PRODUCT FICHE according to European Regulation n° 2016/2281:

Information requirements for air‐to‐air air conditioners

Model(s): UATYQ50ABAY1 / UATYQ50AFC2Y1 / UATYQ50AFC3Y1

Outdoor side heat exchanger of air conditioner:  Air

Indoor side heat exchanger of air conditioner:  Air

Type:  compressor driven vapour compression

If applicable: driver of the compressor :  electric motor

Item Symbol Value Unit Item Symbol Value Unit

Seasonal space 
Rated cooling 
Prated,c 49,2 kW cooling energy  ηs,c  134,1 %
capacity
efficiency

Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27°/19 °C 
Declared energy efficiency ratio at given outdoor temperature Tj
(dry/wet bulb)

Tj =+ 35°C Pdc 49,2 kW Tj =+ 35°C EERd 2,50 –

Tj =+ 30°C Pdc 36,3 kW Tj =+ 30°C EERd 3,77 –

Tj =+ 25°C Pdc 35,0 kW Tj =+ 25°C EERd 4,27 –

Tj =+ 20°C Pdc 36,6 kW Tj =+ 20°C EERd 4,78 –

Degradation          
coefficient for air  Cdc 0,25 —
conditioners(*)

Power consumption in modes other than "active mode"

Crankcase heater 
Off mode POFF  0,150 kW PCK  0,000 kW
mode

Thermostat‐off 
PTO  0,749 kW Standby mode PSB  0,150 kW
mode

Other items

For air‐to‐air air 
conditioner: air flow 
Capacity control Staged – 19000 m3/h
rate, outdoor 
measured

Sound power level, 
LWA  81,5 dB(A)
indoors

Sound power level, 
LWA  81,5 dB(A)
outdoors

Emissions of  mg/kWh fuel input 
NOx (**) N/A
nitrogen oxides GCV

GWP of the  kg CO2 eq              
2088
refrigerant (100 years)

Contact details Daikin Europe N.V. Zandvoordestraat 300, B‐8400 Oostende, Belgium

(*) If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.                                                                                                                                                                  
(**) From 26 September 2018.
Where information relates to multi‐split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or 
importer.
PRODUCT FICHE according to European Regulation n° 2016/2281:
Information requirements for heat pumps

Model(s): UATYQ50ABAY1 / UATYQ50AFC2Y1 / UATYQ50AFC3Y1

Outdoor side heat exchanger of air conditioner:  Air

Indoor side heat exchanger of air conditioner:  Air

Indication if the heater is equipped with a supplementary heater: no

If applicable: driver of the compressor :  electric motor

Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons are optional.

Item Symbol Value Unit Item Symbol Value Unit

Rated heating capacity Prated,h 52,0 kW Seasonal space heating energy efficiency ηs,h  125,2 %

Declared heating capacity for part load at indoor temperature 20 °C and outdoor temperature Tj Declared coefficient of performance at given outdoor temperature Tj

Tj = ‐ 7 °C Pdh 32,9 kW Tj = ‐ 7 °C COPd 2,33 –

Tj =+ 2°C Pdh 23,3 kW Tj =+ 2°C COPd 3,43 –

Tj =+ 7°C Pdh 29,7 kW Tj =+ 7°C COPd 4,10 –

Tj =+ 12°C Pdh 34,2 kW Tj =+ 12°C COPd 4,70 –

Tbiv  = bivalent temperature Pdh 34,9 kW Tbiv  = bivalent temperature COPd 2,57 –

TOL  = operation limit Pdh 31,0 kW TOL  = operation limit COPd 2,23 –

For air‐to‐water heat pumps: Tj = –  For air‐to‐water heat pumps: Tj = – 15 °C (if 
Pdh N/A kW COPd N/A –
15 °C (if TOL < – 20 °C) TOL < – 20 °C)

For water‐to‐air heat pumps: Operation 
Bivalent temperature Tbiv ‐5 °C TOL N/A °C
limit temperature

Degradation          coefficient for air 
Cdh 0,25 —
conditioners(**)

Power consumption in modes other than "active mode" Supplementary heater

Off mode POFF  0,150 kW Back‐up heating capacity (*) elbu N/A kW

Thermostat‐off mode PTO  0,718 kW Type of energy input N/A

Crankcase heater mode PCK  0,000 kW Standby mode PSB  0,150 kW

Other items

For air‐to‐air air conditioner: air flow rate,  3
Capacity control Staged – 19000 m /h
outdoor measured

Sound power level, indoors LWA  81,5 dB(A)


For water/brine‐to‐air heat pumps: Rated 
brine or water flow rate, outdoor side heat  – N/A m3/h
exchanger
Sound power level, outdoors LWA  81,5 dB(A)

mg/kWh fuel input 
Emissions of nitrogen oxides NOx (***) N/A
GCV

kg CO2 eq               (100 
GWP of the refrigerant 2088
years)

Contact details Daikin Europe N.V. Zandvoordestraat 300, B‐8400 Oostende, Belgium
(*)                                                                                                                                                           
(**)If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0,25.
(***)From 26 September 2018.

Where information relates to multi‐split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.