to give you the most realistic information possible. Please note that the
numeric values in the screens displayed in this chapter do not represent the actual situation. However there was no solution for
getting a 100% identical picture. Also keep in mind that some of the texts are pop-up texts and are therefore only visible when
activated on the real Human Machine Interface (hereafter called “HMI”)..
PASSWORDS
In this paragraph a description of password levels valid for all screens in general is given. For operating the HMI there are four access
levels installed, protected by different passwords:
2.2.1 LEVELS
Level Persons Login Password Log-Out Time
0 Guest Everybody n/a n/a n/a
3 Operator Operators OPER 1234 5 [min]
5 Supervisor Shift Engineer / Supervisor / Utility Manager SUPER 2345 5 [min]
6 Engineer Automation Engineer ENG 1357 5 [min]
9 Expert JCI EXPERT **** 60 [min]
2.2.2 ACCESS
Supervisor
Operator
Engineer
Expert
Guest
Action
Navigation between screens
Acknowledge alarms and warnings
Change product specific set points
Change equipment mode from auto to manual and vice versa
Change equipment sequence
Change calculated / fixed set point condensers
Adjust control parameters (except warning and alarm levels)
Adjust warning and alarm settings
Empty warning and alarm buffer
Full authority
2.2.3 LOGIN
- Go to the login screen and enter the password. This login ensures access to all settings corresponding to the level of the
password entered, and all lower levels.
- Go directly to a screen to operate a certain function or modify a certain parameter. If the function you want to operate is
restricted, the system will ask for the password. Once the correct password is entered, access is granted to all functions and
parameters corresponding to the level of password entered. When trying to change a setting protected by a higher level the
system will ask again for a password. Only entering of the password corresponding to that level will give access.
Page 8
Vung Tau Vietnam Brewery – Control Philosophy
SAFETY PRECAUTIONS
This part describes all safety related items for the cooling plant. All actions related to the safety and control items are described in
more detail in the Cause & Effect diagram.
All actions related to these contacts are described in more detail in the Cause & Effect diagram
2.3.2.2 POSITION
In total fourteen (14) (ZS 307.100.01 – ZS 307.100.14) emergency stop pushbuttons are placed in the field. Eight (8) (ZS 307.100.02-
09) at the entrance doors of the engine room (in and outside), two (2) (ZS 307.100.10/11) are placed on the roof near the condensers
and three (3) (ZS 307.100.12-14) are placed in the utility cooling room. One (1) ZS 307.100.01 is placed in the LV Room.
The emergency stop relay will switch off the total cooling plant. All field equipment will be made powerless. The power supply
towards the panels will be switched off.
2.3.2.3 RESET
After an emergency stop the installation can be reset operating as follow:
At an ammonia alarm 800ppm or emergency stop activation the complete system will shut down. All motors
of compressors, pumps, etc. will stop. Also the HMI will be made powerless.
In case of ammonia detection the ammonia scrubber will be active; in case of emergency stop the ammonia
scrubber will not be active.
Page 9
Vung Tau Vietnam Brewery – Control Philosophy
Example:
For each louvre that not opened a warning is displayed on the HMI.
In “Manual mode” the PLC starts the exhaust fan that is in manual mode.
- In case of ammonia alarm > 200ppm stop fan immediately.
- The fan will start again if the ammonia value is under 200ppm and the alarm is reset.
It must be possible to activate the scrubber with a button on the HMI for service purpose only.
Page 10
Vung Tau Vietnam Brewery – Control Philosophy
Liquid receiver:
- V 95.100.02, V 95.100.03, V 95.100.04, and V 95.100.05.
Each block-in valve has an open and close position feedback switch for alarm purpose. If the applicable solenoid is activated or de-
activated and the position feedback is not valid within monitoring time an alarm is displayed on the HMI.
Page 11
Vung Tau Vietnam Brewery – Control Philosophy
2.4.1 SCREENS
Furthermore there are several screens for:
- Compressors
- Condensers
- Coolant freezing system
- Coolant chilling system
- Make-up
- Trending
- Energy
- Events
- Alarms
- Ventilation
- System settings
- Control overview
Example:
Valve activated is color GREEN. Valve deactivated is color GREY
If a part of the cooling plant is in alarm or warning the applicable button to navigate to that part must have a border in the color RED
or ORANGE. If there is an item in manual mode the border will be the color BLUE. See example with alarm and warning below.
2.4.4 ALARMS
When there is an alarm, an alarm message will be shown in the second line of the screen, no matter which screen you are in. There
will also be a blue alarm indicator flashing in the top right corner as long there is an active alarm. In case of multiple active alarms
the most recent alarm message will be shown and the underlying alarms become visible, one by one, when acknowledging the alarm
on the display. When acknowledging an active alarm, the alarm message will disappear however the blue indicator will stay on until
the alarm has been reset.
Note that alarms can only be reset after the concerning problem has been rectified; so when the alarm is no longer active.
Page 12
Vung Tau Vietnam Brewery – Control Philosophy
In case of an alarm the horn (installed inside the engine room) will sound. This audio alarm will stop by acknowledging the alarm.
With a new alarm the horn will sound again. All alarms are registered in the alarm buffer.
If a system has an alarm or warning a color mark will appear around the applicable button of the system.
2.4.5 EVENTS
For warranty issues and customer checks all the operator actions needs to be traceable. Therefore all the changes of setpoint or
acknowledge of alarms (and alarms from user administration) will be saved as an event in a log file on the HMI. The software for
creating the event log is WinCC Audit. The log file is stored in CSV format.
MAIN SCREEN
The main screen gives on overall view on the operating state and running conditions of the cooling plant. Note that the main screen
is only a display of information: nothing can be operated directly from this screen.
You can log on with the key and log off with the key with cross and the system will store the person who is logged on in the event
list. (The logged on person’s name appears in the right upper corner).
- Status of individual fans and pumps on condensers (grey is off, green is on, red is failure, yellow is maintenance).
- Status of all compressors. (Grey is off, green is run, red is failure, yellow is not ready).
- Status of coolant freezing and coolant chilling coolers (yellow is in operation or grey is not used).
- Status of all pumps. (Grey is off, green is run, red is failure).
- Status of the ammonia blocking valves (green is open, grey is closed).
- Level liquid receiver
- Temperature separator ammonia.
- Level separator ammonia.
- Level economizer.
- Suction pressure economizer.
- Discharge pressure condensers.
- Ammonia detection indicators.
- Level coolant stratification tanks.
3.1.1 CONDENSERS
3.1.1.1 OVERVIEW
This screen gives an overview of the status of all condensers, liquid vessel, scaling and operating possibilities.
Page 13
Vung Tau Vietnam Brewery – Control Philosophy
3.1.1.1.1 Sequence
There are four (for phase 1) evaporative condensers. Each condenser is equipped with 2 water spray pumps and 1 variable speed
fan. The sequence of the condensers in regulation can be set manually through the HMI. The condensers are controlled per
condenser, there is a sequence for 4 condensers.
Component N
See component conditions
conditions OK
Level in N
condenser OK Alarm on HMI
LA 95.xxx.01
Pump standby
Condenser standby: a condenser is standby whenever both spray pumps are standby.
Remarks:
- Only water pumps in operation results in approximately 5% of condenser capacity.
- Fan speed 1.500 rpm at 50Hz. Frequency controlled fans within 30-100% (15-50 Hz).
- Compressor start/stop causes major capacity (discharge pressure) changes within short time. For this reason the calculated
discharge pressure set point will be adjusted in time steps.
The rate of the regulation (by stepping up or down) will change automatically depending on the difference between the actual
discharge pressure and the calculated discharge pressure setpoint. With the stepping up and down time in combination with the
dead zone (i.e. dead band) the rate of regulation is changed.
stepping up
+ time
Then pulse up
+ (if step 3 regulation down and fans running minimal) calculated time
or
Remark: Calculated time
stepping down Then pulse down
Page 14
Vung Tau Vietnam Brewery – Control Philosophy
pressure up
min.stepping up time (15 sec.)
If the condenser pump or fan that has to start by step regulation can’t start when the related condenser isn’t standby then an extra
“pulse regulate up” will be created to go to the next step in the sequence. So the "normal” step time will not be used in this
situation to avoid high discharge pressure.
- If a pump on the condenser is not in a standby state, the condenser will be stopped in automatic mode (i.e. protection against
dry running).
- Both condenser pumps will always run with an adjustable off-delay during a biocide dosage on the related condenser. Biocide
dosage is only possible if the condenser pumps are standby.
- Each component can be switched from automatic to manual through the HMI. If there is an object in manual, the total
automatic regulation will stay in regulation.
- When a particular condenser is not in a standby state, the next condenser will take over in the step regulation based on
discharge pressure.
3.1.1.1.2 PI Control
When regulation is in step (7), the speed of the fans is controlled by a PI controller between minimal and 100%. Maximum speed
can be changed on the HMI.
Page 15
Vung Tau Vietnam Brewery – Control Philosophy
Remarks:
- Wet bulb temperature (Twb) is been determined by MT 95.120.01.
- Formula changed into the following:
Calculated discharge pressure set point = ((0,8095 x Twb) + 10,87)
(10,87 = constant adjustable value in software).
- As you can see we have not taken the number of (running / total) compressors into account as it
influences the outcome in a negative way.
This applied formula ensures at limited required condensing capacity the condensers will operate
in part load conditions.
This implies in practice it can be better energy wise to condensate a couple of degrees higher
(increase compressor power consumption), but running in part load on the condenser (decrease
condenser power consumption).
If the basic conditions are correct the condenser regulation will start when the first compressor cuts in (cooling on). Condenser
capacity will be regulated up or down in steps.
The following table describes these steps. From every single step the regulation can switch between up or down regulation until the
first step is reached or the final step is reached.
Page 16
Vung Tau Vietnam Brewery – Control Philosophy
sequence
Operation
Pumps and fans can all be operated in the same way. By pressing the button “Mode A/M” a pop-up screen appears and in this screen
all manual/auto buttons are shown:
- Pressing the manual/automatic button will switch the component from manual to auto or auto to manual (in case of manual
mode a ‘hand’ icon will appear).
- Pressing the manual on/off button will put the component in manual to on or in manual to off, depending on running state at
switch-over (if it was running in auto it will stop, until you press the manual on/off button). The component is completely off
when switch automatic/manual is in manual position and switch manual on/off is in off position.
Note that dry operation of a section is permitted but definitely not recommended. Therefore a fan will start,
even when the corresponding water pump is not running.
Note that in case of power failure all “manual” selections will be stored but automatically set to “off”. The
components must be switched to “on” again manually.
“Automatic” selections will be remembered, but always the systems must be started up again manually. As
result of a power failure all systems will be switched to “off”.
3.1.1.3 SETTINGS
In this condenser settings screen one can change all condenser settings. You must be logged on before you can change anything.
- When the contact of this level switch is continuously interrupted for a period of 5 seconds the pump will be switched off
and an alarm is issued.
Page 17
Vung Tau Vietnam Brewery – Control Philosophy
Note that dry operation of the condenser (fans running while the corresponding circulation pump is not
running) is possible, but not preferable. At full speed the fan motors absorb app. 25% more power. When
setting a maximal current in the frequency converter software the fans will run on a maximum speed which
is lower than 1.500 rpm.
Dry operation is possible on one condenser section while the other section is operating wet.
Condenser fans are frequency controlled and are protected by a thermal overload relay.
3.1.2 AIRPURGER
To keep the system free of non-condensable gasses, an airpurger A95.120.01 is installed. The airpurger is a stand-alone condenser-
unit, it will condensate the ammonia gasses and collects the non-condensable gasses. When enough non-condensable gasses are
collected, the airpurger will blow off the non-condensable gasses. On each point where non condensable gasses will collect in the
system during operation a solenoid valve is placed to bring the gasses to the airpurger. Each condenser is equipped with two
solenoid valves for purging purpose (V95.11X.01/02) and the liquid receiver has one V95.100.01.
The airpurger has a 230 VAC supply, this supply is continuous active and switched off by emergency stop alarm and ammonia
detection HH alarm (800 ppm). The airpurger is activated by a potential free contact in the cooling control panel and gives a signal
to the PLC (DI) when the airpurger starts to blow off.
The airpurger system can be switched on and off on the HMI, initial setting is “on”.
Once a day a purge cycle will be performed automatically at an adjustable start time if at least one of the cooling systems is started.
This means that all solenoid purge valves will open for an adjustable time one after each other. If a condenser is not in operation,
the purge valves of this condenser are skipped in the sequence. When the airpurger blow-off valve is active, the cycle is paused.
The purge valve that is open at that time will remain open and the airpurger keeps running. When the blow-off valve is closed
again, the cycle continuous. The number of started purge cycles and the number of blow-off are counted and presented on the
HMI, with a reset possibility.
Also an air purging auto cycle can be started by pressing the “Start Auto Cycle” button on the HMI.
The circuit breaker inside the control panel contains a trip contact that is connected to the PLC. If the circuit breaker is tripped a
warning is displayed on the HMI.
Page 18
Vung Tau Vietnam Brewery – Control Philosophy
3.1.3.1 BLEED-OFF
The function of the circulating water is that a part of it will evaporate. As a result of this, the minerals concentration in the remaining
water will increase. Each condenser has a transmitter (CE 95.11x.01) that measures the conductivity of the circulating water, this
transmitter gives his signal to the PLC. When the conductivity (= concentration of dissolved minerals) reaches its high limit value the
bleed-off valves V.95.xxx.03 of the applicable condenser will be opened, bleeding off the highly concentrated water. The amount of
water that is bled off, is replenished by fresh make-up water. A mechanical float valve controls make-up water supply. When the
conductivity reaches its low limit value, the bleed-off valve is closed again. The opening time of the bleed-off valve is time limited
(adjustable on HMI). If the opening time is exceeded a warning is displayed on HMI. Bleed-off system is activated after an adjustable
time delay when the water pump of that condenser is in operation.
3.1.3.3 BIOCIDE
Beside corrosion inhibitor the water treatment system also takes care of the dosing of a biocide, meant to kill all micro-organisms
that grow in the pan water. The biocide is dosed once or twice a week (timer based) with a relative large quantity per dosage in order
to reach a concentration that is sufficient to kill the microbiological activity. The timer is in the PLC, day, start time and duration of
biocide dosage is adjustable on the HMI.
The biocide system has one biocide supply pump P95.120.01 mounted on the biocide drum and each condenser has its own solenoid
valve V95.120.0x for dosing biocide tot the condenser. The dosing of biocide is a continue cycle, after dosing biocide in the first
condenser for a set time (adjustable on HMI), dosing in the second condenser will start and so on. The dosing pump can’t be operated
when all solenoids are closed. When the water pump of the condenser is not in operation during dosing biocide, it is forced on and
keeps running for an adjustable delay after dosing. When the water pump is not stand-by or running, dosing biocide for this condenser
is skipped. During and after dosing biocide the bleed-off of the applicable condenser will be blocked during an adjustable (HMI) time.
Water meter (CE 95.120.01) is located close to the condensers. Bleed off valves (V 95.***.03) and conductivity measuring cells (CE
95.***.03) are located on the condensers.
Containers for biocide and corrosion inhibitor, with built on dosing pump and level transmitters are located in the engine room.
Page 19
Vung Tau Vietnam Brewery – Control Philosophy
A minimum level inside the liquid receiver is necessary for the oil cooling of the compressors. The liquid receiver is equipped with a
level transmitter LT95.100.01 for visualization and alarm purpose only. If the level inside the liquid receiver comes below low level
setpoint the valve to the freezing system V95.100.03 and the chilling system V95.100.04 will be de-energized and a warning will be
displayed on the HMI.
Page 20
Vung Tau Vietnam Brewery – Control Philosophy
4.1.1 ECONOMIZER
The high pressure liquid from the liquid receiver expands to economizer pressure. Due to this expansion a liquid and gas mixture
arises. The gas is sucked off by the compressors toward their economizer port. The entering liquid will be led to the ammonia
separator. To be able to operate the economizer at least 1 compressor has to be running at an adjustable capacity or higher. If there
is no compressor running or under the capacity setpoint minus offset, the economizer has to be by-passed by closing YV97.112.01,
YV97.112.02 and V97.112.03 and V97.112.04 has to be opened. If the capacity of at least 1 compressor is above setpoint for activating
the economizer, PV97.112.02 should be forced open to an adjustable value. If the pressure in the economizer PT97.112.01 drops
below its setpoint, PV97.112.02 is closed again and the economizer is released. Releasing the economizer means opening
YV97.112.01, YV97.112.02 and V97.112.03 and V97.112.04 has to be closed
4.1.1.1 LEVEL
The level of the ammonia liquid inside the economizer is measured by LT 97.112.01. The output to level control valve LV97.112.01 is
based on the output to LV 97.111.01 (level control valve separator) with an adjustable factor. A PID regulator will change this output
according the level measured by LT 97.112.01 and setpoint level economizer.
If the level inside the economizer comes above high level setpoint the level control valve LV97.112.01 will be controlled close and a
warning is displayed on the HMI. If the level inside the economizer falls under setpoint level the level control valve LV97.112.01 is
released to controlled open again. If the level inside the economizer comes above high-high level setpoint or LS 97.112.01 is activated
the block-in function of the level control valve LV97.112.01 and also pressure control valve PV97.112.01 will be activated. The
activation of the block-in is done by de-activating of the solenoids valves for air supply YV97.112.01 (level control valve) and
YV97.112.02 (pressure control valve). If the level control valve is disabled the economizer is out of order and the bypass valve
V97.112.04 will be controlled open after an adjustable delay-time to supply liquid to the separator. If the bypass valve V97.112.04 is
open the liquid line valve V97.112.03 will be controlled closed. If the level inside the economizer comes below high level setpoint the
system can be reset and the block-in will be de-activated.
A too high level in the economizer will not stop the compressors.
4.1.1.2 PRESSURE
The pressure inside the economizer is measured by PT97.112.01 and will only be regulated when the economizer is active. The output
to pressure control valve PV97.112.02 is based on the setpoint economizer pressure and the output to LV 97.112.01 with an
adjustable factor. A PID regulator will change this output according the pressure measured by PT 97.112.01.
4.1.2 SEPARATOR
The ammonia separator is a thermosiphon system, the separator is direct connected with the heat plate exchangers of the freezing
system. The ammonia liquid is circulating through the primary side of the heat plate exchangers. The heat of the coolant on the
secondary side will evaporate the ammonia in the heat plate exchangers. The mixture of liquid and gas rises upwards into the
separator. The liquid ammonia flushes at the bottom side of the separator. The suction gas is led to the compressors.
4.1.2.1 LEVEL
The level of the ammonia liquid inside the separator is measured by LT 97.111.01. The level control valve LV97.111.01 is regulating
on level setpoint separator with a PID regulator and is released when there is at least one compressor running.
If the level inside the separator comes above high level setpoint the level control valve LV97.111.01 will be controlled close and a
warning is displayed on the HMI. If the level inside the separator falls under setpoint level the level control valve LV97.111.01 is
released to controlled open again. If the level inside the separator comes above high-high level setpoint or LS 97.111.01 is activated
the block-in function of the level control valve LV97.111.01 will be activated. The activation of the block-in is done by de-activating
of the solenoid valve for air supply YV97.112.01 (level control valve).
Only the compressors will stop (and therefore also the control valves will close to stop water flow); the distribution pump(s) will keep
on running!
To lower the ammonia level in high level condition it is necessary to run a compressor. Because of the high-
high level in the separator the compressor will not run. For that we need to override the high-high level alarm
by pressing the Override button in the HMI screen. Switching operation in override mode is restricted to
Page 21
Vung Tau Vietnam Brewery – Control Philosophy
password level 5 (supervisor) and higher. When the system is in override mode there is a warning displayed
on the ammonia separator page and the alarm list.
During override mode (with an high-high level in the separator) only one compressor of the freezing system can start-up with a
limited capacity of a maximum 50% to prevent the compressor sucks liquid from the separator instead of gas.
4.1.2.2 PRESSURE
The pressure inside the separator is measured by PT97.111.01. If the pressure inside the separator comes below low pressure setpoint
a warning is displayed on the HMI and no more compressors can start-up, independent on the request for cooling capacity. This is
because more compressor capacity will create even lower separator pressure. If the pressure comes below low-low pressure setpoint
an alarm is displayed on the HMI and the compressors will be controlled stopped. If the pressure in the separator comes above high
pressure setpoint a warning is displayed and the compressor capacity will be limited until the suction pressure is under high pressure
setpoint.
4.1.3 COMPRESSORS
Compressor unit C 99.***.01 will receive a start signal on command of cold buffer level of the stratification tank. This signal results
in a “capacity demand” for the compressor unit. This capacity demand is the “start/normal stop” signal (sent by the PLC through a
bus signal) towards the Unisab compressor controller. The PLC also gives a signal for the demand of capacity. Under normal conditions
the capacity demand will be regulated up in a short time and the compressor will run continuously on maximum capacity.
A serial hardware wired contacts from the compressor safety circuit processes into a “instant stop” signal towards the starter panel,
releasing the compressor for start and cause an immediate stop when one of the plant safeties fails. If the compressor is released for
start and the Unisab receives his start command (by Profibus) it will give a start feedback to the PLC. The PLC will start the compressor
motor.
As the compressor is designed for “full load” operation the compressor will regulate to 100% capacity when started and will keep
running at this capacity unless:
1. it is stopped because the “start/normal stop” signal is no longer present, requested level is reached, indicating that the
stratification tank is filled up. A normal stop means that the compressor regulates back to 0% and stops after the stop delay
timer.
2. It is stopped because the “instant stop” signal fails as a result of one of the process safeties, bearing or winding temperature
protection. In this case the compressor will stop instantly.
3. It is regulated back by the Unisab III compressor controller as a result of one of the limiting functions coming into operation.
Following limiting functions are present:
- Limiting on low suction pressure.
- Limiting on high discharge pressure.
- Limiting on high motor current.
In case the pre-alarm setting of one of the above process values is reached, the Unisab III compressor controller will reduce the
compressor capacity, thus overriding the capacity demand, in order to try and prevent the compressor from tripping when
reaching the actual alarm setting.
Page 22
Vung Tau Vietnam Brewery – Control Philosophy
The fact that a limiting function is in operation means that there is something wrong in the balance of the total system. Therefore
the actual operation of a limiting function indicates as warning on the HMI, furthermore it is indicated in the compressor screen at
“Unisab III compressor mode”.
When one compressor unit C 99.***.01 is not available for automatic operation, the next compressor in the sequence that is selected
on the HMI for operation on the coolant freezing cooling system starts up. This unit will automatically take over replacing the function
of the unit with a fault.
Compressor units will receive a start demand depending on the calculated cold level in the coolant freezing tank.
This is described in chapter 4.1.4.2
On the HMI the pressures, temperatures, capacity, current and status from each Unisab is visible in a pop-up, for more details see
the Profibus manual from the Unisab III controller.
The compressor unit can now be started and stopped and increased and decreased in capacity by operating the corresponding keys
on the Unisab III, if there’s provided that:
- The “instant stop” signal is present (process safeties are OK).
- The internal safeties of the Unisab III are OK.
- PS 99.***.01 is safe.
- The machine stop on the unit is safe.
For detailed information on manual operation refer to the Unisab III manual. If a compressor is not in state “remote” a message will
appear.
Page 23
Vung Tau Vietnam Brewery – Control Philosophy
If a compressor is running on a different system the calculation of the COP must be changed accordingly.
Page 24
Vung Tau Vietnam Brewery – Control Philosophy
4.1.4.1 OVERVIEW
The following compressors can be operated for the coolant freezing system:
Remarks:
- The start/stop sequence of the compressors will be determined by the cold level in the stratification tank and the set points
and delay times for that are adjustable on HMI.
- The maximal amount of compressors on the freezing system is maximum 2 compressors.
= compressor might be limited on capacity slide by the Unisab (due of high motor current) - value cooling capacity
(table) to be multiplied with the Yield (value from Unisab)
Page 25
Vung Tau Vietnam Brewery – Control Philosophy
d Adjustable parameter
This parameter is the parameter that gives the range of the cold level inside the stratification tank. For example:
Page 26
Vung Tau Vietnam Brewery – Control Philosophy
4.1.4.4 SEQUENCE
Remarks:
- At all times the following general primary conditions should be taken into account:
Ammonia detection OK, emergency stop OK, ammonia separator LS 97.111.01 is “1” (OK), LT 97.111.01 actual value under H-
alarm value (adjustable) and PT 97.111.01 actual value above L-alarm value, condensing pressure PT 95.120.01 actual value
under H-alarm value and Unisab ready.
- Compressor should ramp up (p) (to 100%) / down (q) (to 0%) within 3 minutes (adjustable in Unisab).
- Between start/start compressor there is a time delay of 15 minutes. (Maximum starts/hour is 4)
- Between stop/start compressor there is a time delay of 5 minutes.
- If a Unisab is not ready, the next compressor in sequence will be started. Desired start sequence is restored when all
compressors are running, stopped or ready.
Page 27
Vung Tau Vietnam Brewery – Control Philosophy
- Determine the temperature difference between the coolant freezing inlet temperature (TinAW) (TT 96.110.03) and set point
of the coolant freezing outlet (TspAW). The set point can be adjusted on the HMI.
- The temperature difference is being multiplied by the specific heat of coolant freezing (CpAW), which a constant value is being
4,2882kJ/kgK. The result (A) of the calculation should be higher as 1 (value g).
- In the table in paragraph 4.1.4.2 the compressor capacity has been specified. From each compressor operating on the coolant
freezing system it can be determined what the nominal cooling capacity is. The actual cooling capacity can be found in this
table based on actual evaporating temperature, condensing temperature and swept volume operating conditions.
- From each compressor it can be determined which nominal water flow (in m³/h) corresponds with the cooling capacity (in kW)
of the compressor using the formula from the control diagram:
To create a balance in energy, the needed coolant flow is calculated based on temperature difference between inlet temperature
PHE’s and desired coolant setpoint, the specific heat of the coolant (J/kg/K).
With a known density of the coolant, this value can be converted to m³/h.
Q(Yxxx)
= FspAW*
CpAW x (TinAW - TspAW ) x ρ
Page 28
Vung Tau Vietnam Brewery – Control Philosophy
Example:
SAB 233LME (C 99.111.001):
To = -8ºC and Tc = +34º => compressor cooling capacity Qo = 1.428,2 kW.
At coolant freezing inlet temperature -2ºC and coolant freezing set point -5ºC this will result into an actual coolant freezing flow of:
1.428,2 kW x 3.600s x 1h
------------------------------------------------------- = 411,2 m³/h
(4,2882 KJ/kgK x (5°C-2°C) x 972,0 kg/m³)
This calculated flow is used for the cascade regulator in the next paragraph.
2) Temperature controller.
The flow rate over the PHE will influence the coolant outlet temperature from the PHE’s.
To maintain the desired coolant temperature setpoint, the flow setpoint (already corrected by the suction pressure
controller) will be corrected by the temperature controller. The coolant outlet temperature transmitter will give the process
value for this controller. A higher outlet temperature from the PHE’s will reduce the primary flow setpoint, a lower outlet
temperature will increase the primary flow setpoint. The compensation for the temperature is limited with a minimum and
a maximum value. All parameters have to be adjustable on the HMI.
Page 29
Vung Tau Vietnam Brewery – Control Philosophy
The output of this controller is divided in a split-range signal towards the primary pumps and the flow regulating valves of the PHE’s.
All parameters have to be adjustable on the HMI.
At first start of a compressor the opening degree of the control valves is forced to 25%; from there the regulation of the opening
degree starts. In the screen you can specify how many and which PHE is in operation. The minimum flow across a coolant chilling PHE
is 25% of the design flow of 420 m3/h, being 105.0 m3/h. Below this flow fouling of the PHE may occur. The flow control valve will
regulated open or close according the calculated flow needed for the compressor(s). If the flow exceeds the minimum flow with 2
times (2x 105.0 m3/h = 210 m3/h) the next flow control valve of the next PHE will be controlled open. If the flow through the PHE’s
falls under the minimum flow for certain time the second PHE flow control valve will be closed.
Whenever a low flow is being detected by the flow transmitters FIT 96.120.0x there will be generated a low flow alarm without any
action. However if a ‘no’ flow (< 8 m3/h for a period of 20 sec.) is detected just after the compressor(s) have received their start
command, the compressor(s) will be stopped immediately as it might result into freezing of the PHE’s.
Page 30
Vung Tau Vietnam Brewery – Control Philosophy
To be sure that water is available from the water treatment plant it’s advisable to make an interlock between water treatment plant
and cooling plant disabling the cooling plant to start when water is not available!
When stopping the compressors the control valves must always close after a delay. If they would close immediately, the ramp down
time of the compressor(s) would cause freezing of the plate heat exchangers.
1. One pump runs after the coolant freezing system has been switched on.
2. Pumps can only start whenever ammonia detection OK and emergency stop is OK.
3. The following pump(s) starts-up whenever requested flow is above the flow (setting) of the leading pump for a certain time.
4. All pumps will regulate speed based on discharge pressure.
5. The following pump(s) stops whenever requested flow is below the flow (setting) of the following pump for a certain time.
6. Pumps switch on/off in a predefined adjustable sequence.
7. Pumps with failure or out of operation status will be skipped in the start sequence.
8. Start/stop and timers high/low are adjustable on the display.
When changing the sequence of pumps first ‘new’ leading pump must be started and after –adjustable- time
delay the ‘old’ leading pump must be switched off.
4.1.4.5.4.1 Sequence
Primary
Pos. Status Control Action Text W A
conditions
All pump(s)
1 Compressor 11x OFF Pump 1 OFF
stop
Startup first
2 Compressor 11x ON Pump 1 ON Pump 1 ON
pump
Flow pump 1 =100%
Increase compressor Startup Pump 1 ON
3 Pump 1 ON and timer 60
capacity 11x second pump Pump 2 ON
seconds
Flow pump 1+2 Pump 1 ON
Increase compressor Pump 1 ON Startup third
4 =100% and timer 60 Pump 2 ON
capacity 11x Pump 2 ON pump
seconds Pump 3 ON
Pump 1 ON Flow pump 1+2+3
Decrease compressor Stop third Pump 1 ON
5 Pump 2 ON <=60% and timer 60
capacity 11x pump Pump 2 ON
Pump 3 ON seconds
Flow pump 1+2
Decrease compressor Pump 1 ON Stop up
6 <=60% and timer 60 Pump 1 ON
capacity 11x Pump 2 ON second pump
seconds
Page 31
Vung Tau Vietnam Brewery – Control Philosophy
- One pump runs after the coolant freezing system has been switched on.
- Pumps can only start whenever ammonia detection OK and emergency stop is OK.
- The following pump(s) starts-up whenever requested flow is above the flow (setting) of the leading pump for a certain time.
- All pumps will regulate speed based on discharge pressure.
- The following pump(s) stops whenever requested flow is below the flow (setting) of the following pump for a certain time.
- Pumps switch on/off in a predefined adjustable sequence.
- Pumps with failure or out of operation status will be skipped in the start sequence.
- Start/stop and timers high/low are adjustable on the display.
When changing the sequence of pumps first ‘new’ leading pump must be started and after –adjustable- time
delay the ‘old’ leading pump must be switched off.
4.1.4.5.5.1 Sequence
Primary
Pos. Status Control Action Text W A
conditions
Calculated cold Stratification tank low
1 Stratification tank empty Pump 1 in x
level < 5% cold level
External contact = All pump(s)
2 No cold request
“0” stop
External contact = Startup first
3 Cold request Pump 1 ON
“1” pump
Total flow FIT
Increase cold request 1 121.110.0x > Startup Pump 1 ON
4 Pump 1 ON
pump in. 400m3/h and timer second pump Pump 2 ON
60 seconds
Total flow FIT
Pump 1 ON
Increase cold request 2 Pump 1 ON 121.110.0x > Startup third
5 Pump 2 ON
pumps in. Pump 2 ON 800m3/h and timer pump
Pump 3 ON
60 seconds
Total flow FIT
Pump 1 ON
Decrease cold request 3 121.110.0x < Stop up third Pump 1 ON
6 Pump 2 ON
pumps in. 800m3/h and timer pump Pump 2 ON
Pump 3 ON
60 seconds
Total flow FIT
Decrease cold request 2 Pump 1 ON 121.110.0x < Stop up
7 Pump 1 ON
pumps in. Pump 2 ON 400m3/h and timer second pump
60 seconds
Total flow FIT
Coolant freezing low
5 Control min. flow Pump 1 ON 121.110.0x < x m3/h x
flow request
and timer 5 seconds
At least 1 pump
TE 121.110.16 > - Coolant freezing
6 Temperature control in + timer 5 x
5°C temperature high
minutes
Calculation coolant Total flow FIT Requested alcohol
7
freezing capacity request 121.110.0x water flow = …m3/h
Calculation coolant Total flow FIT Coolant freezing
8
freezing consumption 121.110.0x consumption = …m³
When operating with one pump the next pump is automatically stand-by for taking over in case the leading pump fails.
The first distribution pump (P 121.111.0x) will run as soon as the coolant freezing system is active. Every pump should have abilities
to on/off, manual and automatic control. The pump will be frequency controlled based upon discharge pressure (PT 121.110.01)
Whenever the pressure switch PS 121.110.01 encounters a low pressure (vacuum) the distribution pumps will automatically be
switched off.
Page 32
Vung Tau Vietnam Brewery – Control Philosophy
The temperature transmitters TT 121.110.13, TT 121.110.14 and TT 121.110.15 are only for indication on the HMI screen and for
energy calculation purposes.
For these temperatures there’s the possibility to adjust values for high/low temperature warnings and alarms.
4.1.4.5.5.3 Control
The coolant freezing supply to the consumers is transported by pumps P 121.11x.01. The leading pump is always active (when coolant
freezing system is switched on) and speed is controlled by means of discharge pressure. Starting and stopping additional pumps is
based on the created flow measured by FIT 121.110.0x.
Page 33
Vung Tau Vietnam Brewery – Control Philosophy
4.2.1 ECONOMIZER
The high pressure liquid from the liquid receiver expands to economizer pressure. Due to this expansion a liquid and gas mixture
arises. The gas is sucked off by the compressors toward their economizer port. The entering liquid will be led to the ammonia
separator. To be able to operate the economizer at least 1 compressor has to be running at an adjustable capacity or higher. If there
is no compressor running or under the capacity setpoint minus offset, the economizer has to be by-passed by closing YV97.122.01,
YV97.122.02 and V97.122.03 and V97.122.04 has to be opened. If the capacity of at least 1 compressor is above setpoint for activating
the economizer, PV97.122.02 should be forced open to an adjustable value. If the pressure in the economizer PT97.122.01 drops
below its setpoint, PV97.122.02 is closed again and the economizer is released. Releasing the economizer means opening
YV97.122.01, YV97.122.02 and V97.122.03 and V97.122.04 has to be closed
4.2.1.1 LEVEL
The level of the ammonia liquid inside the economizer is measured by LT 97.122.01. The output to level control valve LV97.122.01 is
based on the output to LV 97.121.01 (level control valve separator) with an adjustable factor. A PID regulator will change this output
according the level measured by LT 97.122.01 and setpoint level economizer.
If the level inside the economizer comes above high level setpoint the level control valve LV97.122.01 will be controlled close and a
warning is displayed on the HMI. If the level inside the economizer falls under setpoint level the level control valve LV97.122.01 is
released to controlled open again. If the level inside the economizer comes above high-high level setpoint or LS 97.122.01 is activated
the block-in function of the level control valve LV97.122.01 and also pressure control valve PV97.122.01 will be activated. The
activation of the block-in is done by de-activating of the solenoids valves for air supply YV97.122.01 (level control valve) and
YV97.122.02 (pressure control valve). If the level control valve is disabled the economizer is out of order and the bypass valve
V97.122.04 will be controlled open after an adjustable delay-time to supply liquid to the separator. If the bypass valve V97.122.04 is
open the liquid line valve V97.122.03 will be controlled closed. If the level inside the economizer comes below high level setpoint the
system can be reset and the block-in will be de-activated.
A too high level in the economizer will not stop the compressors.
4.2.1.2 PRESSURE
The pressure inside the economizer is measured by PT97.122.01 and will only be regulated when the economizer is active. The output
to pressure control valve PV97.122.02 is based on the setpoint economizer pressure and the output to LV 97.122.01 with an
adjustable factor. A PID regulator will change this output according the pressure measured by PT 97.122.01.
4.2.2 SEPARATOR
The ammonia separator is a thermosiphon system, the separator is direct connected with the heat plate exchangers of the freezing
system. The ammonia liquid is circulating through the primary side of the heat plate exchangers. The heat of the coolant on the
secondary side will evaporate the ammonia in the heat plate exchangers. The mixture of liquid and gas rises upwards into the
separator. The liquid ammonia flushes at the bottom side of the separator. The suction gas is led to the compressors.
4.2.2.1 LEVEL
The level of the ammonia liquid inside the separator is measured by LT 97.121.01. The level control valve LV97.121.01 is regulating
on level setpoint separator with a PID regulator and is released when there is at least one compressor running.
If the level inside the separator comes above high level setpoint the level control valve LV97.121.01 will be controlled close and a
warning is displayed on the HMI. If the level inside the separator falls under setpoint level the level control valve LV97.121.01 is
released to controlled open again. If the level inside the separator comes above high-high level setpoint or LS 97.121.01 is activated
the block-in function of the level control valve LV97.121.01 will be activated. The activation of the block-in is done by de-activating
of the solenoid valve for air supply YV97.122.01 (level control valve).
Only the compressors will stop (and therefore also the control valves will close to stop water flow); the distribution pump(s) will keep
on running!
To lower the ammonia level in high level condition it is necessary to run a compressor. Because of the high-
high level in the separator the compressor will not run. For that we need to override the high-high level alarm
by pressing the Override button in the HMI screen. Switching operation in override mode is restricted to
password level 5 (supervisor) and higher. When the system is in override mode there is a warning displayed
on the ammonia separator page and the alarm list.
During override mode (with an high-high level in the separator) only one compressor of the chilling system can start-up with a limited
capacity of a maximum 50% to prevent the compressor sucks liquid from the separator instead of gas.
Page 34
Vung Tau Vietnam Brewery – Control Philosophy
4.2.2.2 PRESSURE
The pressure inside the separator is measured by PT97.121.01. If the pressure inside the separator comes below low pressure setpoint
a warning is displayed on the HMI and no more compressors can start-up, independent on the request for cooling capacity. This is
because more compressor capacity will create even lower separator pressure. If the pressure comes below low-low pressure setpoint
an alarm is displayed on the HMI and the compressors will be controlled stopped. If the pressure in the separator comes above high
pressure setpoint a warning is displayed and the compressor capacity will be limited until the suction pressure is under high pressure
setpoint.
Page 35
Vung Tau Vietnam Brewery – Control Philosophy
4.2.3 COMPRESSORS
Compressor unit C 99.***.01 will receive a start signal on command of cold buffer level of the stratification tank. This signal results
in a “capacity demand” for the compressor unit. This capacity demand is the “start/normal stop” signal (sent by the PLC through a
bus signal) towards the Unisab compressor controller. The PLC also gives a signal for the demand of capacity. Under normal conditions
the capacity demand will be regulated up in a short time and the compressor will run continuously on maximum capacity.
A serial hardware wired contacts from the compressor safety circuit processes into an “instant stop” signal towards the starter panel,
releasing the compressor for start and cause an immediate stop when one of the plant safeties fails. If the compressor is released for
start and the Unisab receives his start command (by Profibus) it will give a start feedback to the PLC. The PLC will start the compressor
motor.
As the compressor is designed for “full load” operation the compressor will regulate to 100% capacity when started and will keep
running at this capacity unless:
4. it is stopped because the “start/normal stop” signal is no longer present, requested level is reached, indicating that the
stratification tank is filled up. A normal stop means that the compressor regulates back to 0% and stops after the stop delay
timer.
5. It is stopped because the “instant stop” signal fails as a result of one of the process safeties, bearing or winding temperature
protection. In this case the compressor will stop instantly.
6. It is regulated back by the Unisab III compressor controller as a result of one of the limiting functions coming into operation.
Following limiting functions are present:
- Limiting on low suction pressure.
- Limiting on high discharge pressure.
- Limiting on high motor current.
In case the pre-alarm setting of one of the above process values is reached, the Unisab III compressor controller will reduce the
compressor capacity, thus overriding the capacity demand, in order to try and prevent the compressor from tripping when
reaching the actual alarm setting.
The fact that a limiting function is in operation means that there is something wrong in the balance of the total system. Therefore
the actual operation of a limiting function indicates as warning on the HMI, furthermore it is indicated in the compressor screen at
“Unisab III compressor mode”.
When one compressor unit C 99.***.01 is not available for automatic operation, the next compressor in the sequence that is selected
on the HMI for operation on the coolant freezing cooling system starts up. This unit will automatically take over replacing the function
of the unit with a fault.
Compressor units will receive a start demand depending on the calculated cold level in the coolant chilling tank.
This is described in chapter 4.2.4.2
On the HMI the pressures, temperatures, capacity, current and status from each Unisab is visible in a pop-up, for more details see
the Profibus manual from the Unisab III controller.
Page 36
Vung Tau Vietnam Brewery – Control Philosophy
The compressor unit can now be started and stopped and increased and decreased in capacity by operating the corresponding keys
on the Unisab III, if there’s provided that:
- The “instant stop” signal is present (process safeties are OK).
- The internal safeties of the Unisab III are OK.
- PS 99.***.01 is safe.
- The machine stop on the unit is safe.
For detailed information on manual operation refer to the Unisab III manual. If a compressor is not in state “remote” a message will
appear.
If a compressor is running on a different system the calculation of the COP must be changed accordingly.
Page 37
Vung Tau Vietnam Brewery – Control Philosophy
Page 38
Vung Tau Vietnam Brewery – Control Philosophy
4.2.4.1 OVERVIEW
The following compressors can be operated for the coolant chilling system:
Remarks:
- The start/stop sequence of the compressors will be determined by the cold level in the stratification tank and the set points
and delay times for that are adjustable on HMI.
- The maximal amount of compressors on the freezing system is maximum 2 compressors.
= compressor might be limited on capacity slide by the Unisab (due of high motor current) - value cooling capacity
(table) to be multiplied with the Yield (value from Unisab)
Page 39
Vung Tau Vietnam Brewery – Control Philosophy
d Adjustable parameter
This parameter is the parameter that gives the range of the cold level inside the stratification tank. For example:
Page 40
Vung Tau Vietnam Brewery – Control Philosophy
4.2.4.4 SEQUENCE
Remarks:
- At all times the following general primary conditions should be taken into account:
Ammonia detection OK, emergency stop OK, ammonia separator LS 97.121.01 is “1” (OK), LT 97.121.01 actual value under H-
alarm value (adjustable) and PT 97.121.01 actual value above L-alarm value, condensing pressure PT 95.120.01 actual value
under H-alarm value and Unisab ready.
- Compressor should ramp up (to 100%) / down (to 0%) within 3 minutes (adjustable in Unisab).
- Between start/start compressor there is a time delay of 15 minutes. (Maximum starts/hour is 4)
- Between stop/start compressor there is a time delay of 5 minutes.
- If a Unisab is not ready, the next compressor in sequence will be started. Desired start sequence is restored when all
compressors are running, stopped or ready.
Page 41
Vung Tau Vietnam Brewery – Control Philosophy
- Determine the temperature difference between the coolant chilling inlet temperature (TinBW) (TT 96.120.03) and set point of
the coolant chilling outlet (TspBW). The set point can be adjusted on the HMI.
- The temperature difference is being multiplied by the specific heat of coolant chilling (CpBW), which a constant value is being
4,3583kJ/kgK. The result (A) of the calculation should be higher as 1 (value g).
- In the table in paragraph 4.2.4.2 the compressor capacity has been specified. From each compressor operating on the coolant
chilling system it can be determined what the nominal cooling capacity is. The actual cooling capacity can be found in this
table based on actual evaporating temperature, condensing temperature and swept volume operating conditions.
- From each compressor it can be determined which nominal water flow (in m³/h) corresponds with the cooling capacity (in kW)
of the compressor using the formula from the control diagram:
To create a balance in energy, the needed coolant flow is calculated based on temperature difference between inlet temperature
PHE’s and desired coolant setpoint, the specific heat of the coolant (J/kg/K).
With a known density of the coolant, this value can be converted to m³/h.
Q(Yxxx)
= FspBW*
CpBW x (TinBW - TspBW ) x ρ
Example:
SAB 233LME (C 99.113.01):
To = -2ºC and Tc = +36º => compressor cooling capacity Qo = 1.955,0 kW.
At coolant chilling inlet temperature 5ºC and coolant chilling set point 2ºC this will result into an actual coolant chilling flow of:
1.955,0 kW x 3.600s x 1h
------------------------------------------------------- = 544. 2 m³/h
(4.3583 KJ/kgK x (5°C-2°C) x 989.0 kg/m³)
This calculated flow is used for the cascade regulator in the next paragraph.
Page 42
Vung Tau Vietnam Brewery – Control Philosophy
5) Temperature controller.
The flow rate over the PHE will influence the coolant outlet temperature from the PHE’s.
To maintain the desired coolant temperature setpoint, the flow setpoint (already corrected by the suction pressure
controller) will be corrected by the temperature controller. The coolant outlet temperature transmitter will give the process
value for this controller. A higher outlet temperature from the PHE’s will reduce the primary flow setpoint, a lower outlet
temperature will increase the primary flow setpoint. The compensation for the temperature is limited with a minimum and
a maximum value. All parameters have to be adjustable on the HMI.
Page 43
Vung Tau Vietnam Brewery – Control Philosophy
The output of this controller is divided in a split-range signal towards the primary pumps and the flow regulating valves of the PHE’s.
All parameters have to be adjustable on the HMI.
At first start of a compressor the opening degree of the control valves is forced to 25%; from there the regulation of the opening
degree starts. In the screen you can specify how many and which PHE is in operation. The minimum flow across a coolant chilling PHE
is 25% of the design flow of 260 m3/h, being 65.0 m3/h. Below this flow fouling of the PHE may occur. The flow control valve will
regulated open or close according the calculated flow needed for the compressor(s). If the flow exceeds the minimum flow with 2
times (2x 65.0 m3/h = 130.0 m3/h) the next flow control valve of the next PHE will be controlled open. The same action for the third
valve. If the flow through the PHE’s falls under the minimum flow for certain time the one PHE flow control valve will be closed.
Whenever a low flow is being detected by the flow transmitters FIT 96.120.0x there will be generated a low flow alarm without any
action. However if a ‘no’ flow (< 8 m3/h for a period of 20 sec.) is detected just after the compressor(s) have received their start
command, the compressor(s) will be stopped immediately as it might result into freezing of the PHE’s.
To be sure that water is available from the water treatment plant it’s advisable to make an interlock between water treatment plant
and cooling plant disabling the cooling plant to start when water is not available!
Page 44
Vung Tau Vietnam Brewery – Control Philosophy
When stopping the compressors the control valves must always close after a delay. If they would close immediately, the ramp down
time of the compressor(s) would cause freezing of the plate heat exchangers.
- One pump runs after the coolant freezing system has been switched on.
- Pumps can only start whenever ammonia detection OK and emergency stop is OK.
- The following pump(s) starts-up whenever requested flow is above the flow (setting) of the leading pump for a certain time.
- All pumps will regulate speed based on discharge pressure.
- The following pump(s) stops whenever requested flow is below the flow (setting) of the following pump for a certain time.
- Pumps switch on/off in a predefined adjustable sequence.
- Pumps with failure or out of operation status will be skipped in the start sequence.
- Start/stop and timers high/low are adjustable on the display.
When changing the sequence of pumps first ‘new’ leading pump must be started and after –adjustable- time
delay the ‘old’ leading pump must be switched off.
4.2.4.5.2.3 Sequence
Primary
Pos. Status Control Action Text W A
conditions
All pump(s)
1 Compressor 12x OFF Pump 1 OFF
stop
Startup first
2 Compressor 12x ON Pump 1 ON Pump 1 ON
pump
Flow pump 1 =100%
Increase compressor Startup Pump 1 ON
3 Pump 1 ON and timer 60
capacity 12x second pump Pump 2 ON
seconds
Flow pump 1+2 Pump 1 ON
Increase compressor Pump 1 ON Startup third
4 =100% and timer 60 Pump 2 ON
capacity 12x Pump 2 ON pump
seconds Pump 3 ON
Pump 1 ON Flow pump 1+2+3
Decrease compressor Stop third Pump 1 ON
5 Pump 2 ON <=60% and timer 60
capacity 12x pump Pump 2 ON
Pump 3 ON seconds
Flow pump 1+2
Decrease compressor Pump 1 ON Stop up
6 <=60% and timer 60 Pump 1 ON
capacity 12x Pump 2 ON second pump
seconds
Page 45
Vung Tau Vietnam Brewery – Control Philosophy
9. One pump runs after the coolant chilling system has been switched on.
10. Pumps can only start whenever ammonia detection OK and emergency stop is OK.
11. The following pump(s) starts-up whenever requested flow is above the flow (setting) of the leading pump for a certain time.
12. All pumps will regulate speed based on discharge pressure.
13. The following pump(s) stops whenever requested flow is below the flow (setting) of the following pump for a certain time.
14. Pumps switch on/off in a predefined adjustable sequence.
15. Pumps with failure or out of operation status will be skipped in the start sequence.
16. Start/stop and timers high/low are adjustable on the display.
When changing the sequence of pumps first ‘new’ leading pump must be started and after –adjustable- time
delay the ‘old’ leading pump must be switched off.
4.2.4.5.3.1 Sequence
Primary
Pos. Status Control Action Text W A
conditions
Calculated cold Stratification tank low
1 Stratification tank empty Pump 1 in x
level < 5% cold level
External contact = All pump(s)
2 No cold request
“0” stop
External contact = Startup first
3 Cold request Pump 1 ON
“1” pump
Total flow FIT
Increase cold request 1 121.120.0x > Startup Pump 1 ON
4 Pump 1 ON
pump in. 400m3/h and timer second pump Pump 2 ON
60 seconds
Total flow FIT
Pump 1 ON
Increase cold request 2 Pump 1 ON 121.120.0x > Startup third
5 Pump 2 ON
pumps in. Pump 2 ON 800m3/h and timer pump
Pump 3 ON
60 seconds
Total flow FIT
Pump 1 ON
Decrease cold request 3 121.120.0x < Stop up third Pump 1 ON
6 Pump 2 ON
pumps in. 800m3/h and timer pump Pump 2 ON
Pump 3 ON
60 seconds
Total flow FIT
Decrease cold request 2 Pump 1 ON 121.120.0x < Stop up
7 Pump 1 ON
pumps in. Pump 2 ON 400m3/h and timer second pump
60 seconds
Total flow FIT
Coolant chilling low
5 Control min. flow Pump 1 ON 121.120.0x < x m3/h x
flow request
and timer 5 seconds
At least 1 pump
TE 121.110.16 > - Coolant chilling
6 Temperature control in + timer 5 x
5°C temperature high
minutes
Calculation coolant Total flow FIT Requested alcohol
7
chilling capacity request 121.120.0x water flow = …m3/h
Calculation coolant Total flow FIT Coolant chilling
8
chilling consumption 121.120.0x consumption = …m³
When operating with one pump the next pump is automatically stand-by for taking over in case the leading pump fails.
The first distribution pump (P 121.121.0x) will run as soon as the coolant chilling system is active. Every pump should have abilities
to on/off, manual and automatic control. The pump will be frequency controlled based upon discharge pressure (PT 121.120.01)
Whenever the pressure switch PS 121.120.01 encounters a low pressure (vacuum) the distribution pumps will automatically be
switched off.
Page 46
Vung Tau Vietnam Brewery – Control Philosophy
The temperature transmitters TT 121.110.13, TT 121.110.14 and TT 121.110.15 are only for indication on the HMI screen and for
energy calculation purposes.
For these temperatures there’s the possibility to adjust values for high/low temperature warnings and alarms.
4.2.4.5.3.3 Control
The coolant freezing supply to the consumers is transported by pumps P 121.11x.01. The leading pump is always active (when coolant
freezing system is switched on) and speed is controlled by means of discharge pressure. Starting and stopping additional pumps is
based on the created flow measured by FIT 121.110.0x.
Page 47
Vung Tau Vietnam Brewery – Control Philosophy
The expansion tank is placed on the highest point in the coolant freezing / chilling system and is keeping the system under static
pressure. Also it is a buffer for the deviation of the coolant freezing liquid density.
The make-up tank is used to mix alcohol and water in the correct ratio and it is a buffer to fill the coolant freezing / chilling system
A selection (manual-off-automatic) for make-up pump P 96.151.01 can be made on the HMI.
Manual selection: The pumps can be started and stopped by means of the corresponding push button near the pump.
This position is only used to make or mix a coolant freezing / chilling solution.
The ethyl alcohol drum pomp is running for a maximum adjustable time (this time delay is adjusted in
the PLC).
Automatic selection: The pump works on command of the start / stop levels in the expansion unit.
4.3.1 SETTINGS
The following settings must be available on the HMI
- Run time make-up pump
- Run time alcohol pump
- Alarm settings
The level of the expansion tank A 96.151.02 is indicated on the HMI by means of LT 96.150.02.
The level of the expansion tank A 96.151.03 is indicated on the HMI by means of LT 96.150.03.
Page 48
Vung Tau Vietnam Brewery – Control Philosophy
The pump can only fill by manual operation, the power supply to the pump is controlled by the plc.
4.3.4.1 GENERAL
Normally an ethanol-water solution is used with a concentration of 20% to 25% by volume for coolant freezing (-5 ºC) and 5% to 10%
for coolant chilling (+3 ºC). Concentration may be adjusted for operation with different coolant temperatures.
In case of low level in the make-up tank, a text on the HMI will be displayed as a warning. In the make-up tank the water and ethanol
have to be mixed first before putting it into the main system.
Note:
Separately filling water and ethanol directly into the main system will lead to mixing problems and possible
freezing of the evaporators!!
The make-up system will now circulate over the make-up tank only (=mixing) if P 96.151.01 is started.
- Fill the make-up tank with factory water by opening valve V 96.150.03.
- On flow meter FIT 96.150.01 the quantity of filled water can be read. Depending on the number of drums/containers with
ethanol and the desired coolant concentration a certain amount of water has to be filled.
- Fill ethyl alcohol with drum pomp P 096.0151.002 till the correct level is reached (a percentage of the amount of filled water,
calculated to a raise of level)
- Start P 96.151.01 for approximately 15 minutes
- Stop P 96.151.01 and take a sample to check the freezing point of the mixture
Page 49
Vung Tau Vietnam Brewery – Control Philosophy
5 BREWMAX SC4U
The cooling plant of the brewery needs to provide data to the brewery scada system for trending and operating purpose. Heineken
has enrolled a new system for integrating external utility suppliers into the overall brewery scada system. Each external utility system
needs to use the same structure and layout to make the work of the operators much easier. Each supplier needs to use the same
pre-defined DB delivered by Heineken inside the PLC for communication with the Brewmax visualization of that particular utility. The
DB has a structure that is visualized in an EXEL file so called SC4U template. In the template is defined the data that the brewery
needs to use for the Brewmax system. Each data has its own unique number. An example can be find below.
The utility supplier needs to fill in the EXEL file accordingly the data that needs to provide. The grey fields in the EXEL may not be
changed by supplier. For each analog value the green fields with the unit type and decimal needs to be provided.
Page 50